Danfoss Electronics ACB, CCB Data Sheet

Data sheet
Cartridge pressure switch Type ACB and CCB
Pressure controls ACB and CCB are compact disc type pressure switches with xed set-points for long-standing use in refrigeration and air conditioning systems. They provide automatic or manual reset limit protection.
The small size, lightness and high degree of protection means that it can be mounted directly on the refrigeration systems.
The cartridge switch is available with dierent pressure settings and pressure connections to suit customer requirements.
All these features reduce installation costs and save space.
Features
Approvals
y Wide range
y Fixed pressure set points
y Normally Closed, Normally Open or SPDT
contact system
y Automatic or manual reset
y Various port ttings for soldering or direct
mounting
y Spades or cables
y CE according to EN 12263
y Technical Inspection Association TÜV
TUV certicate no. 01 202 931/Q-04 0018 and 01 202 971/B-17-0002
y Low Voltage Directive 2014/35/EU
y Stripped ends or customer specic electrical
plug
y Open or water-proof (IP65) version
y Type ACB for use as high and low pressure cut
in and cut out as well as fan cycling
y Type CCB available for CO2 refrigerants
y Compact design and easy to install
y UL recognized (type ACB only):
- UL 873 and CSA C22.2 No. 24-93
- UL 121201 and CSA C22/2 No.213-17 (for ammable refrigerants only)
© Danfoss | DCS (rm) | 2019.02 DKRCC.PD.CH0.B8.02 | 520H11785 | 1
Data sheet | Cartridge pressure switch, type CB
High
Pressure
Low
Pressure
Fan Control
Compressor
Condenser
Evaporator
Expansion valve
Air conditioning and Refrigeration
Applications Low Pressure safety pressure switch
Condenser fan switch
Compressor stop – start
High Pressure safety pressure switch
Pump-down switch
2 | 520H11785 | DKRCC.PD.CH0.B8.02
© Danfoss | DCS (rm) | 2019.02
Data sheet | Cartridge pressure switch, type CB
Technical data
Typ e
ACB CCB
Water-proof (W) Open – spade connector (O) Water-proof (W)
R22, R134a, R404A, R407C, R407F, R410A, R438A,
R448A, R449A, R452A, R513A
For flammable refrigerants please contact your
Medium
For complete list of approved refrigerants, visit www.
nearest Danfoss office.
R74 4 (CO2)
products.danfoss.com and search for individual code
numbers, where refrigerants are listed as part of
technical data
Range
-0.5 – 45 bar
-7 – 652 psi
100 – 150 bar 1450 –2176 psi
Reset Automatic, Manual Automatic
Contact function SPST-NO, SPST-NC, SPDT SPS T-NC
Electrical connections AWG18 cables Spades (size 6.35mm x 0.8 mm) AWG18 cables
Cable length 150 cm (black) 150 cm (black)
6 A @ 250 V AC for SPST
Contact load
4 A @ 250 V AC for SPDT
0,01 - 0,05 A @ 12/24 V DC
1
4 in ODM solder
Pressure connections
1
4 in SAE female flare
6.35 mm solder
with depressure pin
6 mm ODM solder
Maximum working pressure PS / MWP
Burst pressure
Media temperature
45 bar
650 psi
140 bar
2030 psi
-55 – 135 °C
-67 – 275 °F
165 bar
2393 psi
375 bar
5440 psi
-30 – 100 °C
-20 – 210 °F
Ambient temperature -30 – 85 °C
Enclosure IP65 No electrical protection IP65
Customer specic features are available in a wide selection. Please refer to Specication Build-up on page 8.
© Danfoss | DCS (rm) | 2019.02 DKRCC.PD.CH0.B8.02 | 520H11785 | 3
Loading...
+ 7 hidden pages