ENGLISH
The electronic unit is a single voltage device.
This means that the unit can only be used with
12V DC power supply systems. Maximum voltage is 17V DC, max. ambient temperature is 55°C.
The electronic unit has a built-in thermal protection which is actuated and stops the compressor
operation if the electronic unit temperature becomes too high (100°C/212°F on the PCB). It can
be connected to a PC through the Secop One
Wire/LIN Gateway communication interface on
the terminal Com and – (Fig. 6). Communication
gateway modules incl. communication cables
can be ordered at Secop. The PC interface allows you to create different settings and reads
out several measurements by using the software
tool TOOL4COOL® supplied by Secop.
Installation (Fig. 3)
Mount the electronic unit directly on the compressor plug and fi x it with screws.
Power supply (Fig. 1)
The electronic unit must always be connected
directly to the battery poles. Connect the plus to
+ and the minus to –, otherwise the electronic
unit will not work. The electronic unit is protected
against reverse battery connection. For protection during installation, a fuse must be mounted
in the + cable as close to the battery as possible. It is recommended to use 12A fuses for 12V
circuits.
When a main switch is connected it must be connected on the terminals DI and +. When there is
no main switch DI must be short circuit with +.
The wire dimensions in Fig. 4 must be observed.
Avoid extra junctions in the power supply system
to prevent voltage drop from affecting the battery
protection setting.
Battery protection (Fig. 2)
The compressor stops and restarts again according to the designated voltage limits measured
on the + and – terminals of the electronic unit.
The standard settings for the power supply systems are shown in Fig. 2a. Other settings are set
through the communication interface (Fig. 2b).
When using a mechanical thermostat battery cut
in and cut out values can be set via a resistor on
the terminals S1 and C.
Thermostat (Fig. 1)
The thermostat is connected between the terminals C and S1. Either a NTC (electrical thermostat) or a mechanical thermostat can be connected.
When using the NTC function it is necessary to
mount another NTC in series with a 4,7kΩ resistor
on the terminals C and S2. This NTC sensor will
then obtain the ambient temperature and switch
off the compressor in case of ambient higher
then 55°C. Three different thermostat modes
can be chosen in the software - Auto (both NTC
and mechanical), NTC or Mechanical. Standard
setting is Auto. When Auto is set and a mechanical thermostat is used it is necessary to mount a
316Ω resistor on the terminals C and S2.
In case of using a NTC the set point in the range
between -40º C and 40º C is set with the software
and the temperature can also be seen by using
the interface. When using the Auto setting in the
software this not possible to obtain NTC failures,
so it is recommended to set the thermostat mode
to NTC when using a NTC.
Speed selection (Fig. 1)
The compressor will run with a fi xed speed of
3,000 rpm when the thermostat is switched on. A
start delay in the range from 2-240 sec. (factory
setting 4 sec.) after thermostat cut-in can also be
chosen.
By default the compressor will start with a speed
of 2,500 rpm for the fi rst 30 sec.
Fan (Fig. 1)
A fan can be connected between the terminals
F+ and F–. Connect the plus to F+ and the minus
to F–. Since the output voltage between the terminals + and F is always regulated to 12V, a 12V
fan must be used. The fan output can supply a
continuous current of 0.65Aavg. A higher current
draw is allowed for 2 seconds during start.
The
factory setting is no fans. If fans are used
without adapting the software settings, the fans
will run but no error signal will be sent in case of
fan failure.
It is also possible to set a start delay on the fans
in the range from 0-240 sec. Factory settings for
the fan is 0 sec. Fan speed is fi xed
Error handling (Fig. 5)
If the electronic unit records an operational error,
the error can be read out in the software.
MMI (Fig. 1)
It is possible to connect 2 switches and 2 LED’s
to the controller. With each switch a set point
for the thermostat can be selected or deselected
and the LEDs show the chosen set point.
Default setting for the set points is +6° C fridge
set point and -6° C freezer set point. Other
set point values can be established via TOOL4COOL®. The switches are connected to the terminals SW1 and C. The switch for choosing the
fridge set point shall be mounted in series with a
1500Ω resistor.
The switch for choosing the freezer set point
shall be mounted in series with a 330Ω resistor.
The LED for indicating the fridge set point shall
be mounted on the terminals D1 and C in series
with 750Ω resistors.
The LED for indicating the freezer set point shall
be mounted on the terminals D2 and C in series
with 750Ω resistors.
The intensity of the LED’s can be controlled via a
pwm 100kHz – 10kHz to the terminal DIM.
Resistors
Marking Value [Ω] Function
R1 see page 2 battery protection
R2 750 resistor LED 1
R3 750 resistor LED 2
R4 1500 coding resistor S1
R5 330 coding resistor S2
Connectors (Tyco Electronics)
Code no Male Female Crimp
Power 178305-5 178289-5 1-175218-20
MMI 1376136-1 1-1318119-3 1-318108-1