Danfoss XGC L430P Data sheet

Danfoss XGC L430P Data sheet

Data sheet

Plate heat exchanger XGC L430P

Dimensions, mm

For LG>3708mm

Height + 200mm

The Plate Heat Exchanger has 4 connections as standard and should be installed with min. 1500 mm space on both sides for service work.

Subject to alterations without prior notice.

 

 

M4 M1

 

 

M3 M2

S4

S1

 

 

 

Movable cover, M

S3

S2

Stationary cover,S

DH-SMT/FI

©VDDanfoss.EJ.G1.0203/2009© Danfoss 03/2009

Data sheet

Plate heat exchanger XGC L430P

 

 

Dimensions, mm

 

Standard connection dimension

 

 

 

 

DN450

 

 

 

 

 

 

Tightening bolt

 

 

 

 

M39

 

 

 

 

 

 

No. of long tightening bolts (TL)

 

 

 

 

4

 

 

 

 

 

 

 

 

 

No. of short tightening bolts (TS)

 

 

 

20

 

 

 

 

 

 

 

 

 

Cover thickness

 

 

 

 

130 mm

 

 

 

 

 

 

Weight of guiding bar

 

 

 

 

46 kg/m

 

 

 

 

 

 

Weight of tightening bolt

 

 

 

 

8,1 kg/m

 

 

 

 

 

 

A-dimension

 

 

 

 

5,1*n mm

 

 

 

 

 

 

C-dimension

 

 

 

 

LG+230 mm

 

 

 

 

 

 

F-dimension

 

 

 

 

LG+10 mm

 

 

 

 

 

 

Weight plate+gasket (W)

AISI 304/316 0,6 mm

 

 

 

20,4kg

 

 

 

 

 

 

 

 

 

 

Titanium 0,6 mm

 

 

 

12,1 kg

 

 

 

 

 

 

Weight Frame

 

 

 

 

11963+n*W kg

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max No of plates

 

 

 

LTL

 

 

LG

 

 

 

C

 

 

F

 

21

 

 

 

500

 

1000

 

 

 

1230

 

1010

 

37

 

 

 

750

 

1000

 

 

 

1230

 

1010

 

57

 

 

 

750

 

1350

 

 

 

1580

 

1360

 

87

 

 

 

1050

 

1350

 

 

 

1580

 

1360

 

100

 

 

 

1050

 

1550

 

 

 

1780

 

1560

 

115

 

 

 

1350

 

1550

 

 

 

1780

 

1560

 

142

 

 

 

1350

 

1900

 

 

 

2130

 

1910

 

165

 

 

 

1650

 

1900

 

 

 

2130

 

1910

 

185

 

 

 

1650

 

2200

 

 

 

2430

 

2210

 

208

 

 

 

1950

 

2200

 

 

 

2430

 

2210

 

228

 

 

 

1950

 

2500

 

 

 

2730

 

2510

 

251

 

 

 

2250

 

2500

 

 

 

2730

 

2510

 

271

 

 

 

2250

 

3000

 

 

 

3230

 

3010

 

322

 

 

 

3000

 

3000

 

 

 

3230

 

3010

 

378

 

 

 

3000

 

3500

 

 

 

3730

 

3510

 

450

 

 

 

3500

 

40001)

 

 

 

4230

 

4010

 

465

 

 

 

4000

 

40001)

 

 

 

4230

 

4010

 

521

 

 

 

4000

 

45001)

 

 

 

4730

 

4510

 

LTL = Length of long tightening bolt, based on 7 x n + 350 mm LG = Length of guiding bar, based on 7 x n + 740 mm

n = number of plates

Please check Fbla-003 for max. working / test pressure for plates

1) LG>3708mm reinforced guiding bar Height + 200mm

Total max no. of plates

AISI 304/316 0,6 mm

700

All data is based on plates with material AISI 304/316 and thickness 0,6 mm.

VD.EJ.G1.02

Produced by Danfoss A/S © 03/2009

Loading...