Danfoss XGC L205P Data sheet

Danfoss XGC L205P Data sheet

Data sheet

Plate heat exchanger XGC L205P

Dimensions, mm

The Plate Heat Exchanger has 4 connections as standard and should be installed with min. 1200 mm space on both sides for service work.

Subject to alterations without prior notice.

 

 

M4 M1

 

 

M3 M2

S4

S1

 

 

 

Movable cover, M

S3

S2

Stationary cover,S

DH-SMT/FI

 

©VDDanfoss.EJ.F1.0203/2009© Danfoss 03/2009

Data sheet

Plate heat exchanger XGC L205P

 

 

Dimensions, mm

Standard connection dimension

DN300

Tightening bolt

M39

No. of long tightening bolts (TL)

4

No. of short tightening (TS)

12

Cover thickness

90 mm

Weight of guiding bar

43 kg/m

Weight of tightening bolt

8,1 kg/m

A-dimension

3,8*n mm

C-dimension

LG+170 mm

F-dimension

LG+9 mm

Weight plate+gasket (W) AISI 304/316 0,5 mm

10,3 kg

AISI 304/316 0,6 mm

12,3 kg

Titanium 0,5 mm

6,0 kg

Titanium 0,6 mm

7,1 kg

Weight Frame

4500+n*W kg

 

 

Max No of plates

 

 

LTL

 

 

 

LG

 

 

C

 

 

F

 

 

 

 

35

 

 

500

 

 

1300

 

1470

 

1309

 

 

 

 

76

 

 

750

 

 

1300

 

1470

 

1309

 

 

 

 

105

 

 

1050

 

 

1300

 

1470

 

1309

 

 

 

 

126

 

 

1050

 

 

1600

 

1770

 

1609

 

 

 

 

155

 

 

1350

 

 

1600

 

1770

 

1609

 

 

 

 

176

 

 

1350

 

 

1950

 

2120

 

1959

 

 

 

 

213

 

 

1650

 

 

1950

 

2120

 

1959

 

 

 

 

226

 

 

1650

 

 

2200

 

2370

 

2209

 

 

 

 

255

 

 

1950

 

 

2200

 

2370

 

2209

 

 

 

 

276

 

 

1950

 

 

2500

 

2670

 

2509

 

 

 

 

305

 

 

2250

 

 

2500

 

2670

 

2509

 

 

 

 

326

 

 

2250

 

 

3000

 

3170

 

3009

 

 

 

 

388

 

 

3000

 

 

3000

 

3170

 

3009

 

 

 

 

451

 

 

3000

 

 

3500

 

3670

 

3509

 

 

 

 

471

 

 

3500

 

 

3500

 

3670

 

3509

 

 

 

 

535

 

 

3500

 

 

4000

 

4170

 

4009

 

 

 

 

555

 

 

4000

 

 

4000

 

4170

 

4009

 

 

 

 

LTL = Length of long tightening bolt, based on 6 x n + 290 mm

 

 

 

 

 

 

 

 

 

 

LG = Length of guiding bar, based on 6 x n + 670 mm

 

 

 

 

 

 

 

 

 

 

n = number of plates

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total max no. of plates

 

All data is based on plates with material AISI 304/316 and thickness 0,5 mm.

 

 

 

 

AISI 304/316 0,5 mm

558

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VD.EJ.F1.02

Produced by Danfoss A/S © 03/2009

Loading...