Data sheet
Plate heat exchanger XGC C008PI
Dimensions, mm
The Plate Heat Exchanger has 4 connections as standard and should be installed with min. 300 mm space on both sides for service work.
Subject to alterations without prior notice.
|
|
M4 M1 |
|
|
M3 M2 |
S4 |
S1 |
|
|
|
Movable cover, M |
S3 |
S2 |
Stationary cover,S |
DH-SMT/FI |
VD.EJ.I1.02 © Danfoss 11/2009 |
Data sheet |
Plate heat exchanger XGC C008PI |
|
|
Dimensions, mm
Standard connection dimension |
DN25/32 |
Tightening bolt |
M16 |
No. of long tightening bolts (T) |
8 |
Cover thickness |
15 mm |
Weight of guiding bar |
0,5 kg/m |
Weight of tightening bolt |
0,8 kg/m |
A-dimension |
2,5*n mm |
C-dimension |
LG + 15 |
F-dimension |
A + 130 |
Weight plate+gasket (W) AISI 304/316 0,4 mm |
0,30 kg |
AISI 304/316 0,5 mm |
0,36 kg |
Titanium 0,4 mm |
0,19 kg |
Titanium 0,5 mm |
0,22 kg |
Weight Frame |
30+n*W kg |
|
Max No of plates |
|
|
LT |
|
|
LG |
|
|
C |
|
|
F |
|
15 |
|
|
120 |
|
105 |
|
120 |
|
|
A+130 |
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
32 |
|
|
180 |
|
165 |
|
180 |
|
|
A+130 |
|
|||
75 |
|
|
325 |
|
310 |
|
325 |
|
|
A+130 |
|
|||
126 |
|
|
500 |
|
485 |
|
500 |
|
|
A+130 |
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
LT = Length of tightening bolt, based on 3,4 x n + 70 mm |
|
|
|
|
|
|
|
|||||||
LG = Length of guiding bar, based on 3,4 x n + 15 mm |
|
|
|
|
|
|
|
|||||||
n = number of plates |
|
|
|
|
|
|
|
|
|
|
|
Total max no. of plates
AISI 304/316 0,5 mm |
126 |
All data is based on plates with material AISI 304/316 and thickness 0,4 mm.
VD.EJ.I1.02 |
Produced by Danfoss A/S © 11/2009 |