PLATE HEAT EXCHANGER
GC-8PI
DIMENSIONS, MM
M2
M3
S2
S3
M1
M4
S1
S4
Movable cover, M
Stationary cover,S
The Plate Heat Exchanger has 4 connections as
standard and should be installed with min. 300 mm
space on both sides for service work.
Subject to alterations without prior notice.
Data sheet
Plate heat exchanger XGC C008PI
Dimensions, mm
DH-SMT/FI
VD.EJ.I1.02 © Danfoss 11/2009
PLATE HEAT EXCHANGER
GC-8PI
DIMENSIONS, MM
Standard connection dimension DN25/32
Tightening bolt M16
No. of long tightening bolts (T) 8
Cover thickness 15 mm
Weight of guiding bar 0,5 kg/m
Weight of tightening bolt 0,8 kg/m
A-dimension 2,5*n mm
C-dimension LG + 15
F-dimension A + 130
Weight plate+gasket (W) AISI 304/316 0,4 mm
AISI 304/316 0,5 mm
Titanium 0,4 mm
Titanium 0,5 mm
0,30 kg
0,36 kg
0,19 kg
0,22 kg
Weight Frame 30+n*W kg
Max No of plates LT LG C F
15 120 105 120
A+130
32 180 165 180
A+130
75 325 310 325
A+130
126 500 485 500
A+130
LT = Length of tightening bolt, based on 3,4 x n + 70 mm
LG = Length of guiding bar, based on 3,4 x n + 15 mm
n = number of plates
Total max no. of plates
AISI 304/316 0,5 mm 126
All data is based on plates with material AISI 304/316 and thickness 0,4 mm.
Data sheet
Dimensions, mm
Plate heat exchanger XGC C008PI
VD.E J.I1.02
Produce d by Danfoss A/S © 11/2009