Danfoss WattNode Installation guide

Danfoss WattNode Installation guide

Installation Guide

WattNode

50/60 Hz -30 – 50°C

(-22°F to 131°F)

L × W × H:

155 mm × 85 mm × 38 mm (6.1” × 3.35” × 1.5”)

Mounting holes: Ø5.1mm (0.200”)

CT:

0,333 V A.C. at rated current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Code

Electrical Service Type (Load type)

Line-to-Neutral

Line-to-Line

Meter Powered by

(V A.C.)

(V A.C.)

 

 

 

 

 

 

 

 

 

 

 

Single Phase 2-wire with neutral

96 - 138

n.a.

N and фA

 

 

 

 

 

080Z2144

Single Phase 3-wire with neutral

96 - 138

166 - 276

N and фA

 

 

 

 

 

 

Three Phase 4-wire wye (star) with neutral

96 - 138

166 - 276

N and фA

 

 

 

 

 

080Z2146

Single Phase 2-wire with neutral

184 - 264

n.a.

N and фA

 

 

 

 

 

 

Three Phase 4-wire wye (star) with neutral

184 - 264

320 - 460

N and фA

 

 

 

 

 

 

 

 

Single Phase 2-wire with neutral

Single Phase 3-wire with neutral

Three Phase 4-wire Wye (star) with neutral

 

 

 

Modbus address

 

 

 

 

 

 

 

 

DIP Switch

1

2

3

4

5

6

7

 

 

 

 

 

 

 

 

 

 

 

Up (1) Value

1

2

4

8

16

32

64

 

 

 

 

 

 

 

 

 

 

Address

 

 

 

Examples

 

 

 

 

1

1, Up

0, Down

0, Down

0, Down

0, Down

0, Down

0, Down

 

 

 

 

 

 

 

 

 

 

1+2+4 = 7

1, Up

1, Up

1, Up

0, Down

0, Down

0, Down

0, Down

 

 

 

 

 

 

 

 

 

 

4+16 = 20

0, Down

0, Down

1, Up

0, Down

1, Up

0, Down

0, Down

 

 

 

 

 

 

 

 

 

 

1+2+16+32+64 =115

1, Up

1, Up

0, Down

0, Down

1, Up

1, Up

1, Up

 

 

 

 

 

 

 

 

 

Power on and off the WattNode after setting the Modbus address

© Danfoss | ADAP-KOOL® | 2016.05

RI8RX102 | 1

Modbus integration with the AK-SM 800

Step 1: Set the Modbus address (see above, remember to power-cycle the WattNode) Step 2: Perform a network scan from the AK-SM 800*

*For more information about data communication see document RC8AC and the AK-SM 800 manual. Pay special attention to the AK-SM 800 manual if devices with a different baud rate than 38.400 baud are connected to the AK-SM 800, e.g. the variable speed compressor type SLV.

Phase Status LED

All/

LED Indication

Description

Single

 

 

phase

 

 

 

 

 

All

Red, Yellow,

Power up sequence

 

Green for 3 x 1

 

 

second

 

 

 

 

All

Red / Green

Overvoltage warning.

 

continuous

Line voltage too high.

 

flashing

DISCONNECT power immediately!

 

 

 

All

OFF

WattNode not operating.

 

 

Check that the wiring and voltages

 

 

are correct

 

 

 

All

Red for 3 seconds

WattNode Error.

 

or more

If you see this happen repeatedly,

 

 

replace the meter

 

 

 

Single

Green

No power but line voltage is

 

 

present on this phase

 

 

 

Single

OFF

No voltage on this phase

 

 

 

Single

Red continuous

Negative power on this phase

 

flashing

(Reversed CT’s, swapped CT wires

 

 

or CT not matching line voltage

 

 

phase)

 

 

 

Modbus Com LED

LED Indication

Description

 

 

Green flash

Valid packet for this device

 

 

Yellow flash

Valid packets for different device

 

 

Red for 1 second

Invalid packet (bad baud rate,

 

noise, ...)

 

 

Red / Yellow

Possible address conflict (two

continuous flashing

devices with same address)

 

 

Red

Address set to 0 (zero)

 

 

Precautions

1.1Only qualified personnel or licensed electricians should install the WattNode meter. The mains voltages can be lethal!

1.2Follow all applicable local and national electrical and safety codes.

1.3The terminal block screws are not insulated. Do not contact metal tools to the screw terminals if the circuit is live!

1.4Verify that circuit voltages and currents are within the proper range for the meter model.

1.5Use only UL listed or UL recognized current transformers (CTs) with built-in burden resistors, that generate 0.333 Vac (333 millivolts AC) at rated current. Do not use current output (ratio) CTs such as 1 amp or 5 amp output CTs: they will destroy the meter and may create a shock hazard.

1.6Protect the line voltage conductors to the meter with fuses or circuit breakers (not needed for the neutral or ground wires).

1.7Equipment must be disconnected from the HAZARDOUS LIVE voltages before access.

1.8If the meter is not installed correctly, the safety protections may be impaired.

© Danfoss | ADAP-KOOL® | 2016.05

RI8RX102 | 2

Loading...