Data sheet | Water mist nozzles with anti-drip
Contents
1. Introduction This nozzle has been widely used within the
1. Introduction ............................................................................2
2. Features ................................................................................2
3. Technical data and code numbers .......................................................3
4. Marking on nozzles .....................................................................3
5. Adapters................................................................................3
6. No dripping operation ..................................................................4
7. Cleaning ................................................................................4
8. Filtration................................................................................4
9. Mounting ...............................................................................4
10. Blind plug...............................................................................4
humidication industry for years. It is tailored for
ne water atomization in applications like
comfort humidity control, open space humidication, adiabatic cooling etc.
All nozzles come with a built-in check valve as
standard. In connection with Danfoss’ advanced
3/2-way valve technology an absolutely ”dripping-free” operation of the system can be
achieved.
The nozzle generates billions of very small
droplets at a size of 20 micron (D90-value),
depending on pressure and water quality. The
nozzle has a long life expectance; due to the
stainless steel design the droplet size and
spraying pattern will not rapidly deteriorate.
The stainless steel design allows operating the
nozzle with ordinary tap water as well as any
treated water like deionized, demineralized or
reverse osmosis water.
2. Features • Dripping-free operation can be achieved
• Suitable for ordinary tap water as well as
treated water
• Long service life
• Excellent spray pattern
• Easy to clean
The impeller inside the nozzle is removeable and
can very easily be cleaned if necessary.
AI369353474543en- 000101 | 02.2021
2

Data sheet | Water mist nozzles with anti-drip
3. Technical data and
code nos.
Liter per
hour
Capacity measured at 70 barg / 1000 psig
Variation of capacity of +/- 10% may occur.
Material Body and spring stainless steel (AISI 303), ball and O-ring Viton
Thread Outer thread of 10/24 or 12/24 UNC 2A, depth 4 mm/0.15 inch
Size and weight Ø9,5mm/0.374 inch, Length 20 mm/0.78 inch; 9,0 g/0.32 oz
Liter per
min.
2.7 0.050 0. 013 6.6 0.15/0.06 60° 70/1000 12/ 24 UNC 180Z1939
4.0 0.067 0.018 8.9 0.20/0.008 60° 70/1000 12/24 UNC 180Z19 40
4.9 0.082 0.022 10.8 0.22/0.009 60° 70/1000 12/ 24 UNC 180Z1941
6.8 0.113 0.030 14.9 0.30/0.012 60° 70/1000 12/ 24 UNC 180Z1949
8.5 0.142 0.037 18.7 0.33/0.013 60° 70/1000 12 /24 UN C 180Z194 4
11. 0 0.172 0.045 22.7 0.40/0.016 60° 70/1000 12/ 24 UNC 18 0Z1945
11. 3 0.189 0.050 25.0 0.50/0.020 60° 70/1000 12 /24 UN C 180Z1948
13. 8 0.230 0.061 30.0 0.60/0.023 60° 70/1000 12/ 24 UNC 180Z1950
16.4 0.273 0.072 36.0 0.80/0.031 60° 70/1000 12/24 U NC 180Z1951
US
Gallonen
per min.
(gpm)
US
Pounds
per hour
Orice
(mm/inch)
Spray
angle
Max.
pressure
(barg/psig)
Nozzle
thread
Nozzles and blind plug must be ordered in
multiplum of 10 pieces.
Codenumber
4. Marking on nozzles
5. Adapters
Orice size in mm
Danfoss ordering code
3
2
1,4
Version Connections Material Weight Lenght
1 12/24 UNC 2B (female) to
Ø12 mm / 0.47 inch pipe (male)
2 12/24 UNC 2B (female) to
Ø10 mm / 0.39 inch pipe (male)
3 12/24 UNC 2B (female) to
3⁄8 inch NPT (male)
4 12/24 UNC 2B (female) to
Ø9,525 mm / 3⁄ 8 inch pipe (male)
AISI 303 20 g/0.7 oz. 3 0/1.18 180Z0 022
AISI 303 12 g/0.4 oz. 3 0/1.18 180Z0 023
AISI 303 55 g/1.94 oz. 34/1.34 180Z0029
AISI 303 12 g/0.4 oz. 3 0/1.18 180Z0 047
(mm/inch)
Code-
number
Adapter no. 2 is suitable to be welded on a
stainless steel pipe.
AI369353474543en- 000101 | 02.2021
3

Data sheet | Water mist nozzles with anti-drip
7. No dripping operation
The integrated spring loaded check valve closes
at a pressure of approx. 5 barg / 70 psig preventing water from dripping when the nozzle is shut
down.
To achieve the optimum performance, the
supply line pressure should be relieved rapidly
the moment the nozzle is shut down.
Danfoss 3/2-way valves allow relieving the
pressure instantaneously to atmosphere.
In tap water applications, calcation of the
nozzles can thus be widely avoided.
During operation During shutdown
7. Cleaning For cleaning purposes, the nozzle can very easily
be taken apart and the impeller can be removed.
8. Filtration Generally, good ltration of the water increases
the service-life of the nozzle and reduces the risk
of clogging.
9. Mounting The nozzle is easy to install; it is hand tightened
and comes with an O-ring seal, by means no
other sealing materials like Loclite or Teon tape
are needed for installation.
To prevent particles from entering into the
system and clogging the nozzles the following
procedure must be followed:
10. Blind plug
Blind plug for 12/24 UNC 180Z1938
Codenumber
• Deburr and clean pipes and ttings prior to
installation
• Flush the system with water after assembling
and before the nozzles are mounted.
4
AI369353474543en- 000101 | 02.2021

Data sheet | Water mist nozzles with anti-drip
AI369353474543en- 000101 | 02.2021
5

Danfoss A/S
High Pressure Pumps
Nordborgvej 81
DK-6430 Nordborg
Denmark
© Danfoss | HPP (im) | 2021.02