Danfoss VX Solo II, VX Solo II Series, VX Solo II H2, VX Solo II H, VX Solo II HWS Instructions Manual

...
Instructions
VX Solo II
VX Solo II VX Solo II H VX Solo II H2 VX Solo II HWP VX Solo II HWS
VX Solo II HWS VX Solo II H2WP VX Solo II H2WS VX Solo OP
1.0 Table of contents .......................................................................................................................................................................................................................1
2.0 Safety notes ................................................................................................................................................................................................................................2
3.0 Storage and Handling .............................................................................................................................................................................................................2
4.0 Disposal ........................................................................................................................................................................................................................................2
5.0 Diagrams - examples ...............................................................................................................................................................................................................3
6.0 Main components .................................................................................................................................................................................................................12
6.1 VX Solo II (T°C ) - 1 HE circuit + prim. connection for DHW cylinder ............................................................................................................12
6.2 VX Solo II H (ECL 210/A230.1a) - 1 HE circuit ........................................................................................................................................................ 13
6.3 VX Solo II H2 (ECL 210/A260.1d) -2 HE circuits.....................................................................................................................................................14
6.4 VX Solo II HWP (ECL 210/A237) - 1 HE circuit + prim. connection for DHW cylinder .............................................................................15
6.5 VX Solo II HWS (ECL 210/A237.1a) - 1 HE circuit + sec. connection for DHW cylinder .......................................................................... 16
6.6 VX Solo II HWS (ECL 210/A247.1c) - 1 HE circuit + mixing loop + sec. connection for DHW cylinder ............................................. 17
6.7 VX Solo II H2WP (ECL 210/A260.1d) - 2 HE circuit + prim. connection for DHW cylinder .................................................................... 18
6.8 VX Solo II H2WS (ECL 310/A367.1d) - 2 HE circuits + sec. connection for DHW cylinder .....................................................................19
6.9 VX Solo OP (ECL 210/A237.1a) - 1 HE circuit + sec. connection for DHW cylinder ................................................................................. 20
7.0 Mounting .................................................................................................................................................................................................................................. 21
7.1 Variable connection possibilities ............................................................................................................................................................................. 21
7.2 Tightening of connections ......................................................................................................................................................................................... 21
7.3 Expansion vessel ............................................................................................................................................................................................................ 21
7.4 Heat meter, Fitting pieces ........................................................................................................................................................................................... 22
7.5 Mounting of outdoor temperature sensor ...........................................................................................................................................................22
7.6 Mounting of immersion sensor ................................................................................................................................................................................ 22
8.0 Filling, Start-up ...................................................................................................................................................................................................................... 23
9.0 Manometer and filling ........................................................................................................................................................................................................ 23
10.0 Electrical connections .........................................................................................................................................................................................................23
11.0 Description of VX Solo variants ........................................................................................................................................................................................ 24
11.1 VX Solo II (T°C 200u) .................................................................................................................................................................................................... 24
11.2 VX Solo II H (ECL 210/A230.1a) ................................................................................................................................................................................ 26
11.3 VX Solo II H2 (ECL 210/A260.1d) ............................................................................................................................................................................. 28
11.4 VX Solo II HWP (ECL 210/A237) ............................................................................................................................................................................... 31
11.5 VX Solo II HWS (ECL 210/A237.1a) ......................................................................................................................................................................... 34
11.6 VX Solo II HWS (ECL 210/A247.1c) .........................................................................................................................................................................37
11.7 VX Solo II H2WP (ECL 210/A260.1d) ...................................................................................................................................................................... 40
11.8 VX Solo II H2WS (ECL 310/A367.1d) ......................................................................................................................................................................43
11.9 VX Solo OP (ECL 210/A237.1a) ................................................................................................................................................................................ 46
12.0 Circulation pumps ................................................................................................................................................................................................................ 48
13.0 Maintenance ........................................................................................................................................................................................................................... 50
14.0 Troubleshooting .................................................................................................................................................................................................................... 51
15.0 EC-Declaration of Conformity ..........................................................................................................................................................................................55
Danfoss District Energy VI.GP.P1.02 DKDHR
1
Instructions VX Solo II
2.0 Safety notes
Instructions
This operating manual should be read carefully before installation and start-up of the substation. The manufacturer accepts no liability for damage or faults that result from non-compliance with the operating manual. Please read and follow all the instructions carefully to prevent acci­dents, injury and damage to property. The risk of persons being injured and equipment damaged increases considerably if the recommended permissible operating parameters are exceeded. Installation, assembly work, first start-up and maintenance work may be carried out only by qualified and authorized personnel in compli­ance with the safety regulations (both heating and electrical work).
Connection
The substation must be equipped with features that ensure that the substation can be separated from all energy sources (also power supply).
Warning of hot surfaces
Parts of the substation may become hot and hot surfaces can cause serious burns. Please be extremely cautious in close prox­imi-ty to the substation.
Energy source
The substation is designed for district heating as the primary source of energy. However, also other energy sources can be used where the operating conditions allow it and always are comparable to district heating.
Application
The substation is designed only to operate with water or a water-glycol mixture (up to 40%), and other heating media may not be used. Connect the substation to the house installation in a frost-free room, where the temperature does not exceed 50 °C and the humidity does not exceed 80%. Do not cover or wall up the substation or in any other way block the entrance to the station.
Choice of material
Choice of materials always in compliance with local legislation.
Corrosion protection
The maximum chloride compounds of the flow medium should not be higher than 300 mg/l. The risk of equipment corrosion increases considerably if the recommended permissible chloride compounds are exceeded.
Safety valve(s)
We recommend mounting of safety valve(s), however, always in com­pliance with local regulations.
Sound level.
≤ 55 dB.
Warning of high pressure and high temperature
The stations work at a maximum supply temperature from the district heating network of 110°C and the stations work with a op­erating pressure of 16 bar, which may put the user at risk of burns from touching the surface or from the emissions of hot media (water/steam). The risk of persons being injured and equipment damaged increases considerably if the recommended permissible operating parameters are exceeded.
Emergency
In case of danger or accidents - fire, leaks or other dangerous cir­cumstances - interrupt all energy sources to the station if possible, and seek expert help. In case of discoloured or bad-smelling domestic hot water, close all shut-off valves on the substation, inform the operating person­nel and call for expert help immediately.
Warning of transport damage
Before substation installation, please make sure that the substa­tion has not been damaged during transport. Always transport the substation with the utmost care and caution.
IMPORTANT - Tightening of connections
Due to vibrations during transport all flange connections, screw joints and electrical clamp and screw connections must be check­ed and tightened before water is added to the system. After water has been added to the system and the system has been put into operation, re-tighten ALL connections.
(Do not overstrain! - See item 7.2)
3.0 Storage and Handling
If the substation is stored before installation, make sure that the place is dry and heated. (Humidity max. 80% and storage temperature 5-70 °C).
Do not stack the unit higher than factory shipped. Units that are shipped in cardboard packaging are to be lifted by the carrying handles of the packaging. Transport / removals over great distances should be carried out on pallets. During and after unpacking, the substation can be lifted by using straps, fitted around the pipes or it can be lifted by hand in the pipes Lifting in the pipes can cause leaks. ALWAYS re-tighten.
Handling
When working on the substation suitable safety shoes must be worn.
4.0 Disposal
Dispose of packaging material in accordance with local regulations. This product consists of materials, which must not be disposed of
together with domestic waste. Switch off the complete power sup­ply and dismantle the product and sort the components in various groups before disposal. Always observe the disposal rules of the local legislation.
2
DKDHR VI.GP.P1.02 Danfoss District Energy
Instructions VX Solo II
5.0 Diagrams - examples
5.1 VX Solo II (T°C 200u) - 1 HE ciruit + primary connection pipes for cylinder
DH Supply
DH Return
1 Plate heat exchanger, HE, with insulation 4 Differential pressure controller AVPL 5 Strainer 7 Ball valve 8 Circulation pump HE 11 Safety valve, HE 2.5 bar 13 Thermometer 14 Pocket for pressure gauge 15 Manometer 16 Expansion vessel 17 Air vent 23 Sensor pocket for heat meter ½“ 24 Fitting piece for heat meter, 3/4” x 110 mm 30 Self-acting thermostatic valve T°C 200/VS 2-15
HE Supply
HE Return
Danfoss District Energy VI.GP.P1.02 DKDHR
33
Instructions VX Solo II
5.2 VX Solo II H (ECL 210/A230.1a) - 1 HE circuit
DH Supply
DH Return
1 Plate heat exchanger, HE, with insulation 5 Strainer 7 Ball valve 8 Circulation pump HE 11 Safety valve, HE 13 Thermometer 14 Pocket for pressure gauge 15 Manometer 16 Expansion vessel 23 Sensor pocket for heat meter ½“ 24 Fitting piece for heat meter, 3/4” x 110 mm 25 Controller Danfoss ECL 210/A230.1a 26 Outdoor sensor Danfoss ESMT 27 Sensor Danfoss ESMC 29 Danfoss actuator AMV150 30 Danfoss flow controller with integrated control valve AHQM
HE Supply
HE Return
4
DKDHR VI.GP.P1.02 Danfoss District Energy
Instructions VX Solo II
5.3 VX Solo II H2 (ECL 210/A260.1d) - 2 HE circuits
Supply limit
FH Supply
FH Return
DH Supply
DH Return
1 Plate heat exchanger, HE, with insulation 5 Strainer 6 Non-return valve 7 Ball valve 8 Circulation pump HE 10 Circulation pump FH 11 Safety valve, HE 13 Thermometer 14 Pocket for pressure gauge 15 Manometer 16 Expansion vessel 23 Sensor pocket for heat meter ½“ 24 Fitting piece for heat meter, 3/4” x 110 mm 25 Controller Danfoss ECL 210/A260.1d 26 Outdoor sensor Danfoss ESMT 27 Sensor Danfoss ESMC 29 Danfoss actuator AMV13 30 Danfoss flow controller with integrated control valve AHQM 33 Danfoss actuator AMV150 34 3-way valve VMV 30/15 57 Safety temperature monitor Jumo AT
HE Supply
HE Return
Danfoss District Energy VI.GP.P1.02 DKDHR
55
Instructions VX Solo II
5.4 VX Solo II HWP (ECL 210/A237) - 1 HE circuit + primary connection pipes for DHW cylinder
Supply limit
Cylinder
Cylinder Supply
Cylinder Return
DH Supply
DH Return
1 Plate heat exchanger, HE, with insulation 4 Differential pressure controller with flow limitation AVPB-F 5 Strainer 7 Ball valve 8 Circulation pump HE 11 Safety valve, HE 13 Thermometer 14 Pocket for pressure gauge 15 Manometer 16 Expansion vessel 23 Sensor pocket for heat meter ½“ 24 Fitting piece for heat meter, 3/4” x 110 mm 25 Controller Danfoss ECL 210/A237 26 Outdoor sensor Danfoss ESMT 27 Sensor Danfoss ESMC 29 Danfoss actuator AMV150 30 2-way valve VS2
HE Supply
HE Return
6
DKDHR VI.GP.P1.02 Danfoss District Energy
Instructions VX Solo II
5.5 VX Solo II HWS (ECL 210/A237.1a) - 1 HE circuit + secondary connection pipes for DHW cylinder
Supply limit
Cylinder
Cylinder Supply
Cylinder Return
DH Supply
DH Return
1 Plate heat exchanger, HE, with insulation 5 Strainer 6 Non-return valve 7 Ball valve 8 Circulation pump HE 8A Circulation pump Cylinder 11 Safety valve, HE 13 Thermometer 14 Pocket for pressure gauge 15 Manometer 16 Expansion vessel 23 Sensor pocket for heat meter ½“ 24 Fitting piece for heat meter, 3/4” x 110 mm 25 Controller Danfoss ECL 210/A237.1a 26 Outdoor sensor Danfoss ESMT 27 Sensor Danfoss ESMC 28 Immersion sensor Danfoss ESMB 29 Danfoss actuator AMV13 30 Danfoss flow controller with integrated control valve AHQM
HE Supply
HE Return
Danfoss District Energy VI.GP.P1.02 DKDHR
77
Instructions VX Solo II
5.6 VX Solo II HWS (ECL 210/A247.1c) - 1 HE circuit + mixing loop + secondary connection pipes for DHW cylinder
Supply limit
HE Supply
HE Return
Radiator heating/ Floor heating
Cylinder
DH Supply
DH Return
1 Plate heat exchanger, HE, with insulation 5 Strainer 6 Non-return valve 7 Ball valve 8A Circulation pump HE 10 Circulation pump Cylinder 11 Safety valve, HE 13 Thermometer 14 Pocket for pressure gauge 15 Manometer 16 Expansion vessel 23 Sensor pocket for heat meter ½“ 24 Fitting piece for heat meter, 3/4” x 110 mm 25 Controller Danfoss ECL 210/A247.1c 26 Outdoor sensor Danfoss ESMT 27 Sensor Danfoss ESMC 28 Immersion sensor Danfoss ESMB 29 Danfoss actuator AMV150 30 Danfoss flow controller with integrated control valve AHQM 33 Danfoss actuator AMV150 34 3-way valve VMV 30/15
Cylinder Supply
Cylinder Return
8
DKDHR VI.GP.P1.02 Danfoss District Energy
Instructions VX Solo II
5.7 VX Solo II H2WP (ECL 210/A260.1d) - 2 HE circuit + primary connection pipes for DHW cylinder
Supply limit
Cylinder
Cylinder Supply
Cylinder Return
Supply limit
FH Supply
FH Return
DH Supply
DH Return
1 Plate heat exchanger, HE, with insulation 4 Differential pressure controller with flow limitation AVPB-F 5 Strainer 6 Non-return valve 7 Ball valve 8 Circulation pump HE 10 Circulation pump FH 11 Safety valve, HE 13 Thermometer 14 Pocket for pressure gauge 15 Manometer 16 Expansion vessel 23 Sensor pocket for heat meter ½“ 24 Fitting piece for heat meter, 3/4” x 110 mm 25 Controller Danfoss ECL 210/A260.1d 26 Outdoor sensor Danfoss ESMT 27 Sensor Danfoss ESMC 29 Danfoss actuator AMV13 30 2-way valve VS2 33 Danfoss actuator AMV150 34 3-way valve VMV 30/15 57 Safety temperature monitor Jumo AT
HE Supply
HE Return
Danfoss District Energy VI.GP.P1.02 DKDHR
99
Instructions VX Solo II
5.8 VX Solo II H2WS (ECL 310/A367.1d) - 2 HE circuits + secondary connection pipes for DHW cylinder
DH Supply
DH Return
Supply limit
Cylinder Supply
Cylinder Return
FH Supply
FH Return
Cylinder
HE Supply
HE Return
1 Plate heat exchanger, HE, with insulation 5 Strainer 6 Non-return valve 7 Ball valve 8 Circulation pump HE 8A Circulation pump Cylinder 10 Circulation pump FH 11 Safety valve, HE 13 Thermometer 15 Manometer 16 Expansion vessel 23 Sensor pocket for heat meter ½“ 24 Fitting piece for heat meter, 3/4” x 110 mm 25 Controller Danfoss ECL 310/A367.1d 26 Outdoor sensor Danfoss ESMT 27 Sensor Danfoss ESMC 28 Immersion sensor Danfoss ESMB 29 Danfoss actuator AMV13 30 Danfoss flow controller with integrated control valve AHQM 33 Danfoss actuator AMV150 34 3-way valve VMV 30/15 57 Safety temperature monitor Jumo AT
10
DKDHR VI.GP.P1.02 Danfoss District Energy
Instructions VX Solo II
5.9 VX Solo OP (ECL 210/A237.1a) - 1 HE circuit + secondary connection pipes for DHW cylinder
Cylinder Supply
DH Supply
DH Return
1 Plate heat exchanger, HE, with insulation 5 Strainer 6 Non-return valve 7 Ball valve 11 Safety valve, HE 13 Thermometer 15 Manometer 17 Air valve 23 Sensor pocket for heat meter ½“ 24 Fitting piece for heat meter, 3/4” x 110 mm 25 Controller Danfoss ECL 210/A237.1a 26 Outdoor sensor Danfoss ESMT 27 Sensor Danfoss ESMC 28 Immersion sensor Danfoss ESMB 29 Danfoss actuator AMV10 30 Danfoss flow controller with integrated control valve AVQM
HE Supply
Conn. for expansion vessel
HE Return
Cylinder Return
Danfoss District Energy VI.GP.P1.02 DKDHR
1111
Instructions VX Solo II
6.0 Main components
6.1 VX Solo II (T°C ) - 1 HE circuit + prim. connection for DHW cylinder
1 Plate heat exchanger 4 Differential pressure controller 8 Circulation pump, HE 16 Expansion vessel 17 Air valve 24 Fitting piece for heat meter 30 Thermostat T°C 200
17
1
The substations offer variable connection possibilities, as connection of pipes can be established both in the top or in the bottom of the substation.
Please note:
Your substation may look different than the substation shown, as variants with other components may be supplied. The control func­tion, however, is basically as stated in this instruction manual.
Instructions for the fitted components will be supplied together with the substation.
16
24
8
24
DH supply
DH returnf
Primary Secundary
30
HE return
4
HE supply
Cylinder return
Cylinder supply
Measurements:
Dimensions without cover H860 x W510 x D345 mm
Dimensions with cover H860 x W550 x D380 mm
Connections:
Order: 1 District heating (DH) supply 2 District heating (DH) return 3 Heating (HE) return 4 Heating (HE) supply 5 Cylinder supply 6 Cylinder return
Connection sizes (example: DH: G¾ (ET) HE: G¾ (IT)
top view
12
DKDHR VI.GP.P1.02 Danfoss District Energy
Wall
Instructions VX Solo II
6.2 VX Solo II H (ECL 210/A230.1a) - 1 HE circuit
1 Plate heat exchanger 8 Circulation pump, HE 16 Expansion vessel 24 Fitting piece for heat meter 25 Electronic controller 29 Actuator AMV 13 30 Flow controller with integrated control valve AHQM
1
25
The substations offer variable connection possibilities, as connection of pipes can be established both in the top or in the bottom of the substation.
Please note:
Your substation may look different than the substation shown, as variants with other components may be supplied. The control func­tion, however, is basically as stated in this instruction manual.
Instructions for the fitted components will be supplied together with the substation.
24
16
24
DH supply
DH return
Primary Secundary
29
30
8
HE return
HE supply
Measurements:
Dimensions without cover H860 x W530 x D365 mm
Dimensions with cover H860 x W550 x D380 mm
Connections:
Order: 1 District heating (DH) supply 2 District heating (DH) return 3 Heating (HE) return 4 Heating (HE) supply
Connection sizes (example: DH: G¾ (ET) HE + FH: G¾ (IT)
top view
Danfoss District Energy VI.GP.P1.02 DKDHR
Wall
1313
Instructions VX Solo II
6.3 VX Solo II H2 (ECL 210/A260.1d) -2 HE circuits
1 Plate heat exchanger 8 Circulation pump, HE 10 Circulation pump, FH 16 Expansion vessel 24 Fitting piece for heat meter 25 Electronic controller 29 Actuator AMV 13) 30 Flow controller with integrated control valve AHQM 33 Actuator AMV150 34 3-way valve VMV 30/15 57 Safety temperature monitor
The substations offer variable connection possibilities, as connection of pipes can be established both in the top or in the bottom of the substation.
Please note:
Your substation may look different than the substation shown, as variants with other components may be supplied. The control func­tion, however, is basically as stated in this instruction manual.
57
34
25
33
1
29
30
16
10
8
Instructions for the fitted components will be supplied together with the substation.
Measurements:
Dimensions without cover H860 x W530 x D365 mm
Dimensions with cover H860 x W550 x D380 mm
Connections:
Order: 1 District heating (DH) supply 2 District heating (DH) return 3 Heating (HE) return 4 Heating (HE) supply 5 Floor heating (FH) supply 6 Floor heating (FH) return
24
DH supply
DH return
Primary Secundary
HE return
HE supply
FH supply
FH return
Connection sizes (example: DH: G¾ (ET) HE + FH: G¾ (IT)
top view
14
DKDHR VI.GP.P1.02 Danfoss District Energy
Wall
Instructions VX Solo II
6.4 VX Solo II HWP (ECL 210/A237) - 1 HE circuit + prim. connection for DHW cylinder
1 Plate heat exchanger 4 Differential pressure controller 8 Circulation pump, HE 16 Expansion vessel 24 Fitting piece for heat meter 25 Electronic controller 29 Actuator AMV 150 30 2-way valve VS2
The substations offer variable connection possibilities, as connection of pipes can be established both in the top or in the bottom of the substation.
Please note:
Your substation may look different than the substation shown, as variants with other components may be supplied. The control func­tion, however, is basically as stated in this instruction manual.
Instructions for the fitted components will be supplied together with the substation.
1
25
16
29
30
8
24
4
Measurements:
Dimensions without cover H860 x W530 x D365 mm
Dimensions with cover H860 x W550 x D380 mm
Connections:
Order: 1 District heating (DH) supply 2 District heating (DH) return 3 Heating (HE) return 4 Heating (HE) supply 5 Cylinder (FH) supply 6 Cylinder (FH) return
Connection sizes (example: DH: G¾ (ET) HE + FH: G¾ (IT)
Wall
HE return
HE supply
DH return
DH supply
Primary Secundary
Cylinder return
Cylinder supply
top view
Danfoss District Energy VI.GP.P1.02 DKDHR
1515
Instructions VX Solo II
6.5 VX Solo II HWS (ECL 210/A237.1a) - 1 HE circuit + sec. connection for DHW cylinder
1 Plate heat exchanger 8 Circulation pump, HE 8A Circulation pump, Cylinder 16 Expansion vessel 24 Fitting piece for heat meter 25 Electronic controller 29 Actuator AMV 150 30 Flow controller with integrated control valve AHQM
The substations offer variable connection possi­bilities, as connection of pipes can be established both in the top or in the bottom of the substa­tion.
Please note:
Your substation may look different than the substation shown, as variants with other components may be supplied. The control func­tion, however, is basically as stated in this instruction manual.
Instructions for the fitted components will be supplied together with the substation.
25
1
16
29
30
8A
8
24
Measurements:
Dimensions without cover H860 x W530 x D365 mm
Dimensions with cover H860 x W550 x D380 mm
Connections:
Order: 1 District heating (DH) supply 2 District heating (DH) return 3 Heating (HE) return 4 Heating (HE) supply 5 Cylinder (FH) supply 6 Cylinder (FH) return
Connection sizes (example: DH: G¾ (ET) HE + FH: G¾ (IT)
DHreturn
DH supply
Primary Secundary
Wall
HE return
HE supply
Cylinder return
Cylinder supply
top view
16
DKDHR VI.GP.P1.02 Danfoss District Energy
Instructions VX Solo II
6.6 VX Solo II HWS (ECL 210/A247.1c) - 1 HE circuit + mixing loop + sec. connection for DHW cylinder
1 Plate heat exchanger 8A Circulation pump, Cylinder 10 Circulation pump, HE 16 Expansion vessel 24 Fitting piece for heat meter 25 Electronic controller 29 Actuator AMV 150 30 Flow controller with integrated control valve AHQM 33 Actuator AMV150 34 3-way valve VMV 30/15
The substations offer variable connection possibilities, as connection of pipes can be established both in the top or in the bottom of the substation.
25
1
30
29
34
33
Please note:
Your substation may look different than the substation shown, as variants with other components may be supplied. The control func­tion, however, is basically as stated in this instruction manual.
Instructions for the fitted components will be supplied together with the substation.
Measurements:
Dimensions without cover H860 x W530 x D365 mm
Dimensions with cover H860 x W550 x D380 mm
16
10
24
DH return
DH supply
Cylinder return
Primär Sek undär
HE supply
Cylinder supply
8A
HE return
Connections:
Order: 1 District heating (DH) supply 2 District heating (DH) return 3 Cylinder (FH) return 4 Cylinder (FH) supply 5 Heating (HE) supply 6 Heating (HE) return
Connection sizes (example: DH: G¾ (ET) HE + FH: G¾ (IT)
top view
Danfoss District Energy VI.GP.P1.02 DKDHR
Wall
1717
Instructions VX Solo II
6.7 VX Solo II H2WP (ECL 210/A260.1d) - 2 HE circuit + prim. connection for DHW cylinder
1 Plate heat exchanger 4 Differential pressure controller 8 Circulation pump, HE 10 Circulation pump, FH 16 Expansion vessel 24 Fitting piece for heat meter 25 Electronic controller 29 Actuator AMV 13 30 Flow controller with integrated control valve AHQM 33 Actuator AMV 150 34 3-way valve VMV 30/15 57 Safety temperature monitor
The substations offer variable connection possibilities, as connection of pipes can be established both in the top or in the bottom of the substation.
Please note:
25
1
16
57
34
33
29
30
10
8
Your substation may look different than the substation shown, as variants with other components may be supplied. The control func­tion, however, is basically as stated in this instruction manual.
Instructions for the fitted components will be supplied together with the substation.
Measurements:
Dimensions without cover H860 x W650 x D365 mm
Dimensions with cover H860 x W700 x D380 mm
Connections:
24
DH return
DH supply
Primary Secundary
HE return
4
FH supply
HE supply
FH return
Cylinder return
Cylinder supply
SecundaryPrimary
Order: 1 District heating (DH) supply 2 District heating (DH) return 3 Heating (HE) return 4 Heating (HE) supply 5 Floor heating (FH) supply 6 Floor heating (FH) return 7 Cylinder supply 8 Cylinder return
Connection sizes:
DH + Cylinder: G¾ (ET) HE + FH: G¾ (IT)
top view
18
DKDHR VI.GP.P1.02 Danfoss District Energy
Wall
Instructions VX Solo II
6.8 VX Solo II H2WS (ECL 310/A367.1d) - 2 HE circuits + sec. connection for DHW cylinder
1 Plate heat exchanger 8 Circulation pump, HE 8A Circulation pump, Cylinder 10 Circulation pump, FH 16 Expansion vessel 24 Fitting piece for heat meter 25 Electronic controller 29 Actuator AMV 13 30 Flow controller with integrated control valve AHQM 33 Actuator AMV 150 34 3-way valve VMV 30/15 57 Safety temperature monitor
The substations offer variable connection possibilities, as connection of pipes can be established both in the top or in the bottom of the substation.
Please note:
25
1
16
57
34
29
33
30
8
8A
10
Your substation may look different than the substation shown, as variants with other components may be supplied. The control func­tion, however, is basically as stated in this instruction manual.
Instructions for the fitted components will be supplied together with the substation.
Measurements:
Dimensions without cover H860 x W650 x D365 mm
Dimensions with cover H860 x W700 x D380 mm
Connections:
Order: 1 District heating (DH) supply 2 District heating (DH) return 3 Heating (HE) return 4 Heating (HE) supply 5 Floor heating (FH) supply 6 Floor heating (FH) return 7 Cylinder supply 8 Cylinder return
24
DH supply
Primary
DH return
HE return
HE supply
Wall
FH supply
Secundary
FH return
Cylinder return
Cylinder supply
Connection sizes:
DH + Cylinder: G¾ (ET) HE + FH: G¾ (IT)
top view
Danfoss District Energy VI.GP.P1.02 DKDHR
1919
Instructions VX Solo II
6.9 VX Solo OP (ECL 210/A237)
1 Plate heat exchanger 25 Electronic controller 29 Actuator AMV 10 30 Flow controller with integrated control valve AVQM
Please note:
Your substation may look different than the substation shown, as variants with other components may be supplied. The control func­tion, however, is basically as stated in this instruction manual.
Instructions for the fitted components will be supplied together with the substation.
DH return
DH supply
Above photo shows VX Solo OP variant for heating only.
HE supply
HE return
1
25
29
30
DH return
DH supply
Cylinder supply
Primary Secundary
HE supply
He return
Cylinder return
Measurements:
Dimensions without cover H640 x W440 x D250 mm
Dimensions with cover H640 x W500 x D380 mm
Connections:
Order: 1 District heating (DH) supply 2 District heating (DH) return 3 Cylinder supply 4 Heating (HE) supply 5 Cylinder return 6 Heating (HE) return
Connection sizes (example: DH: G¾ (ET) HE + Cylinder: G¾ (IT)
Wall
top view
20
DKDHR VI.GP.P1.02 Danfoss District Energy
Instructions VX Solo II
7.0 Mounting
Necessary assembly, start-up and maintenance work must be per­formed by qualified and authorized personnel only, and always in compliance with local regulations and this instruction manual. The substation must be easily accessible, enabling maintenance work without undue discomfort. The substation is intended for wall mounting and the mounting sheet on the back of the substation has got holes for screw instal­lation. Lift the substation in the back plate and fix it to a solid wall, which has the necessary load-bearing capacity, in a workmanlike manner with two strong bolts, screws or expansion plugs. All pipes and connections must be cleaned and rinsed before start­up. After that the strainers should be cleaned. A label for each of the different connections is placed on the substa­tion. Connect the substation to the household piping according to these symbols as well as the instructions in this manual.
7.1 Variable connection possibilities
The substations offer variable connection possibilities (not VX Solo II HWS OP), as connection of pipes can be established in the top or in the bottom of the substation. Upon delivery the substation is prepared for connection in bottom of the substation. For change of connection from bottom to top, demount plugs on connection pipes in top of substation and ball valves on connection pipes in bottom of substation, and mount plugs in connection pipes in bottom of substation and ball valves on connection pipes in top of substation. Please note that the air screw, which originally is mounted on the heating supply pipe in top of substation must be relocated to the highest point of the substation.PLEASE NOTE that the variable con- nection possibilities makes it possible to establish some of the con­nections in the top and others in the bottom of the substation. This may be desirable in some cases.
7.2 Tightening of connections
Check and tighten all connections before adding water to the system, as vibrations during transport may have caused leaks. After having added water to the system, tighten all the connections before performing leak test. If the substation operates in accordance with the dimensioning basis, re-tighten the connections and take the substation into continuous use. Please note that the connections may be supplied with EPDM rub­ber gaskets - in general connection sizes from ¾” to and incl. 1½” for Kompakt H stations. Therefore take care not to overstrain the union nuts, as this may result in leaks. The manufacturer accepts no liability for leaks that result from overstrain of union nuts.
7.3 Expansion vessel
The VX Solo II substations are equipped with an expansion vessel, which is factory set to 0,5 bar.
Please note that for type HWS OP the expansion vessel is not part of the delivery.
Danfoss District Energy VI.GP.P1.02 DKDHR
2121
Instructions VX Solo II
7.4 Heat meter, Fitting pieces
The substation is equipped with fitting pieces for heat meter in district heating return.
Assembly of heat meters
- Loosen nuts from fitting piece. Remove fitting piece and replace with heat meter.
- do not forget gaskets.
- After mounting of heat meter remember to check and tighten all threaded connections.
7.5 Mounting of outdoor temperature sensor
The outdoor temperature sensor is delivered separately and must be mounted on site according to the enclosed illustrations.
The outdoor sensor is always to be mounted on the coldest side of the property (normally the north side of the property). The sensor must not be exposed to the morning sun, and should not be mounted above windows, doors, air vents or other heat sources, and not under balconies and roof eaves.
Mounting height approx. 2.5 m above ground.
Temperature range: -50 to 50° C
Electrical connections
Two wire non polarized (can be crossed) Sensor cable: 2 x 0.4 - 1.5 mm²
Connect the cable ends to ECL controller in clamps 29 and 30.
7.6 Mounting of immersion sensor
The immersion sensor for accurate temperature measurement and control in the cylinder is supplied separately and must be mounted and connected to the controller on site.
Temperature range immersion sensor: 0 to 100 °C Temperature range immersion pocket: 0 to 180 °C
2-wire cable (2 x 0.34 mm²) spliced is preassembled in the control­ler.
1) Mount sensor pocket (separately delivered) in top or bottom of cylinder.
2) Lay immersion sensor and cable from substation to cylinder and mount immersion sensor in immersion pocket.
In case the length of the sensor cable is not long enough for your property, it is recommendable to change the whole cable. The mini­mum area for the cable is 0,4 mm² and max. length is 125 m.
For electrical connections please refer to enclosed Danfoss instruc­tions for the ECL controller.
22
DKDHR VI.GP.P1.02 Danfoss District Energy
Instructions VX Solo II
8.0 Filling, Start-up
Check and tighten all connections before adding water to the system, as vibrations during transport may have caused leaks.
After having added water to the system, tighten all the connections before performing leak test. Then heat up the system and tighten the connections once again.
Before adding water to the system and first start-up, check if:
- pipes are connected according to the circuit diagram,
- expansion vessel, if any, is connected,
- heat meter is mounted,
- shut-off valves are closed,
- threaded and flanged connections are tightened.
Adding water to the system:
1. Pump must be switched off when water is added to the system.
2. Fill heat exchanger and system with water until the manometer shows a working pressure, which corresponds to the system height + 5 m (approx. 1.5 - 2.0 bar)
3. Deaerate the system completely.
4. Start the pump.
9.0 Manometer and filling
If the pressure drops below 1 bar, water must be added to the system. The operating pressure should never exceed 2.5 bar. (The safety valves open at 3 bar)
If system pressure drops dramatically within a short time, heating system should be examined for leakage, - this includes checking the factory set pressure of the expansion vessel.
Note; Filling of water to the heating system must be done outside the substation.
10.0 Electrical connections
The station is wired and tested in the factory. Electrical connections between the controller, pump (s), sensor and actuator (s) are made.
The electrical connection of the substation must be performed by a qualified and authorised electrician in compliance with all applicable rules and regulations.
The station should be connected to a 230 V AC power supply.
Connection of power supply must be established in accordance with current regulations and local standards.
The station must be wired and connected to an external main switch so that it can be turned off during maintenance, cleaning or repair work.
Controller ECL 210/310
Supply voltage: 230 V a.c. - 50 Hz Voltage range: 207 bis 244 V a.c. (IEC 60038) Power consumption 5 VA Load on relay outputs: 4(2) A - 230 V a.c Load on triac outputs: 0,2 A - 230 V a.c.
Actuator AMV10 / AMV13 / AMV 150
Supply voltage: 230 V a.c. - 50 Hz Power consumption: 2 / 7 VA For further information please refer to the enclosed instructions.
Pump(s) (Alpha2 L)
Supply voltage: 230 V a.c. - 50 Hz Protection class: IP42 Power consumption: Max. 25 Watt (UPS pump max. 45 Watt)
For further information please refer to the enclosed installation and operating instructions for the pump(s).
Danfoss District Energy VI.GP.P1.02 DKDHR
2323
Instructions VX Solo II (T°C 200u)
7369316-0 SIBC VI.CB.T1.6K © Danfoss 05/03 1
Instructions
AVPL 1.0/1.6
1 5
3 4 7
r kPa
20 25 19 24 18 23 17 22 16 21 15 20 14 19 13 18 12 17 11 16 10 15 9 14 8 13 7 12 6 11 5 10 4 9 3 8 2 7 1 6 0 5
2 6
11.0 Description of VX Solo variants
11.1 VX Solo II (T°C 200u)
Substation for indirect heating for single-family, semi-detatched and terraced houses as well as flats. With one heating circuit for radiator or floor heating. For wall-mounting.
The temperature for the heating circuit is controlled by a self-acting thermostatic valve T°C 200u.
Please note: Your substation may look different than the substation shown, as variants with other components may be supplied. Instructions for the fitted components will always be supplied to­gether with the substation.
Differential pressure controller
(Standard on systems with self-acting thermostatic valve). The differential pressure controller reduces the fluctuating pressure in the district heating network to a small and invariable operating pressure in the substation. The required room temperature is controlled on your radiator ther­mostats.
Differential pressure controller AVPL
AVPL is a self-acting differential pressure controller for PN 16 with adjustable differential pressure setting and the differential pressure controller can be set at any differential pressure between 5 kPa and 25 kPa (0.05 bar and 0.25 bar). The preset factory setting of the controller is 10 kPa (0.1 bar). The differential pressure can be set by means of an Allen key NV 3. 1 turn corresponds with 1 kPa (0.01 bar). The controller settings can be changed in accordance with the en­closed producer instructions:
Differential pressure controller (PN 16) AVPL Return mounting, adjustable setting
Alternative differential pressure controller TD200
Alternatively a diffferential pressure controller type TD200 can be mounted in the substation. This type of differential pressure controller is preset from factory and should not be adjusted afterwards.
AVPL
24
DKDHR VI.GP.P1.02 Danfoss District Energy
Instructions VX Solo II (T°C 200u)
Control of heating circuit
The temperature for the heating circuit is controlled by a thermo­static valve T°C 200. Approximate thermostat scale setting: Pos. 1 = 20°C 2 = 30°C 3 = 40°C 4 = 50°C 5 = 60°C 6 = 70°C
Please note that the values are intended as a guide and may vary according to the district heating operating conditions. Approximate supply temperatures at: 10 °C outdoor temperature approx. 40°C 0 °C outdoor temperature approx. 55°C
-10 °C outdoor temperature approx. 65°C
It is important to keep the supply temperature to the radiators as low as possible (the temperature is indicated by thermometer mounted in HE return). The room temperature is controlled by radiator ther­mostats.
Floor heating (substation with heat exchanger for floor heating) It is important to keep the supply temperature to the floor heating system as low as possible, approx. 30-35° (the temperature is indi­cated by thermometer mounted in HE return),
The T°C is typically set in pos. 2-2.5 (intended as a guide). The supply temperature should not exceed 40°C (ALWAYS refer to the instruc­tions of the floor supplier).
Circulation pump, heating circuit
See chapter 12 on page 49 for more information about circulation pump.
Danfoss District Energy VI.GP.P1.02 DKDHR
2525
Instruction VX Solo II H (ECL 210/A230)
11.2 VX Solo II H (ECL 210/A230.1a)
Substation for indirect heating for single-family, semi-detatched and terraced houses as well as flats. With one heating circuit for radiator or floor heating. For wall-mounting.
The temperature for the heating circuit is controlled by a Danfoss ECL 210 controller in combination with an electronic actuator. The ECL controller acts as the brain of the heating system. It lets you easily control and optimise system performance and operation.
Please note: Your substation may look different than the substation shown, as variants with other components may be supplied. Instructions for the fitted components will always be supplied to­gether with the substation.
Heating circuit
The temperature for the heating circuit is controlled electronically by the Danfoss ECL controller. The supply temperature ist calculated by the controller on basis of the outdoor temperature. The ECL Comfort 210 controller is loaded with a selected application by means of an ECL Application Key (Plug-&-Play). The Application Key contains information about application, languages and factory settings. From factory the VX Solo II H is loaded with Application 1a. Other applications can, however, be loaded by means of the ECL Application Key, and it is possible to update the controller with new application software.
The controller is factory preset to turn off the heating automatically in the summer period.
The controller settings can be changed in accordance with the en­closed producer instructions for the mounted controller.
See ECL Application Key Box with ECL Comfort 210/310 user guide and mounting guide, for further information.
We also refer to Danfoss Installation Guide für ECL Comfort 210, application A230, which can be found on www.heating.danfoss.com
26
DKDHR VI.GP.P1.02 Danfoss District Energy
Instructions VX Solo II H (ECL 210/A230)
Instructions AVQM, AVQMT – PN 16, 25 / DN 15-50
DN 15-32 DN 15-50 DN 32-50 DN 15-50 DN 32-50 DN 15-50 DN 32-50  ∆p = 0.2 p = 0.2 p = 0.2 p = 0.2 p = 0.2 p = 0.2 p = 0.2
AVQM (PN 16) AVQM (PN 25) AVQMT (PN 25) AVQMT/AVT (PN 25)
ENGLISH
Flow (and temperature) controller with integrated control valve AVQM, AVQMT
www.danfoss.com Page 7
DANSK
Flow- (og temperatur-)regulator med indbygget motorventil AVQM, AVQMT
www.danfoss.dk Side 9
DEUTSCH
Volumenstrom (und Temperatur-) Regler mit Motorstellventil AVQM, AVQMT
www.danfoss.de Seite 11
ESPAÑOL
Regulador de caudal (y temperatura) con válvula de control integrada AVQM, AVQMT
www.danfoss.es Página 13
SLOVENŠČINA
Regulator pretoka (in temperature) z regulacijskim ventilom AVQM, AVQMT
www.danfoss.si Stran 15
POLSKI
Regulator przepływu (i temperatury) z zaworem regulacyjnym AVQM, AVQMT
www.danfoss.pl Strona 17
MAGYAR
Térfogatáram(és hőmérséklet) szabályozó, motoros szabályozó-szeleppel egybeépítve AVQM, AVQMT
www.danfoss.hu Oldal 19
SRPSKI
Uputstvo AVQM, AVQMT-PN 16, 25/DN 15-50 grejanje.danfoss.com Strana 21
Instructions AMV 150
ENGLISH
Actuators for three point control AMV 150 www.danfoss.com Page 2
DANSK
Motorer til 3-punkts styring AMV 150 www.danfoss.dk Side 3
DEUTSCH
Stellantriebe für 3-Pkt.- Eingangssignal AMV 150 www.danfoss.de Seite 3
SVENSKA
Motor för 3-punktsreglering AMV 150 varme.danfoss.se Sida 4
NEDERLANDS
Servomotor met 3-puntssturing AMV 150 www.danfoss.nl Pagina 4
LIETUVIŲ K.
Pavaros trijų padėčių valdymui AMV 150 www.danfoss.lt 5 puslapis
LATVISKI
Motori trīs punktu kontrolei AMV 150 www.danfoss.com Lpp. 5
MAGYAR
Szelepmozgatók hárompontos szabályozáshoz AMV 150 www.danfoss.com 6. oldal
ČESKY
Servopohony s tříbodovým regulačním signálem AMV 150 w ww.danfoss.cz Strana 6
POLSKI
Siłowniki sterowane sygnałem 3-punktowym AMV 150 www.danfoss.pl Strona 7
РУССКИЙ
Электроприводы для трехпозиционного регулирования AMV 150
www.danfoss.ru Страница 7
AMV 150 + AMV 150 + AMV 150 + VS2 (DN 15) VMV AVQM (DN 15)
Control of heating circuit
For controlling the heating circuit the VX Solo II H is supplied with a self-acting flow controller with integrated control valve Danfoss AHQM and an electrical actuator AMV 150, which in combination with the ECL controller controls the heating circuit. The controller closes when set max. flow is exceeded. The flow-controller is equipped with excess pressure safety valve, which protects the actuator from too high differential pressure.
The electrical actuator has undergone a functional test from factory. In case of operating disturbances the actuator can be closed manu­ally turning the manual override knob on top of actuator counter­clockwise.
Please see enclosed instructions, Electrical actuator AMV 150 Flow-controller with integrated control valve AHQM
Manual override (AMV 150)
Circulation pump, heating circuit
See chapter 12 on page 48 for more information about circulation pump
AHQM
Press and hold the button (on the bottom side of the actuator) during manual override.
Danfoss District Energy VI.GP.P1.02 DKDHR
2727
Instructions VX Solo II H2 (ECL 210/A260)
11.3 VX Solo II H2 (ECL 210/A260.1d)
Substation for indirect heating for single-family, semi-detatched and terraced houses as well as flats. With two heating circuits for radiator and floor heating. For wall-mounting.
The temperature for the heating circuit is controlled by a Danfoss ECL 210 controller in combination with an electronic actuator. The ECL controller acts as the brain of the heating system. It lets you easily control and optimise system performance and operation.
Please note: Your substation may look different than the substation shown, as variants with other components may be supplied. Instructions for the fitted components will always be supplied to­gether with the substation.
Heating circuit
The temperature for the heating circuit is controlled electronically by the Danfoss ECL controller. The supply temperature ist calculated by the controller on basis of the outdoor temperature. The ECL Comfort 210 controller is loaded with a selected application by means of an ECL Application Key (Plug-&-Play). The Application Key contains information about application, languages and factory settings. From factory the VX Solo II H2 is loaded with Application 1d. Other applications can, however, be loaded by means of the ECL Application Key, and it is possible to update the controller with new application software.
The controller is factory preset to turn off the heating automatically in the summer period.
The controller settings can be changed in accordance with the en­closed producer instructions for the mounted controller.
See ECL Application Key Box with ECL Comfort 210/310 user guide and mounting guide, for further information.
We also refer to Danfoss Installation Guide für ECL Comfort 210, application A260, which can be found on www.heating.danfoss.com
28
DKDHR VI.GP.P1.02 Danfoss District Energy
Instructions VX Solo II H2 (ECL 210/A260)
Instructions AVQM, AVQMT – PN 16, 25 / DN 15-50
DN 15-32 DN 15-50 DN 32-50 DN 15-50 DN 32-50 DN 15-50 DN 32-50  ∆p = 0.2 p = 0.2 p = 0.2 p = 0.2 p = 0.2 p = 0.2 p = 0.2
AVQM (PN 16) AVQM (PN 25) AVQMT (PN 25) AVQMT/AVT (PN 25)
ENGLISH
Flow (and temperature) controller with integrated control valve AVQM, AVQMT
www.danfoss.com Page 7
DANSK
Flow- (og temperatur-)regulator med indbygget motorventil AVQM, AVQMT
www.danfoss.dk Side 9
DEUTSCH
Volumenstrom (und Temperatur-) Regler mit Motorstellventil AVQM, AVQMT
www.danfoss.de Seite 11
ESPAÑOL
Regulador de caudal (y temperatura) con válvula de control integrada AVQM, AVQMT
www.danfoss.es Página 13
SLOVENŠČINA
Regulator pretoka (in temperature) z regulacijskim ventilom AVQM, AVQMT
www.danfoss.si Stran 15
POLSKI
Regulator przepływu (i temperatury) z zaworem regulacyjnym AVQM, AVQMT
www.danfoss.pl Strona 17
MAGYAR
Térfogatáram(és hőmérséklet) szabályozó, motoros szabályozó-szeleppel egybeépítve AVQM, AVQMT
www.danfoss.hu Oldal 19
SRPSKI
Uputstvo AVQM, AVQMT-PN 16, 25/DN 15-50 grejanje.danfoss.com Strana 21
'+6076, (,+  'DQIRVV
,QVWUXFWLRQV
$09
5
5
$099096 $09$940 $099%
1
1
7369311-0 VI.52.D3.003-2005
INSTRUCTIONS
VMV
065R9179
065R9179
NC (normally closed) RAVK (only VMV DN 15, 20) ABV - NC
NO (normally open) ABV - NO
NC (normally closed) RAVK (only VMV DN 15, 20) RAVI (only VMV DN 15, 20) ABV - NC
NO (normally open) ABV - NO
Instructions AMV 150
ENGLISH
Actuators for three point control AMV 150 www.danfoss.com Page 2
DANSK
Motorer til 3-punkts styring AMV 150 www.danfoss.d k Side 3
DEUTSCH
Stellantriebe für 3-Pkt.- Eingangssignal AMV 150 www.danfoss.de Seite 3
SVENSKA
Motor för 3-punktsreglering AMV 150 varme.danfoss.se Sida 4
NEDERLANDS
Servomotor met 3-puntssturing AMV 150 www.danfoss.nl Pagina 4
LIETUVIŲ K.
Pavaros trijų padėčių valdymui AMV 150 www.danfoss.lt 5 puslapis
LATVISKI
Motori trīs punktu kontrolei AMV 150 www.danfoss.com Lpp. 5
MAGYAR
Szelepmozgatók hárompontos szabályozáshoz AMV 150 www.danfoss.com 6. oldal
ČESKY
Servopohony s tříbodovým regulačním signálem AMV 150 w ww.danfoss.cz Strana 6
POLSKI
Siłowniki sterowane sygnałem 3-punktowym AMV 150 www.danfoss.pl Strona 7
РУССКИЙ
Электроприводы для трехпозиционного регулирования AMV 150
www.danfoss.ru Страница 7
AMV 150 + AMV 150 + AMV 150 + VS2 (DN 15) VMV AVQM (DN 15)
Control of heating circuit
For controlling the heating circuit the VX Solo II H2 is supplied with a self-acting flow controller with integrated control valve Danfoss AHQM and an electrical actuator AMV 13, which in combination with the ECL controller controls the heating circuit. The controller closes when set max. flow is exceeded.
The flow-controller is equipped with excess pressure safety valve, which protects the actuator from too high differential pressure.
The electrical actuator has undergone a functional test from factory.
Please see enclosed instructions, Electrical actuator AMV 13 Flow-controller with integrated control valve AHQM
AMV 13 AHQM
Circulation pump
See chapter 12 on page 48 for more information about circulation pump.
Control of floor heating circuit
For controlling the floor heating circuit the VX Solo II H2 is supplied with a 3-way valve VMV and an electrical actuator AMV 150, which in combination with the ECL controller controls the floor heating circuit.
The electrical actuator has undergone a functional test from factory. In case of operating disturbances the actuator can be closed manu­ally turning the manual override knob on top of actuator counter­clockwise.
Please see enclosed instructions, Electrical actuator AMV 150 3-way seated mixing valve VMV
Manual override (AMV)
VMV
Press and hold the button (on the bottom side of the actuator) during manual override.
Danfoss District Energy VI.GP.P1.02 DKDHR
2929
Instructions VX Solo II H2 (ECL 210/260)
Safety temperature monitor
The floor heating circuit can be supplied with a safety thermostat for protection against overheating.
Please see enclosed operating instructions Jumo AT
30
DKDHR VI.GP.P1.02 Danfoss District Energy
Instructions VX Solo II HWP (ECL 210/237)
11.4 VX Solo II HWP (ECL 210/A237)
Substation for indirect heating for single-family, semi-detatched and terraced houses as well as flats. With one heating circuit for radiator or floor heating and with connection pipes for domestic hot water cylinder on the primary side. For wall-mounting.
The temperature for the heating circuit is controlled by a Danfoss ECL 210 controller in combination with an electronic actuator. The ECL controller acts as the brain of the heating system. It lets you easily control and optimise system performance and operation.
Please note: Your substation may look different than the substation shown, as variants with other components may be supplied. Instructions for the fitted components will always be supplied to­gether with the substation.
Heating circuit
The temperature for the heating circuit is controlled electronically by the Danfoss ECL controller. The supply temperature ist calculated by the controller on basis of the outdoor temperature. The ECL Comfort 210 controller is loaded with a selected application by means of an ECL Application Key (Plug-&-Play). The Application Key contains information about application, languages and factory settings. Various applications can be loaded by means of the ECL Application Key, and it is possible to update the controller with new application software.
The controller is factory preset to turn off the heating automatically in the summer period.
The controller settings can be changed in accordance with the en­closed producer instructions for the mounted controller.
See ECL Application Key Box with ECL Comfort 210/310 user guide and mounting guide, for further information.
We also refer to Danfoss Installation Guide für ECL Comfort 210, application A230, which can be found on www.heating.danfoss.com
Danfoss District Energy VI.GP.P1.02 DKDHR
3131
Instructions VX Solo II HWP (ECL 210/237)
INSTRUCTIONS
VS2 2-way
065R9075
065R9075
DN L (mm)
15 65
20 70
25 75
DN L1(mm)
15 131
20 142
25 159
DN L2(mm)
15 139
20 154
25 159
DN L3(mm)
15 69
20 74
25 79
Instructions AMV 150
ENGLISH
Actuators for three point control AMV 150 www.danfoss.com Page 2
DANSK
Motorer til 3-punkts styring AMV 150 www.danfoss.d k Side 3
DEUTSCH
Stellantriebe für 3-Pkt.- Eingangssignal AMV 150 www.danfoss.de Seite 3
SVENSKA
Motor för 3-punktsreglering AMV 150 varme.danfoss.se Sida 4
NEDERLANDS
Servomotor met 3-puntssturing AMV 150 www.danfoss.nl Pagina 4
LIETUVIŲ K.
Pavaros trijų padėčių valdymui AMV 150 www.danfoss.lt 5 puslapis
LATVISKI
Motori trīs punktu kontrolei AMV 150 www.danfoss.com Lpp. 5
MAGYAR
Szelepmozgatók hárompontos szabályozáshoz AMV 150 www.danfoss.com 6. oldal
ČESKY
Servopohony s tříbodovým regulačním signálem AMV 150 w ww.danfoss.cz Strana 6
POLSKI
Siłowniki sterowane sygnałem 3-punktowym AMV 150 www.danfoss.pl Strona 7
РУССКИЙ
Электроприводы для трехпозиционного регулирования AMV 150
www.danfoss.ru Страница 7
AMV 150 + AMV 150 + AMV 150 + VS2 (DN 15) VMV AVQM (DN 15)
Instructions
AVPB, AVPB-F, AVPBT, AVPBT-F – PN 16,25/DN 15 – 50
ENGLISH
ESPAÑOL
DEUTSCH
DANSK
NEDERLANDS
SLOVENŠČINA
POLSKI
ČESKY
MAGYAR
РУССКИЙ
73695220 DH-SMT/SICO 02 / 2006 VI.DB.O1.8H 1
Page 2
www.danfoss.com
Side 2
www.danfoss.dk
Seite 2
www.danfoss.de
Page 2
www.danfoss.es
Blz. 2
www.danfoss.com
Stran 20
www.danfoss.com
20. oldal
www.danfoss.hu
Strana 20
www.danfoss.com
Strona 20
www.danfoss.pl
Стр. 20
www.danfoss.com
Differential pressure controller with flow limitation AVPB, AVPB-F, AVPBT, AVPBT-F
Differenstrykregulator med flowbegrænsning AVPB, AVPB-F, AVPBT, AVPBT-F
Differenzdruck-- (und Temperatur-) Regler mit Durchflussbegrenzung AVPB, AVPB-F, AVPBT, AVPBT-
F
Regulador de presión diferencial con limitación de caudal AVPB, AVPB-F, AVPBT, AVPBT-F
Drukverschil- (en temperatuur-) regelaar met debietbegrenzing AVPB, AVPB-F, AVPBT, AVPBT-F
Regulator diferenčnega tlaka in omejevalnik pretoka AVPB, AVPB-F, AVPBT, AVPBT-F
Nyomáskülönbség-szabályozó és térfogatáram korlátozó AVPB, AVPB-F, AVPBT, AVPBT-F
Regulátor diferenčního tlaku s omezovačem průtoku AVPB, AVPB-F, AVPBT, AVPBT-F
Regulator różnicy ciśnień z ograniczeniem przepływu AVPB, AVPB-F, AVPBT, AVPBT-F
Регулятор перепада давлений с ручным ограничением расхода AVPB, AVPB-F, AVPBT, AVPBT-F
AVPB AVPB-F AVPB AVPB-F AVPB AVPB-F
(PN 16) (PN 16) (PN25) (PN25) (PN25) (PN25)
AVPBT-F AVT/AVPBT-F AVPBT AVT/AVPBT
(PN25) (PN25) (PN25) (PN25)
DN 15 - 32 DN 15 - 32 DN 15 - 50 DN 15 - 50 DN 32 - 50 DN 32 - 50 p = 0.05 - 0.5p = 0.2p = 0.2 - 1.0 p = 0.5 p = 0.2 - 1.0 p = 0.5 p = 0.2 - 1.0 p = 0.3 p = 0.3 - 2.0 p = 0.3 - 2.0 p = 0.8 - 1.6 p = 0.5
DN 15 - 25 DN 32 - 50 DN 15 - 25 DN 32 - 50 DN 15 - 25 DN 32 - 50 DN 15 - 25 DN 32 - 50
p = 0.5 p = 0.5 p = 0.5 p = 0.5 p = 0.2 - 1.0 p = 0.2 - 1.0 p = 0.2 - 1.0 p = 0.2 - 1.0
Control of heating circuit
For controlling the heating circuit the VX Solo II HWP (ECL 210), AVPB-F is supplied with a 2-way valve VS 2 and an electrical actuator AMV 150, which in combination with the ECL controller controls the heat­ing circuit.
The electrical actuator has undergone a functional test from factory. In case of operating disturbances the actuator can be closed manu­ally turning the manual override knob on top of actuator counter­clockwise.
Please see enclosed instructions, Electrical actuator AMV 150 2-way valve VS 2
Manual override (AMV)
Differential pressure controller
The self-acting differential pressure controller AVPB-F with flow limitation reduces the fluctuating pressure in the district heating network to a small and invariable operating pressure in the substa­tion and thereby ensures the best possible operating conditions.
The control valve opens on falling differential pressure to maintain constant differential pressure, and closes on rising differential pres­sure or when set max. flow is exceeded.
The differential pressure controller is preset from factory and should not be adjusted afterwards.
The controller has a control valve with adjustable flow restrictor and flow setting is being done by the adjustment of the flow restrictor position.
The controller is equipped with excess pressure safety valve, which protects the actuator from too high differential pressure.
Please see enclosed instructions, AVPB-F
VS 2
Press and hold the button (on the bottom side of the actuator) during manual override.
32
DKDHR VI.GP.P1.02 Danfoss District Energy
Flow setting
Flow setting is being done by the adjust­ment of the flow restrictor position.
Instructions VX Solo II HWP (ECL 210/237)
Circulation pump, heating circuit
See chapter 12 on page 48 for more information about circulation pump.
Domestic hot water
The VX Solo II HWP (ECL 210/230) substations are supplied with con­nection pipes for domestic hot water cylinder on the primary side. (Please note that cylinder control is not included in delivery).
Danfoss District Energy VI.GP.P1.02 DKDHR
3333
Instructions VX Solo II HWS (ECL 210/A237)
11.5 VX Solo II HWS (ECL 210/A237.1a)
Substation for indirect heating for single-family, semi-detatched and terraced houses as well as flats. With one heating circuit for radiator or floor heating and with connection pipes for cylinder on the secondary side. For wall-mounting.
The temperature for the heating circuit is controlled by a Danfoss ECL 210 controller in combination with an electronic actuator. The ECL controller acts as the brain of the heating system. It lets you easily control and optimise system performance and operation.
Please note: Your substation may look different than the substation shown, as variants with other components may be supplied. Instructions for the fitted components will always be supplied to­gether with the substation.
Heating circuit
The temperature for the heating circuit is controlled electronically by the Danfoss ECL controller. The supply temperature ist calculated by the controller on basis of the outdoor temperature. The ECL Comfort 210 controller is loaded with a selected application by means of an ECL Application Key (Plug-&-Play). The Application Key contains information about application, languages and factory settings. From factory the VX Solo II HWS (ECÆ210/A237) is loaded with Ap­plication 1a. Other applications can, however, be loaded by means of the ECL Application Key, and it is possible to update the controller with new application software.
The controller is factory preset to turn off the heating automatically in the summer period.
The controller settings can be changed in accordance with the en­closed producer instructions for the mounted controller.
See ECL Application Key Box with ECL Comfort 210/310 user guide and mounting guide, for further information.
We also refer to Danfoss Installation Guide für ECL Comfort 210, application A237, which can be found on www.heating.danfoss.com
34
DKDHR VI.GP.P1.02 Danfoss District Energy
Instructions VX Solo II HWS (ECL 210/A237)
Instructions AVQM, AVQMT – PN 16, 25 / DN 15-50
DN 15-32 DN 15-50 DN 32-50 DN 15-50 DN 32-50 DN 15-50 DN 32-50  ∆p = 0.2 p = 0.2 p = 0.2 p = 0.2 p = 0.2 p = 0.2 p = 0.2
AVQM (PN 16) AVQM (PN 25) AVQMT (PN 25) AVQMT/AVT (PN 25)
ENGLISH
Flow (and temperature) controller with integrated control valve AVQM, AVQMT
www.danfoss.com Page 7
DANSK
Flow- (og temperatur-)regulator med indbygget motorventil AVQM, AVQMT
www.danfoss.dk Side 9
DEUTSCH
Volumenstrom (und Temperatur-) Regler mit Motorstellventil AVQM, AVQMT
www.danfoss.de Seite 11
ESPAÑOL
Regulador de caudal (y temperatura) con válvula de control integrada AVQM, AVQMT
www.danfoss.es Página 13
SLOVENŠČINA
Regulator pretoka (in temperature) z regulacijskim ventilom AVQM, AVQMT
www.danfoss.si Stran 15
POLSKI
Regulator przepływu (i temperatury) z zaworem regulacyjnym AVQM, AVQMT
www.danfoss.pl Strona 17
MAGYAR
Térfogatáram(és hőmérséklet) szabályozó, motoros szabályozó-szeleppel egybeépítve AVQM, AVQMT
www.danfoss.hu Oldal 19
SRPSKI
Uputstvo AVQM, AVQMT-PN 16, 25/DN 15-50 grejanje.danfoss.com Strana 21
Instructions AMV 150
ENGLISH
Actuators for three point control AMV 150 www.danfoss.com Page 2
DANSK
Motorer til 3-punkts styring AMV 150 www.danfoss.d k Side 3
DEUTSCH
Stellantriebe für 3-Pkt.- Eingangssignal AMV 150 www.danfoss.de Seite 3
SVENSKA
Motor för 3-punktsreglering AMV 150 varme.danfoss.se Sida 4
NEDERLANDS
Servomotor met 3-puntssturing AMV 150 www.danfoss.nl Pagina 4
LIETUVIŲ K.
Pavaros trijų padėčių valdymui AMV 150 www.danfoss.lt 5 puslapis
LATVISKI
Motori trīs punktu kontrolei AMV 150 www.danfoss.com Lpp. 5
MAGYAR
Szelepmozgatók hárompontos szabályozáshoz AMV 150 www.danfoss.com 6. oldal
ČESKY
Servopohony s tříbodovým regulačním signálem AMV 150 w ww.danfoss.cz Strana 6
POLSKI
Siłowniki sterowane sygnałem 3-punktowym AMV 150 www.danfoss.pl Strona 7
РУССКИЙ
Электроприводы для трехпозиционного регулирования AMV 150
www.danfoss.ru Страница 7
AMV 150 + AMV 150 + AMV 150 + VS2 (DN 15) VMV AVQM (DN 15)
Control of heating circuit
For controlling the heating circuit the VX Solo II HWS (ECL 210/A237) is supplied with a self-acting flow controller with integrated control valve Danfoss AHQM and an electrical actuator AMV 150, which in combination with the ECL controller controls the heating circuit. The controller closes when set max. flow is exceeded. The flow-controller is equipped with excess pressure safety valve, which protects the actuator from too high differential pressure.
The electrical actuator has undergone a functional test from factory. In case of operating disturbances the actuator can be closed manu­ally turning the manual override knob on top of actuator counter­clockwise.
Please see enclosed instructions, Electrical actuator AMV 150 Flow-controller with integrated control valve AHQM
Manual override (AMV 150)
Circulation pump
See chapter 12 on page 48 for more information about circulation pump.
Domestic hot water
The VX Solo II HWS (ECL 210/A237) substations are supplied with connection pipes for domestic hot water cylinder on the second­ary side, and the temperature in the cylinder is controlled by the Danfoss ECL controller.
AHQM
Press and hold the button (on the bottom side of the actuator) during manual override.
Danfoss District Energy VI.GP.P1.02 DKDHR
3535
Instructions VX Solo II HWS (ECL 210/A237)
Grundfos UP UPS
UPD, UPSD
UP, UPS, UPD, UPSD
GRUNDFOS INSTRUCTIONS
Domestic hot water circulation pump
It is recommended to set the pump at highest speed of rotation (set­ting 3) before start-up. Then set the pump at lowest possible speed of rotation (setting 1), in due consideration of the electricity consump­tion and the heating comfort. Factory setting of the selector switch is centre position (default). Select setting 2 and 3 only if the pump setting does not meet actual system requirements.
Please see enclosed instructions, GRUNDFOS UPS
Installation and operating instructions
Selector switch
36
DKDHR VI.GP.P1.02 Danfoss District Energy
Instructions VX Solo II HWS (ECL 210/A247)
11.6 VX Solo II HWS (ECL 210/A247.1c)
Substation for indirect heating for single-family, semi-detatched and terraced houses as well as flats. With one heating circuit for radiator or floor heating , with mixing loop and with connection pipes for cylinder on the secondary side. For wall-mounting.
The temperature for the heating circuit is controlled by a Danfoss ECL 210 controller in combination with an electronic actuator. The ECL controller acts as the brain of the heating system. It lets you easily control and optimise system performance and operation.
Please note: Your substation may look different than the substation shown, as variants with other components may be supplied. Instructions for the fitted components will always be supplied to­gether with the substation.
Heating circuit
The temperature for the heating circuit is controlled electronically by the Danfoss ECL controller. The supply temperature ist calculated by the controller on basis of the outdoor temperature. The ECL Comfort 210 controller is loaded with a selected application by means of an ECL Application Key (Plug-&-Play). The Application Key contains information about application, languages and factory settings. From factory the VX Solo II HWS (ECL 210/A247) is loaded with Ap­plication 1c. Other applications can, however, be loaded by means of the ECL Application Key, and it is possible to update the controller with new application software.
The controller is factory preset to turn off the heating automatically in the summer period.
The controller settings can be changed in accordance with the en­closed producer instructions for the mounted controller.
See ECL Application Key Box with ECL Comfort 210/310 user guide and mounting guide, for further information.
We also refer to Danfoss Installation Guide für ECL Comfort 210, application A247, which can be found on www.heating.danfoss.com
Danfoss District Energy VI.GP.P1.02 DKDHR
3737
Instructions VX Solo II HWS (ECL 210/A247)
Instructions AVQM, AVQMT – PN 16, 25 / DN 15-50
DN 15-32 DN 15-50 DN 32-50 DN 15-50 DN 32-50 DN 15-50 DN 32-50  ∆p = 0.2 p = 0.2 p = 0.2 p = 0.2 p = 0.2 p = 0.2 p = 0.2
AVQM (PN 16) AVQM (PN 25) AVQMT (PN 25) AVQMT/AVT (PN 25)
ENGLISH
Flow (and temperature) controller with integrated control valve AVQM, AVQMT
www.danfoss.com Page 7
DANSK
Flow- (og temperatur-)regulator med indbygget motorventil AVQM, AVQMT
www.danfoss.dk Side 9
DEUTSCH
Volumenstrom (und Temperatur-) Regler mit Motorstellventil AVQM, AVQMT
www.danfoss.de Seite 11
ESPAÑOL
Regulador de caudal (y temperatura) con válvula de control integrada AVQM, AVQMT
www.danfoss.es Página 13
SLOVENŠČINA
Regulator pretoka (in temperature) z regulacijskim ventilom AVQM, AVQMT
www.danfoss.si Stran 15
POLSKI
Regulator przepływu (i temperatury) z zaworem regulacyjnym AVQM, AVQMT
www.danfoss.pl Strona 17
MAGYAR
Térfogatáram(és hőmérséklet) szabályozó, motoros szabályozó-szeleppel egybeépítve AVQM, AVQMT
www.danfoss.hu Oldal 19
SRPSKI
Uputstvo AVQM, AVQMT-PN 16, 25/DN 15-50 grejanje.danfoss.com Strana 21
Instructions AMV 150
ENGLISH
Actuators for three point control AMV 150 www.danfoss.com Page 2
DANSK
Motorer til 3-punkts styring AMV 150 www.danfoss.d k Side 3
DEUTSCH
Stellantriebe für 3-Pkt.- Eingangssignal AMV 150 www.danfoss.de Seite 3
SVENSKA
Motor för 3-punktsreglering AMV 150 varme.danfoss.se Sida 4
NEDERLANDS
Servomotor met 3-puntssturing AMV 150 www.danfoss.nl Pagina 4
LIETUVIŲ K.
Pavaros trijų padėčių valdymui AMV 150 www.danfoss.lt 5 puslapis
LATVISKI
Motori trīs punktu kontrolei AMV 150 www.danfoss.com Lpp. 5
MAGYAR
Szelepmozgatók hárompontos szabályozáshoz AMV 150 www.danfoss.com 6. oldal
ČESKY
Servopohony s tříbodovým regulačním signálem AMV 150 w ww.danfoss.cz Strana 6
POLSKI
Siłowniki sterowane sygnałem 3-punktowym AMV 150 www.danfoss.pl Strona 7
РУССКИЙ
Электроприводы для трехпозиционного регулирования AMV 150
www.danfoss.ru Страница 7
AMV 150 + AMV 150 + AMV 150 + VS2 (DN 15) VMV AVQM (DN 15)
7369311-0 VI.52.D3.003-2005
INSTRUCTIONS
VMV
065R9179
065R9179
NC (normally closed) RAVK (only VMV DN 15, 20) ABV - NC
NO (normally open) ABV - NO
NC (normally closed) RAVK (only VMV DN 15, 20) RAVI (only VMV DN 15, 20) ABV - NC
NO (normally open) ABV - NO
Instructions AMV 150
ENGLISH
Actuators for three point control AMV 150 www.danfoss.com Page 2
DANSK
Motorer til 3-punkts styring AMV 150 www.danfoss.d k Side 3
DEUTSCH
Stellantriebe für 3-Pkt.- Eingangssignal AMV 150 www.danfoss.de Seite 3
SVENSKA
Motor för 3-punktsreglering AMV 150 varme.danfoss.se Sida 4
NEDERLANDS
Servomotor met 3-puntssturing AMV 150 www.danfoss.nl Pagina 4
LIETUVIŲ K.
Pavaros trijų padėčių valdymui AMV 150 www.danfoss.lt 5 puslapis
LATVISKI
Motori trīs punktu kontrolei AMV 150 www.danfoss.com Lpp. 5
MAGYAR
Szelepmozgatók hárompontos szabályozáshoz AMV 150 www.danfoss.com 6. oldal
ČESKY
Servopohony s tříbodovým regulačním signálem AMV 150 w ww.danfoss.cz Strana 6
POLSKI
Siłowniki sterowane sygnałem 3-punktowym AMV 150 www.danfoss.pl Strona 7
РУССКИЙ
Электроприводы для трехпозиционного регулирования AMV 150
www.danfoss.ru Страница 7
AMV 150 + AMV 150 + AMV 150 + VS2 (DN 15) VMV AVQM (DN 15)
Control of heating circuit
For controlling the heating circuit the VX Solo II HWS (ECL300/C47-1) is supplied with a self-acting flow controller with integrated control valve Danfoss AHQM and an electrical actuator AMV 150, which in combination with the ECL controller controls the heating circuit. The controller closes when set max. flow is exceeded. The flow-controller is equipped with excess pressure safety valve, which protects the actuator from too high differential pressure.
The electrical actuator has undergone a functional test from factory. In case of operating disturbances the actuator can be closed manu­ally turning the manual override knob on top of actuator counter­clockwise.
Please see enclosed instructions, Electrical actuator AMV 150 Flow-controller with integrated control valve AHQM
Manual override (AMV 150)
Control of heating circuit, mixing loop
The VX Solo II HWS (ECL 210/AS247) is supplied with mixing loop, which provides a suitable temperature level e.g. for floor heating. The VX Solo II HWS (ECL 300/C47-1) is supplied with a 3-way valve VMV and an electrical actuator AMV 150, which in combination with the ECL controller controls the mixing loop.
The electrical actuator has undergone a functional test from factory. In case of operating disturbances the actuator can be closed manu­ally turning the manual override knob on top of actuator counter­clockwise.
Please see enclosed instructions, Electrical actuator AMV 150 3-way seated mixing valve VMV
AHQM Press and hold the button (on the
bottom side of the actuator) during manual override.
Manual override (AMV 150)
VMV
Press and hold the button (on the bottom side of the actuator) during manual override.
Circulation pump, heating circuit
See chapter 12 on page 48 for more information about circulation pump.
38
DKDHR VI.GP.P1.02 Danfoss District Energy
Instructions VX Solo II HWS (ECL 210/A247)
Grundfos UP UPS
UPD, UPSD
UP, UPS, UPD, UPSD
GRUNDFOS INSTRUCTIONS
Domestic hot water
The VX Solo II HWS substations are supplied with connection pipes for domestic hot water cylinder on the secondary side, and the tem­perature in the cylinder is controlled by the Danfoss ECL controller.
Domestic hot water circulation pump
It is recommended to set the pump at highest speed of rotation (set­ting 3) before start-up. Then set the pump at lowest possible speed of rotation (setting 1), in due consideration of the electricity consump­tion and the heating comfort. Factory setting of the selector switch is centre position (default). Select setting 2 and 3 only if the pump setting does not meet actual system requirements.
Please see enclosed instructions, GRUNDFOS UPS
Installation and operating instructions
Danfoss District Energy VI.GP.P1.02 DKDHR
3939
Instructions VX Solo II H2WP (ECL 210/A260)
11.7 VX Solo II H2WP (ECL 210/A260.1d)
Substation for indirect heating for single-family, semi-detatched and terraced houses as well as flats. With two heating circuits for radiator and floor heating, and connection pipes for cylinder on the primary side. For wall-mounting.
The temperature for the heating circuit is controlled by a Danfoss ECL 210 controller in combination with an electronic actuator. The ECL controller acts as the brain of the heating system. It lets you easily control and optimise system performance and operation.
Please note: Your substation may look different than the substation shown, as variants with other components may be supplied. Instructions for the fitted components will always be supplied to­gether with the substation.
Heating circuit
The temperature for the heating circuit is controlled electronically by the Danfoss ECL controller. The supply temperature ist calculated by the controller on basis of the outdoor temperature. The ECL Comfort 210 controller is loaded with a selected application by means of an ECL Application Key (Plug-&-Play). The Application Key contains information about application, languages and factory settings. From factory the VX Solo II H2WP is loaded with Application 1d. Other applications can, however, be loaded by means of the ECL Application Key, and it is possible to update the controller with new application software.
The controller is factory preset to turn off the heating automatically in the summer period.
The controller settings can be changed in accordance with the en­closed producer instructions for the mounted controller.
See ECL Application Key Box with ECL Comfort 210/310 user guide and mounting guide, for further information.
We also refer to Danfoss Installation Guide für ECL Comfort 210, application A260, whcih can be found on www.heating.danfoss.com
40
DKDHR VI.GP.P1.02 Danfoss District Energy
Instructions VX Solo II H2WP (ECL 210/A260)
INSTRUCTIONS
VS2 2-way
065R9075
065R9075
DN L (mm)
15 65
20 70
25 75
DN L1(mm)
15 131
20 142
25 159
DN L2(mm)
15 139
20 154
25 159
DN L3(mm)
15 69
20 74
25 79
Instructions AMV 150
ENGLISH
Actuators for three point control AMV 150 www.danfoss.com Page 2
DANSK
Motorer til 3-punkts styring AMV 150 www.danfoss.d k Side 3
DEUTSCH
Stellantriebe für 3-Pkt.- Eingangssignal AMV 150 www.danfoss.de Seite 3
SVENSKA
Motor för 3-punktsreglering AMV 150 varme.danfoss.se Sida 4
NEDERLANDS
Servomotor met 3-puntssturing AMV 150 www.danfoss.nl Pagina 4
LIETUVIŲ K.
Pavaros trijų padėčių valdymui AMV 150 www.danfoss.lt 5 puslapis
LATVISKI
Motori trīs punktu kontrolei AMV 150 www.danfoss.com Lpp. 5
MAGYAR
Szelepmozgatók hárompontos szabályozáshoz AMV 150 www.danfoss.com 6. oldal
ČESKY
Servopohony s tříbodovým regulačním signálem AMV 150 w ww.danfoss.cz Strana 6
POLSKI
Siłowniki sterowane sygnałem 3-punktowym AMV 150 www.danfoss.pl Strona 7
РУССКИЙ
Электроприводы для трехпозиционного регулирования AMV 150
www.danfoss.ru Страница 7
AMV 150 + AMV 150 + AMV 150 + VS2 (DN 15) VMV AVQM (DN 15)
7369311-0 VI.52.D3.003-2005
INSTRUCTIONS
VMV
065R9179
065R9179
NC (normally closed) RAVK (only VMV DN 15, 20) ABV - NC
NO (normally open) ABV - NO
NC (normally closed) RAVK (only VMV DN 15, 20) RAVI (only VMV DN 15, 20) ABV - NC
NO (normally open) ABV - NO
Instructions AMV 150
ENGLISH
Actuators for three point control AMV 150 www.danfoss.com Page 2
DANSK
Motorer til 3-punkts styring AMV 150 www.danfoss.d k Side 3
DEUTSCH
Stellantriebe für 3-Pkt.- Eingangssignal AMV 150 www.danfoss.de Seite 3
SVENSKA
Motor för 3-punktsreglering AMV 150 varme.danfoss.se Sida 4
NEDERLANDS
Servomotor met 3-puntssturing AMV 150 www.danfoss.nl Pagina 4
LIETUVIŲ K.
Pavaros trijų padėčių valdymui AMV 150 www.danfoss.lt 5 puslapis
LATVISKI
Motori trīs punktu kontrolei AMV 150 www.danfoss.com Lpp. 5
MAGYAR
Szelepmozgatók hárompontos szabályozáshoz AMV 150 www.danfoss.com 6. oldal
ČESKY
Servopohony s tříbodovým regulačním signálem AMV 150 w ww.danfoss.cz Strana 6
POLSKI
Siłowniki sterowane sygnałem 3-punktowym AMV 150 www.danfoss.pl Strona 7
РУССКИЙ
Электроприводы для трехпозиционного регулирования AMV 150
www.danfoss.ru Страница 7
AMV 150 + AMV 150 + AMV 150 + VS2 (DN 15) VMV AVQM (DN 15)
Control of heating circuit
For controlling the heating circuit the VX Solo II H2WP (ECL 210) is supplied with a 2-way valve VS 2 and an electrical actuator AMV 150, which in combination with the ECL controller controls the heating circuit.
The electrical actuator has undergone a functional test from factory. In case of operating disturbances the actuator can be closed manu­ally turning the manual override knob on top of actuator counter­clockwise.
Please see enclosed instructions, Electrical actuator AMV 150 2-way valve VS 2
Manual override (AMV 150)
Circulation pump, heating circuit
See chapter 12 on page 48 for more information about circulation pumps.
Control of floor heating circuit
For controlling the floor heating circuit the VX Solo II H2WP is supplied with a 3-way valve VMV and an electrical actuator AMV 150, which in combination with the ECL controller controls the floor heating circuit.
The electrical actuator has undergone a functional test from factory. In case of operating disturbances the actuator can be closed manu­ally turning the manual override knob on top of actuator counter­clockwise.
VS2
Press and hold the button (on the bottom side of the actuator) during manual override.
Please see enclosed instructions, Electrical actuator AMV 150 3-way seated mixing valve VMV
Manual override (AMV 150)
VMV
Press and hold the button (on the bottom side of the actuator) during manual override.
Danfoss District Energy VI.GP.P1.02 DKDHR
4141
Instructions VX Solo II H2WS (ECL 310/A367)
Safety temperature monotor
The heating circuit can be supplied with a safety thermostat for protection against overheating.
Please see enclosed operating instructions Jumo AT
Domestic hot water
The VX Solo II H2WS (ECL 310/A367) substations are supplied with connection pipes for domestic hot water cylinder on the secondary side. (Please note that cylinder control is not included in the delivery).
42
DKDHR VI.GP.P1.02 Danfoss District Energy
Instructions VX Solo II H2WS (ECL 310/A367)
11.8 VX Solo II H2WS (ECL 310/A367.1d)
Substation for indirect heating for single-family, semi-detatched and terraced houses as well as flats. With two heating circuits for radiator and floor heating, and connection pipes for cylinder on the secondary side. For wall-mounting.
The temperature for the heating circuit is controlled by a Danfoss ECL 310 controller in combination with an electronic actuator. The ECL controller acts as the brain of the heating system. It lets you easily control and optimise system performance and operation. .
Please note: Your substation may look different than the substation shown, as variants with other components may be supplied. Instructions for the fitted components will always be supplied to­gether with the substation.
Heating circuit
The temperature for the heating circuit is controlled electronically by the Danfoss ECL controller. The supply temperature ist calculated by the controller on basis of the outdoor temperature. The ECL Comfort 310 controller is loaded with a selected application by means of an ECL Application Key (Plug-&-Play). The Application Key contains information about application, languages and factory settings. From factory the VX Solo II H2WS is loaded with Application 1d. Other applications can, however, be loaded by means of the ECL Application Key, and it is possible to update the controller with new application software.
The controller is factory preset to turn off the heating automatically in the summer period.
The controller settings can be changed in accordance with the en­closed producer instructions for the mounted controller.
See ECL Application Key Box with ECL Comfort 210/310 user guide and mounting guide, for further information.
We also refer to Danfoss Installation Guide für ECL Comfort 210, application A367, which can be found on www.heating.danfoss.com
Danfoss District Energy VI.GP.P1.02 DKDHR
4343
Instructions VX Solo II H2WS (ECL 310/A367)
Instructions AVQM, AVQMT – PN 16, 25 / DN 15-50
DN 15-32 DN 15-50 DN 32-50 DN 15-50 DN 32-50 DN 15-50 DN 32-50  ∆p = 0.2 p = 0.2 p = 0.2 p = 0.2 p = 0.2 p = 0.2 p = 0.2
AVQM (PN 16) AVQM (PN 25) AVQMT (PN 25) AVQMT/AVT (PN 25)
ENGLISH
Flow (and temperature) controller with integrated control valve AVQM, AVQMT
www.danfoss.com Page 7
DANSK
Flow- (og temperatur-)regulator med indbygget motorventil AVQM, AVQMT
www.danfoss.dk Side 9
DEUTSCH
Volumenstrom (und Temperatur-) Regler mit Motorstellventil AVQM, AVQMT
www.danfoss.de Seite 11
ESPAÑOL
Regulador de caudal (y temperatura) con válvula de control integrada AVQM, AVQMT
www.danfoss.es Página 13
SLOVENŠČINA
Regulator pretoka (in temperature) z regulacijskim ventilom AVQM, AVQMT
www.danfoss.si Stran 15
POLSKI
Regulator przepływu (i temperatury) z zaworem regulacyjnym AVQM, AVQMT
www.danfoss.pl Strona 17
MAGYAR
Térfogatáram(és hőmérséklet) szabályozó, motoros szabályozó-szeleppel egybeépítve AVQM, AVQMT
www.danfoss.hu Oldal 19
SRPSKI
Uputstvo AVQM, AVQMT-PN 16, 25/DN 15-50 grejanje.danfoss.com Strana 21
'+6076, (,+  'DQIRVV
,QVWUXFWLRQV
$09
5
5
$099096 $09$940 $099%
1
1
7369311-0 VI.52.D3.003-2005
INSTRUCTIONS
VMV
065R9179
065R9179
NC (normally closed) RAVK (only VMV DN 15, 20) ABV - NC
NO (normally open) ABV - NO
NC (normally closed) RAVK (only VMV DN 15, 20) RAVI (only VMV DN 15, 20) ABV - NC
NO (normally open) ABV - NO
Instructions AMV 150
ENGLISH
Actuators for three point control AMV 150 www.danfoss.com Page 2
DANSK
Motorer til 3-punkts styring AMV 150 www.danfoss.d k Side 3
DEUTSCH
Stellantriebe für 3-Pkt.- Eingangssignal AMV 150 www.danfoss.de Seite 3
SVENSKA
Motor för 3-punktsreglering AMV 150 varme.danfoss.se Sida 4
NEDERLANDS
Servomotor met 3-puntssturing AMV 150 www.danfoss.nl Pagina 4
LIETUVIŲ K.
Pavaros trijų padėčių valdymui AMV 150 www.danfoss.lt 5 puslapis
LATVISKI
Motori trīs punktu kontrolei AMV 150 www.danfoss.com Lpp. 5
MAGYAR
Szelepmozgatók hárompontos szabályozáshoz AMV 150 www.danfoss.com 6. oldal
ČESKY
Servopohony s tříbodovým regulačním signálem AMV 150 w ww.danfoss.cz Strana 6
POLSKI
Siłowniki sterowane sygnałem 3-punktowym AMV 150 www.danfoss.pl Strona 7
РУССКИЙ
Электроприводы для трехпозиционного регулирования AMV 150
www.danfoss.ru Страница 7
AMV 150 + AMV 150 + AMV 150 + VS2 (DN 15) VMV AVQM (DN 15)
Control of heating circuit
For controlling the heating circuit the VX Solo II H2WS is supplied with a self-acting flow controller with integrated control valve Danfoss AHQM and an electrical actuator AMV 13, which in combination with the ECL controller controls the heating circuit. The controller closes when set max. flow is exceeded. The flow-controller is equipped with excess pressure safety valve, which protects the actuator from too high differential pressure.
The electrical actuator has undergone a functional test from fac­tory.
Please see enclosed instructions, Electrical actuator AMV 13 Flow-controller with integrated control valve AHQM
AMV 13 AHQM
Circulation pump, heating circuit
See chapter 12 on page 48 for more information about circulation pump
Control of floor heating circuit
For controlling the floor heating circuit the VX Solo II H2WS is supplied with a 3-way valve VMV and an electrical actuator AMV 150, which in combination with the ECL controller controls the floor heating circuit.
The electrical actuator has undergone a functional test from factory. In case of operating disturbances the actuator can be closed manu­ally turning the manual override knob on top of actuator counter­clockwise.
Please see enclosed instructions, Electrical actuator AMV 150 3-way seated mixing valve VMV
Manual override (AMV)
44
DKDHR VI.GP.P1.02 Danfoss District Energy
VMV Press and hold the button (on
the bottom side of the actuator) during manual override.
Instructions VX Solo II H2WS (ECL 310/A367)
Grundfos UP UPS
UPD, UPSD
UP, UPS, UPD, UPSD
GRUNDFOS INSTRUCTIONS
Safety temperature monitor
The heating circuit can be supplied with a safety thermostat for pro­tection against overheating.
Please see enclosed operating instructions Jumo AT
Domestic hot water
The VX Solo II H2WS substations are supplied with connection pipes for domestic hot water cylinder on the secondary side, and the tem­perature in the cylinder is controlled by the Danfoss ECL controller.
Domestic hot water circulation pump
It is recommended to set the pump at highest speed of rotation (set­ting 3) before start-up. Then set the pump at lowest possible speed of rotation (setting 1), in due consideration of the electricity consump­tion and the heating comfort. Factory setting of the selector switch is centre position (default). Select setting 2 and 3 only if the pump set­ting does not meet actual system requirements.
Please see enclosed instructions, GRUNDFOS UPS
Selector switch
Danfoss District Energy VI.GP.P1.02 DKDHR
4545
Instructions VX Solo OP
11.9 VX Solo OP (ECL 210/A237.1a)
Substation for indirect heating for single-family, semi-detatched and terraced houses as well as flats. With one heating circuit and with connection pipes for cylinder on the secondary side. For wall-mounting.
The temperature for the heating circuit is controlled by a Danfoss ECL 210 controller in combination with an electronic actuator. The ECL controller acts as the brain of the heating system. It lets you easily control and optimise system performance and operation.
Please note: Your substation may look different than the substation shown, as variants with other components may be supplied. Instructions for the fitted components will always be supplied to­gether with the substation.
Heating circuit
The temperature for the heating circuit is controlled electronically by the Danfoss ECL controller. The supply temperature ist calculated by the controller on basis of the outdoor temperature. The ECL Comfort 210 controller is loaded with a selected application by means of an ECL Application Key (Plug-&-Play). The Application Key contains information about application, languages and factory settings. From factory the VX Solo OP is loaded with Application 1a. Other applications can, however, be loaded by means of the ECL Application Key, and it is possible to update the controller with new application software.
The controller is factory preset to turn off the heating automatically in the summer period.
The controller settings can be changed in accordance with the en­closed producer instructions for the mounted controller.
See ECL Application Key Box with ECL Comfort 210/310 user guide and mounting guide, for further information.
We also refer to Danfoss Installation Guide für ECL Comfort 210, application A237, whcih can be found on www.heating.danfoss.com
46
DKDHR VI.GP.P1.02 Danfoss District Energy
Instructions VX Solo OP
Instructions AVQM, AVQMT – PN 16, 25 / DN 15-50
DN 15-32 DN 15-50 DN 32-50 DN 15-50 DN 32-50 DN 15-50 DN 32-50  ∆p = 0.2 p = 0.2 p = 0.2 p = 0.2 p = 0.2 p = 0.2 p = 0.2
AVQM (PN 16) AVQM (PN 25) AVQMT (PN 25) AVQMT/AVT (PN 25)
ENGLISH
Flow (and temperature) controller with integrated control valve AVQM, AVQMT
www.danfoss.com Page 7
DANSK
Flow- (og temperatur-)regulator med indbygget motorventil AVQM, AVQMT
www.danfoss.dk Side 9
DEUTSCH
Volumenstrom (und Temperatur-) Regler mit Motorstellventil AVQM, AVQMT
www.danfoss.de Seite 11
ESPAÑOL
Regulador de caudal (y temperatura) con válvula de control integrada AVQM, AVQMT
www.danfoss.es Página 13
SLOVENŠČINA
Regulator pretoka (in temperature) z regulacijskim ventilom AVQM, AVQMT
www.danfoss.si Stran 15
POLSKI
Regulator przepływu (i temperatury) z zaworem regulacyjnym AVQM, AVQMT
www.danfoss.pl Strona 17
MAGYAR
Térfogatáram(és hőmérséklet) szabályozó, motoros szabályozó-szeleppel egybeépítve AVQM, AVQMT
www.danfoss.hu Oldal 19
SRPSKI
Uputstvo AVQM, AVQMT-PN 16, 25/DN 15-50 grejanje.danfoss.com Strana 21
2
3
Instructions
AMV 10
082R9086
082R9086
1
AMV 10 + VM2, VS2 AMV 10 + VB2 AMV 10 + VMV AMV 10 + AVQM
N - 1
N - 3
Control of heating circuit
For controlling the heating circuit the VX Solo II HWS OP is supplied with a self-acting flow controller with integrated control valve Danfoss AHQM and an electrical actuator AMV 10, which in combination with the ECL controller controls the heating circuit. The controller closes when set max. flow is exceeded.
The flow-controller is equipped with excess pressure safety valve, which protects the actuator from too high differential pressure. The electrical actuator has undergone a functional test from factory. In case of operating disturbances the actuator can be closed manu­ally turning the manual override knob on top of actuator counter­clockwise.
Please see enclosed instructions, Electrical actuator AMV 10 Flow-controller with integrated control valve AVQM
Manual override
Domestic hot water
The VX Solo OP substations are supplied with connection pipes for domestic hot water cylinder on the secondary side, and the tem­perature in the cylinder is controlled by the Danfoss ECL controller.
VX Solo OP for heating only
The VX Solo OP is available as a variant for hating only. - See photo to the right.
AVQM Press and hold the button (on
the bottom side of the actuator) during manual override.
Danfoss District Energy VI.GP.P1.02 DKDHR
4747
Instructions VX Solo II
12.0 Circulation pumps
Grundfos Pumpe ALPHA2 L
Substation start-up / pump
Do not start the pump until the system has been filled with liquid and vented. The required minimum inlet pressure must be available at the pump inlet. See Grundfos instructions for the pump.
The heating system can be vented via an air escape valve installed above the pump.
The pump is self-venting. It need not be vented before start-up. Air in the pump may cause noise, This noise ceases after a few minu­tes running.
Please note, that the system cannot be vented through the pump Please note, that the pump must not run dry.
Pump setting
The pump is factory-set to start on the highest proportional-pres­sure curve PP2. This setting is suitable for a large majority of all single-family houses In this pump setting the pump performance and consequently the power consumption is adjusted according to hte heat demand in the system.
Grundfos Alpha2 L has seven optional settings, which can be select­ed with the push-button.
Enclosed photo shows the recommended and alternative pump set­tings for system types.
For further information about pump settings please refer to the en­closed Grundfos Instructions.
ALPHA2 L,
Installation and operating instructions
Summer operation
The circulation pump for heating is automatically switched off in pe­riods without heat demand. To prevent the pump from blocking in periods without heat demand, the controller automatically switches on the pump for some minutes every third day. In this period the circulation pump should be set at the highest speed of rotation.
If the heating requirement increases the pump setting can be changed by means of the selector switch.
For more information about venting of pump etc. please refer to en­closed installation and operating instructions.
Recommended and alternative pump settings for system type.
Pump setting
Pos. System type
A. Floor heating Lowest constant-pressure
B. Two-pipe systems Highest constant-pressure
Recommended Alternative
Highest constant-pressure
curve (CP1)
curve (PP2)
curve (CP2)
Lowest constant-pressure
curve (PP1)
C. One-pipe systems Lowest constant-pressure
curve (PP1)
48
DKDHR VI.GP.P1.02 Danfoss District Energy
Highest constant-pressure
curve (PP2)
Instructions VX Solo II
Grundfos Pumpe ALPHA2
Substation start-up / pump
Do not start up the pump until the system has been filled with the flow media and vented. It is recommended to set the pump at highest speed of rotation before start-up. Then set the pump at lowest possi­ble speed of rotation, in due consideration of the electricity consump­tion and the heating comfort.
Factory-setting of the pump is AUTOADAPT. AUTOADAPT is suita­ble for most systems. In this pump setting the pump performance will continuously be adjusted to the actual system requirements. For floor heating AUTOADAPT is recommended.
Pump settings:
Floor heating and two-pipe systems:
Choose AUTOADAPT-function (adjusts the pump performance to the actual system requirements).
One-pipe systems:
Setting of pump according to the enclosed instructions.
ALPHA2 GRUNDFOS INSTRUCTIONS
Summer operation
Substation with T°C thermostat:
In periods without heating demand the pump can be switched of on the switch and the shut-off valve/”summer valve” S in top of the sta­tion can be closed during this period. Switch on the pump (for a short period) at least once per month. For start-up follow the above start-up instructions. It is recommend­able to vent the system after the summer periodagain.
Substation with Danfoss ECL:
The circulation pump for heating is automatically switched off in pe­riods without heat demand. To prevent the pump from blocking in periods without heat demand, the controller automatically switch­eson the pump for some minutes every third day. In this period the circulation pump should be set at the highest speed of rotation.
If the heating requirement increases the pump setting can be changed by means of the selector switch.
For more information about venting of pumps ect. please refer to the enclosed Grundfoss instructions.
S
Danfoss District Energy VI.GP.P1.02 DKDHR
4949
Instructions VX Solo II
13.0 Maintenance
Maintenance work
Is only to be carried out by qualified and authorised personnel.
Inspection
The operator or other authorised personnel is obliged to perform in­spections at regular intervals and if necessary carry out maintenance work according to these and other instructions. Within the scope of the above maintenance work all strainers should be cleaned, all connections should be tightened and the operation of the safety valves should be checked by turning the valve head in the indicated direction.
Rinsing/cleaning of plate heat exchanger
Brazed heat exchangers can be rinsed. For optimum cleaning the flow rate should be a min. of 1.5 times normal flow rate, preferably in back­flush mode. This will remove any deposits formed on the inside of the plate heat exchanger. In case of more serious deposits, a cleaning liquid, approved by Danfoss (f.ex. Kaloxi or Radiner FI) can be pumped through the heat exchanger. Both are environmentally friendly cleaning fluids and can be disposed of through the usual domestic sewerage system. Afterwards rinse thoroughly with large amounts of water.
Deacidification of plate heat exchanger
After long operation, because of the relatively high temperatures in the plates or tubes, the heat exchangers are expecially subject to calification. Any deacidification of the plate heat exchanger is done as shown on the drawing to the right. For brazed plate heat exchangers weak inhibited acid solutions (e.g. 5% formic, acetic or phosphoric acid) may be used.
Measures after maintenance work
After maintenance work and before switching the system on again: – Check that all screwed connections are tight. – Check that all safety features, covers, that were removed, have been
replaced properly. – Clean the working area and remove any spilled materials. – Make sure that all tools, materials and other quipment that were
used, have been removed from the working area. – Connect to energy supply and check for leaks. – Vent the system. – If necessary adjust the system again. – Make sure that all safety features on the device and the system work
properly.
For the janitor or other supervisors Meter reading
It is recommended to read the heat meter at regular intervals, and to write down the meter readings.
Cooling / Return temperature reading
The cooling, i.e. the temperature difference between district heating supply and district heating return is of great importance for the total heat economy. It is therefore very important to observe the supply and return temperatures. Normal temperature difference is 30-35 °C. Please note, that the lowest district heating return temperature is di­rectly dependent on the return temperature from the heating circuit and the cylinder circuit. Therefore, please observe these return tem­peratures.
Tightening of connections
When reading the heat meter, all fittings and connections should be checked for leaks. If leaks are detected, contact qualified and authori­zed personnel immediately. Please note that the connections may be supplied with EPDM rub­ber gaskets - in general connection sizes from ¾” to and incl. 1½” for Kompakt H stations. Therefore take care not to overstrain the union nuts, as this may result in leaks. The manufacturer accepts no liability for leaks that result from overstrain of union nuts.
50
DKDHR VI.GP.P1.02 Danfoss District Energy
Instructions VX Solo II
14.0 Troubleshooting
If operating disturbances occur, the following basic features should be checked before carrying out actual troubleshooting:
- the substation is connected to electricity,
- the strainer on the district heating supply is clean,
14.1 Troubleshooting - Heating
Problem Possible cause Solution
Strainer clogged on DH og HE side (radiator circuit).
Filter in district heating meter clogged. Clean the filter (after consulting the
Defective differential pressure controller. Check the functions of the differential
Defective sensor Replace sensor
Defektive actuator. Check the functioning of the actuator.
Defective motor valve - or possibly dirt in the valve housing.
No heat
Automatic controls wrongly set or defec­tive - possibly power failure.
- the district heating flow temperature is at normal level (summer at least 60 °C, winter at least 70 °C),
- the differential pressure is higher than or equal to the normal (local) differential pressure in the district heating network. - If in doubt, ask the district heating plant,
- there is pressure on the system.
Clean strainer.
district heating plant).
pressure controller - clean valve seat if required.
Check the functions of the motor valve ­clean valve housing if required.
Check if the setting of the controller is correct - see separate instructions. Check the power supply. Temporary setting of actuator to “man­ual” control - see instruction on heating circuit, manual control.
Uneven heat distribution
Supply temperature too high
Pump out of operation.
The pump is set at too low speed of rotation.
Air pockets in the system. Vent the installation thoroughly.
Air pockets in the system. Vent the installation thoroughly.
Wrong setting of automatic controls. Adjust automatic controls, see instruc-
Defective sensor. Replace sensor.
Defective controller. The controller does not react as it is should in accordance with the instructions.
Check that the pump is receiving power and that it runs. Control that there is no air in the pump housing - see pump manual.
Set the pump at higher speed of rotation
- see instructions on heating circuit.
tions for automatic controls.
Call in automatic controls manufacturer or replace controller.
Danfoss District Energy VI.GP.P1.02 DKDHR
5151
Instructions VX Solo II
Problem Possible cause Solution
Wrong setting of automatic controls.
Adjust automatic controls, see instruc­tions for automatic controls.
Supply temperature too low
Poor cooling
Defective controller. The controller does not react as it is should in accordance with the instructions.
Outdoor sensor mounted or placed incorrectly.
Strainer clogged. Clean strainer.
Too small heating surface/ too small radiators compared to the total heating requirement of the building.
Poor utilization of existing heating surface.
The system is single-pipe. It is extremely important to keep the
Call in automatic controls manufacturer or replace controller.
Mount/place outdoor sensor correctly.
Increase total heating surface.
Make sure that the heat is distributed evenly across the full heating surface ­open all radiators and keep the radiator in the system from heating up at the bottom. Higher temperature at the top and lower temperature at the bottom part of the radiators means that the system operation is correct.
supply temperature to the radiators as low as ever possible, while maintaining a reasonable level of comfort.
52
DKDHR VI.GP.P1.02 Danfoss District Energy
Instructions VX Solo II
14.2 Troubleshooting - Domestic hot water
Problem Possible cause Solution
Defective or wrongly set differential pressure controller.
Strainer on DH supply clogged. Clean strainer.
Defective actuator - or possibly dirt in the valve housing.
No domestic hot water
Not enough pressure on the hot water Strainer in cold water meter clogged. Clean strainer - possibly in consultation
Long waiting time
Automatic controls wrongly set or defec­tive - possibly power failure.
Calified heating element. Clean DHW cylinder with acid solution or
Inadequate cylinder capacity. Wait for heating / loading of the cylinder.
Circulation pump out of operation. Check whether the pump is running -
Check the functions of the differential pressure controller - clean valve seat and capillary tubes if required, - air and rinse capillary tubes.
Check the functions of the actuator ­clean valve seat if required.
Check if the setting of the controller is correct, - see separate instructions. Check the power supply; Temporary setting of actuator to “manu­al” control - see instructions on heating circuit, manual control.
replace heating element.
You may check the specifications of the manufacturer conc. cylinder capacity.
with the water supply company.
whether the pump is receiving power. control that there is no air in the pump housing - see pump manual.
Temperature too low
Temperature too high
Variations in temperature
See “No domestic hot water”. See “No domestic hot water”.
Non-return valve on the circulation line defective (leads to mixing - and the circulation water pipes become cold dur­ing tapping).
Defective actuator - possibly dirt in the valve housing.
Automatic controls wrongly set or defec­tive.
Defective immersion sensor. Replace immersion sensor.
Non-return valve on the circulation line defective (leads to mixing - and the circulation water pipes become cold dur­ing tapping).
Replace non-return valve.
Check the functions of the actuator ­clean valve seat if required.
Check if the setting of the controller is correct, - see separate instructions.
Replace non-return valve.
Danfoss District Energy VI.GP.P1.02 DKDHR
5353
Instructions VX Solo II
Problem Possible cause Solution
Declining temperature during tapping
Poor cooling
Defective or wrongly set differential pressure controller (set too low).
Automatic controls wrongly set. Check that the controller has been cor-
Immersion sensor placed incorrectly. Place immersion sensor correctly in ac-
Calified heating element. Clean DHW cylinder with acid solution or
Calified heating element. Clean DHW cylinder with acid solution or
Check the functions of the differential pressure controller - clean valve seat and capillary tubes if required, - air and rinse capillary tubes.
rectly set - see separate instructions.
cordance with the manufacturer instruc­tions for the cylinder. You may contact Danfoss Redan A/S for further information.
replace heating element.
replace heating element. You may check the specifications of the manufacturer conc. cylinder capacity.
54
DKDHR VI.GP.P1.02 Danfoss District Energy
Instructions VX Solo II
15.0 EC-Declaration of Conformity
Danfoss Redan A/S
DK-8382 Hinnerup
Telephone +45 87 43 89 43
EC-DECLARATION OF CONFORMITY
For CE marking in EU (European Union)
Danfoss Redan A/S District Energy
DK-8382 Hinnerup
Declares under our sole responsibility that below products including all available power and control options:
VX Solo II
Main components: See Instruction Manual
Covered by this declaration is in conformity with the following directive(s), standard(s) or other norma­tive document(s), provided that the products are used in accordance with our instructions.
EU Directives:
EMC Directive 2004/108/EEC
EN 61000-6-1 2007
industry.
EN 61000-6-2 2007 Electromagnetic compatibility- Generic standard: Immunity industry. EN 61000-6-3 2007 Electromagnetic compatibility- Generic standard: Emission for residential, commercial and light
industry.
EN 61000-6-4 2007 Electromagnetic compatibility- Generic standard: Emission industry.
Machinery Directive 2006/42/EEC
EN ISO 14121-
EN 60204-1-Safety of machinery - Electrical equipment of machines — Part 1: General requirements
PED Directive 97/23/EEC
Conformity assessment procedure followed: Module A - Internal control of production
All substations that falls under Article 3 §3 and category 1 shall not be CE-marked according to this directive
CE marked affixed year 2010
Approved by:
Electromagnetic compatibility- Generic standard: Immunity for residential, commercial and light
1 Safety of machinery -- Risk assessment
District Energy
Omega 7, Søften
Danfoss District Energy VI.GP.P1.02 DKDHR
5555
Danfoss Redan A/S · Omega 7, Søften · DK-8382 Hinnerup Phone: +45 87 43 89 43 · Fax: +45 87 43 89 44 · redan@danfoss.com · www.redan.danfoss.dk
Produced by Danfoss Redan A/S © 09/2011
Loading...