VX Solo II
Substation for single-family, semi-detached and terraced houses as well as flats
District heating substation for indirect heating. With connection pipes for DHW cylinder. Designed for wall-mounting with pipes connection in top or bottom
Application
The VX Solo II is a substation featuring high performance and simple operation. The VX Solo II is especially suitable for two-pipe systems and systems with floor heating.
District heating (DH)
The substation is prefabricated with interconnecting components such as fitting piece and sensor pockets for insertion of a heat meter mounted in the DH return pipe, as well as strainer, ball valves and pockets for pressure gauges.
As a standard the substation is supplied with fitting piece for mounting of heat meter in the DH return pipe.
Heating (HE)
The heating side consists of a stainless steel plate heat exchanger, manometer, thermometers, expansion vessel and circulation pump(s) and the heating temperature is controlled by an self-acting thermostatic valve or an electronic temperature controller with an outdoor temperature sensor, in combination with an actuator.
Dependingonsubstation’sapplication, different heat exchangers dimensioned for central or floor heating can be used. As an option the substation can be equipped with a thermostat with safety monitor.
Domestic hot water (DHW)
The substation can be supplied with connection pipes for DHW cylinder on the supply or return line.
Construction
All pipes are made of stainless steel. The connections are made by nuts and gaskets. The substation offers variable connection possibilities, as connection of pipes can be established both in the top or in the bottom of the substation. The VX Solo II can be delivered with white-lacquered steel cover, with door.
Variants
VX Solo II is available in various variants. The circuit diagram and the technical data on the back page illustrates VX Solo II HWS with 1 heating circuit and secondary connection for DHW cylinder, however, variants with 2 heating circuits, mixing loop and primary connection for cylinder are also available.
Enclosed application sheet illustrates the available variants.
FeATURES AND BENEFITS
••Substation for single-family houses
••Indirect heating, - one or two heating circuits
••Selfacting or electronic control of heating (HE) temperature
••Connections for DHW cylinder on DH supply or return line
••Pipes connection in top or bottom of substation = Savings in installations costs
••Pipes and heat exchanger made of stainless steel, connections with EPDM gaskets.
••Minimized risk of lime scale and bacteria formation
••Electrical wiring from factory - Plug & Play
••Capacity: 20-30 kW HE / 15 kW FH
districtenergy.danfoss.com
VX Solo II
Circuit diagram – example, VX Solo II HWS (ECL 210/A237) - 1 HE circuit + sec. connection for DHW cylinder
1 |
Plate heat exchanger HE, |
23 |
Sensor pocket for heat meter |
|
with insulation |
24 |
Fitting piece for heat meter |
5 |
Strainer |
|
3/4” x 110 mm |
6 |
Non-return valve |
25 |
Controller Danfoss |
7 |
Ball valve |
|
ECL210/A237 |
8 |
Circulation pump, HE |
26 |
Outdoor sensor, ESMT |
8A |
Circulation pump, cylinder |
27 |
Sensor Danfoss, ESMC |
11 |
Safety valve HE, 3 bar ½” |
28 |
Immersion sensor ESMB |
13 |
Thermometer |
29 |
Danfoss actuator AMV 150 |
14 |
Pocket for pressure gauge |
30 |
Danfoss flow controller with |
15 |
Manometer |
|
integrated control valve |
16 |
Expansion vessel 12 l |
|
AHQM |
|
DH |
|
|
|
Supply |
|
|
|
DH |
|
|
|
Reurn |
|
|
Design specifications: |
|
Nominal pressure (prim/sec.): |
PN 16 / PN 3 |
Max. supply temperature: |
120 °C (design temp.) |
Min. ΔP: |
See capacity examples |
Brazing material (HEX): |
Copper |
Weight incl. cover: |
46 kg |
(incl. packing) |
|
Cover: |
White-lacquered steel |
Dimensions (mm): |
|
Without cover: |
H 861 × W min. 510*/max. 525** × D 365 |
With cover: |
H 861 × W 550 × D 381 |
*Units with insulated plate heat exchanger type XB06H-1 26.
*** Units with insulated plate heat exchanger type XB06H-1 40.
Electrical supply: |
230 V AC |
Connections sizes: |
|
DH: |
G ¾“ ET (ext. thread) |
HE, DHW cylinder: |
G ¾“ ET (int. thread) |
Supply limit
Cylinder
|
Cylinder |
|
Return |
|
Cylinder |
|
Supply |
|
HE |
|
Supply |
|
HE |
|
Return |
550 |
Connections: |
<![if ! IE]> <![endif]>40 |
1. District heating (DH) supply
2.District heating (DH) return
3.Heating (HE) return
4.Heating (HE) supply
5.DHW cylinder supply
6.DHW cylinder return
|
|
|
<![if ! IE]> <![endif]>780 |
<![if ! IE]> <![endif]>861 |
Options: |
|
|
|
|
|
• Cover, white-lacquered steel, with door |
|
|
|
|
|
• Electronic controller Danfoss ECL310 |
|
|
|
|
|
• Safety function - safety thermostat + actuator |
|
|
|
|
|
• Connection of pipes can be established in the top |
|
|
|
|
|
or in the bottom of the substation |
|
|
|
|
|
• Pipe insulation |
1 |
2 |
3 4 5 6 |
<![if ! IE]> <![endif]>41 |
|
• Mounting of heat meter (supplied by customer) |
|
• Supplementary fitting set for change of fitting |
top view |
|
piece size ¾ x 110 mm to fitting piece size 1“ x 190 |
|
Wall |
mm |
||
|
|||
|
|
Heating: Capacity examples
Heating |
Plate heat |
HE circuit |
HE circuit |
Pressure loss |
Pressure loss |
Flow rate |
Flow rate |
|
(only sec. side of |
||||||||
primary |
sedondary |
primary* |
primary |
secondary |
||||
capacity |
exchanger |
heat exchanger) |
||||||
[° C] |
[° C] |
[kPa] |
([l/h] |
[l/h] |
||||
|
|
[kPa] |
||||||
|
|
|
|
|
|
|
||
20 |
XB06H-1 26 |
75/44 |
40/65 |
35 |
6.0 |
555 |
688 |
|
20 |
XB06H-1 26 |
80/49 |
45/70 |
35 |
6.0 |
555 |
688 |
|
20 |
XB06H-1 26 |
90/51 |
50/70 |
29 |
8.5 |
441 |
860 |
|
30 |
XB06H-1 40 |
75/44 |
40/65 |
55 |
6.0 |
842 |
1032 |
|
30 |
XB06H-1 40 |
80/49 |
45/70 |
55 |
6.0 |
832 |
1032 |
|
30 |
XB06H-1 40 |
90/51 |
50/70 |
40 |
9.0 |
662 |
1290 |
* Heat meter not incl.
Danfoss Redan A/S · District Heating · Omega 7, Søften · DK-8382 Hinnerup · Denmark
Tel.: +45 87 43 89 43 · Fax: +45 87 43 89 44 · redan@danfoss.com · www.redan.danfoss.dk
VL.GP.O3.02 © Danfoss 08/2014 |
DKDHR |
ApplicationSheet
VX Solo II
District heating substation for indirect heating and connection pipes for primary or secondary connnection of DHW cylinder
VX Solo II (T°C)
1 HE circuit, primary connection for DHW cylinder
1Plate heat exchanger, HE, with insulation
4Differential pressure controller AVPL
5Strainer
7Ball valve
8Circulation pump HE
11Safety valve HE
13Thermometer
14Pocket for pressure gauge
15 |
Manometer |
Cylinder |
16 |
Expansion vessel |
Supply |
17 |
Air vent |
|
23 |
Sensor pocket for heat meter |
Cylinder |
24 |
Fitting piece for heat meter |
Return |
|
3/4” x 110 mm |
|
|
|
30Self-acting thermostatic valve T°C 200/VS2
Options: |
DH |
|
- |
RAVK 25-65/VMA thermostatic |
Supply |
actuator for temperature control of DHW cylinder.
Dimensions w/o cover: |
DH |
|
H801 x W 510*/max. 525** x D 345 mm |
||
Return |
||
* insulated plate heat exchanger XB06H-1 26. |
||
|
||
**insulated plate heat exchanger type XB06H-1 40 |
|
|
Dimensions w/cover: |
|
|
H801 x W 550 x D 381 mm |
|
HE |
Supply |
HE |
Return |
VX Solo II H, ECL 210/A230 1 HE circuit.
1 Plate heat exchanger HE
5 Strainer
7Ball valve
8Circulation pump HE
11Safety valve HE
13Thermometer
14Pocket for pressure gauge
15Manometer
16Expansion vessel
23Sensor pocket for heat meter
24Fitting piece for heat meter 3/4” x 110 mm
25Controller Danfoss ECL 210/A230
26Outdoor sensor, ESMT
27Sensor Danfoss, ESMC
29Danfoss actuator AMV
30Danfoss flow controller with integrated control valve AHQM
Options:
57 Safety thermostat
Dimensions w/o cover:
H861 x W 510*/max. 525** x D 365 mm
* insulated plate heat exchanger XB06H-1 26. **insulated plate heat exchanger type XB06H-1 40
Dimensions w/cover: H861 x W 550 x D 381 mm
DH
Supply
DH
Return
HE
Supply
HE
Return
VL.GP.O3.02 |
Produced by Danfoss Redan A/S · 08.2014 |
3 |