VX Solo HWS

Indirect substation for one-family houses, semi-detached and terraced houses as well as apartments.

Wall mounted district heating substation for indirect heating. With connection for domestic hot water cylinder on the secondary side.

Application

The VX Solo HWS is a substation featuring high performance and simple operation. The VX Solo HWS is especially suitable for two-pipe systems for heating and DHW connection on the secondary side.

District heating (DH)

The substation is prefabricated with interconnecting components such as differential pressure control, fitting piece and sensor pockets for insertion of a heat meter, as well as strainer, ball valves and pockets for pressure gauges.

Control

The optional TP9000 controller, which must be placed in a reference room, allows heating and DHW operation according to demand. The integrated room thermostat will open/close a zone valve for heating operation, and

the DHW sensor in the cylinder or the DHW timer will open/close a zone valve for DHW operation.

Heating (HE)

The heating side consists of a stainless steel plate heat exchanger, safety valves, manometer, air valve, expansion vessel and circulation pump. The secondary flow temperature is controlled thermostatically. Depending on substation’s application different heat exchangers dimensioned for central heating can be used.

Domestic hot water (DHW)

The substation is supplied with connection pipes for cylinder on the secondary side. Control valves and DHW cylinder sensor is included.

Construction

All pipes are made of stainless steel. The connections are made by nuts

and gaskets. The VX Solo HWS can be delivered with white-lacquered steel cover.

FEATURES AND BENEFITS

Substation for district heating for onefamily houses and apartments

Indirectheating, connectionpipesfor

DHW cylinder on secondary side

Thermostatic regulation of secondary flow temperature

Capacity: 19/25kW heating

Minimum space requiredfor installation

Pipes and plate heatexchanger made of stainless steel

VL.HE.Q1.12 © Danfoss 05/2013

Danfoss VX Solo HWS Fact sheet

VX Solo HWS

Circuit diagram

 

 

 

 

 

 

 

1 Plate heat exchanger HE

14

Pockets for pressure gauge 1/4”

 

 

4

Differential pressure controller

15

Manometer

 

 

5

Strainer

16

Expansion vessel 12 L

Cylinder

 

8

Circulation pump HE

17

Air valve

 

11 Safety valve HE

19

Tapping point / Fill valve

 

 

 

Cylinder

13 Thermometer

23

Sensor pocket ½”

 

 

 

24

Fitting piece for heat meter

 

Supply

 

 

 

 

 

 

3/4” x 110 mm

 

 

Top

 

 

 

Common

 

30

Thermostatic valve AVTB

 

 

 

52

Zone valve VMT/TWA-V

 

Return

 

Terminal Box

60

Terminal box

 

 

 

 

 

Radiator return

 

 

 

 

 

 

DH

 

 

 

HE

 

Supply

 

 

 

 

 

 

 

Supply

 

 

 

 

 

 

 

Top

 

 

Bottom

 

 

 

 

 

 

DH

 

 

 

 

 

Return

 

 

 

 

Technical parameters:

 

Connections:

Nominal pressure:

PN 10/10

DH supply temperature:

Tmax = 110 °C

1

Cylinder (DHW) supply

DH differential pressure:

See capacity examples

2

Common return

Weight incl. cover:

 

3

District heating (DH) return

42.0 kg

4

District heating (DH) supply

 

(incl. packing)

5

Heating (HE) supply

Cover:

White-lacquered

Options:

 

steel sheet

Energy meter

Electrical supply:

 

HE/DHW controllerTP9000

230V AC

DHW sensor

Dimensions (mm):

 

Ball valves

 

PN 16

Without cover:

H 850 xW 560 xW 350

White-lacquered steel sheet cover

With cover:

H 1000 xW 600 x D 400

 

 

Connections sizes:

 

DH:

G ¾”(int. thread)

HE:

G ¾”(int. thread)

Cylinder:

G ¾”(int. thread)

Wall

Top view

Heating: Capacity examples

 

Plate heat ex-

Heating circuit

Heating circuit

Pressure loss

 

 

 

Available pump

Heating Capacity

 

 

 

head

Prim.

Sec.

Prim.

Flow rate prim.

Flow rate sec.

Pump

changer

secondary

kW

°C

°C

*bar

l/h

l/h

 

 

 

bar

 

 

 

 

 

 

 

 

19

XB06H-1 26

70/40

30/60

0.30

488

545

UPS 15-60

0.37

19

XB06H-1 26

90/55

50/80

0.27

467

545

UPS 15-60

0.37

25

XB06H-1 40

70/40

30/60

0.45

616

717

UPS 15-60

0.33

25

XB06H-1 40

90/55

50/80

0.45

599

717

UPS 15-60

0.33

* Heat meter not incl.

Danfoss Randall Ltd. · District Energy · Ampthill Road · DK-Bedford MK42 9ER

Tel. +0845 1217 400 · Fax: +0845 1217 515 · danfossrandall@danfoss.com · www.danfoss-randall.co.dk

VL.HE.Q1.02 © Danfoss 05/2013