Danfoss VX Compact – Floor Station Operating guide

OperatingGuide
TermixVXCompact–FloorStation

1.0TableofContents

1.0TableofContents.............................................1
........................................................................2
2.0Functionaldescription......................................3
3.0Safetynotes.....................................................4
3.1SafetyNotes–general............................................4
4.0Mounting........................................................5
4.2Start-up..............................................................7
4.3Electricalconnections.............................................9
5.0Design.............................................................10
5.1Design...............................................................10
5.2Schematicdiagram................................................11
6.0Controls..........................................................12
6.1Heatingcircuit......................................................12
6.2Other.................................................................15
6.3Maintenance........................................................17
7.0Troubleshooting..............................................18
7.1Troubleshootingingeneral......................................18
7.2TroubleshootingHE...............................................19
7.3Disposal.............................................................21
8.0Declaration......................................................22
8.1Declarationofconformity........................................22
©Danfoss|2019.04VI.EH.I3.02/LUK44360|1
OperatingGuideTermixVXCompact–FloorStation
2|©Danfoss|2019.04
VI.EH.I3.02/LUK44360
OperatingGuideTermixVXCompact–FloorStation

2.0Functionaldescription

Districtheatingsubstationforindirectheating.
Application
TheT ermixVXCompact–FloorStationisacompletesolution forspaceheatingwithoptimalsafety,efficientenergytransfer, service-friendlyconstructionandacompactdesign.Thesubstation isapplicable,ifaheatexchangerisrequiredoronaconversion todistrictheating,wheretheexistingequipmentisunsuitable fordirectconnection.TheTermixVXCompact–FloorStationis ideal,whereahighlevelofsecurityagainstburstpipesandwater damageintheheatingsystemisrequired.
Districtheating(DH)
Thedistrictheatingcircuitisprefabricatedwithaflowcontroller withintegratedcontrolvalve,thermometersandballvalves.
Heating(HE)
Theheatingcircuitconsistsofaplateheatexchanger,safetyvalve, manometer,thermometers,ballvalves,drainvalve,airvalveand circulationpump.Theheatingtemperaturecanbecontrolled thermostaticallyorbyanelectroniccontrollerwithanoutdoor temperaturesensor.Dependingontheapplication,differentheat exchangersdimensionedforcentralorfloorheatingcanbeused.
Domestichotwater(DHW)
TermixVXCompact–FloorStationissuppliedwithconnection pipesforaDHWtankonthesupplyline.
VI.EH.I3.02/LUK44360
©Danfoss|2019.04|3
OperatingGuideTermixVXCompact–FloorStation

3.0Safetynotes

3.1SafetyNotes–general

Thefollowinginstructionsrefertothestandarddesignof substation.Specialversionsofsubstationsareavailableon request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation andstart-upofthesubstation.Themanufactureracceptsno liabilityfordamageorfaultsthatresultfromnon-compliancewith theoperatingmanual.Pleasereadandfollowalltheinstructions carefullytopreventaccidents,injuryanddamagetoproperty. Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly. Pleasecomplywiththeinstructionsissuedbythesystem manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass. Themaximumchloridecompoundsoftheflowmediumshouldnot behigherthan150mg/l. Theriskofequipmentcorrosionincreasesconsiderablyifthe recommendedlevelofpermissiblechloridecompoundsis exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary sourceofenergy.However,alsootherenergysourcescanbeused wheretheoperatingconditionsallowitandalwaysarecomparable todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse installationinafrost-freeroom,wherethetemperaturedoesnot exceed50°Candthehumiditydoesnotexceed60%.Donotcover orwallupthesubstationorinanyotherwayblocktheentrance tothestation.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallation’spermissiblesystempressureand temperature.
Themaximumtemperatureoftheflowmediuminthesubstationis 120°C.
Themaximumoperatingpressureofthesubstationis16bar.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases considerablyiftherecommendedpermissibleoperatingparameters areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves, however,alwaysinaccordancewithlocalregulations.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat thesubstationcanbeseparatedfromallenergysources(also powersupply).
Emergency
Incaseofdangeroraccidents-fire,leaksorotherdangerous circumstances-interruptallenergysourcestothestationif possible,andseekexperthelp. Incaseofdiscolouredorbad-smellingdomestichotwater,closeall shut-offvalvesonthesubstation,informtheoperatingpersonnel andcallforexperthelpimmediately.
REACH
AllDanfossA/SproductsfulfilltherequirementsinREACH. OneoftheobligationsinREACHistoinformcustomersabout presenceofCandidatelistsubstancesifany,weherebyinform youaboutonesubstanceonthecandidatelist:Theproduct containsbrasspartswhichcontainslead(CASno:7439-92-1)ina concentrationabove0.1%w/w.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto installationshouldbeinconditionswhicharedryandheated.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns. Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen position.Thesurfacesofthesubstationcangethot,whichcancause skinburns.Theballvalvesondistrictheatingsupplyandreturnshould beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallflangeconnections,screwjoints andelectricalclampandscrewconnectionsmustbecheckedand tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen addedtothesystemandthesystemhasbeenputintooperation, re-tightenALLconnections.
4|©Danfoss|2019.04
VI.EH.I3.02/LUK44360
OperatingGuideTermixVXCompact–FloorStation

4.0Mounting

4.1Mounting

Installationmustbeincompliancewithlocalstandardsand regulations. Districtheating(DH)-Inthefollowingsections,DHreferstothe heatsourcewhichsuppliesthesubstations.Avarietyofenergy sources,suchasoil,gasorsolarpower,couldbeusedasthe primarysupplytoDanfosssubstations.Forthesakeofsimplicity, DHcanbetakentomeantheprimarysupply.
Connections:
1.Heating(HE)supply
2.Heating(HE)return
3.Districtheating(DH)supply
4.Districtheating(DH)return
5.Tankflowline(TFL)
6.Tankreturnline(TRL)
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly.
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote themarkingsonthestation.
VI.EH.I3.02/LUK44360
©Danfoss|2019.04|5
OperatingGuideTermixVXCompact–FloorStation
4.1.1Installation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes andlabelsareplacedcorrectly.Ifyouwishtomountthestation differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe cleanedandrinsed.
Tightening
Duetovibrationduringtransport,allsubstationconnectionsmust becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha plug.Shouldtheplugsrequireremoval,thismustonlybedoneby anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbefittedaccording toschematicdiagram.Pleasenotethatthestrainermaybe suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe madeusingthreaded,flangedorweldedconnections.
6|©Danfoss|2019.04
VI.EH.I3.02/LUK44360
OperatingGuideTermixVXCompact–FloorStation

4.2Start-up

Start-up,Indirectheating
Filling:
1:Firstfill
Whencarryingoutfirstfill,theheatexchangermustbeslowlyfilled withwateruntilitreachesworkingpressure.
2:Pressuregauge
TheHEpressuregaugeindicatesthepressureoftheHEsystem.This instructionmustbefollowedstrictly,toavoiddangeroussituations.
3:Supplyhose
AballvalvewithplugisinstalledintheHEreturnline.Tofillthe system,theballvalvemustfirstbeclosed,theplugremovedand asupplyhoseconnected.Onre-openingtheballvalve,system fillcancommence.
4:Pre-pressure
Whenfillingthesystemwithwater,thepressuregaugeshouldbe observedclosely.Theexpansionvesselissuppliedpre-pressurised to0.5bar.Thepre-pressurerequiredateachsubstationwill dependonsystemhead(thedistancebetweenthelowestand highestpointinthesystem),forexample:
5:Fillingstop
Fillingmuststopwhenthepressuregaugeshowsapressure approximately1-2barhigherthanthepre-pressuresetting.The ballvalveisthenclosed,thehoseremovedandtheplugputback in.
Re-tightenconnections
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen putintooperation,re-tightenALLconnections.
Pump
Thepumpmustbeswitchedoffduringsystemfill.
Height(m)Pressure(bar)
0–50,5
5–101,0
10–15
1,5
15–202,0
Start-up:
1:Pumpspeed
Setthepumptohighestspeedbeforestart-up.
2:Startpump
Startthepumpandheatthroughthesystem.
3:Openshut-offvalves
Theshut-offvalvesshouldthenbeopenedandtheunitobserved asitentersservice.Visualcheckingshouldconfirmtemperatures, pressures,acceptablethermalexpansionandabsenceofleakage. Iftheheatexchangeroperatesinaccordancewithdesign,itcanbe puttoregularuse.
4:Ventsystem
Switchoffthepumpandventtheinstallationaftertheradiators havebeenwarmedup.
5:Adjustpumpspeed
Setthepumptothelowestspeedconsistentwithcomfortand electricityconsumption. Normallythechange-overswitchissetinthemidposition(default). Howeverforsystemswithunderfloorheatingorsinglepipeloop systems,itmaybenecessarytoturnthechange-overswitch upwards. Higherpumpspeedsareonlyusediftheheatingrequirement increases.
VI.EH.I3.02/LUK44360
©Danfoss|2019.04|7
OperatingGuideTermixVXCompact–FloorStation
Underfloorheating:
Pumpstopfunction
Ifthesubstationisusedinconnectionwithunderfloorheating,the circulationpumpmustbeconnectedtothepumpstopfunctionin theunderfloorheatingcontroller.Thepumpmustbestoppedif allunderfloorheatingcircuitsareclosed.
Warranty
Ifthisisnotpossible,thenflowmustbecontinuedthroughthe by-pass.Failingthis,thepumpwillbeatriskofseizureandany remainingwarrantywillbewithdrawn.
Summeroperation:
Switchoffpump
Insummerthecirculationpumpmustbeswitchedoffandthe shut-offvalvetoHEsupplyclosed.
Runningpumpbi-weekly
Itisrecommendedtostartupthecirculationpump(for2minutes) onceamonthduringsummer;theshut-offvalveoftheHEsupply mustbeshut.
Electroniccontroller
Mostelectroniccontrollerswillstartupthepumpautomatically (pleasenotemanufacturer´sinstructions).
8|©Danfoss|2019.04
VI.EH.I3.02/LUK44360