Fact sheet
Termix VVX-ID 22-22 fully insulated
P-Marked district heating unit for single family houses
FEATURES AND BENEFITS
• District heating unit for houses
• Indirect heating, Hot water
temperature regulation using
athermostatic / ow control valve
• Electronic heating regulation using
outdoor sensors and supply sensors
• Capacity for up to 15 kW heating
and 0.32 liter/second hot water
• Functions independently of
dierential pressure (0.5 – 6.0 bar)
• Low installation space requirement
• Stainless steel piping and plates
• Minimal risk of scaling and
bacteria formation
• Fully insulated
Application
Termix VVX is a complete solution
for hot water and heating, oering
optimum safety, ecient heat transfer, service-friendly construction and
acompact design. The district heating
unit is used on a conversion or a new
connection to district heating.
District heating (DH)
The district heating unit is provided
with tting pieces and sensor pockets for installation of heat meters,
and horizontally-mounted strainers
on all circuits. Primary and secondary
connections are optionally up and/or
down. Cold and hot water connections
are up as standard, but can locally be
easily changed to down (also available
as accessories with connectors that
are both up and down).
Heating (HE)
The heating circuit consists of aplate
heat exchanger, safety valve, manometer, thermometer (supply temperature), shut-o valves, air vent
valve, expansion vessel and circulation pump. The supply temperature is
regulated electronically with outdoor
sensors and supply sensors. Various
sizes of heat exchangers can be used,
depending on the capacity needed.
Domestic hot water (DHW)
Hot water is produced in the heat exchanger and the temperature is regulated with a self-acting thermostatic
valve that checks the hot water temperature using the ow control principle. Rapid closure of the thermostat
valve protects the heat exchanger
from overheating and scaling. The
control valve guarantees a stable
hot water temperature, even during
a changing duty cycle. The heat exchanger cools the district heating
water very eectively, which provides
excellent operational economy. The
thermostat valve also functions as
a bypass, keeping the district heating culvert heated. This means shorter waiting times during the summer
when the district heating is supplied
at a lower temperature.
Options
The district heating unit can also be
supplied with a thermal bypass that
is tted before the heat meter.
Construction
All pipes and plates are made of
stainless steel. Connectors are made
of brass that is sealed with gaskets.
Heat exchanger for the primary system for heating and direct hot water
heating with a self-acting thermostatic/ow control valve. Intended
for wall-mounting, P-labeled district
heating unit for houses connected to
a district heating system.
heating.danfoss.com
E-mail: danfoss@danfoss.se
www.danfoss.com/sweden
CIRCUIT DIAGRAM EXAMPLE
DHW
16
230 V
24
4
DCW
35
14
63
9
DHF
41
DHR
A Heat exchanger, HE
B Heat exchanger, DHW
F Electronic controller
1 Ball valve
4 Safety valve
9 Strainer
10 Circulator pump
14 Sensor pocket, energy meter
16 Outdoor sensor
18 Thermometer
19 Surface sensor
24 Delivered loose with unit
Technical parameters:
Nominal pressure: PN 16
DH supply temperature: T
Min. di. pressure: p
Brazing material (HEX): Koppar
= 120 °C
max
= 0.5 bar
min
Weight incl. cover: 35 kg
Electrical supply: 230 V AC
Dimensions (mm):
Without cover: H 750 × W 500 × D 360
With cover: H 800 × W 540 × D 430
B
35A
55 100 70 70 70 70
1 2 3 4 5 6
800
1 2 3 4
74
27
A
29
26 Pressure gauge
27 Actuator
29 2-way motorized valve
35 Ball valve / non-return valve
35A Fitting piece, energy meter
38 Expansion tank
530
45
F
A
4 bar
48
26
18
4
38
24
1
63
1
HFL
HRL
10
41 Fitting piece, energy meter
48 Air vent, manual
63 Sieve
74 IHPT
Connections:
1. DH supply
2. DH return
3. HE supply
4. HE return
5. DHW
6. CW
Connections:
DH + HE + DHW + CW: G ¾“ (int. thread)
Options:
• VVC kit
• Thermostatic bypass
• Room thermostat
• Danfoss ECL Comfort 310
30
42 70 140 70
DHW: CAPACITY EXAMPLES
Typ e
VVX-ID 22-x
Capacity
[kW]
Primary
supply
Tem p. [ °C]
33 65 18,0 10 / 50 73 0,17 / 0,2
50 65 20,2 10 / 50 108 0,27 / 0,3
55 65 21,0 10 / 50 149 0,3 / 0,33
Primary
return
Tem p. [°C ]
CW/DHW
Tem p.
[°C]
Pressure
loss sec.
[kPa]
Flow
Prim./
Sec . [l/s]
Danfoss AB · Marieholmsgatan 10C · 415 02 Göteborg
Tel.: 031-197 400 · Fax: 031-196 650 · ddh.info@danfoss.com · varme.danfoss.se
© Danfoss | DHS-SRMT/ PL | 2016 . 12
45
390
HEATING: CAPACITY EXAMPLES
Typ e
VVX-ID x-22
Capacity
[kW]
Primary
supply
Tem p. [ °C]
15 100 60,2 60 / 80 19,7 0,1 / 0,19
8 65 45,1 45 / 55 19,1 0,1 / 0,18
Primary
return
Tem p. [°C ]
Second-
ary Temp.
[°C]
Pressure
loss sec.
[kPa]
Flow
Prim./
Sec . [l/s]
VL.IE.U3.02