Danfoss VVX-I Operating guide

OperatingGuide
TermixVVX-Iwithcompleteinsulation

1.0TableofContents

1.0TableofContents.............................................1
2.0Functionaldescription......................................2
3.0Safetynotes.....................................................3
3.1SafetyNotes–general............................................3
4.0Mounting........................................................4
4.1Mounting...........................................................4
4.3Electricalconnections.............................................9
5.0Design.............................................................10
5.1Design...............................................................10
5.2Schematicdiagram................................................11
6.0Controls..........................................................12
6.1Heatingcircuit......................................................12
6.2DHWtemperaturecontrol........................................16
6.3Other.................................................................17
6.4Extras................................................................19
6.5Maintenance........................................................20
7.0Troubleshooting..............................................21
7.1Troubleshootingingeneral......................................21
7.2TroubleshootingDHW............................................22
7.3TroubleshootingHE...............................................23
7.4Disposal.............................................................25
8.0Declaration......................................................27
8.1Declarationofconformity........................................27
©Danfoss|2019.01VI.HE.J4.02/LUK40443|1
OperatingGuideT ermixVVX-Iwithcompleteinsulation

2.0Functionaldescription

Indirectsubstationforflatsandsinglefamilyhouses.
Application
TheTermixVVX-Iisacompletesolutionforhotwaterand spaceheatingwithoptimalsafety,efficientenergytransfer, service-friendlyconstructionandacompactdesign.Thesubstation isusedifaheatexchangerisrequiredoronaconversiontodistrict heatingwheretheexistingequipmentisunsuitablefordirect connection.
Districtheating(DH)
Thesubstationisprefabricatedwithadifferentialpressure controller,fittingpieceandsensorpocketsforinsertionofan energymeteraswellasstrainers.
Heating(HE)
Theheatingsideconsistsofaplateheatexchanger,safetyvalve, manometer,drainvalve,airvalve,expansionvesselandcirculation pump.Thetemperatureoftheheatingcanbecontrolled thermostaticallyorbyanelectroniccontrollerwithanoutdoor temperaturesensor.Dependingontheapplication,differentheat exchangersdimensionedforcentralorfloorheatingwillbeused.
Domestichotwater(DHW)
Thedomestichotwaterispreparedintheheatexchangerandthe temperatureisregulatedwithaflow-compensatedtemperature controllerwithintegrateddifferentialpressurecontroller.The DHwateriscooledveryefficientlybytheheatexchanger, therebycreatinganexcellentoperatingeconomy.TheIHPT valveensuresastablehotwatertemperaturebyvaryingloads, supplytemperaturesandbyhighandvaryingdifferentialpressure withouttheneedforreadjustingthevalve.Thisprotectsthe heatexchangeragainstoverheatingandlimescaleformation. FurthermoretheIHPTvalvehasanintegratedidletemperature controller,whichkeepsthehousesupplylinewarm.Thisshortens thewaitingperiodsduringsummerwhentheheatingsystemisin reducedoperation,whichisidealwherehighcomfortisrequested.
2|©Danfoss|2019.01
VI.HE.J4.02/LUK40443
OperatingGuideT ermixVVX-Iwithcompleteinsulation

3.0Safetynotes

3.1SafetyNotes–general

Thefollowinginstructionsrefertothestandarddesignof substation.Specialversionsofsubstationsareavailableon request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation andstart-upofthesubstation.Themanufactureracceptsno liabilityfordamageorfaultsthatresultfromnon-compliancewith theoperatingmanual.Pleasereadandfollowalltheinstructions carefullytopreventaccidents,injuryanddamagetoproperty. Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly. Pleasecomplywiththeinstructionsissuedbythesystem manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass. Themaximumchloridecompoundsoftheflowmediumshouldnot behigherthan150mg/l. Theriskofequipmentcorrosionincreasesconsiderablyifthe recommendedlevelofpermissiblechloridecompoundsis exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary sourceofenergy.However,alsootherenergysourcescanbeused wheretheoperatingconditionsallowitandalwaysarecomparable todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse installationinafrost-freeroom,wherethetemperaturedoesnot exceed50°Candthehumiditydoesnotexceed60%.Donotcover orwallupthesubstationorinanyotherwayblocktheentrance tothestation.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallation’spermissiblesystempressureand temperature.
Themaximumtemperatureoftheflowmediuminthesubstationis 120°C.
Themaximumoperatingpressureofthesubstationis10bar.PN16 versionsareavailableonenquiry.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases considerablyiftherecommendedpermissibleoperatingparameters areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves, however,alwaysinaccordancewithlocalregulations.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat thesubstationcanbeseparatedfromallenergysources(also powersupply).
Emergency
Incaseofdangeroraccidents-fire,leaksorotherdangerous circumstances-interruptallenergysourcestothestationif possible,andseekexperthelp. Incaseofdiscolouredorbad-smellingdomestichotwater,closeall shut-offvalvesonthesubstation,informtheoperatingpersonnel andcallforexperthelpimmediately.
REACH
AllDanfossA/SproductsfulfilltherequirementsinREACH. OneoftheobligationsinREACHistoinformcustomersabout presenceofCandidatelistsubstancesifany,weherebyinform youaboutonesubstanceonthecandidatelist:Theproduct containsbrasspartswhichcontainslead(CASno:7439-92-1)ina concentrationabove0.1%w/w.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto installationshouldbeinconditionswhicharedryandheated.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns. Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen position.Thesurfacesofthesubstationcangethot,whichcancause skinburns.Theballvalvesondistrictheatingsupplyandreturnshould beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallflangeconnections,screwjoints andelectricalclampandscrewconnectionsmustbecheckedand tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen addedtothesystemandthesystemhasbeenputintooperation, re-tightenALLconnections.
VI.HE.J4.02/LUK40443
©Danfoss|2019.01|3
OperatingGuideT ermixVVX-Iwithcompleteinsulation

4.0Mounting

4.1Mounting

Installationmustbeincompliancewithlocalstandardsand regulations. Districtheating(DH)-Inthefollowingsections,DHreferstothe heatsourcewhichsuppliesthesubstations.Avarietyofenergy sources,suchasoil,gasorsolarpower,couldbeusedasthe primarysupplytoDanfosssubstations.Forthesakeofsimplicity, DHcanbetakentomeantheprimarysupply.
Connections:
1.Districtheating(DH)supply
2.Districtheating(DH)return
3.Heating(HE)supply
4.Heating(HE)return
5.Domestichotwater(DHW)
6.Domesticcoldwater(DCW)
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly.
Connectionsizes:
DH+HE: DCW+DHW:
Dimensions(mm):
Withinsulation: Withcover:
Weight(approx.):35kg
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote themarkingsonthestation.
G¾”(int.thread) G¾”(int.thread)
H800xW530xD375 H800xW540xD430
4|©Danfoss|2019.01
VI.HE.J4.02/LUK40443
OperatingGuideT ermixVVX-Iwithcompleteinsulation
4.1.1Installation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes andlabelsareplacedcorrectly.Ifyouwishtomountthestation differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe cleanedandrinsed.
Keyholeformounting.
Tightening
Duetovibrationduringtransport,allsubstationconnectionsmust becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha plug.Shouldtheplugsrequireremoval,thismustonlybedoneby anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbefittedaccording toschematicdiagram.Pleasenotethatthestrainermaybe suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe madeusingthreaded,flangedorweldedconnections.
4.1.2Dismantletheinsulationfront
Pulltheinsulationfrontusingthehandleinthetopofthecover whilstkeepingtheECLcontrollerinitsplace.
VI.HE.J4.02/LUK40443
©Danfoss|2019.01|5
OperatingGuideT ermixVVX-Iwithcompleteinsulation
KeeptheECLcontrollerinitspositionwhileremovingtheinsulation frontcompletelybypullingatthelowerendoftheinsulationfront.
4.1.3Mountingthedisplayoftheenergymeter
Markthepositionofthefixationpointsofthebracketfortheenergy displayandscrewthetwoplugssuppliedintotheinsulationfront.
Mountthebracketforthedisplayoftheenergymeter.
Mountthedisplay/calculatoroftheenergymeterontothebracket. Pullthewiresfromthesensorsinsidetheunitthroughthe duct/cut-outintheinsulationplate.
6|©Danfoss|2019.01
VI.HE.J4.02/LUK40443
OperatingGuideT ermixVVX-Iwithcompleteinsulation

4.2Start-up

Start-up,Indirectheating
Filling:
1:Firstfill
Whencarryingoutfirstfill,theheatexchangermustbeslowlyfilled withwateruntilitreachesworkingpressure.
2:Pressuregauge
TheHEpressuregaugeindicatesthepressureoftheHEsystem.This instructionmustbefollowedstrictly,toavoiddangeroussituations.
3:Supplyhose
AballvalvewithplugisinstalledintheHEreturnline.Tofillthe system,theballvalvemustfirstbeclosed,theplugremovedand asupplyhoseconnected.Onre-openingtheballvalve,system fillcancommence.
4:Pre-pressure
Whenfillingthesystemwithwater,thepressuregaugeshouldbe observedclosely.Theexpansionvesselissuppliedpre-pressurised to0.5bar.Thepre-pressurerequiredateachsubstationwill dependonsystemhead(thedistancebetweenthelowestand highestpointinthesystem),forexample:
5:Fillingstop
Fillingmuststopwhenthepressuregaugeshowsapressure approximately1-2barhigherthanthepre-pressuresetting.The ballvalveisthenclosed,thehoseremovedandtheplugputback in.
Re-tightenconnections
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen putintooperation,re-tightenALLconnections.
Pump
Thepumpmustbeswitchedoffduringsystemfill.
Height(m)Pressure(bar)
0–50,5
5–101,0
10–15
1,5
15–202,0
Start-up:
1:Pumpspeed
Setthepumptohighestspeedbeforestart-up.
2:Startpump
Startthepumpandheatthroughthesystem.
3:Openshut-offvalves
Theshut-offvalvesshouldthenbeopenedandtheunitobserved asitentersservice.Visualcheckingshouldconfirmtemperatures, pressures,acceptablethermalexpansionandabsenceofleakage. Iftheheatexchangeroperatesinaccordancewithdesign,itcanbe puttoregularuse.
4:Ventsystem
Switchoffthepumpandventtheinstallationaftertheradiators havebeenwarmedup.
5:Adjustpumpspeed
Setthepumptothelowestspeedconsistentwithcomfortand electricityconsumption. Normallythechange-overswitchissetinthemidposition(default). Howeverforsystemswithunderfloorheatingorsinglepipeloop systems,itmaybenecessarytoturnthechange-overswitch upwards. Higherpumpspeedsareonlyusediftheheatingrequirement increases.
VI.HE.J4.02/LUK40443
©Danfoss|2019.01|7
OperatingGuideT ermixVVX-Iwithcompleteinsulation
Underfloorheating:
Pumpstopfunction
Ifthesubstationisusedinconnectionwithunderfloorheating,the circulationpumpmustbeconnectedtothepumpstopfunctionin theunderfloorheatingcontroller.Thepumpmustbestoppedif allunderfloorheatingcircuitsareclosed.
Warranty
Ifthisisnotpossible,thenflowmustbecontinuedthroughthe by-pass.Failingthis,thepumpwillbeatriskofseizureandany remainingwarrantywillbewithdrawn.
Summeroperation:
Switchoffpump
Insummerthecirculationpumpmustbeswitchedoffandthe shut-offvalvetoHEsupplyclosed.
Runningpumpbi-weekly
Itisrecommendedtostartupthecirculationpump(for2minutes) onceamonthduringsummer;theshut-offvalveoftheHEsupply mustbeshut.
Electroniccontroller
Mostelectroniccontrollerswillstartupthepumpautomatically (pleasenotemanufacturer´sinstructions).
8|©Danfoss|2019.01
VI.HE.J4.02/LUK40443
OperatingGuideT ermixVVX-Iwithcompleteinsulation

4.3Electricalconnections

Beforemakingelectricalconnections,pleasenotethe following:
Safetynotes
Pleasereadtherelevantpartsofthesafetynotes.
230V
Thesubstationmustbeconnectedto230VACandearth.
Potentialbonding
Potentialbondingshouldbecarriedoutaccording to60364-4-41:2007andIEC60364-5-54:2011. Bondingpointonthemountingplatebelowrightcornermarked withearthsymbol.
Disconnection
Thesubstationmustbeelectricallyconnectedsothatitcanbe disconnectedforrepairs.
Outdoortemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto directsunlight.Theyshouldnotbeplacedclosetodoors,windows orventilationoutlets.
Theoutdoorsensormustbeconnectedtothestationonthe terminalblockundertheelectroniccontrol.
4.3.1Thermoactuators
Activatingthethermoactuators
Thethermoactuatorsaresuppliedwitha“firstopen”function,such thattheyareslightlyopenforfrostprotectionuntiltheelectrical controllerisinstalled.Duringcommissioning,the“firstopen” functionisdisabledbyremovingtheredmountingsplitonthe thermoactuator. Pleasecheckthatthethermoactuatorscanfullyclosefollowing disablementofthe“-firstopen”function. Seetheinstallationguideincludedwiththethermoactuator.
Authorizedelectrician
Electricalconnectionsmustbemadebyanauthorizedelectricianonly.
Localstandards
Electricalconnectionsmustbemadeinaccordancewithcurrent regulationsandlocalstandards.
VI.HE.J4.02/LUK40443
©Danfoss|2019.01|9
OperatingGuideT ermixVVX-Iwithcompleteinsulation

5.0Design

5.1Design

Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
A
Heatexchanger,HE
B
Heatexchanger,DHW
1
Summervalve
4
Safetyvalve
7
Thermostaticcontroller,HE
9
Strainer
10|©Danfoss|2019.01
10
Circulatorpump
14
Sensorpocket,energymeter
20
Filling/drainvalve
26
Pressuregauge,HE
31
Differentialpressurecontroller
38
Expansiontank
41
Fittingpiece,energymeter
48
Airvent,manual
63
Sieve
74
IHPTcontroller,DHW
VI.HE.J4.02/LUK40443
OperatingGuideT ermixVVX-Iwithcompleteinsulation

5.2Schematicdiagram

DHW
DCW
DH
Supply
DH
Return
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
A
Heatexchanger,HE
B
Heatexchanger,DHW
1
Ballvalve
4
Safetyvalve
7
Thermostaticvalve
9
Strainer
10
Circulatorpump
DHW:DomesticHotWater DCW: DHSupply:DistrictHeatingSupply DHReturn:DistrictHeatingReturn HESupply:HeatingSupply HEReturn:HeatingReturn
DomesticColdWater
14
Sensorpocket,energymeter
18
Thermometer
20
Filling/drainvalve
24
Deliveredloosewithunit
26
Pressuregauge
31
Differentialpressurecontroller
38
Expansiontank
39
Connectionclosed
41
Fittingpiece,energymeter
48
Airvent,manual
63
Sieve
74
IHPTcontroller
HE Supply
HE Return
5.2.1Technicalparameters
Technicalparameters
Nominalpressure:PN10(PN16versionsareavailableonenquiry) Max.DHsupplytemperature: Min.DCWstaticpressure: Brazingmaterial(HEX): Heatexchangerstestpressure:30bar Soundlevel:≤55dB
VI.HE.J4.02/LUK40443
120°C
1.0bar Copper
©Danfoss|2019.01|11
OperatingGuideT ermixVVX-Iwithcompleteinsulation

6.0Controls

6.1Heatingcircuit

6.1.1Differentialpressurecontroller
Thedifferentialpressurecontrollersmoothsoutthefluctuationsin pressurearrivingfromthedistrictheatingnetwork.Theoperating pressureinthesubstationisthusheldsteady.
6.1.2HEtemperaturecontrol
TheHEflowtemperatureintheheatingcircuitiscontrolledbythe HEtemperaturecontroller.
6.1.3RAVKcontroller
RAVKcontroller(25-65°C).Thetemperaturesettingisasfollows: 1=25°C 2=35°C 3=45°C 4=55°C 5=65°C
Thevaluesareintendedasaguide.
Thermostaticcontrol
ThetemperatureoftheHEflowlineisadjustedasfollows: Toincreasetemperature,turnthehandleonthethermostatic controllertoselectahighernumber. Todecreasetemperature,turnthehandleonthethermostatic controllertoselectalowernumber.
12|©Danfoss|2019.01
VI.HE.J4.02/LUK40443
OperatingGuideT ermixVVX-Iwithcompleteinsulation
6.1.4Electroniccontrol
Substationswithelectroniccontrolmustbesetinaccordancewith manufacturer´sinstructions. Wheretheroomtemperatureiscontrolledbyradiatorthermostats, itisrecommendedthatthermostatsbesetforminimum temperatureineachroom.
6.1.5Outsidetemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto directsunlight.Theyshouldnotbeplacedclosetodoors,windows orventilationoutlets.
VI.HE.J4.02/LUK40443
©Danfoss|2019.01|13
OperatingGuideT ermixVVX-Iwithcompleteinsulation
6.1.6TP7000
TP7000electronic7dayprogrammableroomthermostat. Signalsfromtheroomthermostatcanbeusedtocontrolzone valves.
6.1.7CirculatorpumpUPM3
UPM3Pumpscanbecontrolledinconstantpressure,proportional pressureorconstantspeedmodedefinedbythemeansofasmart userinterface. Thevariablespeedmodulatingmodesallowthepumptomatchits performancetothesystemrequirements,helpingtoreducenoise whenthermostaticvalvesareclosingdown. EnergylabellingclassA
14|©Danfoss|2019.01
VI.HE.J4.02/LUK40443
OperatingGuideT ermixVVX-Iwithcompleteinsulation
6.1.8GrundfosUPM3AUTOLinstructions
Controlmode
Youcanswitchfromtheperformanceviewtothesettingsviewbypressingthepushbutton.Thesettingsviewshowswhichmode controlsthecirculator.After2seconds,thedisplayswitchesbacktoperformanceview.
Ifyoupressthebuttonfor2to10seconds,theuserinterfaceswitchesto"settingselection"iftheuserinterfaceisunlocked.Youcan changethesettingsastheyappear.Theselectionofthecontrolmodedependsonthesystemtypeandtheallocationofpressurelosses.
Ifyoupressthekeylockformorethan10seconds,youcantogglebetweenenabling/disablingthekeylockfunction.
Function
Proportionalpressure1
Proportionalpressure2
Proportionalpressure3
Constantpressure1
Constantpressure2
Constantpressure3
ConstantCurve1
ConstantCurve2
ConstantCurve3
ConstantCurveMax.
Operationstatus
Function
Standby**OnlyPWMcontrolled
0%≤P1≤25%
25%≤P1≤50%
50%≤P1≤75%
75%≤P1≤100%
Recommendedfor
2-pipesystems
1-pipesystems
Underfloorheating
Green
Green
YellowYellowYellowYellow
YellowYellowYellowYellow
Alarmstatus
Function
Blocked
Supplyvoltagelow
Electricalerror
6.1.9HEpressuregauge
TheHEpressuregaugeindicatesthepressureoftheHEsystem.
RedYellowYellowYellowYellow
VI.HE.J4.02/LUK40443
©Danfoss|2019.01|15
OperatingGuideT ermixVVX-Iwithcompleteinsulation

6.2DHWtemperaturecontrol

DHWtemperaturecontrol
TherearevarioustypesofDHWtemperaturecontrolusedin Danfosssubstations. DHWtemperatureshouldbeadjustedto45-50°C,asthisprovides optimalutilisationofDHwater.AtDHWtemperaturesabove55°C, thepossibilityoflimescaledepositsincreasessignificantly.
6.2.1IHPT90controller(45–65°)
IHPTisaself-actingflow-compensatedtemperaturecontrollerwith integrateddifferentialpressurecontroller. TheIHPToperatesatitsbestatDHsupplytemperaturesofupto 100°C. Byturningthehandlefortemperaturesettingin(+)direction thesettingisincreased,byturningitin(-)directionthesettingis decreased.
Turns*
0
1
2
3
4
5
6
7
*Startposition:Handleturnedfullyin(+)direction. Thevaluesareintendedasaguide.
Scale
7
661
5
455
352
248
144
043
DHWT emperatureSetting[°C]
64
58
16|©Danfoss|2019.01
VI.HE.J4.02/LUK40443
OperatingGuideT ermixVVX-Iwithcompleteinsulation

6.3Other

6.3.1Safetyvalve
Thepurposeofthesafetyvalveistoprotectthesubstationfrom excessivepressure. Theblow-offpipefromthesafetyvalvemustnotbeclosed.The blow-offpipeoutletshouldbeplacedsothatitdischargesfreely anditispossibletoobserveanydrippingfromthesafetyvalve. Itisrecommendedtochecktheoperationofsafetyvalvesat intervalsof6months.Thisisdonebyturningthevalveheadin directionindicated.
6.3.2Strainer
Strainersshouldbecleanedregularlybyauthorizedpersonnel.The frequencyofcleaningwoulddependonoperatingconditionsand themanufacturer’sinstructions.
6.3.3GTUPressureEqualizer
TheGTUPressureEqualizerabsorbstheexpansiononthe secondarysideoftheTermixwaterheatersandcanbeusedasa substitutetothesafetyvalve. Furthermorethepressureequalizerabsorbsapossibleincreasein pressure,soadischargeoutletisomitted. TheGTUPressureEqualizermaynotbeappliedinsystemswithhot watercirculation.
VI.HE.J4.02/LUK40443
©Danfoss|2019.01|17
OperatingGuideT ermixVVX-Iwithcompleteinsulation
6.3.4Fittingpiece
Thesubstationisequippedwithafittingpieceforenergymeter.
Assemblyofenergymeters:
1:Closeballvalves
ClosetheballvalvesonDHSupplyandDHReturn,ifthereiswater onthesystem.
2:Loosennuts
Loosenthenutsonthefittingpiece.
3:Removefittingpiece
Removethefittingpieceandreplaceitwiththeenergymeter.Do notforgetthegaskets.
4:Tightenconnections
Aftermountingoftheenergymeterremembertocheckand tightenallthreadedconnections.
Sensorpocket,energymeter
Thesensorsoftheenergymeterismountedinthesensorpockets.
18|©Danfoss|2019.01
VI.HE.J4.02/LUK40443
OperatingGuideT ermixVVX-Iwithcompleteinsulation

6.4Extras

6.4.1Circulationpipe
Thecirculationpipesetismounteddirectlyonthecontroller. Thesetincludescirculationpipe,singlecheckvalveandfitting. Whenmountingthehotwatercirculationdirectlyonthecontroller thehotwatercirculationtemperaturewillbeequaltotheidle temperature.Theidletemperatureisafewdegreeslowerthanthe setdomestichotwatertemperature.
VI.HE.J4.02/LUK40443
©Danfoss|2019.01|19
OperatingGuideT ermixVVX-Iwithcompleteinsulation

6.5Maintenance

Thesubstationrequireslittlemonitoring,apartfromroutine checks.Itisrecommendedtoreadtheenergymeteratregular intervals,andtowritedownthemeterreadings.
RegularinspectionsofthesubstationaccordingtothisInstruction arerecommended,whichshouldinclude:
Strainers
Cleaningofstrainers.
Meters
Checkingofalloperatingparameterssuchasmeterreadings.
Temperatures
Checkingofalltemperatures,suchasDHsupplytemperatureand DHWtemperature.
Connections
Checkingallconnectionsforleakages.
Safetyvalves
Theoperationofthesafetyvalvesshouldbecheckedbyturning thevalveheadintheindicateddirection.
Venting
Checkingthatthesystemisthoroughlyvented.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly.
Inspectionsshouldbecarriedoutminimumeverytwoyears.
SparepartscanbeorderedfromDanfoss.Pleaseensurethatany enquiryincludesthesubstationserialnumber.
20|©Danfoss|2019.01
VI.HE.J4.02/LUK40443
OperatingGuideT ermixVVX-Iwithcompleteinsulation

7.0Troubleshooting

7.1Troubleshootingingeneral

Intheeventofoperatingdisturbances,thefollowingbasicfeatures shouldbecheckedbeforecarryingoutactualtroubleshooting:
thesubstationisconnectedtoelectricity,
thestrainerontheDHsupplypipeisclean,
thesupplytemperatureoftheDHisatthenormallevel (summer,atleast60°C-winter,atleast70°C),
thedifferentialpressureisequaltoorhigherthanthenormal (local)differentialpressureintheDHnetwork–ifindoubt,ask theDHplantsupervisor,
pressureonthesystem-checktheHEpressuregauge.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly.
VI.HE.J4.02/LUK40443
©Danfoss|2019.01|21
OperatingGuideT ermixVVX-Iwithcompleteinsulation

7.2TroubleshootingDHW

ProblemPossiblecauseSolution
ToolittleornoDHW.
Taptemperaturetoohigh;DHWtapload toohigh.
Temperaturedropduringtapping.
Thermostaticcontrolvalvedoesnotclose
Idletemperaturetoolow(forstations equippedwithIHPT).
Strainerinsupplyorreturnlineclogged.Cleanstrainer(s).
DHWcirculationpumpoutoforderorwith toolowsetting.
Defectiveorcloggednon-returnvalve.
Noelectricity.Check.
Wrongsettingofautomaticcontrols,ifany.Toadjustanelectroniccontrollerfor
Scalingoftheplateheatexchanger.
Defectivemotorizedvalve.Check(usemanualfunction)–replace.
Defectivetemperaturesensors.
Defectivecontroller.
DCWisbeingmixedwiththeDHW,e.g.ina defectivethermostaticmixingvalve.
Defectiveorcloggednon-returnvalveon circulationvalve.
Thermostaticvalveadjustedtoatoohigh level.
Scalingoftheplateheatexchanger.
LargerDHWflowthanthesubstationhas beendesignedfor.
TemperaturedifferencebetweenDH supplyandDHWsetpointtoolow.
Setpointtoolow.Turnthermostatin(+)direction.
Checkcirculationpump.
Replace–clean.
DHW,pls.noteenclosedinstructionsfor electroniccontroller.
Replace–rinseout.
Check–replace.
Check–replace.
Check–replace. Hotwaterinsometapsbutnotinall.
Replace–clean.
Check–set.
Replace–rinseout.
ReduceDHWflow.
Lowerthesetpointtemperatureorincrease theDHsupplytemperature.
22|©Danfoss|2019.01
VI.HE.J4.02/LUK40443
OperatingGuideT ermixVVX-Iwithcompleteinsulation

7.3TroubleshootingHE

ProblemPossiblecauseSolution
Toolittleornoheat.StrainercloggedinDHorHEcircuit
Unevenheatdistribution.Airpocketsinthesystem.Venttheinstallationthoroughly.
DHsupplytemperaturetoohigh.
DHsupplytemperaturetoolow.
(radiatorcircuit).
ThefilterintheenergymeteronDHcircuit clogged.
Defectiveorwronglyadjusteddifferential pressurecontroller.
Sensordefective–orpossiblydirtinthe valvehousing.
Automaticcontrols,ifany,wronglysetor defective-possiblypowerfailure.
Pumpoutofoperation.Checkifthepumpisreceivingpowerand
Thepumpissetattoolowspeedof rotation.
Pressuredrop–thepressuredropon theradiatorcircuitshowslowerthan recommendedoperatingpressure.
Airpocketsinthesystem.Venttheinstallationthoroughly.
Limitingofthereturntemperatureadjusted toolow.
Defectiveradiatorvalves.
Unevenheatdistributioninbuilding becauseofincorrectlysetbalancingvalves, orbecausetherearenobalancingvalves.
Diameterofpipetosubstationtoosmallor branchpipetoolong.
Wrongsettingofthermostatorof automaticcontrols,ifany.
Defectivecontroller.Thecontrollerdoes notreactasitshouldaccordingtothe instructions.
Defectivesensoronself-actingthermostat.
Wrongsettingofautomaticcontrols,ifany.
Defectivecontroller.Thecontrollerdoes notreactasitshouldaccordingtothe instructions.
Defectivesensoronself-actingthermostat.
Wrongplacement/fittingofoutdoor temperaturesensor.
Strainerclogged.Cleangate/strainer.
Cleangate/strainer(s).
Cleanthefilter(afterconsultingtheDH plantoperator).
Checktheoperationofthedifferential pressurecontroller–cleanthevalveseatif required.
Checktheoperationofthethermostat– cleanthevalveseatifrequired.
Checkifthesettingofthecontroller iscorrect–seeseparateinstructions. Checkthepowersupply.Temporary settingofmotorto“manual”control–see instructionsonautomaticcontrols.
thatitturns.Checkifthereisairtrappedin thepumphousing–seepumpmanual.
Setthepumpathigherspeedofrotation.
Fillwateronthesystemandcheckthe functioningofthepressureexpansion vesselifrequired.
Adjustaccordingtoinstructions.
Check–replace.
Adjust/installbalancingvalves.
Checkpipedimensions.
Adjustautomaticcontrols,–see instructionsforautomaticcontrols.
Callautomaticcontrolsmanufactureror replacetheregulator.
Replacethermostat–orsensoronly.
Adjustautomaticcontrols–seeinstructions forautomaticcontrols.
Callinautomaticcontrolsmanufactureror replacecontroller.
Replacethermostat–orsensoronly.
Adjustlocationofoutdoortemperature sensor.
VI.HE.J4.02/LUK40443
©Danfoss|2019.01|23
OperatingGuideT ermixVVX-Iwithcompleteinsulation
ToohighDHreturntemperature.
Noiseinsystem.
Heatloadtoohigh.
Toosmallheatingsurface/toosmall radiatorscomparedtothetotalheating requirementofthebuilding.
Poorutilizationofexistingheatingsurface. Defectivesensoronself-actingthermostat.
Thesystemissinglepipeloop.
Pumppressuretoohigh.Adjustpumptoalowerlevel.
Airinsystem.
Defectiveorincorrectlysetradiatorvalve(s). Singlepipeloopsystemsrequirespecial one-piperadiatorvalves.
Dirtinthemotorizedvalveorinthe differentialpressurecontroller.
Defectivemotorizedvalve,sensoror automaticcontroller.
Electroniccontrollernotadjustedcorrectly.Adjustaccordingtoinstructions.
Pumppressuretoohigh.Adjustpumptoalowerlevel.
Defectivemotorizedvalve,sensoror electroniccontroller.
Increasetotalheatingsurface.
Makesuretheheatisdistributedevenly acrossthefullheatingsurface–openall radiatorsandkeeptheradiatorsinthe systemfromheatingupatthebottom.It isextremelyimportanttokeepthesupply temperaturetotheradiatorsaslowas possible,whilemaintainingareasonable levelofcomfort.
Thesystemshouldfeatureelectronic controlsaswellasreturnsensors.
Ventthesystem.
Check–set/replace.
Check–cleanout.
Check–replace.
Check–replace.
24|©Danfoss|2019.01
VI.HE.J4.02/LUK40443
OperatingGuideT ermixVVX-Iwithcompleteinsulation

7.4Disposal

Disposal
Thisproductshouldbedismantledanditscomponents sorted,ifpossible,invariousgroupsbeforerecycling ordisposal.
Alwaysfollowthelocaldisposalregulations.
VI.HE.J4.02/LUK40443
©Danfoss|2019.01|25
OperatingGuideT ermixVVX-Iwithcompleteinsulation
26|©Danfoss|2019.01
VI.HE.J4.02/LUK40443
OperatingGuideT ermixVVX-Iwithcompleteinsulation

8.0Declaration

8.1Declarationofconformity

Category0withelectricalequipment
VI.HE.J4.02/LUK40443
©Danfoss|2019.01|27
OperatingGuideT ermixVVX-Iwithcompleteinsulation
28|©Danfoss|2019.01
VI.HE.J4.02/LUK40443
Loading...