Danfoss VVX Compact Operating guide

OperatingGuide
TermixVVXCompact–Floorstation

1.0TableofContents

1.0TableofContents.............................................1
........................................................................2
2.0Functionaldescription......................................3
3.0Safetynotes.....................................................4
3.1SafetyNotes–general............................................4
4.0Mounting........................................................5
4.2Start-up..............................................................7
4.3Electricalconnections.............................................9
5.0Design.............................................................10
5.1Design...............................................................10
5.2Schematicdiagram................................................11
6.0Controls..........................................................12
6.1Heatingcircuit......................................................12
6.2DHWtemperaturecontrol........................................15
6.3Other.................................................................16
6.4Maintenance........................................................17
7.0Troubleshooting..............................................18
7.1Troubleshootingingeneral......................................18
7.2TroubleshootingDHW............................................19
7.3TroubleshootingHE...............................................20
7.4Disposal.............................................................22
8.0Declaration......................................................26
8.1Declarationofconformity........................................26
©Danfoss|2019.04VI.GP .J3.02/LUK44460|1
OperatingGuideTermixVVXCompact–Floorstation
2|©Danfoss|2019.04
VI.GP .J3.02/LUK44460
OperatingGuideTermixVVXCompact–Floorstation

2.0Functionaldescription

Districtheatingsubstationforindirectheatingand instantaneousdomestichotwaterwiththermostaticor electroniccontrols.
Application
TheTermixVVXCompact–Floorstationisathecompletesolution forhotwaterandspaceheatingwithoptimalsafety,efficient energytransfer,service-friendlyconstructionandacompact design.Thesubstationisapplicable,ifaheatexchangeris requiredoronaconversiontodistrictheating,wheretheexisting equipmentisunsuitablefordirectconnection.
Districtheating(DH)
Thedistrictheatingcircuitisprefabricatedwithaflowcontroller withintegratedcontrolvalveaswellasthermometersandball valves.
Heating(HE)
Theheatingcircuitconsistsofaplateheatexchanger,safety valve,manometer,thermometers,ballvalves,drainvalve,airvalve andcirculationpumpandcanbecontrolledthermostaticallyor byelectroniccontrollerwithanoutdoortemperaturesensor. Dependingontheapplication,differentheatexchangerswillbe dimensioned.
Domestichotwater(DHW)
Thedomestichotwaterispreparedintheheatexchangerand thetemperatureisregulatedwiththermostaticorelectronic controls.Theefficientheatexchangeroffersexceptionallygood heatextractionwithhighoutput.NoreadjustmentoftheDHW temperatureisrequiredafterinstallationandinitialsettingofthe controls.Thethermostaticcontrolvalveautomaticallyretainsthe comforttemperatureofthehotwater,evenwhentheheating systemisinreducedoperationduringsummerorifthedistrict heatingplantchangesoperatingparametersbetweensummerand winter.Thiseitherbyloweringorincreasingtheflowtemperature ofthedistrictheatingwaterand/ortheoperatingpressureinthe network.
VI.GP .J3.02/LUK44460
©Danfoss|2019.04|3
OperatingGuideTermixVVXCompact–Floorstation

3.0Safetynotes

3.1SafetyNotes–general

Thefollowinginstructionsrefertothestandarddesignof substation.Specialversionsofsubstationsareavailableon request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation andstart-upofthesubstation.Themanufactureracceptsno liabilityfordamageorfaultsthatresultfromnon-compliancewith theoperatingmanual.Pleasereadandfollowalltheinstructions carefullytopreventaccidents,injuryanddamagetoproperty. Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly. Pleasecomplywiththeinstructionsissuedbythesystem manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass. Themaximumchloridecompoundsoftheflowmediumshouldnot behigherthan150mg/l. Theriskofequipmentcorrosionincreasesconsiderablyifthe recommendedlevelofpermissiblechloridecompoundsis exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary sourceofenergy.However,alsootherenergysourcescanbeused wheretheoperatingconditionsallowitandalwaysarecomparable todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse installationinafrost-freeroom,wherethetemperaturedoesnot exceed50°Candthehumiditydoesnotexceed60%.Donotcover orwallupthesubstationorinanyotherwayblocktheentrance tothestation.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallation’spermissiblesystempressureand temperature.
Themaximumtemperatureoftheflowmediuminthesubstationis 120°C.
Themaximumoperatingpressureofthesubstationis16bar.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases considerablyiftherecommendedpermissibleoperatingparameters areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves, however,alwaysinaccordancewithlocalregulations.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat thesubstationcanbeseparatedfromallenergysources(also powersupply).
Emergency
Incaseofdangeroraccidents-fire,leaksorotherdangerous circumstances-interruptallenergysourcestothestationif possible,andseekexperthelp. Incaseofdiscolouredorbad-smellingdomestichotwater,closeall shut-offvalvesonthesubstation,informtheoperatingpersonnel andcallforexperthelpimmediately.
REACH
AllDanfossA/SproductsfulfilltherequirementsinREACH. OneoftheobligationsinREACHistoinformcustomersabout presenceofCandidatelistsubstancesifany,weherebyinform youaboutonesubstanceonthecandidatelist:Theproduct containsbrasspartswhichcontainslead(CASno:7439-92-1)ina concentrationabove0.1%w/w.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto installationshouldbeinconditionswhicharedryandheated.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns. Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen position.Thesurfacesofthesubstationcangethot,whichcancause skinburns.Theballvalvesondistrictheatingsupplyandreturnshould beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallflangeconnections,screwjoints andelectricalclampandscrewconnectionsmustbecheckedand tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen addedtothesystemandthesystemhasbeenputintooperation, re-tightenALLconnections.
4|©Danfoss|2019.04
VI.GP .J3.02/LUK44460
OperatingGuideTermixVVXCompact–Floorstation

4.0Mounting

4.1Mounting

Installationmustbeincompliancewithlocalstandardsand regulations. Districtheating(DH)-Inthefollowingsections,DHreferstothe heatsourcewhichsuppliesthesubstations.Avarietyofenergy sources,suchasoil,gasorsolarpower,couldbeusedasthe primarysupplytoDanfosssubstations.Forthesakeofsimplicity, DHcanbetakentomeantheprimarysupply.
Connections:
1.Heating(HE)supply
2.Heating(HE)return
3.Districtheating(DH)supply
4.Districtheating(DH)return
5.Domestichotwater(DHW)
6.Domesticcoldwater(DCW)
7.Hotwatercirculation(HCW)
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly.
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote themarkingsonthestation.
VI.GP .J3.02/LUK44460
©Danfoss|2019.04|5
OperatingGuideTermixVVXCompact–Floorstation
4.1.1Installation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes andlabelsareplacedcorrectly.Ifyouwishtomountthestation differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe cleanedandrinsed.
Tightening
Duetovibrationduringtransport,allsubstationconnectionsmust becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha plug.Shouldtheplugsrequireremoval,thismustonlybedoneby anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbefittedaccording toschematicdiagram.Pleasenotethatthestrainermaybe suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe madeusingthreaded,flangedorweldedconnections.
6|©Danfoss|2019.04
VI.GP .J3.02/LUK44460
OperatingGuideTermixVVXCompact–Floorstation

4.2Start-up

Start-up,Indirectheating
Filling:
1:Firstfill
Whencarryingoutfirstfill,theheatexchangermustbeslowlyfilled withwateruntilitreachesworkingpressure.
2:Pressuregauge
TheHEpressuregaugeindicatesthepressureoftheHEsystem.This instructionmustbefollowedstrictly,toavoiddangeroussituations.
3:Supplyhose
AballvalvewithplugisinstalledintheHEreturnline.Tofillthe system,theballvalvemustfirstbeclosed,theplugremovedand asupplyhoseconnected.Onre-openingtheballvalve,system fillcancommence.
4:Pre-pressure
Whenfillingthesystemwithwater,thepressuregaugeshouldbe observedclosely.Theexpansionvesselissuppliedpre-pressurised to0.5bar.Thepre-pressurerequiredateachsubstationwill dependonsystemhead(thedistancebetweenthelowestand highestpointinthesystem),forexample:
5:Fillingstop
Fillingmuststopwhenthepressuregaugeshowsapressure approximately1-2barhigherthanthepre-pressuresetting.The ballvalveisthenclosed,thehoseremovedandtheplugputback in.
Re-tightenconnections
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen putintooperation,re-tightenALLconnections.
Pump
Thepumpmustbeswitchedoffduringsystemfill.
Height(m)Pressure(bar)
0–50,5
5–101,0
10–15
1,5
15–202,0
Start-up:
1:Pumpspeed
Setthepumptohighestspeedbeforestart-up.
2:Startpump
Startthepumpandheatthroughthesystem.
3:Openshut-offvalves
Theshut-offvalvesshouldthenbeopenedandtheunitobserved asitentersservice.Visualcheckingshouldconfirmtemperatures, pressures,acceptablethermalexpansionandabsenceofleakage. Iftheheatexchangeroperatesinaccordancewithdesign,itcanbe puttoregularuse.
4:Ventsystem
Switchoffthepumpandventtheinstallationaftertheradiators havebeenwarmedup.
5:Adjustpumpspeed
Setthepumptothelowestspeedconsistentwithcomfortand electricityconsumption. Normallythechange-overswitchissetinthemidposition(default). Howeverforsystemswithunderfloorheatingorsinglepipeloop systems,itmaybenecessarytoturnthechange-overswitch upwards. Higherpumpspeedsareonlyusediftheheatingrequirement increases.
VI.GP .J3.02/LUK44460
©Danfoss|2019.04|7
OperatingGuideTermixVVXCompact–Floorstation
Underfloorheating:
Pumpstopfunction
Ifthesubstationisusedinconnectionwithunderfloorheating,the circulationpumpmustbeconnectedtothepumpstopfunctionin theunderfloorheatingcontroller.Thepumpmustbestoppedif allunderfloorheatingcircuitsareclosed.
Warranty
Ifthisisnotpossible,thenflowmustbecontinuedthroughthe by-pass.Failingthis,thepumpwillbeatriskofseizureandany remainingwarrantywillbewithdrawn.
Summeroperation:
Switchoffpump
Insummerthecirculationpumpmustbeswitchedoffandthe shut-offvalvetoHEsupplyclosed.
Runningpumpbi-weekly
Itisrecommendedtostartupthecirculationpump(for2minutes) onceamonthduringsummer;theshut-offvalveoftheHEsupply mustbeshut.
Electroniccontroller
Mostelectroniccontrollerswillstartupthepumpautomatically (pleasenotemanufacturer´sinstructions).
8|©Danfoss|2019.04
VI.GP .J3.02/LUK44460
OperatingGuideTermixVVXCompact–Floorstation

4.3Electricalconnections

Beforemakingelectricalconnections,pleasenotethe following:
Safetynotes
Pleasereadtherelevantpartsofthesafetynotes.
230V
Thesubstationmustbeconnectedto230VACandearth.
Potentialbonding
Potentialbondingshouldbecarriedoutaccording to60364-4-41:2007andIEC60364-5-54:2011. Bondingpointonthemountingplatebelowrightcornermarked withearthsymbol.
Disconnection
Thesubstationmustbeelectricallyconnectedsothatitcanbe disconnectedforrepairs.
Outdoortemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto directsunlight.Theyshouldnotbeplacedclosetodoors,windows orventilationoutlets.
Theoutdoorsensormustbeconnectedtothestationonthe terminalblockundertheelectroniccontrol.
Authorizedelectrician
Electricalconnectionsmustbemadebyanauthorizedelectricianonly.
Localstandards
Electricalconnectionsmustbemadeinaccordancewithcurrent regulationsandlocalstandards.
VI.GP .J3.02/LUK44460
©Danfoss|2019.04|9
OperatingGuideTermixVVXCompact–Floorstation

5.0Design

5.1Design

Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
A
Heatexchanger,HE
B
Heatexchanger,DHW
F
Electroniccontroller
2
Singlecheckvalve
4
Safetyvalve
9
Strainer
10|©Danfoss|2019.04
10
Circulationpump
11
Domestichotwaterpump
20
Filling/drainvalve
22
Testconnection
25
Pressuregaugewithballvalve
26
Pressuregauge
27AActuator,HE 27BActuator,DHW 30
Flowcontrollerwithintegratedcontrolvalve
36
Balancingvalve
40
Immersionsensor
VI.GP .J3.02/LUK44460
OperatingGuideTermixVVXCompact–Floorstation

5.2Schematicdiagram

DH
Supply
DH
Return
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
A
Heatexchanger,HE
B
Heatexchanger,DHW
F
Electroniccontroller
I
Connectionexpansiontank
1
Ballvalve
2
Singlecheckvalve
4
Safetyvalve
9
Strainer
10
Circulatorpump
11
Domestichotwaterpump
16
Outdoorsensor
18
Thermometer
19
Surfacesensor
20
Filling/drainvalve
24
Deliveredloosewithunit
25
Pressuregaugewithballvalve
26
Pressuregauge
27
Actuator
30
Flowcontrollerwithintegratedcontrolvalve
36
Balancingvalve
39
Connectionclosed
40
Immersionsensor
HE Supply
HE Return
DHW
DCW
HWC
DHW:DomesticHotWater DCW: HWC: DHSupply:DistrictHeatingSupply DHReturn:DistrictHeatingReturn HESupply:HeatingSupply HEReturn:HeatingReturn
5.2.1Technicalparameters
Technicalparameters
Nominalpressure: Max.DHsupplytemperature: Min.DCWstaticpressure: Brazingmaterial(HEX): Heatexchangerstestpressure:30bar Soundlevel:≤55dB
DomesticColdWater HotWaterCirculation
PN16 120°C
0.5bar Copper
VI.GP .J3.02/LUK44460
©Danfoss|2019.04|11
OperatingGuideTermixVVXCompact–Floorstation

6.0Controls

6.1Heatingcircuit

6.1.1Differentialpressurecontroller
Thedifferentialpressurecontrollersmoothsoutthefluctuationsin pressurearrivingfromthedistrictheatingnetwork.Theoperating pressureinthesubstationisthusheldsteady.
6.1.2Flowcontrollerwithintegratedcontrolvalve
Thecontrollerisaself-actingflowcontrollerwithintegratedcontrol valve.Thecontrollercloseswhensetmax.flowisexceededand canbeusedincombinationwithDanfosselectricalactuatorswith orwithoutsafetyfunction.Springreturnmotorcanbeusedas safetyfunctionbypowerfailure.
6.1.3Electric2–waymotorizedvalve
Actuatorswithorwithoutsafetyfunctionareavailablefor3-point controls.Spring-returnactuatorscanbeusedtoprovidesafety shut-offintheeventofpowerfailure.
12|©Danfoss|2019.04
VI.GP .J3.02/LUK44460
OperatingGuideTermixVVXCompact–Floorstation
6.1.4Electroniccontrol
Substationswithelectroniccontrolmustbesetinaccordancewith manufacturer´sinstructions. Wheretheroomtemperatureiscontrolledbyradiatorthermostats, itisrecommendedthatthermostatsbesetforminimum temperatureineachroom.
6.1.5Outdoortemperaturesensor(ESMT)
Outdoorsensorsshouldbemountedsoastoavoidexposureto directsunlight.Theyshouldnotbeplacedclosetodoors,windows orventilationoutlets.
6.1.6Circulationpump
TheGrundfosMAGNArangeisdesignedforheating,district heatinganddomestichotwatersupplyinbuildingsonanyscale. TheMAGNAsarespeed-controlledpumpswithbuilt-inintelligence thatletsthemanalyzecurrentconditionsandadjusttheir performanceaccordingly. EnergylabellingclassA
VI.GP .J3.02/LUK44460
©Danfoss|2019.04|13
OperatingGuideTermixVVXCompact–Floorstation
6.1.7HEpressuregauge
TheHEpressuregaugeindicatesthepressureoftheHEsystem.
14|©Danfoss|2019.04
VI.GP .J3.02/LUK44460
OperatingGuideTermixVVXCompact–Floorstation

6.2DHWtemperaturecontrol

DHWtemperaturecontrol
TherearevarioustypesofDHWtemperaturecontrolusedin Danfosssubstations. DHWtemperatureshouldbeadjustedto45-50°C,asthisprovides optimalutilisationofDHwater.AtDHWtemperaturesabove55°C, thepossibilityoflimescaledepositsincreasessignificantly.
6.2.1Flowcontrollerwithintegratedcontrolvalve
Thecontrollerisaself-actingflowcontrollerwithintegratedcontrol valve.Thecontrollercloseswhensetmax.flowisexceededand canbeusedincombinationwithDanfosselectricalactuatorswith orwithoutsafetyfunction.Springreturnmotorcanbeusedas safetyfunctionbypowerfailure.
6.2.2Electric2–waymotorizedvalve
Actuatorswithorwithoutsafetyfunctionareavailablefor3-point controls.Spring-returnactuatorscanbeusedtoprovidesafety shut-offintheeventofpowerfailure.
VI.GP .J3.02/LUK44460
©Danfoss|2019.04|15
OperatingGuideTermixVVXCompact–Floorstation

6.3Other

6.3.1Safetyvalve
Thepurposeofthesafetyvalveistoprotectthesubstationfrom excessivepressure. Theblow-offpipefromthesafetyvalvemustnotbeclosed.The blow-offpipeoutletshouldbeplacedsothatitdischargesfreely anditispossibletoobserveanydrippingfromthesafetyvalve. Itisrecommendedtochecktheoperationofsafetyvalvesat intervalsof6months.Thisisdonebyturningthevalveheadin directionindicated.
6.3.2Strainer
Strainersshouldbecleanedregularlybyauthorizedpersonnel.The frequencyofcleaningwoulddependonoperatingconditionsand themanufacturer’sinstructions.
6.3.3Domestichotwaterpump
Important!
Itisnecessarytomountadomestichotwatercirculationpumpon thewaterheatertoavoidregulationproblems. Thecirculationpumpcannotbeswitchedoff,sincethiswillresult inregulationproblems.(noflowatthesensor).
16|©Danfoss|2019.04
VI.GP .J3.02/LUK44460
OperatingGuideTermixVVXCompact–Floorstation

6.4Maintenance

Thesubstationrequireslittlemonitoring,apartfromroutine checks.Itisrecommendedtoreadtheenergymeteratregular intervals,andtowritedownthemeterreadings.
RegularinspectionsofthesubstationaccordingtothisInstruction arerecommended,whichshouldinclude:
Strainers
Cleaningofstrainers.
Meters
Checkingofalloperatingparameterssuchasmeterreadings.
Temperatures
Checkingofalltemperatures,suchasDHsupplytemperatureand DHWtemperature.
Connections
Checkingallconnectionsforleakages.
Safetyvalves
Theoperationofthesafetyvalvesshouldbecheckedbyturning thevalveheadintheindicateddirection.
Venting
Checkingthatthesystemisthoroughlyvented.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly.
Inspectionsshouldbecarriedoutminimumeverytwoyears.
SparepartscanbeorderedfromDanfoss.Pleaseensurethatany enquiryincludesthesubstationserialnumber.
VI.GP .J3.02/LUK44460
©Danfoss|2019.04|17
OperatingGuideTermixVVXCompact–Floorstation

7.0Troubleshooting

7.1Troubleshootingingeneral

Intheeventofoperatingdisturbances,thefollowingbasicfeatures shouldbecheckedbeforecarryingoutactualtroubleshooting:
thesubstationisconnectedtoelectricity,
thestrainerontheDHsupplypipeisclean,
thesupplytemperatureoftheDHisatthenormallevel (summer,atleast60°C-winter,atleast70°C),
thedifferentialpressureisequaltoorhigherthanthenormal (local)differentialpressureintheDHnetwork–ifindoubt,ask theDHplantsupervisor,
pressureonthesystem-checktheHEpressuregauge.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly.
18|©Danfoss|2019.04
VI.GP .J3.02/LUK44460
OperatingGuideTermixVVXCompact–Floorstation

7.2TroubleshootingDHW

ProblemPossiblecauseSolution
ToolittleornoDHW.
Taptemperaturetoohigh;DHWtapload toohigh.
Temperaturedropduringtapping.
Thermostaticcontrolvalvedoesnotclose
Strainerinsupplyorreturnlineclogged.Cleanstrainer(s).
DHWcirculationpumpoutoforderorwith toolowsetting.
Defectiveorcloggednon-returnvalve.
Noelectricity.Check.
Wrongsettingofautomaticcontrols,ifany.Toadjustanelectroniccontrollerfor
Scalingoftheplateheatexchanger.
Defectivemotorizedvalve.Check(usemanualfunction)–replace.
Defectivetemperaturesensors.
Defectivecontroller.
DCWisbeingmixedwiththeDHW,e.g.ina defectivethermostaticmixingvalve.
Defectiveorcloggednon-returnvalveon circulationvalve.
Thermostaticvalveadjustedtoatoohigh level.
Scalingoftheplateheatexchanger.
LargerDHWflowthanthesubstationhas beendesignedfor.
TemperaturedifferencebetweenDH supplyandDHWsetpointtoolow.
Checkcirculationpump.
Replace–clean.
DHW,pls.noteenclosedinstructionsfor electroniccontroller.
Replace–rinseout.
Check–replace.
Check–replace.
Check–replace. Hotwaterinsometapsbutnotinall.
Replace–clean.
Check–set.
Replace–rinseout.
ReduceDHWflow.
Lowerthesetpointtemperatureorincrease theDHsupplytemperature.
VI.GP .J3.02/LUK44460
©Danfoss|2019.04|19
OperatingGuideTermixVVXCompact–Floorstation

7.3TroubleshootingHE

ProblemPossiblecauseSolution
Toolittleornoheat.StrainercloggedinDHorHEcircuit
Unevenheatdistribution.Airpocketsinthesystem.Venttheinstallationthoroughly.
DHsupplytemperaturetoohigh.
DHsupplytemperaturetoolow.
(radiatorcircuit).
ThefilterintheenergymeteronDHcircuit clogged.
Defectiveorwronglyadjusteddifferential pressurecontroller.
Sensordefective–orpossiblydirtinthe valvehousing.
Automaticcontrols,ifany,wronglysetor defective-possiblypowerfailure.
Pumpoutofoperation.Checkifthepumpisreceivingpowerand
Thepumpissetattoolowspeedof rotation.
Pressuredrop–thepressuredropon theradiatorcircuitshowslowerthan recommendedoperatingpressure.
Airpocketsinthesystem.Venttheinstallationthoroughly.
Limitingofthereturntemperatureadjusted toolow.
Defectiveradiatorvalves.
Unevenheatdistributioninbuilding becauseofincorrectlysetbalancingvalves, orbecausetherearenobalancingvalves.
Diameterofpipetosubstationtoosmallor branchpipetoolong.
Wrongsettingofthermostatorof automaticcontrols,ifany.
Defectivecontroller.Thecontrollerdoes notreactasitshouldaccordingtothe instructions.
Defectivesensoronself-actingthermostat.
Wrongsettingofautomaticcontrols,ifany.
Defectivecontroller.Thecontrollerdoes notreactasitshouldaccordingtothe instructions.
Defectivesensoronself-actingthermostat.
Wrongplacement/fittingofoutdoor temperaturesensor.
Strainerclogged.Cleangate/strainer.
Cleangate/strainer(s).
Cleanthefilter(afterconsultingtheDH plantoperator).
Checktheoperationofthedifferential pressurecontroller–cleanthevalveseatif required.
Checktheoperationofthethermostat– cleanthevalveseatifrequired.
Checkifthesettingofthecontroller iscorrect–seeseparateinstructions. Checkthepowersupply.Temporary settingofmotorto“manual”control–see instructionsonautomaticcontrols.
thatitturns.Checkifthereisairtrappedin thepumphousing–seepumpmanual.
Setthepumpathigherspeedofrotation.
Fillwateronthesystemandcheckthe functioningofthepressureexpansion vesselifrequired.
Adjustaccordingtoinstructions.
Check–replace.
Adjust/installbalancingvalves.
Checkpipedimensions.
Adjustautomaticcontrols,–see instructionsforautomaticcontrols.
Callautomaticcontrolsmanufactureror replacetheregulator.
Replacethermostat–orsensoronly.
Adjustautomaticcontrols–seeinstructions forautomaticcontrols.
Callinautomaticcontrolsmanufactureror replacecontroller.
Replacethermostat–orsensoronly.
Adjustlocationofoutdoortemperature sensor.
20|©Danfoss|2019.04
VI.GP .J3.02/LUK44460
OperatingGuideTermixVVXCompact–Floorstation
ToohighDHreturntemperature.
Noiseinsystem.
Heatloadtoohigh.
Toosmallheatingsurface/toosmall radiatorscomparedtothetotalheating requirementofthebuilding.
Poorutilizationofexistingheatingsurface. Defectivesensoronself-actingthermostat.
Thesystemissinglepipeloop.
Pumppressuretoohigh.Adjustpumptoalowerlevel.
Airinsystem.
Defectiveorincorrectlysetradiatorvalve(s). Singlepipeloopsystemsrequirespecial one-piperadiatorvalves.
Dirtinthemotorizedvalveorinthe differentialpressurecontroller.
Defectivemotorizedvalve,sensoror automaticcontroller.
Electroniccontrollernotadjustedcorrectly.Adjustaccordingtoinstructions.
Pumppressuretoohigh.Adjustpumptoalowerlevel.
Defectivemotorizedvalve,sensoror electroniccontroller.
Increasetotalheatingsurface.
Makesuretheheatisdistributedevenly acrossthefullheatingsurface–openall radiatorsandkeeptheradiatorsinthe systemfromheatingupatthebottom.It isextremelyimportanttokeepthesupply temperaturetotheradiatorsaslowas possible,whilemaintainingareasonable levelofcomfort.
Thesystemshouldfeatureelectronic controlsaswellasreturnsensors.
Ventthesystem.
Check–set/replace.
Check–cleanout.
Check–replace.
Check–replace.
VI.GP .J3.02/LUK44460
©Danfoss|2019.04|21
OperatingGuideTermixVVXCompact–Floorstation

7.4Disposal

Disposal
Thisproductshouldbedismantledanditscomponents sorted,ifpossible,invariousgroupsbeforerecycling ordisposal.
Alwaysfollowthelocaldisposalregulations.
22|©Danfoss|2019.04
VI.GP .J3.02/LUK44460
OperatingGuideTermixVVXCompact–Floorstation
23|©Danfoss|2019.04
VI.GP .J3.02/LUK44460
OperatingGuideTermixVVXCompact–Floorstation
24|©Danfoss|2019.04
VI.GP .J3.02/LUK44460
OperatingGuideTermixVVXCompact–Floorstation
25|©Danfoss|2019.04
VI.GP .J3.02/LUK44460
OperatingGuideTermixVVXCompact–Floorstation

8.0Declaration

8.1Declarationofconformity

8.1.1Substationlabel
Normallythebelowmentioneddeclarationofconformityapplies: "Substations-Category0withelectricalequipment".
Unlessfittedwithayellowlabel(PEDKAT.1)onthesubstationlabel thenthefollowingdeclarationofconformityapplies:"Substations­Category1withelectricalequipment" .
Category0withelectricalequipment
26|©Danfoss|2019.04
VI.GP .J3.02/LUK44460
OperatingGuideTermixVVXCompact–Floorstation
Category1withelectricalequipment
VI.GP .J3.02/LUK44460
©Danfoss|2019.04|27
OperatingGuideT ermixVVXCompact–Floorstation
28|©Danfoss|2019.04
VI.GP .J3.02/LUK44460
Loading...