Danfoss VSH170AGANA Installation guide

INSTRUCTIONS
VSH COMPRESSORS
A
B
C
D E
F
G
Oil injection control assembly
3 2 1
Oil injection
control valve
A: Model number B: Serial number C: Refrigerant D: Supply voltage & Locked rotor current
70
65
60
55
50
45
(°C)
C
T
40
35
30
25
20
15
-30 -25 -20 -15 -10 -5 0 5 10 15 20
4
SH=6K
50 - 90 Hz
5 6
E: Housing service pressure F: Factory charged lubricant G: Compressor frequency & Max Must trip cur-
rent
R410A
50 - 90 Hz
30 - 90 Hz
T0 (°C)
Put the clip-on coil (1) with the gasket (2) over the valve body (3) on the compressor
Oil injection control dismantling
1
Attach the connector (4) to the coil using the delivered accessories (5) and (6).
Remove the clip-on coil by using a screw driver.
Under all circumstances, the EN378 (or other applicable local safety regulation) requirements must be fulfilled.
FRCC.EI.005.A3.02 © Danfoss Commercial Compressors 09/10
The compressor is delivered under nitrogen gas pressure (between 0.3 and 0.7 bar) and hence cannot be connected as is; refer to the «assem­bly» section for further details.
220V
2 A max
Wire the connector as indicated.
The compressor must be handled with caution in the vertical position (maximum offset from the vertical : 15°)
RELAY
2
CDS302
Instructions
Basic connections
- Depending on the frequency converter version, the physical position of individual connectors may differ from below diagram.
- Always make sure that the compressor termi­nals T1, T2, T3 are connected to the frequency converter terminals 96, 97, 98 respectively.
- The compressor motor cable must be shielded
L1 91 L1 W 98 T3
L2 92 L2 V 97 T2
L3 93 L3 U 96 T1
95 PE PE 99
39 39 Ana out COM
42 42 Ana out +
50 50 Ana in +10 V NC 03
53 53 Ana in 0 ± 10 V NO 02
54 54 Ana in 0 ± 10 V COM 01
55 55 Ana in COM
12 12 +24V COM 04
13 13 +24V
18 18 Dig in
19 19 Dig in
27 27 Dig in/out
29 29 Dig in/out
32 32 Dig in N- RS485 69 69
33 33 Dig in P+ RS485 68 68
20 20 Dig in COM COM RS485 61 61
37 37 Dig in
and the armoured part must be connected to ground on both cable ends; at the side of the compressor and at the side of the frequency converter.
- Use an EMC cable gland for cable installation and perfect grounding; The metallic terminal box of the compressor has a paint-free surface around
1
RELAY
NC 06
NO 05
the connection hole for better conductivity.
- A low pressure safety switch is mandatory
to avoid compressor vacuum operation.
- At start-up, verfiy that the compressor rotates in the right direction and pumps.
Legends: Ana: Analogue Dig: Digital in: Input out: Output COM: Common NC: Normally-closed NO: Normally-open
230 V
2 A max
91, 92, 93: 3 Phase mains input X X
Open loop Process loop
95: Earth X X 39, 42 Analogue output - ­50: Analogue input - ­53: PLC+ (0 to 10 V) X ­54: Sensor - - X 55: PLC- X ­12: HP/LP switch X X 12: External On/Off (NO) X X 13: Factory bridged to 37 X X 13: Sensor + - X 18: External On/Off (NO) X X 19: Digital input - ­27: HP/LP switch (NC) / safety devices X X 29: Digital input/output - ­32, 33 Digital input - ­20: Digital input Common - ­37: Factory bridged to 13 X X 98: To compressor terminal T3 X X 97: To compressor terminal T2 X X 96: To compressor terminal T1 X X 99: To compressor earth connection X X 02, 01: Relay 1 to oil solenoid valve X X 06, 05, 04: Relay 2 - ­69, 68: RS485 Bus - ­61: RS485 Bus Common - -
- Optional connection X : Mandatory connection
The CDS302 frequency converter is factory pre­set with parameters for the open loop control principle. The process loop control principle can be selected by changing parameters in the «Quick menu».
Open loop:
0 - 10 V control Frequency converter in slave mode
Process loop:
4 - 20 mA control Frequency converter under own PID controller
2
FRCC.EI.005.A3.02 © Danfoss Commercial Compressors 09/10