Copyright, Limitation of Liability and Revision Rights3
Approvals4
Symbols4
Abbreviations5
Definitions5
2. Introduction to VLT HVAC Drive
Safety11
CE labelling12
Air humidity13
Aggressive Environments14
Vibration and shock14
VLT HVAC Drive Controls28
PID30
General aspects of EMC39
Galvanic isolation (PELV)41
PELV - Protective Extra Low Voltage41
3
11
Control with brake function42
Extreme running conditions45
Safe Stop48
3. VLT HVAC Drive Selection
Options and Accessories51
4. How to Order
Ordering Numbers63
5. How to Install
Mechanical Dimensions72
Electrical Installation79
Final Set-Up and Test104
Additional Connections106
DC bus connection106
Brake Connection Option106
Relay Connection107
Installation of misc. connections111
51
61
71
Safety113
EMC-correct Installation114
Mains supply interference/Harmonics118
Residual Current Device
MG.11.B7.02 - VLT® is a registered Danfoss trademark
118
1
ContentsVLT® HVAC Drive Design Guide
6. Application Examples
Start/Stop119
Pulse Start/Stop119
Potentiometer Reference120
Automatic Motor Adaptation (AMA)120
Smart Logic Control Programming120
SLC Application Example121
BASIC Cascade Controller122
Pump Staging with Lead Pump Alternation123
System Status and Operation123
Fixed Variable Speed Pump Wiring Diagram124
Lead Pump Alternation Wiring Diagram124
Cascade Controller Wiring Diagram124
Start/Stop conditions125
7. RS-485 Installation and Set-up
RS-485 Installation and Set-up127
FC Protocol Overview129
119
127
Network Configuration130
FC Protocol Message Framing Structure130
Examples
Modbus RTU Overview135
Modbus RTU Message Framing Structure137
How to Access Parameters140
Examples142
Danfoss FC Control Profile148
8. General Specifications and Troubleshooting
General Specifications153
Efficiency164
Acoustic noise165
Peak voltage on motor165
Special Conditions166
Alarms and warnings167
Alarm words171
Warning words172
134
153
Extended status words173
Fault messages174
Index
2
MG.11.B7.02 - VLT® is a registered Danfoss trademark
177
VLT® HVAC Drive Design Guide1. How to Read this Design Guide
1. How to Read this Design Guide
1
VLT HVAC Drive
FC 100 Series
Software version: 2.8.x
This guide can be used with all VLT HVAC Drive frequency converters
with software version 2.8.x.
The actual software version number can be read from
par. 15-43 Software
1.1.1. Copyright, Limitation of Liability and Revision Rights
This publication contains information proprietary to Danfoss. By accepting and using this manual the user agrees that the information contained herein
will be used solely for operating equipment from Danfoss or equipment from other vendors provided that such equipment is intended for communication
with Danfoss equipment over a serial communication link. This publication is protected under the Copyright laws of Denmark and most other countries.
Danfoss does not warrant that a software program produced according to the guidelines provided in this manual will function properly in every physical,
hardware or software environment.
Although Danfoss has tested and reviewed the documentation within this manual, Danfoss makes no warranty or representation, neither expressed nor
implied, with respect to this documentation, including its quality, performance, or fitness for a particular purpose.
In no event shall Danfoss be liable for direct, indirect, special, incidental, or consequential damages arising out of the use, or the inability to use information
contained in this manual, even if advised of the possibility of such damages. In particular, Danfoss is not responsible for any costs, including but not
limited to those incurred as a result of lost profits or revenue, loss or damage of equipment, loss of computer programs, loss of data, the costs to substitute
these, or any claims by third parties.
Version
.
Danfoss reserves the right to revise this publication at any time and to make changes to its contents without prior notice or any obligation to notify former
or present users of such revisions or changes.
MG.11.B7.02 - VLT® is a registered Danfoss trademark
3
1. How to Read this Design GuideVLT® HVAC Drive Design Guide
1.1.2. Available Literature
1
-Operating Instructions MG.11.Ax.yy provide the neccessary information for getting the frequency converter up and running.
-Design Guide MG.11.Bx.yy entails all technical information about the frequency converter and customer design and applications.
-Programming Guide MG.11.Cx.yy provides information on how to programme and includes complete parameter descriptions.
-Mounting Instruction, Analog I/O Option MCB109, MI.38.Bx.yy
-
PC-based Configuration Tool MCT 10, MG.10.Ax.yy enables the user to configure the frequency converter from a Windows
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide1. How to Read this Design Guide
1.1.5. Abbreviations
1
Alternating currentAC
American wire gaugeAWG
Ampere/AMPA
Automatic Motor AdaptationAMA
Current limitI
Degrees Celsius°C
Direct currentDC
Drive DependentD-TYPE
Electro Magnetic CompatibilityEMC
Electronic Thermal RelayETR
driveFC
Gramg
HertzHz
KilohertzkHz
Local Control Panel
Meterm
Millihenry InductancemH
MilliamperemA
Millisecondms
Minutemin
Motion Control ToolMCT
NanofaradnF
Newton MetersNm
Nominal motor currentI
Nominal motor frequencyf
Nominal motor powerP
Nominal motor voltageU
Parameterpar.
Protective Extra Low VoltagePELV
Printed Circuit BoardPCB
Rated Inverter Output CurrentI
Revolutions Per MinuteRPM
Regenerative terminalsRegen
Seconds
Synchronous Motor Speedn
Torque limitT
VoltsV
LIM
M,N
M,N
M,N
M,N
INV
s
LIM
1.1.6. Definitions
Drive:
I
VLT,MAX
The maximum output current.
I
VLT,N
The rated output current supplied by the frequency converter.
U
VLT, MAX
The maximum output voltage.
Input:
Control command
You can start and stop the connected motor by means of
LCP and the digital inputs.
Functions are divided into two groups.
Functions in group 1 have higher priority than functions in
group 2.
Motor:
Group 1
Group 2
Reset, Coasting stop, Reset and Coasting stop, Quickstop, DC braking, Stop and the "Off" key.
Start, Pulse start, Reversing, Start reversing, Jog and
Freeze output
f
JOG
The motor frequency when the jog function is activated (via digital terminals).
MG.11.B7.02 - VLT® is a registered Danfoss trademark
5
1. How to Read this Design GuideVLT® HVAC Drive Design Guide
f
M
The motor frequency.
1
f
MAX
The maximum motor frequency.
f
MIN
The minimum motor frequency.
f
M,N
The rated motor frequency (nameplate data).
I
M
The motor current.
I
M,N
The rated motor current (nameplate data).
n
M,N
The rated motor speed (nameplate data).
P
M,N
The rated motor power (nameplate data).
T
M,N
The rated torque (motor).
U
M
The instantaneous motor voltage.
U
M,N
The rated motor voltage (nameplate data).
Break-away torque
η
VLT
The efficiency of the frequency converter is defined as the ratio between the power output and the power input.
Start-disable command
A stop command belonging to the group 1 control commands - see this group.
Stop command
See Control commands.
6
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide1. How to Read this Design Guide
References:
Analog Reference
A signal transmitted to the analog inputs 53 or 54, can be voltage or current.
Bus Reference
A signal transmitted to the serial communication port (FC port).
Preset Reference
A defined preset reference to be set from -100% to +100% of the reference range. Selection of eight preset references via the digital terminals.
Pulse Reference
A pulse frequency signal transmitted to the digital inputs (terminal 29 or 33).
Ref
MAX
Determines the relationship between the reference input at 100% full scale value (typically 10 V, 20mA) and the resulting reference. The maximum
reference value set in par. 3-03.
Ref
MIN
Determines the relationship between the reference input at 0% value (typically 0V, 0mA, 4mA) and the resulting reference. The minimum reference value
set in par. 3-02.
Miscellaneous:
Analog Inputs
The analog inputs are used for controlling various functions of the frequency converter.
There are two types of analog inputs:
Current input, 0-20 mA and 4-20 mA
Voltage input, 0-10 V DC.
1
Analog Outputs
The analog outputs can supply a signal of 0-20 mA, 4-20 mA, or a digital signal.
Automatic Motor Adaptation, AMA
AMA algorithm determines the electrical parameters for the connected motor at standstill.
Brake Resistor
The brake resistor is a module capable of absorbing the brake power generated in regenerative braking. This regenerative braking power increases the
intermediate circuit voltage and a brake chopper ensures that the power is transmitted to the brake resistor.
CT Characteristics
Constant torque characteristics used for screw and scroll refrigeration compressors.
Digital Inputs
The digital inputs can be used for controlling various functions of the frequency converter.
Digital Outputs
The frequency converter features two Solid State outputs that can supply a 24 V DC (max. 40 mA) signal.
DSP
Digital Signal Processor.
Relay Outputs:
The frequency converter features two programmable Relay Outputs.
MG.11.B7.02 - VLT® is a registered Danfoss trademark
7
1. How to Read this Design GuideVLT® HVAC Drive Design Guide
ETR
Electronic Thermal Relay is a thermal load calculation based on present load and time. Its purpose is to estimate the motor temperature.
1
GLCP:
Graphical Local Control Panel (LCP102)
Initialising
If initialising is carried out (par. 14-22), the programmable parameters of the frequency converter return to their default settings.
Intermittent Duty Cycle
An intermittent duty rating refers to a sequence of duty cycles. Each cycle consists of an on-load and an off-load period. The operation can be either
periodic duty or none-periodic duty.
LCP
The Local Control Panel (LCP) makes up a complete interface for control and programming of the frequency converter. The control panel is detachable
and can be installed up to 3 metres from the frequency converter, i.e. in a front panel by means of the installation kit option.
The Local Control Panel is available in two versions:
-Numerical LCP101 (NLCP)
-Graphical LCP102 (GLCP)
lsb
Least significant bit.
MCM
Short for Mille Circular Mil, an American measuring unit for cable cross-section. 1 MCM 0.5067 mm
2
.
msb
Most significant bit.
NLCP
Numerical Local Control Panel LCP101
On-line/Off-line Parameters
Changes to on-line parameters are activated immediately after the data value is changed. Changes to off-line parameters are not activated until you enter
[OK] on the LCP.
PID Controller
The PID controller maintains the desired speed, pressure, temperature, etc. by adjusting the output frequency to match the varying load.
RCD
Residual Current Device.
Set-up
You can save parameter settings in four Set-ups. Change between the four parameter Set-ups and edit one Set-up, while another Set-up is active.
SFAVM
Switching pattern called
Slip Compensation
The frequency converter compensates for the motor slip by giving the frequency a supplement that follows the measured motor load keeping the motor
speed almost constant..
Stator Flux oriented Asynchronous V ector M odulation (par. 14-00).
Smart Logic Control (SLC)
The SLC is a sequence of user defined actions executed when the associated user defined events are evaluated as true by the SLC.
8
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide1. How to Read this Design Guide
Thermistor:
A temperature-dependent resistor placed where the temperature is to be monitored (frequency converter or motor).
Trip
A state entered in fault situations, e.g. if the frequency converter is subject to an over-temperature or when the frequency converter is protecting the
motor, process or mechanism. Restart is prevented until the cause of the fault has disappeared and the trip state is cancelled by activating reset or, in
some cases, by being programmed to reset automatically. Trip may not be used for personal safety.
Trip Locked
A state entered in fault situations when the frequency converter is protecting itself and requiring physical intervention, e.g. if the frequency converter is
subject to a short circuit on the output. A locked trip can only be cancelled by cutting off mains, removing the cause of the fault, and reconnecting the
frequency converter. Restart is prevented until the trip state is cancelled by activating reset or, in some cases, by being programmed to reset automatically.
Trip locked may not be used for personal safety.
VT Characteristics
Variable torque characteristics used for pumps and fans.
plus
VVC
If compared with standard voltage/frequency ratio control, Voltage Vector Control (VVC
reference is changed and in relation to the load torque.
60° AVM
Switching pattern called 60°
Asynchronous Vector Modulation (See par. 14-00).
plus
) improves the dynamics and the stability, both when the speed
1.1.7. Power Factor
1
The power factor is the relation between I1 and I
The power factor for 3-phase control:
The power factor indicates to which extent the frequency converter im-
poses a load on the mains supply.
The lower the power factor, the higher the I
formance.
In addition, a high power factor indicates that the different harmonic currents are low.
The frequency converters' built-in DC coils produce a high power factor, which minimises the imposed load on the mains supply.
.
RMS
for the same kW per-
RMS
Power factor
I
cos
×
1
=
I
RMS
I
RMS
2
=
I
1
=
ϕ1
+
=
I
3×U×
3×U×
I
1
I
RMS
2
2
I
+
5
7
I
1×
since cos
+..+
COS
I
RMS
ϕ1=1
ϕ
2
I
n
MG.11.B7.02 - VLT® is a registered Danfoss trademark
9
2
2. Introduction to VLT HVAC DriveVLT® HVAC Drive Design Guide
10
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide2. Introduction to VLT HVAC Drive
2. Introduction to VLT HVAC Drive
2.1. Safety
2.1.1. Safety note
The voltage of the frequency converter is dangerous whenever connected to mains. Incorrect installation of the motor, frequency
converter or fieldbus may cause damage to the equipment, serious personal injury or death. Consequently, the instructions in this
manual, as well as national and local rules and safety regulations, must be complied with.
Safety Regulations
1.The frequency converter must be disconnected from mains if repair work is to be carried out. Check that the mains supply has been disconnected
and that the necessary time has passed before removing motor and mains plugs.
2.The [STOP/RESET] key on the control panel of the frequency converter does not disconnect the equipment from mains and is thus not to be
used as a safety switch.
3.Correct protective earthing of the equipment must be established, the user must be protected against supply voltage, and the motor must be
protected against overload in accordance with applicable national and local regulations.
4.The earth leakage currents are higher than 3.5 mA.
5.Protection against motor overload is set by par. 1-90
(default value) or data value [ETR warning]. Note: The function is initialised at 1.16 x rated motor current and rated motor frequency. For the
North American market: The ETR functions provide class 20 motor overload protection in accordance with NEC.
6.Do not remove the plugs for the motor and mains supply while the frequency converter is connected to mains. Check that the mains supply has
been disconnected and that the necessary time has passed before removing motor and mains plugs.
7.Please note that the frequency converter has more voltage inputs than L1, L2 and L3, when load sharing (linking of DC intermediate circuit) and
external 24 V DC have been installed. Check that all voltage inputs have been disconnected and that the necessary time has passed before
commencing repair work.
Installation at High Altitudes
Motor Thermal Protection
. If this function is desired, set par. 1-90 to data value [ETR trip]
2
By altitudes above 2 km, please contact Danfoss regarding PELV.
Warning against Unintended Start
1.The motor can be brought to a stop by means of digital commands, bus commands, references or a local stop, while the frequency converter
is connected to mains. If personal safety considerations make it necessary to ensure that no unintended start occurs, these stop functions are
not sufficient.
2.While parameters are being changed, the motor may start. Consequently, the stop key [STOP/RESET] must always be activated; following which
data can be modified.
3.A motor that has been stopped may start if faults occur in the electronics of the frequency converter, or if a temporary overload or a fault in
the supply mains or the motor connection ceases.
Warning:
Touching the electrical parts may be fatal - even after the equipment has been disconnected from mains.
Also make sure that other voltage inputs have been disconnected, such as external 24 V DC, load sharing (linkage of DC intermediate circuit), as well as
the motor connection for kinetic back up. Refer to
MG.11.B7.02 - VLT® is a registered Danfoss trademark
11
2
2. Introduction to VLT HVAC DriveVLT® HVAC Drive Design Guide
2.1.2. Caution
Caution
The frequency converter DC link capacitors remain charged after power has been disconnected. To avoid an electrical shock hazard, disconnect the
frequency converter from the mains before carrying out maintenance. Wait at least as follows before doing service on the frequency converter:
Be aware that there may be high voltage on the DC link even when the LEDs are turned off.
Minimum Waiting Time
Equipment containing electrical components may not be disposed of together with domestic
waste.
It must be separately collected with electrical and electronic waste according to local and currently
valid legislation.
2.2. CE labelling
2.2.1. CE Conformity and Labelling
What is CE Conformity and Labelling?
The purpose of CE labelling is to avoid technical trade obstacles within EFTA and the EU. The EU has introduced the CE label as a simple way of showing
whether a product complies with the relevant EU directives. The CE label says nothing about the specifications or quality of the product. Frequency
converters are regulated by three EU directives:
The machinery directive (98/37/EEC)
All machines with critical moving parts are covered by the machinery directive of January 1, 1995. Since a frequency converter is largely electrical, it does
not fall under the machinery directive. However, if a frequency converter is supplied for use in a machine, we provide information on safety aspects
relating to the frequency converter. We do this by means of a manufacturer's declaration.
The low-voltage directive (73/23/EEC)
Frequency converters must be CE labelled in accordance with the low-voltage directive of January 1, 1997. The directive applies to all electrical equipment
and appliances used in the 50 - 1000 V AC and the 75 - 1500 V DC voltage ranges. Danfoss CE-labels in accordance with the directive and issues a
declaration of conformity upon request.
The EMC directive (89/336/EEC)
EMC is short for electromagnetic compatibility. The presence of electromagnetic compatibility means that the mutual interference between different
components/appliances does not affect the way the appliances work.
The EMC directive came into effect January 1, 1996. Danfoss CE-labels in accordance with the directive and issues a declaration of conformity upon
request. To carry out EMC-correct installation, see the instructions in this Design Guide. In addition, we specify which standards our products comply
with. We offer the filters presented in the specifications and provide other types of assistance to ensure the optimum EMC result.
The frequency converter is most often used by professionals of the trade as a complex component forming part of a larger appliance, system or installation.
It must be noted that the responsibility for the final EMC properties of the appliance, system or installation rests with the installer.
12
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide2. Introduction to VLT HVAC Drive
2.2.2. What Is Covered
The EU "
Guidelines on the Application of Council Directive 89/336/EEC
coverage and CE labelling.
" outline three typical situations of using a frequency converter. See below for EMC
1.The frequency converter is sold directly to the end-consumer. The frequency converter is for example sold to a DIY market. The end-consumer
is a layman. He installs the frequency converter himself for use with a hobby machine, a kitchen appliance, etc. For such applications, the
frequency converter must be CE labelled in accordance with the EMC directive.
2.The frequency converter is sold for installation in a plant. The plant is built up by professionals of the trade. It could be a production plant or a
heating/ventilation plant designed and installed by professionals of the trade. Neither the frequency converter nor the finished plant has to be
CE labelled under the EMC directive. However, the unit must comply with the basic EMC requirements of the directive. This is ensured by using
components, appliances, and systems that are CE labelled under the EMC directive.
3.The frequency converter is sold as part of a complete system. The system is being marketed as complete and could e.g. be an air-conditioning
system. The complete system must be CE labelled in accordance with the EMC directive. The manufacturer can ensure CE labelling under the
EMC directive either by using CE labelled components or by testing the EMC of the system. If he chooses to use only CE labelled components,
he does not have to test the entire system.
2.2.3. Danfoss Frequency Converter and CE Labelling
CE labelling is a positive feature when used for its original purpose, i.e. to facilitate trade within the EU and EFTA.
However, CE labelling may cover many different specifications. Thus, you have to check what a given CE label specifically covers.
The covered specifications can be very different and a CE label may therefore give the installer a false feeling of security when using a frequency converter
as a component in a system or an appliance.
Danfoss CE labels the frequency converters in accordance with the low-voltage directive. This means that if the frequency converter is installed correctly,
we guarantee compliance with the low-voltage directive. Danfoss issues a declaration of conformity that confirms our CE labelling in accordance with the
low-voltage directive.
2
The CE label also applies to the EMC directive provided that the instructions for EMC-correct installation and filtering are followed. On this basis, a
declaration of conformity in accordance with the EMC directive is issued.
The Design Guide offers detailed instructions for installation to ensure EMC-correct installation. Furthermore, Danfoss specifies which our different prod-
ucts comply with.
Danfoss gladly provides other types of assistance that can help you obtain the best EMC result.
2.2.4. Compliance with EMC Directive 89/336/EEC
As mentioned, the frequency converter is mostly used by professionals of the trade as a complex component forming part of a larger appliance, system,
or installation. It must be noted that the responsibility for the final EMC properties of the appliance, system or installation rests with the installer. As an
aid to the installer, Danfoss has prepared EMC installation guidelines for the Power Drive system. The standards and test levels stated for Power Drive
systems are complied with, provided that the EMC-correct instructions for installation are followed, see the section
EMC Immunity
.
2.3. Air humidity
2.3.1. Air Humidity
The frequency converter has been designed to meet the IEC/EN 60068-2-3 standard, EN 50178 pkt. 9.4.2.2 at 50°C.
MG.11.B7.02 - VLT® is a registered Danfoss trademark
13
2. Introduction to VLT HVAC DriveVLT® HVAC Drive Design Guide
2.4. Aggressive Environments
A frequency converter contains a large number of mechanical and electronic components. All are to some extent vulnerable to environmental effects.
2
The frequency converter should not be installed in environments with airborne liquids, particles, or gases capable of affecting and
damaging the electronic components. Failure to take the necessary protective measures increases the risk of stoppages, thus reducing
the life of the frequency converter.
Liquids can be carried through the air and condense in the frequency converter and may cause corrosion of components and metal parts. Steam, oil, and
salt water may cause corrosion of components and metal parts. In such environments, use equipment with enclosure rating IP 54/55. As an extra
protection, coated printet circuit boards can be orded as an option.
Particles such as dust may cause mechanical, electrical, or thermal failure in the frequency converter. A typical indicator of excessive levels of
Airborne
airborne particles is dust particles around the frequency converter fan. In very dusty environments, use equipment with enclosure rating IP 54/55 or a
cabinet for IP 00/IP 20/TYPE 1 equipment.
In environments with high temperatures and humidity,
on the frequency converter components.
Such chemical reactions will rapidly affect and damage the electronic components. In such environments, mount the equipment in a cabinet with fresh
air ventilation, keeping aggressive gases away from the frequency converter.
An extra protection in such areas is a coating of the printed circuit boards, which can be ordered as an option.
NB!
Mounting frequency converters in aggressive environments increases the risk of stoppages and considerably reduces the life of the
converter.
corrosive gases such as sulphur, nitrogen, and chlorine compounds will cause chemical processes
Before installing the frequency converter, check the ambient air for liquids, particles, and gases. This is done by observing existing installations in this
environment. Typical indicators of harmful airborne liquids are water or oil on metal parts, or corrosion of metal parts.
Excessive dust particle levels are often found on installation cabinets and existing electrical installations. One indicator of aggressive airborne gases is
blackening of copper rails and cable ends on existing installations.
2.5. Vibration and shock
The frequency converter has been tested according to the procedure based on the shown standards:
The frequency converter complies with requirements that exist for units mounted on the walls and floors of production premises, as well as in panels
bolted to walls or floors.
IEC/EN 60068-2-6:Vibration (sinusoidal) - 1970
IEC/EN 60068-2-64:Vibration, broad-band random
14
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide2. Introduction to VLT HVAC Drive
2.6. Advantages
2.6.1. Why use a frequency converter for controlling fans and pumps?
A frequency converter takes advantage of the fact that centrifugal fans and pumps follow the laws of proportionality for such fans and pumps. For further
information see the text
The Laws of Proportionality
.
2.6.2. The clear advantage - energy savings
The very clear advantage of using a frequency converter for controlling the speed of fans or pumps lies in the electricity savings.
When comparing with alternative control systems and technologies, a frequency converter is the optimum energy control system for controlling fan and
pump systems.
Illustration 2.1: The graph is showing fan curves (A, B and C) for re-
duced fan volumes.
2
Illustration 2.2: When using a frequency converter to reduce fan ca-
pacity to 60% - more than 50% energy savings may be obtained in
typical applications.
2.6.3. Example of energy savings
As can be seen from the figure (the laws of proportionality), the flow is controlled by changing the rpm. By reducing the speed only 20% from the rated
speed, the flow is also reduced by 20%. This is because the flow is directly proportional to the rpm. The consumption of electricity, however, is reduced
by 50%.
If the system in question only needs to be able to supply a flow that corresponds to 100% a few days in a year, while the average is below 80% of the
rated flow for the remainder of the year, the amount of energy saved is even more than 50%.
MG.11.B7.02 - VLT® is a registered Danfoss trademark
15
2
2. Introduction to VLT HVAC DriveVLT® HVAC Drive Design Guide
The laws of proportionality
The figure below describes the dependence of flow, pressure and power consumption on rpm.
Q = FlowP = Power
Q1 = Rated flowP1 = Rated power
Q
= Reduced flowP2 = Reduced power
2
H = Pressuren = Speed regulation
H1 = Rated pressuren1 = Rated speed
H
= Reduced pressuren2 = Reduced speed
2
2.6.4. Comparison of energy savings
The Danfoss frequency converter solution offers major savings compared
with traditional energy saving solutions. This is because the frequency
converter is able to control fan speed according to thermal load on the
system and the fact that the frequency converter has a build-in facility
that enables the frequency converter to function as a Building Manage-
ment System, BMS.
Flow
:
Pressure
Power
Q
Q
:
:
n
1
2
P
P
1
=
n
2
H
H
1
2
n
(
2
1
(
)
n
2
n
3
1
)
n
2
1
=
2
=
The graph below illustrates typical energy savings obtainable with 3 well-
known solutions when fan volume is reduced to i.e. 60%.
As the graph shows, more than 50% energy savings can be achieved in
typical applications.
16
MG.11.B7.02 - VLT® is a registered Danfoss trademark
Illustration 2.3: The three common energy saving systems.
VLT® HVAC Drive Design Guide2. Introduction to VLT HVAC Drive
2
Illustration 2.4: Discharge dampers reduce power consumption somewhat. Inlet Guide Vans offer a 40% reduction but are expensive to install. The
Danfossfrequency converter solution reduces energy consumption with more than 50% and is easy to install.
2.6.5. Example with varying flow over 1 year
The example below is calculated on the basis of pump characteristics ob-
tained from a pump datasheet.
The result obtained shows energy savings in excess of 50% at the given
flow distribution over a year. The pay back period depends on the price
per kwh and price of frequency converter. In this example it is less than
a year when compared with valves and constant speed.
Energy savings
P
shaft=Pshaft output
Flow distribution over 1 year
MG.11.B7.02 - VLT® is a registered Danfoss trademark
17
2
2. Introduction to VLT HVAC DriveVLT® HVAC Drive Design Guide
m3/h
DistributionValve regulationFrequency converter control
%HoursPowerConsumptionPowerConsumption
A1 - B
If a frequency converter is used for controlling the flow or pressure of a system, improved control is obtained.
A frequency converter can vary the speed of the fan or pump, thereby obtaining variable control of flow and pressure.
Furthermore, a frequency converter can quickly adapt the speed of the fan or pump to new flow or pressure conditions in the system.
Simple control of process (Flow, Level or Pressure) utilizing the built in PID control.
kWh
18
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide2. Introduction to VLT HVAC Drive
2.6.7. Cos φ compensation
Generally speaking, a frequency converter with a cos φ of 1 provides power factor correction for the cos φ of the motor, which means that there is no
need to make allowance for the cos φ of the motor when sizing the power factor correction unit.
2.6.8. Star/delta starter or soft-starter not required
When larger motors are started, it is necessary in many countries to use equipment that limits the start-up current. In more traditional systems, a star/
delta starter or soft-starter is widely used. Such motor starters are not required if a frequency converter is used.
As illustrated in the figure below, a frequency converter does not consume more than rated current.
1 = VLT HVAC Drive
2 = Star/delta starter
3 = Soft-starter
4 = Start directly on mains
2.6.9. Using a frequency converter saves money
The example on the following page shows that a lot of equipment is not required when a frequency converter is used. It is possible to calculate the cost
of installing the two different systems. In the example on the following page, the two systems can be established at roughly the same price.
2
2.6.10. Without a frequency converter
The figure shows a fan system made in the traditional way.
D.D.C.=Direct Digital ControlE.M.S.=Energy Management system
V.A.V.=Variable Air Volume
Sensor P=PressureSensor T=Temperature
MG.11.B7.02 - VLT® is a registered Danfoss trademark
19
2
2. Introduction to VLT HVAC DriveVLT® HVAC Drive Design Guide
2.6.11. With a frequency converter
The figure shows a fan system controlled by frequency converters.
20
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide2. Introduction to VLT HVAC Drive
2.6.12. Application examples
The next few pages give typical examples of applications within HVAC.
If you would like to receive further information about a given application, please ask your Danfoss supplier for an information sheet that gives a full
description of the application.
Variable Air Volume
Ask for The Drive to...Improving Variable Air Volume Ventilation Systems MN.60.A1.02
Constant Air Volume
Ask for The Drive to...Improving Constant Air Volume Ventilation Systems MN.60.B1.02
Cooling Tower Fan
Ask for The Drive to...Improving fan control on cooling towers MN.60.C1.02
Condenser pumps
Ask for The Drive to...Improving condenser water pumping systems MN.60.F1.02
Primary pumps
Ask for The Drive to...Improve your primary pumping in primay/secondary pumping systems MN.60.D1.02
Secondary pumps
Ask for The Drive to...Improve your secondary pumping in primay/secondary pumping systems MN.60.E1.02
2
MG.11.B7.02 - VLT® is a registered Danfoss trademark
21
2
2. Introduction to VLT HVAC DriveVLT® HVAC Drive Design Guide
2.6.13. Variable Air Volume
VAV or Variable Air Volume systems, are used to control both the ventilation and temperature to satisfy the requirements of a building. Central VAV
systems are considered to be the most energy efficient method to air condition buildings. By designing central systems instead of distributed systems, a
greater efficiency can be obtained.
The efficiency comes from utilizing larger fans and larger chillers which have much higher efficiencies than small motors and distributed air-cooled chillers.
Savings are also seen from the decreased maintenance requirements.
2.6.14. The VLT solution
While dampers and IGVs work to maintain a constant pressure in the ductwork, a frequency converter solution saves much more energy and reduces
the complexity of the installation. Instead of creating an artificial pressure drop or causing a decrease in fan efficiency, the frequency converter decreases
the speed of the fan to provide the flow and pressure required by the system.
Centrifugal devices such as fans behave according to the centrifugal laws. This means the fans decrease the pressure and flow they produce as their
speed is reduced. Their power consumption is thereby significantly reduced.
The return fan is frequently controlled to maintain a fixed difference in airflow between the supply and return. The advanced PID controller of the HVAC
frequency converter can be used to eliminate the need for additional controllers.
Pressure
Cooling coil
D1
D2
Heating coil
Filter
signal
Supply fan
3
Flow
Pressure
transmitter
VAV boxes
T
Return fan
D3
Flow
3
22
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide2. Introduction to VLT HVAC Drive
2.6.15. Constant Air Volume
CAV, or Constant Air Volume systems are central ventilation systems usually used to supply large common zones with the minimum amounts of fresh
tempered air. They preceded VAV systems and therefore are found in older multi-zoned commercial buildings as well. These systems preheat amounts
of fresh air utilizing Air Handling Units (AHUs) with a heating coil, and many are also used to air condition buildings and have a cooling coil. Fan coil units
are frequently used to assist in the heating and cooling requirements in the individual zones.
2.6.16. The VLT solution
2
With a frequency converter, significant energy savings can be obtained while maintaining decent control of the building. Temperature sensors or CO
sensors can be used as feedback signals to frequency converters. Whether controlling temperature, air quality, or both, a CAV system can be controlled
to operate based on actual building conditions. As the number of people in the controlled area decreases, the need for fresh air decreases. The CO
sensor detects lower levels and decreases the supply fans speed. The return fan modulates to maintain a static pressure setpoint or fixed difference
between the supply and return air flows.
With temperature control, especially used in air conditioning systems, as the outside temperature varies as well as the number of people in the controlled
zone changes, different cooling requirements exist. As the temperature decreases below the set-point, the supply fan can decrease its speed. The return
fan modulates to maintain a static pressure set-point. By decreasing the air flow, energy used to heat or cool the fresh air is also reduced, adding further
savings.
Several features of the Danfoss HVAC dedicated frequency converter can be utilized to improve the performance of your CAV system. One concern of
controlling a ventilation system is poor air quality. The programmable minimum frequency can be set to maintain a minimum amount of supply air
regardless of the feedback or reference signal. The frequency converter also includes a 3-zone, 3 setpoint PID controller which allows monitoring both
temperature and air quality. Even if the temperature requirement is satisfied, the frequency converter will maintain enough supply air to satisfy the air
quality sensor. The controller is capable of monitoring and comparing two feedback signals to control the return fan by maintaining a fixed differential
air flow between the supply and return ducts as well.
Temperature
Cooling coil
D1
Heating coil
Filter
signal
Supply fan
Temperature
transmitter
2
2
D2
D3
Pressure
signal
Return fan
Pressure
transmitter
MG.11.B7.02 - VLT® is a registered Danfoss trademark
23
2
2. Introduction to VLT HVAC DriveVLT® HVAC Drive Design Guide
2.6.17. Cooling Tower Fan
Cooling Tower Fans are used to cool condenser water in water cooled chiller systems. Water cooled chillers provide the most efficient means of creating
chilled water. They are as much as 20% more efficient than air cooled chillers. Depending on climate, cooling towers are often the most energy efficient
method of cooling the condenser water from chillers.
They cool the condenser water by evaporation.
The condenser water is sprayed into the cooling tower onto the cooling towers “fill” to increase its surface area. The tower fan blows air through the fill
and sprayed water to aid in the evaporation. Evaporation removes energy from the water dropping its temperature. The cooled water collects in the
cooling towers basin where it is pumped back into the chillers condenser and the cycle is repeated.
2.6.18. The VLT solution
With a frequency converter, the cooling towers fans can be controlled to the required speed to maintain the condenser water temperature. The frequency
converters can also be used to turn the fan on and off as needed.
Several features of the Danfoss HVAC dedicated frequency converter, the HVAC frequency converter can be utilized to improve the performance of your
cooling tower fans application. As the cooling tower fans drop below a certain speed, the effect the fan has on cooling the water becomes small. Also,
when utilizing a gear-box to frequency control the tower fan, a minimum speed of 40-50% may be required.
The customer programmable minimum frequency setting is available to maintain this minimum frequency even as the feedback or speed reference calls
for lower speeds.
Also as a standard feature, you can program the frequency converter to enter a “sleep” mode and stop the fan until a higher speed is required. Additionally,
some cooling tower fans have undesireable frequencies that may cause vibrations. These frequencies can easily be avoided by programming the bypass
frequency ranges in the frequency converter.
Water Inlet
Temperature
Sensor
BASIN
Water Outlet
Conderser
Water pump
CHILLER
Supply
24
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide2. Introduction to VLT HVAC Drive
2.6.19. Condenser pumps
Condenser Water pumps are primarily used to circulate water through the condenser section of water cooled chillers and their associated cooling tower.
The condenser water absorbs the heat from the chiller's condenser section and releases it into the atmosphere in the cooling tower. These systems are
used to provide the most efficient means of creating chilled water, they are as much as 20% more efficient than air cooled chillers.
2.6.20. The VLT solution
Frequency converters can be added to condenser water pumps instead of balancing the pumps with a throttling valve or trimming the pump impeller.
Using a frequency converter instead of a throttling valve simply saves the energy that would have been absorbed by the valve. This can amount to savings
of 15-20% or more. Trimming the pump impeller is irreversible, thus if the conditions change and higher flow is required the impeller must be replaced.
2
MG.11.B7.02 - VLT® is a registered Danfoss trademark
25
2
2. Introduction to VLT HVAC DriveVLT® HVAC Drive Design Guide
2.6.21. Primary pumps
Primary pumps in a primary/secondary pumping system can be used to maintain a constant flow through devices that encounter operation or control
difficulties when exposed to variable flow. The primary/ secondary pumping technique decouples the “primary” production loop from the “secondary”
distribution loop. This allows devices such as chillers to obtain constant design flow and operate properly while allowing the rest of the system to vary in
flow.
As the evaporator flow rate decreases in a chiller, the chilled water begins to become over-chilled. As this happens, the chiller attempts to decrease its
cooling capacity. If the flow rate drops far enough, or too quickly, the chiller cannot shed its load sufficiently and the chiller’s low evaporator tempera-
ture safety trips the chiller requiring a manual reset. This situation is common in large installations especially when two or more chillers in parallel are
installed if primary/ secondary pumping is not utilized.
2.6.22. The VLT solution
Depending on the size of the system and the size of the primary loop, the energy consumption of the primary loop can become substantial.
A frequency converter can be added to the primary system, to replace the throttling valve and/or trimming of the impellers, leading to reduced operating
expenses. Two control methods are common:
The first method uses a flow meter. Because the desired flow rate is known and is constant, a flow meter installed at the discharge of each chiller, can
be used to control the pump directly. Using the built-in PID controller, the frequency converter will always maintain the appropriate flow rate, even
compensating for the changing resistance in the primary piping loop as chillers and their pumps are staged on and off.
The other method is local speed determination. The operator simply decreases the output frequency until the design flow rate is achieved.
Using a frequency converter to decrease the pump speed is very similar to trimming the pump impeller, except it doesn’t require any labor and the pump
efficiency remains higher. The balancing contractor simply decreases the speed of the pump until the proper flow rate is achieved and leaves the speed
fixed. The pump will operate at this speed any time the chiller is staged on. Because the primary loop doesn’t have control valves or other devices that
can cause the system curve to change and the variance due to staging pumps and chillers on and off is usually small, this fixed speed will remain
appropriate. In the event the flow rate needs to be increased later in the systems life, the frequency converter can simply increase the pump speed
instead of requiring a new pump impeller.
Flowmeter
F
CHILLER
Flowmeter
F
CHILLER
26
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide2. Introduction to VLT HVAC Drive
2.6.23. Secondary pumps
Secondary pumps in a primary/secondary chilled water pumping system are used to distribute the chilled water to the loads from the primary production
loop. The primary/secondary pumping system is used to hydronically de-couple one piping loop from another. In this case. The primary pump is used to
maintain a constant flow through the chillers while allowing the secondary pumps to vary in flow, increase control and save energy.
If the primary/secondary design concept is not used and a variable volume system is designed, when the flow rate drops far enough or too quickly, the
chiller cannot shed its load properly. The chiller’s low evaporator temperature safety then trips the chiller requiring a manual reset. This situation is
common in large installations especially when two or more chillers in parallel are installed.
2.6.24. The VLT solution
While the primary-secondary system with two-way valves improves energy savings and eases system control problems, the true energy savings and
control potential is realized by adding frequency converters.
With the proper sensor location, the addition of frequency converters allows the pumps to vary their speed to follow the system curve instead of the
pump curve.
This results in the elimination of wasted energy and eliminates most of the over-pressurization, two-way valves can be subjected too.
As the monitored loads are reached, the two-way valves close down. This increases the differential pressure measured across the load and two-way
va lv e. A s t his di ffe re ntia l p res su re sta rt s to r is e , the p um p is slowed to maintain the control head also called setpoint value. This set-point value is calculated
by summing the pressure drop of the load and two way valve together under design conditions.
2
NB!
Please note that when running multiple pumps in parallel, they must run at the same speed to maximize energy savings, either with
individual dedicated drives or one frequency converter running multiple pumps in parallel.
MG.11.B7.02 - VLT® is a registered Danfoss trademark
27
2. Introduction to VLT HVAC DriveVLT® HVAC Drive Design Guide
2.7. VLT HVAC Drive Controls
2.7.1. Control Principle
2
A frequency converter rectifies AC voltage from mains into DC voltage, after which this DC voltage is converted into a AC current with a variable amplitude
and frequency.
The motor is supplied with variable voltage / current and frequency, which enables infinitely variable speed control of three-phased, standard AC motors.
2.7.2. Control Structure
Control structure in open loop and closed loop configurations:
In the configuration shown in the illustration above, par. 1-00 is set to
received and fed through the ramp limitation and speed limitation before being sent to the motor control. The output of the motor control is then limited
by the maximum frequency limit.
Closed loop
Select
parameters are located in par. group 20-**.
[3] in par. 1-00 to use the PID controller for closed loop control of e.g. flow, level or pressure in the controlled application. The PID
Open loop
[0]. The resulting reference from the reference handling system is
2.7.3. Local (Hand On) and Remote (Auto On) Control
The frequency converter can be operated manually via the local control panel (LCP) or remotely via analog and digital inputs and serial bus.
If allowed in par. 0-40, 0-41, 0-42, and 0-43, it is possible to start and stop the frequency converter via the LCP using the [Hand ON] and [Off] keys.
Alarms can be reset via the [RESET] key. After pressing the [Hand On] key, the frequency converter goes into Hand Mode and follows (as default) the
Local reference set by using the LCP arrow keys.
28
MG.11.B7.02 - VLT® is a registered Danfoss trademark
0
VLT® HVAC Drive Design Guide2. Introduction to VLT HVAC Drive
After pressing the [Auto On] key, the frequency converter goes into Auto
mode and follows (as default) the Remote reference. In this mode, it is
possible to control the frequency converter via the digital inputs and var-
ious serial interfaces (RS-485, USB, or an optional fieldbus). See more
about starting, stopping, changing ramps and parameter set-ups etc. in
par. group 5-1* (digital inputs) or par. group 8-5* (serial communica-
tion).
130BP046.1
Active Reference and Configuration Mode
The active reference can be either the local reference or the remote ref-
erence.
2
In par. 3-13
lected by selecting
To permanently select the remote reference select
lecting
on which mode is active. (Hand Mode or Auto Mode).
Hand Off
Auto
LCP Keys
HandLinked to Hand / AutoLocal
Hand -> OffLinked to Hand / AutoLocal
AutoLinked to Hand / AutoRemote
Auto -> OffLinked to Hand / AutoRemote
All keysLocalLocal
All keysRemoteRemote
The table shows under which conditions either the Local reference or the Remote reference is active. One of them is always active, but both can not be
active at the same time.
NB!
Local Ref. will be restored at power-down.
Reference Site
Par. 3-13
Reference Site
Linked to Hand/Auto
the local reference can be permanently se-
Local
[2].
Remote
[0] (default) the reference site will depend
Active Reference
[1]. By se-
Par. 1-00
is active (see table above for the conditions).
Reference Handling - Local Reference
Configuration Mode
determines what kind of application control principle (i.e. Open Loop or Closed loop) is used when the Remote reference
MG.11.B7.02 - VLT® is a registered Danfoss trademark
29
2. Introduction to VLT HVAC DriveVLT® HVAC Drive Design Guide
2.8. PID
2.8.1. Closed Loop (PID) Controller
2
The frequency converter’s Closed Loop Controller allows the frequency converter to become an integral part of the controlled system. The frequency
converter receives a feedback signal from a sensor in the system. It then compares this feedback to a setpoint reference value and determines the error,
if any, between these two signals. It then adjusts the speed of the motor to correct this error.
For example, consider a ventilation system where the speed of the supply fan is to be controlled so that the static pressure in the duct is constant. The
desired static pressure value is supplied to the frequency converter as the setpoint reference. A static pressure sensor measures the actual static pressure
in the duct and supplies this to the frequency converter as a feedback signal. If the feedback signal is greater than the setpoint reference, the frequency
converter will slow down to reduce the pressure. In a similar way, if the duct pressure is lower than the setpoint reference, the frequency converter will
automatically speed up to increase the pressure provided by the fan.
NB!
While the default values for the frequency converter’s Closed Loop Controller will often provide satisfactory performance, the control
of the system can often be optimized by adjusting some of the Closed Loop Controller’s parameters.
The figure is a block diagram of the frequency converter’s Closed Loop Controller. The details of the Reference Handling block and Feedback Handling
block are described in their respective sections below.
The following parameters are relevant for a simple PID control application:
30
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide2. Introduction to VLT HVAC Drive
ParameterDescription of function
Feedback 1 Sourcepar. 20-00Select the source for Feed back 1 . This is most commonl y an analog inpu t, but other sources are
also available. Use the scaling of this input to provide the appropriate values for this signal. By
default, Analog Input 54 is the default source for Feedback 1.
Reference/Feedback Unitpar 20-12Select the unit for the setpoint referenceand feedback for the frequency converter’s Closed Loop
Controller. Note: Because a conversion can be applied to the feedback signal before it is used
by the Closed Loop Controller, the Reference/Feedback Unit (par. 20-12) may not be the same
as the Feedback Source Unit (par. 20-02, 20-05 and 20-08).
PID Normal/Inverse Controlpar. 20-81Select
PID Proportional Gainpar. 20-93This parameter adjusts the output of the frequency converter’s closed loop controlled based on
PID Integral Timepar. 20-94The integrator adds over time (integrates) the error between the feedback and the setpoint
This table summarizes the parameters that are needed to set up the frequency converter’s Closed Loop Controller when a single feedback signal with no
conversion is compared to a single setpoint. This is the most common type of Closed Loop Controller.
Normal
[0] if the motor’s speed should decrease when the feedback is greater than the
Inverse
setpoint reference. Select
is greater than the setpoint reference.
the error between the feedback and the setpoint reference. Quick controller response is obtained
when this value is large. However, if too large of a value is used, the frequency converter’s output
frequency may become unstable.
reference. This is required to ensure that the error approaches zero. Quick controller response
is obtained when this value is small. However, if too small of a value is used, the frequency
converter’s output frequency may become unstable. A setting of 10000 s disables the integrator.
[1] if the motor’s speed should increase when the feedback
2
2.8.2. Closed Loop Control Relevant Parameters
The frequency converter’s Closed Loop Controller is capable of handling more complex applications, such as situations where a conversion function is
applied to the feedback signal or situations where multiple feedback signals and/or setpoint references are used. The below table summarizes the
additional parameters than may be useful in such applications.
Parameter
Feedback 2 Source
Feedback 3 Source
Feedback 1 Conversion
Feedback 2 Conversion
Feedback 3 Conversion
Feedback 1 Source Unit
Feedback 2 Source Unit
Feedback 3 Source Unit
Feedback Functionpar. 20-20When multiple feedbacks or setpoints are used, this determines how they will be pro-
Setpoint 1
Setpoint 2
Setpoint 3
Refrigerantpar. 20-30If any Feedback Conversion (par. 20-01, 20-04 or 20-07) is set to
par. 20-03
par. 20-06
par. 20-01
par. 20-04
par. 20-07
par. 20-02
par. 20-05
par. 20-08
par. 20-21
par. 20-22
par. 20-23
Description of function
Select the source, if any, for Feedback 2 or 3. This is most commonly a frequency con-
verter analog input, but other sources are also available. Par. 20-20 determines how
multiple feedback signals will be processed by the frequency converter’s Closed Loop
Controller. By default, these are set to
These are used to convert the feedback signal from one type to another, for example
from pressure to flow or from pressure to temperature (for compressor applications).
If
Pressure to temperature
Group 20-3*, Feedback Adv. Conv. By default, these are set to
Select the unit for a feedback source, prior to any conversions. This is used for display
purposes only. This parameter is only available when using
feedback conversion.
cessed by the frequency converter’s Closed Loop Controller.
These setpoints can be used to provide a setpoint reference to the frequency converter’s
Closed Loop Controller. Par. 20-20 determines how multiple setpoint references will be
processed. Any other references that are activated in par. group 3-1* will add to these
values.
[2] is selected, the refrigerant must be specified in par.
No function
[0].
Linear
Pressure to Temperature
[0].
Pressure to Temper-
ature
[2], the refrigerant type must be selected here. If the refrigerant used is not listed
here, select
20-31, 20-32 and 20-33.
User defined
[7] and specify the characteristics of the refrigerant in par.
MG.11.B7.02 - VLT® is a registered Danfoss trademark
31
2
2. Introduction to VLT HVAC DriveVLT® HVAC Drive Design Guide
ParameterDescription of function
Custom Refrigerant A1
Custom Refrigerant A2
Custom Refrigerant A3
PID Start Speed [RPM]
PID Start Speed [Hz]
On Reference Bandwidthpar. 20-84This determines how close the feedback must be to the setpoint reference for the fre-
PID Anti Winduppar. 20-91
PID Differentiation Timepar. 20-95This controls the output of the frequency converter’s Closed Loop Controller based on
PID Diff. Gain Limitpar. 20-96Because the differentiator responds to the rate of change of the feedback, a rapid
Lowpass Filter Time :
Analog Input 53
Analog Input 54
Digital (pulse) input 29
Digital (pulse) input 33
par. 20-31
par. 20-32
par. 20-33
par. 20-82
par. 20-83
par. 6-16
par. 6-26
par. 5-54
par. 5-59
When par. 20-30 is set to
value of coefficients A1, A2 and A3 in the conversion equation:
Temperature
The parameter that is visible will depend on the setting of par. 0-02, Motor Speed Unit.
In some applications, after a start command it is important to quickly ramp the motor
up to some pre-determined speed before activating the frequency converter’s Closed
Loop Controller. This parameter defines that starting speed.
quency converter to indicate that the feedback is equal to the setpoint.
On
[1] effectively disables the Closed Loop Controller’s integral function when it is not
possible to adjust the output frequency of the frequency converter to correct the error.
This allows the controller to respond more quickly once it can again control the system.
Off
[0] disables this function, making the integral function stay active continuously.
the rate of change of feedback. While this can provide fast controller response, such
response is seldom needed in HVAC systems. The default value for this parameter is
Off, or 0.00 s.
change can cause a large, undesired change in the output of the controller. This is used
to limit the maximum effect of the differentiator. This is not active when par. 20-95 is
set to Off.
This is used to filter out high frequency noise from the feedback signal. The value en-
tered here is the time constant for the low pass filter. The cut-off frequency in Hz can
be calculated as follows:
F
cut
Variations in the feedback signal whose frequency is below F
frequency converter’s Closed Loop Controller, while variations at a higher frequency are
considered to be noise and will be attenuated. Large values of Lowpass Filter Time will
provide more filtering, but may cause the controller to not respond to actual variations
in the feedback signal.
=
−
off
=
(
ln(pressure
T
2π
lowpass
User defined
1
[7], these parameters are used to define the
A
2
+1)−A1
−
A
3
)
will be used by the
cut-off
2.8.3. Example of Closed Loop PID Control
The following is an example of a Closed Loop Control for a ventilation system:
32
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide2. Introduction to VLT HVAC Drive
In a ventilation system, the temperature is to be maintained at a constant
value. The desired temperature is set between -5 and +35°C using a 0-10
volt potentiometer. Because this is a cooling application, if the tempera-
ture is above the setpoint value, the speed of the fan must be increased
1. Start/Stop via switch connected between terminals 12 (+24 V) and 18.
2. Temperature reference via a potentiometer (-5 to +35°C, 0 10 V)
connected to terminals 50 (+10 V), 53 (input) and 55 (common).
3. Temperature feedback via transmitter (-10-40°C, 4-20 mA) connected
to terminal 54. Switch S202 behind the Local Control Panel set to ON
(current input).
to provide more cooling air flow. The temperature sensor has a range of
-10 to +40°C and uses a two-wire transmitter to provide a 4-20 mA signal.
The output frequency range of the frequency converter is 10 to 50 Hz.
2
MG.11.B7.02 - VLT® is a registered Danfoss trademark
33
2
2. Introduction to VLT HVAC DriveVLT® HVAC Drive Design Guide
2.8.4. Programming Order
FunctionPar. no.Setting
1) Make sure the motor runs properly. Do the following:
Set the frequency converter to control the motor
based on frequency converter output frequency.
Set the motor parameters using nameplate data.1-2*As specified by motor name plate
Run Automatic Motor Adaptation.1-29
2) Check that the motor is running in the right direction.
Pressing [Hand On] starts the motor at 5Hz in forward
direction and the display shows: “Motor is running.
Check if motor rotation direction is correct.
3) Make sure the frequency converter limits are set to safe values
Check that the ramp settings are within capabilities
of the frequency converter and allowed application
operating specifications.
Prohibit the motor from reversing (if necessary)4-10
Set acceptable limits for the motor speed.4-12
Switch from open loop to closed loop.1-00
4) Configure the feedback to the PID controller.
Set up Analog Input 54 as a feedback input.20-00
Select the appropriate reference/feedback unit.20-12
5) Configure the setpoint reference for the PID controller.
Set acceptable limits for the setpoint reference.
Set up Analog Input 53 as Reference 1 Source.3-15
6) Scale the analog inputs used for setpoint reference and feedback.
Scale Analog Input 53 for the temperature range of
the potentiometer (-5 to +35°C, 0-10 V).
Scale Analog Input 54 for the temperature range of
the temperature sensor (-10 to +40°C, 4-20 mA)
7) Tune the PID controller parameters.
Select inverse control because motor’s speed should
increase when the feedback is greater than the setpoint reference.
Adjust the frequency converter’s Closed Loop Controller, if needed.
8) Finished!
Save the parameter setting to the LCP for safe keeping
0-02
If motor rotation direction is incorrect, two motor
3-41
3-42
4-14
4-19
3-02
3-03
6-10
6-11
6-14
6-15
6-22
6-23
6-24
6-25
20-81
20-93
20-94
0-50
Hz
[1]
Enable complete AMA
function.
phase cables should be interchanged.
60 sec.
60 sec.
Depends on motor/load size!
Also active in Hand mode.
Clockwise
10 Hz
50 Hz
50 Hz
Closed Loop
[0]
[3]
Analog input 54
°C
[60]
-5 °C
35 °C
Analog input 53
0 V
10 V (default)
-5 °C
35 °C
4 mA
20 mA (default)
-10 °C
40 °C
Inverse
[1]
See Optimization of the PID Controller, below.
All to LCP
[1]
[1] and then run the AMA
[2] (default)
[1] (default)
34
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide2. Introduction to VLT HVAC Drive
2.8.5. Tuning the Drive's Closed Loop Controller
Once the frequency converter’s Closed Loop Controller has been set up, the performance of the controller should be tested. In many cases, its performance
may be acceptable using the default values of PID Proportional Gain (par. 20-93) and PID Integral Time (par. 20-94). However, in some cases it may be
helpful to optimize these parameter values to provide faster system response while still controlling speed overshoot. In many situations, this can be done
by following the procedure below.
1.Start the motor
2.Set par. 20-93 (PID Proportional Gain) to 0.3 and increase it until the feedback signal begins to oscillate. If necessary, start and stop the frequency
converter or make step changes in the setpoint reference to attempt to cause oscillation. Next reduce the PID Proportional Gain until the feedback
signal stabilizes. Then reduce the proportional gain by 40-60%.
3.Set par. 20-94 (PID Integral Time) to 20 sec. and reduce it until the feedback signal begins to oscillate. If necessary, start and stop the frequency
converter or make step changes in the setpoint reference to attempt to cause oscillation. Next, increase the PID Integral Time until the feedback
signal stabilizes. Then increase of the Integral Time by 15-50%.
4.Par. 20-95 (PID Differentiation Time) should only be used for very fast-acting systems. The typical value is 25% of the PID Integral Time (par.
20-94). The differentiator should only be used when the setting of the proportional gain and the integral time has been fully optimized. Make
sure that oscillations of the feedback signal are sufficiently dampened by the lowpass filter for the feedback signal (par 6 16, 6 26, 5 54 or 5 59,
as required).
2.8.6. Ziegler Nichols Tuning Method
2
In general, the above procedure is sufficient for HVAC applications. However, other, more sophisticated procedures can also be used. The Ziegler Nichols
tuning method is a technique which was developed in the 1940s, but is still commonly used today. It generally provides acceptable control performance
using a simple experiment and parameter calculation.
NB!
This method must not be used on applications that could be damaged by oscillations created by marginally stable control settings.
2.Increase the value of the PID Proportional Gain (par 20-93) until
the point of instability is reached, as indicated by sustained os-
cillations of the feedback signal. The PID Proportional Gain that
Illustration 2.5: Marginally stable system
1.Select proportional control only. That is, PID Integral Time (par.
20-94) is set to Off (10000 s) and PID Differentiation Time (par.
20 95) is also set to Off (0 s, in this case).
causes sustained oscillations is called the critical gain, K
3.Measure the period of oscillation, P
NOTE: P
should be measured when the amplitude of oscillation
u
is relatively small. The output must not saturate (i.e., the max-
imum or minimum feedback signal must not be reached during
the test).
4.Use the table below to calculate the necessary PID control pa-
rameters.
.
u
.
u
Type of ControlProportional GainIntegral TimeDifferentiation Time
PI-control0.45 *
PID tight control0.6 *
PID some overshoot0.33 *
Ziegler Nichols tuning for regulator, based on a stability boundary
Experience has shown that the control setting according to Ziegler Nichols rule provides a good closed loop response for many systems. If necessary,
the operator can do the final tuning of the control iteratively to modify the response of the control loop.
K
u
K
u
K
u
MG.11.B7.02 - VLT® is a registered Danfoss trademark
0.833 *
0.5 *
P
0.5 *
P
P
u
u
u
-
0.125 *
0.33 *
P
u
P
u
35
2
2. Introduction to VLT HVAC DriveVLT® HVAC Drive Design Guide
2.8.7. Reference Handling
A block diagram of how the drive produces the Remote Reference is shown below.
36
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide2. Introduction to VLT HVAC Drive
The Remote Reference is comprised of:
•Preset references.
•External references (analog inputs, pulse frequency inputs, digital potentiometer inputs and serial communication bus references).
•The Preset relative reference.
•Feedback controlled setpoint.
Up to 8 preset references can be programmed in the drive. The active preset reference can be selected using digital inputs or the serial communications
bus. The reference can also be supplied externally, most commonly from an analog input. This external source is selected by one of the 3 Reference
Source parameters (par. 3-15, 3-16 and 3-17). Digipot is a digital potentiometer. This is also commonly called a Speed Up/Speed Down Control or a
Floating Point Control. To set it up, one digital input is programmed to increase the reference while another digital input is programmed to decrease the
reference. A third digital input can be used to reset the Digipot reference. All reference resources and the bus reference are added to produce the total
External Reference. The External Reference, the Preset Reference or the sum of the two can be selected to be the active reference. Finally, this reference
can by be scaled using the Preset Relative Reference (par. 3-14).
The scaled reference is calculated as follows:
Reference=X+X
Where X is the external reference, the preset reference or the sum of these and Y is the Preset Relative Reference (par. 3-14) in [%].
Y
×
(
)
100
2
NB!
If Y, the Preset Relative Reference (par. 3-14) is set to 0%, the reference will not be affected by the scaling
2.8.8. Feedback Handling
A block diagram of how the frequency converter processes the feedback signal is shown below.
Feedback handling can be configured to work with applications requiring advanced control, such as multiple setpoints and multiple feedbacks. Three
types of control are common.
Single Zone, Single Setpoint
Single Zone Single Setpoint is a basic configuration. Setpoint 1 is added to any other reference (if any, see Reference Handling) and the feedback signal
is selected using par. 20-20.
MG.11.B7.02 - VLT® is a registered Danfoss trademark
37
2
2. Introduction to VLT HVAC DriveVLT® HVAC Drive Design Guide
Multi Zone, Single Setpoint
Multi Zone Single Setpoint uses two or three feedback sensors but only one setpoint. The feedbacks can be added, subtracted (only feedback 1 and 2)
or averaged. In addition, the maximum or minimum value may be used. Setpoint 1 is used exclusively in this configuration.
Multi Zone Multi Setpoint
applies an individual setpoint reference to each feedback. The frequency converter’s Closed Loop Controller chooses one pair to control the frequency
converter based on the user’s selection in par. 20-20. If
the frequency converter’s speed. (Note that a negative value is always smaller than a positive value).
Multi Setpoint Max
[14] is selected, the setpoint/feedback pair with the smallest difference controls
Multi Setpoint Min
If
Maximum
[14] attempts to keep all zones at or below their respective setpoints, while
respective setpoints.
Example:
A two zone two setpoints application Zone 1 setpoint is 18°C and the feedback is 19°C. Zone 2 setpoint is 22°C and the feedback is 20°C. If
[14] is selected, Zone 1’s setpoint and feedback are sent to the PID controller, since this has the smaller difference (feedback is higher than setpoint,
Max
resulting in a negative difference). If
larger difference (feedback is lower than setpoint, resulting in a positive difference).
[13] is selected, the setpoint/feedback pair with the largest difference controls the speed of the frequency converter.
Multi Setpoint Min
Multi Setpoint Min
[13] is selected, Zone 2’s setpoint and feedback is sent to the PID controller, since this has the
[13] attempts to keep all zones at or above their
Multi Setpoint
Multi Setpoint
2.8.9. Feedback Conversion
In some applications it may be useful to convert the feedback signal. One example of this is using a pressure signal to provide flow feedback. Since the
square root of pressure is proportional to flow, the square root of the pressure signal yields a value proportional to the flow. This is shown below.
Another application that may benefit from feedback conversion is compressor control. In such applications the output of a pressure sensor may be
converted to the refrigerant temperature using the equation:
A
Temperature
where A1, A2 and A3 are refrigerant-specific constants.
=
(
ln(pressure
2
+1)−A1
38
−
A
3
)
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide2. Introduction to VLT HVAC Drive
2.9. General aspects of EMC
2.9.1. General Aspects of EMC Emissions
Electrical interference is usually conducted at frequences in the range 150 kHz to 30 MHz. Airborne interference from the drive system in the range 30
MHz to 1 GHz is generated from the inverter, motor cable, and the motor.
As shown in the illustration below, capacitive currents in the motor cable coupled with a high dV/dt from the motor voltage generate leakage currents.
The use of a screened motor cable increases the leakage current (see illustration below) because screened cables have higher capacitance to earth than
unscreened cables. If the leakage current is not filtered, it will cause greater interference on the mains in the radio frequency range below approx. 5
MHz. Since the leakage current (I
from the screened motor cable according to the below figure.
The screen reduces the radiated interference but increases the low-frequency interference on the mains. The motor cable screen must be connected to
the frequency converter enclosure as well as on the motor enclosure. This is best done by using integrated screen clamps so as to avoid twisted screen
ends (pigtails). These increase the screen impedance at higher frequencies, which reduces the screen effect and increases the leakage current (I
If a screened cable is used for Fieldbus, relay, control cable, signal interface and brake, the screen must be mounted on the enclosure at both ends. In
some situations, however, it will be necessary to break the screen to avoid current loops.
) is carried back to the unit through the screen (I 3), there will in principle only be a small electro-magnetic field (I4)
1
).
4
2
If the screen is to be placed on a mounting plate for the frequency converter, the mounting plate must be made of metal, because the screen currents
have to be conveyed back to the unit. Moreover, ensure good electrical contact from the mounting plate through the mounting screws to the frequency
converter chassis.
NB!
When unscreened cables are used, some emission requirements are not complied with, although the immunity requirements are ob-
served.
In order to reduce the interference level from the entire system (unit + installation), make motor and brake cables as short as possible. Avoid placing
cables with a sensitive signal level alongside motor and brake cables. Radio interference higher than 50 MHz (airborne) is especially generated by the
control electronics.
2.9.2. Emission Requirements
According to the EMC product standard for adjustable speed frequency converters EN/IEC61800-3:2004 the EMC requirements depend on the intended
use of the frequency converter. Four categories are defined in the EMC product standard. The definitions of the four categories together with the
requirements for mains line conducted emissions are given in the table below:
MG.11.B7.02 - VLT® is a registered Danfoss trademark
39
2. Introduction to VLT HVAC DriveVLT® HVAC Drive Design Guide
2
Category
C1frequency converters installed in the first environment (home and office) with a supply
C2frequency converters installed in the first environment (home and office) with a supply
C3frequency converters installed in the second environment (industrial) with a supply
C4frequency converters installed in the second environment with a supply voltage above
When the generic emission standards are used the frequency converters are required to comply with the following limits:
Environment
First environment
(home and office)
Second environment
(industrial environment)
DefinitionConducted emission requirement accord-
ing to the limits given in EN55011
voltage less than 1000 V.
voltage less than 1000 V which are neither plug-in nor movable and are intended to be
installed and commissioned by a professional.
voltage lower than 1000 V.
1000 V and rated current above 400 A or intended for use in complex systems.
EN/IEC61000-6-3 Emission standard for residential, commercial and
light industrial environments.
EN/IEC61000-6-4 Emission standard for industrial environments.Class A Group 1
An EMC plan should be made.
ing to the limits given in EN55011
2.9.3. EMC Test Results (Emission)
Class B
Class A Group 1
Class A Group 2
No limit line.
Class B
The following test results have been obtained using a system with a frequency converter (with options if relevant),
a screened control cable, a control box with potentiometer, as well as a motor and motor screened cable.
RFI filter typeConducted emission.
Radiated emission
Maximum shielded cable length.
Industrial environmentHousing,
trades and
Industrial envi-
ronment
Housing, trades and
light industries
light industries
SetupEN 55011
Class A2
EN 55011
Class A1
EN 55011
Class B
EN 55011 ClassA1EN 55011 Class B
H1
1.1-45 kW 200-240 V
150 m150 m50 mYesNo
1.1-90 kW 380-480 V150 m150 m50 mYesNo
H2
1.1-3.7 kW 200-240 V
5 mNoNoNoNo
5.5-45 kW 200-240 V25 mNoNoNoNo
1.1-7.5 kW 380-480 V
11-90 kW 380-480 V
110-450 kW 380-480 V
75-500 kW 525-600 V
5 mNoNoNoNo
25 mNoNoNoNo
50 mNoNoNoNo
150 mNoNoNoNo
H3
1.1-45 kW 200-240 V
75 m50 m10 mYesNo
1.1-90 kW 380-480 V75 m50 m10 mYesNo
H4
110-450 kW 380-480 V
150 m150 mNoYesNo
75-315 kW 525-600 V150 m30 mNoNoNo
Hx
1.1-90 kW 525-600 V
-----
Table 2.1: EMC Test Results (Emission)
40
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide2. Introduction to VLT HVAC Drive
2.9.4. Immunity Requirements
The immunity requirements for frequency converters depend on the environment where they are installed. The requirements for the industrial environment
are higher than the requirements for the home and office environment. All Danfoss frequency converters comply with the requirements for the industrial
environment and consequently comply also with the lower requirements for home and office environment with a large safety margin.
In order to document immunity against electrical interference from electrical phenomena, the following immunity tests have been made on a system
consisting of a frequency converter (with options if relevant), a screened control cable and a control box with potentiometer, motor cable and motor.
The tests were performed in accordance with the following basic standards:
•EN 61000-4-2 (IEC 61000-4-2): Electrostatic discharges (ESD): Simulation of electrostatic discharges from human beings.
•EN 61000-4-3 (IEC 61000-4-3): Incoming electromagnetic field radiation, amplitude modulated simulation of the effects of radar and radio
communication equipment as well as mobile communications equipment.
•EN 61000-4-4 (IEC 61000-4-4): Burst transients: Simulation of interference brought about by switching a contactor, relay or similar devices.
•EN 61000-4-5 (IEC 61000-4-5): Surge transients: Simulation of transients brought about e.g. by lightning that strikes near installations.
•EN 61000-4-6 (IEC 61000-4-6): RF Common mode: Simulation of the effect from radio-transmission equipment joined by connection cables.
See following EMC immunity form.
Voltage range: 200-240 V, 380-480 V
Basic standardBurst
IEC 61000-4-4
Surge
IEC 61000-4-5
ESD
IEC
61000-4-2
Radiated electromagnetic
field
IEC 61000-4-3
RF common
mode voltage
IEC 61000-4-6
Acceptance criterionBBBAA
Line
Motor
4 kV CM
4 kV CM
Brake4 kV CM
Load sharing4 kV CM
Control wires
2 kV CM
Standard bus2 kV CM
Relay wires2 kV CM
Application and Fieldbus
2 kV CM
options
LCP cable
External 24 V DC
Enclosure
2 kV CM
2 kV CM
——
2 kV/2 Ω DM
4 kV/12 Ω CM
4 kV/2 Ω
4 kV/2 Ω
4 kV/2 Ω
1)
1)
2 kV/2 Ω
2 kV/2 Ω
2 kV/2 Ω
2 kV/2 Ω
2 kV/2 Ω
0.5 kV/2 Ω DM
1 kV/12 Ω CM
——
1)
——
——
1)
1)
1)
1)
1)
——
——
——
——
——
——
——
8 kV AD
6 kV CD
10 V/m—
10 V
10 V
10 V
10 V
10 V
10 V
10 V
10 V
10 V
10 V
RMS
RMS
RMS
RMS
RMS
RMS
RMS
RMS
RMS
RMS
AD: Air Discharge
CD: Contact Discharge
CM: Common mode
DM: Differential mode
1. Injection on cable shield.
2
Table 2.2: Immunity
2.10. Galvanic isolation (PELV)
2.10.1. PELV - Protective Extra Low Voltage
PELV offers protection by way of extra low voltage. Protection against electric shock is ensured when the electrical supply is of the PELV type and the
installation is made as described in local/national regulations on PELV supplies.
All control terminals and relay terminals 01-03/04-06 comply with PELV (Protective Extra Low Voltage) (Does not apply to 525-600 V units and at grounded
Delta leg above 300 V).
Galvanic (ensured) isolation is obtained by fulfilling requirements for higher isolation and by providing the relevant creapage/clearance distances. These
requirements are described in the EN 61800-5-1 standard.
MG.11.B7.02 - VLT® is a registered Danfoss trademark
41
2. Introduction to VLT HVAC DriveVLT® HVAC Drive Design Guide
The components that make up the electrical isolation, as described below, also comply with the requirements for higher isolation and the relevant test
as described in EN 61800-5-1.
The PELV galvanic isolation can be shown in six locations (see illustration):
In order to maintain PELV all connections made to the control terminals must be PELV, e.g. thermistor must be reinforced/double insulated.
2
1.Power supply (SMPS) incl. signal isolation of U
intermediate current voltage.
2.Gate drive that runs the IGBTs (trigger transformers/opto-cou-
plers).
3.Current transducers.
4.Opto-coupler, brake module.
5.Internal inrush, RFI, and temperature measurement circuits.
6.Custom relays.
The functional galvanic isolation (a and b on drawing) is for the 24 V back-up option and for the RS 485 standard bus interface.
Installation at high altitude
380 - 500 V: At altitudes above 3 km, please contact Danfoss regarding PELV.
525 - 690 V: At altitudes above 2 km, please contact Danfoss regarding PELV.
, indicating the
DC
Illustration 2.6: Galvanic isolation
2.11.1. Earth Leakage Current
Warning:
Touching the electrical parts may be fatal - even after the equipment has been disconnected from mains.
Also make sure that other voltage inputs have been disconnected, such as load-sharing (linkage of DC intermediate circuit), as well as
the motor connection for kinetic back-up.
Before touching any electrical parts, wait at least: Please consult the section
Shorter time than stated in the table is allowed only if indicated on the nameplate for the specific unit.
Safety>Caution
.
Leakage Current
The earth leakage current from the frequency converter exceeds 3.5 mA. To ensure that the earth cable has a good mechanical
connection to the earth connection (terminal 95), the cable cross section must be at least 10 mm
separately.
Residual Current Device
This product can cause a d.c. current in the protective conductor. Where a residual current device (RCD) is used for extra protection,
only an RCD of Type B (time delayed) shall be used on the supply side of this product. See also RCD Application Note MN.90.Gx.yy.
Protective earthing of the frequency converter and the use of RCD's must always follow national and local regulations.
2
or 2 rated earth wires terminated
2.12. Control with brake function
2.12.1. Selection of Brake Resistor
In certain applications, for instance in tunnel or underground railway station ventilation systems, it is desirable to bring the motor to a stop more rapidly
than can be achieved through controlling via ramp down or by free-wheeling. In such applications, dynamic braking with a braking resistor may be utilized.
Using a braking resistor ensures that the energy is absorbed in the resistor and not in the frequency converter.
42
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide2. Introduction to VLT HVAC Drive
If the amount of kinetic energy transferred to the resistor in each braking period is not known, the average power can be calculated on the basis of the
cycle time and braking time also called intermitted duty cycle. The resistor intermittent duty cycle is an indication of the duty cycle at which the resistor
is active. The below figure shows a typical braking cycle.
The intermittent duty cycle for the resistor is calculated as follows:
Duty Cycle = tb / T
T = cycle time in seconds
t
is the braking time in seconds (as part of the total cycle time)
b
Danfoss offers brake resistors with duty cycle of 5%, 10% and 40% suitable for use with the VLT FC102 HVAC frequency converter series. If a 10% duty
cycle resistor is applied, this is able of absorbing braking power upto 10% of the cycle time with the remaining 90% being used to dissipate heat from
the resistor.
2
For further selection advice, please contact Danfoss.
NB!
If a short circuit in the brake transistor occurs, power dissipation in the brake resistor is only prevented by using a mains switch or
contactor to disconnect the mains for the frequency converter. (The contactor can be controlled by the frequency converter).
2.12.2. Brake Resistor Calculation
The brake resistance is calculated as shown:
R
Ω =
br
where
P
= P
peak
As can be seen, the brake resistance depends on the intermediate circuit voltage (UDC).
The brake function of the frequency converter is settled in 3 areas of mains power supply:
SizeBrake activeWarning before cut out Cut out (trip)
3 x 200-240 V390 V (UDC)405 V410 V
3 x 380-480 V778 V810 V820 V
3 x 525-600 V943 V965 V975 V
motor
2
U
dc
P
peak
x Mbr x η
motor
x η[W]
MG.11.B7.02 - VLT® is a registered Danfoss trademark
43
2. Introduction to VLT HVAC DriveVLT® HVAC Drive Design Guide
NB!
Check that the brake resistor can cope with a voltage of 410 V, 820 V or 975 V - unless Danfoss brake resistors are used.
2
Danfoss recommends the brake resistance R
) of 110%. The formula can be written as:
(%)
η
is typically at 0.90η is typically at 0.98
motor
For 200 V, 480 V and 600 V frequency converters, R
200V:
480V:
600
1) For frequency converters ≤ 7.5 kW shaft output
2) For frequency converters > 7.5 kW shaft output
V:R
R
rec
R
rec
rec
107780
=
P
motor
375300
=
P
motor
630137
=
P
motor
NB!
The resistor brake circuit resistance selected sho ul d n ot be higher t ha n t ha t recommended by Danfoss. If a brake resistor with a higher
ohmic value is selected, the braking torque may not be achieved because there is a risk that the frequency converter cuts out for safety
reasons.
Ω
Ω
Ω
, i.e. one that guarantees that the frequency converter is able to brake at the highest braking torque (M
rec
R
rec
at 160% braking torque is written as:
rec
)
1
480
V:R
Ω =
rec
P
motor
=
xM
428914
P
motor
br
2
U
x
100
dc
xηx
br
(%)
Ω
)
2
η
motor
NB!
If a short circuit in the brake transistor occurs, power dissipation in the brake resistor is only prevented by using a mains switch or
contactor to disconnect the mains for the frequency converter. (The contactor can be controlled by the frequency converter).
NB!
Do not touch the brake resistor as it can get very hot while/after braking.
2.12.3. Control with Brake Function
The brake is to limit the voltage in the intermediate circuit when the motor acts as a generator. This occurs, for example, when the load drives the motor
and the power accumulates on the DC link. The brake is built up as a chopper circuit with the connection of an external brake resistor.
Placing the brake resistor externally offers the following advantages:
-The brake resistor can be selected on the basis of the application in question.
-The brake energy can be dissipated outside the control panel, i.e. where the energy can be utilized.
-The electronics of the frequency converter will not be overheated if the brake resistor is overloaded.
The brake is protected against short-circuiting of the brake resistor, and the brake transistor is monitored to ensure that short-circuiting of the transistor
is detected. A relay/digital output can be used for protecting the brake resistor against overloading in connection with a fault in the frequency converter.
In addition, the brake makes it possible to read out the momentary power and the mean power for the latest 120 seconds. The brake can also monitor
the power energizing and make sure it does not exceed a limit selected in par. 2-12. In par. 2-13, select the function to carry out when the power
transmitted to the brake resistor exceeds the limit set in par. 2-12.
44
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide2. Introduction to VLT HVAC Drive
NB!
Monitoring the brake power is not a safety function; a thermal switch is required for that purpose. The brake resistor circuit is not earth
leakage protected.
Over voltage control (OVC)
The function ensures that a trip can be avoided if the DC link voltage increases. This is done by increasing the output frequency to limit the voltage from
the DC link. It is a very useful function, e.g. if the ramp-down time is too short since tripping of the frequency converter is avoided. In this situation the
ramp-down time is extended.
(exclusive brake resistor) can be selected as an alternative brake function in par. 2-17. This function is active for all units.
2.12.4. Brake Resistor Cabling
EMC (twisted cables/shielding)
To reduce the electrical noise from the wires between the brake resistor and the frequency converter, the wires must be twisted.
For enhanced EMC performance a metal screen can be used.
2.13. Extreme running conditions
Short Circuit (Motor Phase – Phase)
The frequency converter is protected against short circuits by means of current measurement in each of the three motor phases or in the DC link. A short
circuit between two output phases will cause an overcurrent in the inverter. The inverter will be turned off individually when the short circuit current
exceeds the permitted value (Alarm 16 Trip Lock).
To protect the frequency converter against a short circuit at the load sharing and brake outputs please see the design guidelines.
Switching on the Output
Switching on the output between the motor and the frequency converter is fully permitted. You cannot damage the frequency converter in any way by
switching on the output. However, fault messages may appear.
2
Motor-generated Over-voltage
The voltage in the intermediate circuit is increased when the motor acts as a generator. This occurs in following cases:
1.The load drives the motor (at constant output frequency from the frequency converter), ie. the load generates energy.
2.During deceleration ("ramp-down") if the moment of inertia is high, the friction is low and the ramp-down time is too short for the energy to be
dissipated as a loss in the frequency converter, the motor and the installation.
3.Incorrect slip compensation setting may cause higher DC link voltage.
The control unit may attempt to correct the ramp if possible (par. 2-17
The inverter turns off to protect the transistors and the intermediate circuit capacitors when a certain voltage level is reached.
See par. 2-10 and par. 2-17 to select the method used for controlling the intermediate circuit voltage level.
Mains Drop-out
During a mains drop-out, the frequency converter keeps running until the intermediate circuit voltage drops below the minimum stop level, which is
typically 15% below the frequency converter's lowest rated supply voltage.
The mains voltage before the drop-out and the motor load determines how long it takes for the inverter to coast.
plus
Static Overload in VVC
When the frequency converter is overloaded (the torque limit in par. 4-16/4-17 is reached), the controls reduces the output frequency to reduce the load.
If the overload is excessive, a current may occur that makes the frequency converter cut out after approx. 5-10 s.
Operation within the torque limit is limited in time (0-60 s) in par. 14-25.
mode
Over-voltage Control)
.
MG.11.B7.02 - VLT® is a registered Danfoss trademark
45
2
2. Introduction to VLT HVAC DriveVLT® HVAC Drive Design Guide
2.13.1. Motor Thermal Protection
This is the way Danfoss is protecting the motor from being overheated. It is an electronic feature that simulates a bimetal relay based on internal
measurements. The characteristic is shown in the following figure:
Illustration 2.7: The X-axis is showing the ratio between I
and trips the drive. The curves are showing the characteristic nominal speed at twice the nominal speed and at 0,2x the nominal speed.
It is clear that at lower speed the ETR cuts of at lower heat due to less cooling of the motor. In that way the motor are protected from being over heated
even at low speed. The ETR feature is calculating the motor temperature based on actual current and speed. The calculated temperature is visible as a
read out parameter in par. 16-18 in the frequency converter.
motor
and I
nominal. The Y- axis is showing the time in seconds before the ETR cuts off
motor
The thermistor cut-out value is > 3 kΩ.
Integrate a thermistor (PTC sensor) in the motor for winding protection.
Motor protection can be implemented using a range of techniques: PTC
sensor in motor windings; mechanical thermal switch (Klixon type); or
Electronic Thermal Relay (ETR).
46
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide2. Introduction to VLT HVAC Drive
Using a digital input and 24 V as power supply:
Example: The frequency converter trips when the motor temperature is
too high.
Parameter set-up:
Set par. 1-90 Motor
Set par. 1-93 Thermistor
Thermal Protection
Source
to
Digital Input 33
to
Thermistor Trip
[2]
[6]
2
Using a digital input and 10 V as power supply:
Example: The frequency converter trips when the motor temperature is
too high.
Parameter set-up:
Set par. 1-90 Motor
Set par. 1-93 Thermistor
Thermal Protection
Source
to
to
Digital Input 33
Thermistor Trip
[6]
[2]
Using an analog input and 10 V as power supply:
Example: The frequency converter trips when the motor temperature is
With the Torque limit feature the motor is protected for being overloaded independent of the speed. With the ETR the motor is protected for being over
heated and there is no need for any further motor protection. That means when the motor is heated up the ETR timer controls for how long time the
motor can be running at the high temperature before it is stopped in order to prevent over heating. If the motor is overloaded without reaching the
temperature where the ETR shuts of the motor, the torque limit is protecting the motor and application for being overloaded.
Thermal Protection
Source
NB!
Check that the chosen supply voltage follows the specification of the used thermistor element.
to
to
Analog Input 54
Supply Voltage
Volt
Thermistor Trip
[2]
[2]
Threshold
Cut-out Values
NB!
ETR is activated in par. 1-90
in par. 14-25.
Torque Limit
and is controlled in par. 4-16. The time before the torque limit warning trips the frequency converter is set
MG.11.B7.02 - VLT® is a registered Danfoss trademark
47
2. Introduction to VLT HVAC DriveVLT® HVAC Drive Design Guide
2.14. Safe Stop
2.14.1. Safe Stop
2
The frequency converter can perform the safety function
60204-1).
It is designed and approved suitable for the requirements of Safety Category 3 in EN 954-1. This functionality is called Safe Stop. Prior to integration and
use of Safe Stop in an installation, a thorough risk analysis on the installation must be carried out in order to determine whether the Safe Stop functionality
and safety category are appropriate and sufficient. In order to install and use the Safe Stop function in accordance with the requirements of Safety
Category 3 in EN 954-1, the related information and instructions of the relevant Design Guide must be followed! The information and instructions of the
Operating Instructions are not sufficient for a correct and safe use of the Safe Stop functionality!
Safe Torque Off
(As defined by draft CD IEC 61800-5-2) or
Stop Category 0
(as defined in EN
Illustration 2.8: Diagram showing all electrical terminals. (Terminal 37 present for units with Safe Stop Function only.)
48
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide2. Introduction to VLT HVAC Drive
2
2.14.2. Safe Stop Installation
To carry out an installation of a Category 0 Stop (EN60204) in conformity with Safety Category 3 (EN954-1), follow these instructions:
1.The bridge (jumper) between Terminal 37 and 24 V DC must be removed. Cutting or breaking the jumper is not sufficient. Remove it entirely
to avoid short-circuiting. See jumper on illustration.
2.Connect terminal 37 to 24 V DC by a short-circuit protected cable. The 24 V DC voltage supply must be interruptible by an EN954-1 Category 3
circuit interrupt device. If the interrupt device and the frequency converter are placed in the same installation panel, you can use an unscreened
cable instead of a screened one.
MG.11.B7.02 - VLT® is a registered Danfoss trademark
49
2
2. Introduction to VLT HVAC DriveVLT® HVAC Drive Design Guide
Illustration 2.9: Bridge jumper between terminal 37 and 24 VDC
The illustration below shows a Stopping Category 0 (EN 60204-1) with safety Category 3 (EN 954-1). The circuit interrupt is caused by an opening door
contact. The illustration also shows how to connect a non-safety related hardware coast.
Illustration 2.10: Illustration of the essential aspects of an installation to achieve a Stopping Category 0 (EN 60204-1) with safety Category 3 (EN
954-1).
50
MG.11.B7.02 - VLT® is a registered Danfoss trademark
3.1.2. General Purpose Input Output Module MCB 101
MCB 101 is used for extension of the number of digital and analog inputs
and outputs of the frequency converter.
Contents: MCB 101 must be fitted into slot B in the frequency converter.
•MCB 101 option module
•Extended LCP frame
•Terminal cover
Galvanic Isolation in the MCB 101
Digital/analog inputs are galvanically isolated from other inputs/outputs on the MCB 101 and in the control card of the frequency converter. Digital/analog
outputs in the MCB 101 are galvanically isolated from other inputs/outputs on the MCB 101, but not from these on the control card of the frequency
converter.
If the digital inputs 7, 8 or 9 are to be switched by use of the internal 24 V power supply (terminal 9) the connection between terminal 1 and 5 which is
illustrated in the drawing has to be established.
Illustration 3.1: Principle Diagram
52
MG.11.B7.02 - VLT® is a registered Danfoss trademark
•See mounting instructions in the beginning of section
•The power to the live part connections on relay terminals must be disconnected.
•Do not mix live parts (high voltage) with control signals (PELV).
•Select the relay functions in par. 5-40 [6-8], 5-41 [6-8] and 5-42 [6-8].
NB! (Index [6] is relay 7, index [7] is relay 8, and index [8] is relay 9)
Options and Accessories
3
Do not combine low voltage parts and PELV systems.
3.1.8. 24 V Back-Up Option MCB 107 (Option D)
External 24 V DC Supply
An external 24 V DC supply can be installed for low-voltage supply to the control card and any option card installed. This enables full operation of the
LCP (including the parameter setting) and fieldbusses without mains supplied to the power section.
External 24 V DC supply specification:
Input voltage range24 V DC ±15 % (max. 37 V in 10 s)
Max. input current2.2 A
Average input current for the frequency converter0.9 A
Max cable length75 m
Input capacitance load< 10 uF
Power-up delay< 0.6 s
The inputs are protected.
Terminal numbers:
Terminal 35: - external 24 V DC supply.
Terminal 36: + external 24 V DC supply.
MG.11.B7.02 - VLT® is a registered Danfoss trademark
Parameter groups for set-up: 26-0*, 26-1*, 26-2* and 26-3* See also
VLT HVAC Drive Programming Guide.
3 x Analog inputsOperating rangeResolutionAccuracySamplingMax loadImpedance
Used as
temperature
sensor input
Used as
voltage input
When used for voltage, analog inputs are scalable by parameters for each input.
When used for temperature sensor, analog inputs scaling is preset to necessary signal level for specified temperature span.
When analog inputs are used for temperature sensors, it is possible to read out feedback value in both °C and °F.
-50 to +150 °C11 bits-50 °C
0 - 10 VDC10 bits
VLT HVAC Drive Programming Guide.
±1 Kelvin
+150 °C
±2 Kelvin
0.2% of full
scale at cal.
temperature
3 Hz--
2.4 Hz
+/- 20 V
continuously
Approximately
5 kΩ
When operating with temperature sensors, maximum cable length to connect sensors is 80 m non-screened / non-twisted wires.
Analog outputs - terminal X42/7-12
Parameter group for read out and write: 18-3* See also
Parameter groups for set-up: 26-4*, 26-5* and 26-6* See also
3 x Analog outputs Output signal level Resolution LinearityMax load
Volt0-10 VDC11 bits1% of full scale 1 mA
Analog outputs are scalable by parameters for each output.
The function assigned is selectable via a parameter and have same options as for analog outputs on control card.
For a more detailed description of parameters, please refer to the
Real-time clock (RTC) with back-up
The data format of RTC includes year, month, date, hour, minutes and weekday.
Accuracy of clock is better than ± 20 ppm at 25° C.
The built-in lithium back-up battery lasts on average for minimum 10 years, when frequency converter is operating at 40 °C ambient temperature. If
battery pack back-up fails, analog I/O option must be exchanged.
VLT HVAC Drive Programming Guide
VLT HVAC Drive Programming Guide
VLT HVAC Drive Programming Guide
.
3.1.10. Brake Resistors
In applications where the motor is used as a brake, energy is generated in the motor and send back into the frequency converter. If the energy can not
be transported back to the motor it will increase the voltage in the converter DC-line. In applications with frequent braking and/or high inertia loads this
increase may lead to an over voltage trip in the converter and finally a shut down. Brake resistors are used to dissipate the excess energy resulting from
the regenerative braking. The resistor is selected in respect to its ohmic value, its power dissipation rate and its physical size. Danfoss offers a wide variety
of different resistors that are specially designed to our frequency converters. See the section
resistors. Code numbers can be found in the section
58
How to order
.
MG.11.B7.02 - VLT® is a registered Danfoss trademark
IP 20/IP 4X top/ TYPE 1 is an optional enclosure element available for IP 20 Compact units, enclosure size A2-A3.
If the enclosure kit is used, an IP 20 unit is upgraded to comply with enclosure IP 21/ 4X top/TYPE 1.
The IP 4X top can be applied to all standard IP 20 VLT HVAC Drive variants.
3
A – Top cover
B – Brim
C – Base part
D – Base cover
E – Screw(s)
Place the top cover as shown. If an A or B option
is used the brim must be fitted to cover the top
inlet. Place the base part C at the bottom of the
drive and use the clamps from the accessory
bag to correctly fasten the cables. Holes for cable glands:
Size A2: 2x M25 and 3xM32
Size A3: 3xM25 and 3xM32
3.1.13. Output Filters
The high speed switching of the frequency converter produces some secondary effects, which influence the motor and the enclosed environment. These
side effects are addressed by two different filter types, -the du/dt and the Sine-wave filter.
du/dt filters
Motor insulation stresses are often caused by the combination of rapid voltage and current increase. The rapid energy changes can also be reflected back
to the DC-line in the inverter and cause shut down. The du/dt filter is designed to reduce the voltage rise time/the rapid energy change in the motor and
by that intervention avoid premature aging and flashover in the motor insulation. du/dt filters have a positive influence on the radiation of magnetic noise
in the cable that connects the drive to the motor. The voltage wave form is still pulse shaped but the du/dt ratio is reduced in comparison with the
installation without filter.
Sine-wave filters
Sine-wave filters are designed to let only low frequencies pass. High frequencies are consequently shunted away which results in a sinusoidal phase to
phase voltage waveform and sinusoidal current waveforms.
With the sinusoidal waveforms the use of special frequency converter motors with reinforced insulation is no longer needed. The acoustic noise from the
motor is also damped as a consequence of the wave condition.
Besides the features of the du/dt filter, the sine-wave filter also reduces insulation stress and bearing currents in the motor thus leading to prolonged
motor lifetime and longer periods between services. Sine-wave filters enable use of longer motor cables in applications where the motor is installed far
from the drive. The length is unfortunately limited because the filter does not reduce leakage currents in the cables.
60
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide4. How to Order
4. How to Order
4.1.1. Drive Configurator
It is possible to design a frequency converter according to the application
requirements by using the ordering number system.
For the frequency converter, you can order standard drives and drives
with integral options by sending a type code string describing the product
a to the local Danfoss sales office, i.e.:
FC-102P18KT4E21H1XGCXXXSXXXXAGBKCXXXXDX
The meaning of the characters in the string can be located in the pages
containing the ordering numbers in the chapter
How to Select Your VLT
In the example above, a Profibus LON works option and a General pur-
pose I/O option is included in the frequency converter.
Ordering numbers for frequency converter standard variants can also be
located in the chapter
How to Select Your VLT
.
From the Internet based Drive Configurator, you can configure the right
frequency converter for the right application and generate the type code
string. The Drive Configurator will automatically generate an eight-digit
sales number to be delivered to your local sales office.
Furthermore, you can establish a project list with several products and
send it to a Danfoss sales representative.
The Drive Configurator can be found on the global Internet site:
www.danfoss.com/drives
.
Example of Drive Configurator interface set-up:
The numbers shown in the boxes refer to the letter/figure number of the
Type Code String - read from left to right. See next page!
Product groups
Frequency Converter ser-
ies
Power rating
Phases
.
Mains Voltage
Enclosure
Enclosure type
Enclosure class
Control supply voltage
Hardware configura-
tion
RFI filter
Brake
Display (LCP)
Coating PCB
Mains option
Adaptation A
Adaptation B
Software release
Software language
A options
B options
C0 options, MCO
C1 options
C option software
D options
1-3
4-6
8-10
11
12
13-15
16-17
18
19
20
21
22
23
24-27
28
29-30
31-32
33-34
35
36-37
38-39
4
MG.11.B7.02 - VLT® is a registered Danfoss trademark
61
4
4. How to OrderVLT® HVAC Drive Design Guide
4.1.2. Type Code String
DescriptionPosPossible choice
Product group & FC Series1-6FC 102
Power rating8-101.1 - 560 kW (P1K1 - P560)
Number of phases11Three phases (T)
C0 options MCO33-34CX: No options
C1 options35X: No options
C option software36-37XX: Standard software
D options38-39
T 2: 200-240 VAC
T 4: 380-480 VAC
T 6: 525-600 VAC
E20: IP20
E21: IP 21/NEMA Type 1
E55: IP 55/NEMA Type 12
E2M: IP21/NEMA Type 1 w/mains shield
E5M: IP 55/NEMA Type 12 w/mains shield
E66: IP66
P21: IP21/NEMA Type 1 w/backplate
P55: IP55/NEMA Type 12 w/backplate
H1: RFI filter class A1/B
H2: RFI filter class A2
H3: RFI filter class A1/B (reduced cable length)
H4: RFI filter class A2/A1
X: No brake chopper included
B: Brake chopper included
T: Safe Stop
U: Safe + brake
G: Graphical Local Control Panel (GLCP)
N: Numeric Local Control Panel (NLCP)
X: No Local Control Panel
X. No coated PCB
C: Coated PCB
X: No Mains disconnect switch
1: With Mains disconnect switch (IP55 only)
DC link connector
IP 21/4X top/TYPE 1 kitEnclosure, frame size A2: IP21/IP 4X Top/TYPE 1130B1122
IP 21/4X top/TYPE 1 kitEnclosure, frame size A3: IP21/IP 4X Top/TYPE 1130B1123
Panel Through Mount KitEnclosure, frame size A5130B1028
Panel Through Mount KitEnclosure, frame size B1130B1046
Panel Through Mount KitEnclosure, frame size B2130B1047
Panel Through Mount KitEnclosure, frame size C1130B1048
Panel Through Mount KitEnclosure, frame size C2130B1049
Profibus D-Sub 9Connector kit for IP20130B1112
Profibus top entry kitTop entry kit for Profibus connection - only A enclosures
Terminal blocks
BackplateIP21 / NEMA 1 enclosure Top Cover A2130B1132
BackplateIP21 / NEMA 1 enclosure Top Cover A3130B1133
BackplateA5 IP55 / NEMA 12130B1098
BackplateB1 IP21 / IP55 / NEMA 12130B3383
BackplateB2 IP21 / IP55 / NEMA 12130B3397
BackplateC1 IP21 / IP55 / NEMA 12130B3910
BackplateC2 IP21 / IP55 / NEMA 12130B3911
BackplateA5 IP66 / NEMA 4x130B3242
BackplateB1 IP66 / NEMA 4x130B3434
BackplateB2 IP66 / NEMA 4x130B3465
BackplateC1 IP66 / NEMA 4x130B3468
BackplateC2 IP66 / NEMA 4x130B3491
LCP
LCP 101Numerical Local Control Panel (NLCP)130B1124
LCP 102Graphical Local Control Panel (GLCP)130B1107
LCP cableSeparate LCP cable, 3 m175Z0929
LCP kitPanel mounting kit including graphical LCP, fasteners, 3 m cable and gasket130B1113
LCP kitPanel mounting kit including numerical LCP, fasteners and gasket130B1114
LCP kitPanel mounting kit for all LCPs including fasteners, 3 m cable and gasket130B1117
LCP kitPanel mounting kit for all LCPs including fasteners and gasket - without cable 130B1170
Options for Slot A Uncoated / CoatedUncoatedCoated
MCA 101Profibus option DP V0/V1130B1100130B1200
MCA 104DeviceNet option130B1102130B1202
MCA 108Lonworks130B1106130B1206
MCA 109BACnet gateway for build-in. Not to be used with Relay Option MCB 105 card 130B1144130B1244
4.2.3. Ordering Numbers: Sine Wave Filter Modules, 200-500 VAC
Typical Motor Used [kW]Danfoss ordering number
AHF 005AHF 010
Frequency converter size
Mains supply 3 x 200 to 500 V
Frequency converter size
200-240V380-440V440-500V
PK25PK37PK375 kHz120 Hz130B2439130B24042.5 A
PK37PK55PK555 kHz120 Hz130B2439130B24042.5 A
PK75PK755 kHz120 Hz130B2439130B24042.5 A
PK55P1K1P1K15 kHz120 Hz130B2441130B24064.5 A
P1K5P1K55 kHz120 Hz130B2441130B24064.5 A
PK75P2K2P2K25 kHz120 Hz130B2443130B24088 A
P1K1P3K0P3K05 kHz120 Hz130B2443130B24088 A
P1K55 kHz120 Hz130B2443130B24088 A
P4K0P4K05 kHz120 Hz130B2444130B240910 A
P2K2P5K5P5K55 kHz120 Hz130B2446130B241117 A
P3K0P7K5P7K55 kHz120 Hz130B2446130B241117 A
P4K05 kHz120 Hz130B2446130B241117 A
P5K5P11KP11K4 kHz60 Hz130B2447130B241224 A
P7K5P15KP15K4 kHz60 Hz130B2448130B241338 A
P18KP18K4 kHz60 Hz130B2448130B241338 A
P11KP22KP22K4 kHz60 Hz130B2307130B228148 A
P15KP30KP30K3 kHz60 Hz130B2308130B228262 A
P18KP37KP37K3 kHz60 Hz130B2309130B228375 A
P22KP45KP55K3 kHz60 Hz130B2310130B2284115 A
P30KP55KP75K3 kHz60 Hz130B2310130B2284115 A
P37KP75KP90K3 kHz60 Hz130B2311130B2285180 A
P45KP90KP1103 kHz60 Hz130B2311130B2285180 A
P110P1323 kHz60 Hz130B2312130B2286260 A
P132P1603 kHz60 Hz130B2312130B2286260 A
P160P2003 kHz60 Hz130B2313130B2287410 A
P200P2503 kHz60 Hz130B2313130B2287410 A
P250P3153 kHz60 Hz130B2314130B2288480 A
P315P3552 kHz60 Hz130B2315130B2289660 A
P355P4002 kHz60 Hz130B2315130B2289660 A
P400P4502 kHz60 Hz130B2316130B2290750 A
P450P5002 kHz60 Hz130B2317130B2291880 A
P500P5602 kHz60 Hz130B2317130B2291880 A
P560P6302 kHz60 Hz130B2318130B22921200 A
P630P7102 kHz60 Hz130B2318130B22921200 A
Minimum switching
frequency
Maximum output
frequency
Part No. IP20 Part No. IP00
Rated filter current at
4
50Hz
NB!
When using Sine-wave filters, the switching frequency should comply with filter specifications in
MG.11.B7.02 - VLT® is a registered Danfoss trademark
PK752 kHz60 Hz130B2341130B232113 A
P1K12 kHz60 Hz130B2341130B232113 A
P1K52 kHz60 Hz130B2341130B232113 A
P2k22 kHz60 Hz130B2341130B232113 A
P3K02 kHz60 Hz130B2341130B232113 A
P4K02 kHz60 Hz130B2341130B232113 A
P5K52 kHz60 Hz130B2341130B232113 A
P7K52 kHz60 Hz130B2341130B232113 A
P11K2 kHz60 Hz130B2342130B232228 A
P11KP15K2 kHz60 Hz130B2342130B232228 A
P15KP18K2 kHz60 Hz130B2342130B232228 A
P18KP22K2 kHz60 Hz130B2342130B232228 A
P22KP30K2 kHz60 Hz130B2343130B232345 A
P30KP37K2 kHz60 Hz130B2343130B232345 A
P37KP45K2 kHz60 Hz130B2344130B232476 A
P45KP55K2 kHz60 Hz130B2344130B232476 A
P55KP75K2 kHz60 Hz130B2345130B2325115 A
P75KP90K2 kHz60 Hz130B2345130B2325115 A
P90KP1102 kHz60 Hz130B2346130B2326165 A
P110P1322 kHz60 Hz130B2346130B2326165 A
P150P1602 kHz60 Hz130B2347130B2327260 A
P180P2002 kHz60 Hz130B2347130B2327260 A
P220P2502 kHz60 Hz130B2348130B2329303 A
P260P3151.5 kHz60 Hz130B2270130B2241430 A
P300P4001.5 kHz60 Hz130B2270130B2241430 A
P375P5001.5 kHz60 Hz130B2271130B2242530 A
P450P5601.5 kHz60 Hz130B2381130B2337660 A
P480P6301.5 kHz60 Hz130B2381130B2337660 A
P560P7101.5 kHz60 Hz130B2382130B2338765 A
P670P8001.5 kHz60 Hz130B2383130B2339940 A
P9001.5 kHz 60 Hz130B2383130B2339940 A
P820P1M01.5 kHz60 Hz130B2384130B23401320 A
P970P1M21.5 kHz60 Hz130B2384130B23401320 A
Minimum switching fre-
quency
Maximum output
frequency
Part No. IP20Part No. IP00
Rated filter cur-
rent at 50Hz
NB!
When using Sine-wave filters, the switching frequency should comply with filter specifications in
par. 14-01 Switching Frequency
.
66
MG.11.B7.02 - VLT® is a registered Danfoss trademark
MG.11.B7.02 - VLT® is a registered Danfoss trademark
Hole diameterk11/0.411/0.411/0.411/0.4
Max weight
(kg)
* The front of the frequency converter is slightly convex. C is the shortest distance from back to front (i.e. measured from corner to corner) of the frequency converter. D is the longest distance from back to front
(i.e. measured in the middle) of the frequency converter.
75
5
5. How to InstallVLT® HVAC Drive Design Guide
Accessory Bags: Find the following parts included in the frequency converter accessory bags
5.1.2. Accessory Bags
76
Frame sizes A1, A2 and A3,Frame size A5,Frame sizes B1 and B2,Frame sizes C1 and C2,
MG.11.B7.02 - VLT® is a registered Danfoss trademark
1 + 2 only available in units with brake chopper. For DC link connection (Load sharing) the connector 1 can be ordered separately (Code no. 130B1064)
An eight pole connector is included in accessory bag for FC 102 without Safe Stop.
VLT® HVAC Drive Design Guide5. How to Install
5.1.3. Mechanical mounting
All IP20 enclosure sizes as well as IP21/ IP55 enclosures sizes except A2 and A3 allow side-by-side installation.
If the IP 21 Enclosure Kit is used on enclosure A2 or A3, there must be a clearance between the drives of min. 50 mm.
For optimal cooling conditions allow a free air passage above and below the frequency converter. See table below.
Air passage for different enclosures
Enclo-
sure:
a (mm): 100100100200200200200200225200225
b (mm): 100100100200200200200200225200225
1.Drill holes in accordance with the measurements given.
2.You must provide screws suitable for the surface on which you want to mount the frequency converter. Retighten all four screws.
A2A3A5B1B2B3B4C1C2C3C4
5
Table 5.1: When mounting enclosure sizes A5, B1, B2, B3, B4, C1, C2, C3 and C4 on a non-solid back wall, the drive must be provided with a back plate
A due to insufficient cooling air over the heat sink.
MG.11.B7.02 - VLT® is a registered Danfoss trademark
77
5
5. How to InstallVLT® HVAC Drive Design Guide
Illustration 5.1: With heavier drives, use a lift. First wall-mount the 2 lower bolts - then lift the drive onto the lower bolts - finally fasten the drive against
the wall with the 2 top bolts.
5.1.4. Safety Requirements of Mechanical Installation
Pay attention to the requirements that apply to integration and field mounting kit. Observe the information in the list to avoid serious
damage or injury, especially when installing large units.
The frequency converter is cooled by means of air circulation.
To protect the unit from overheating, it must be ensured that the ambient temperature
frequency converter
Derating for Ambient Temperature
If the ambient temperature is in the range of 45 °C - 55 ° C, derating of the frequency converter will become relevant, see
Temperature
The service life of the frequency converter is reduced if derating for ambient temperature is not taken into account.
and that the 24-hour average temperature
.
.
is not exceeded
. Locate the maximum temperature and 24-hour average in the paragraph
does not exceed the maximum temperature stated for the
5.1.5. Field Mounting
For field mounting the IP 21/IP 4X top/TYPE 1 kits or IP 54/55 units are recommended.
Derating for Ambient
78
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide5. How to Install
5.2. Electrical Installation
5.2.1. Cables General
NB!
For the VLT HVAC Drive High Power series mains and motor connections, please see VLT HVAC Drive
tions,MG.11.FX.YY
NB!
Cables General
Always comply with national and local regulations on cable cross-sections.
1) For different cable dimensions x/y, where x ≤ 95 mm² and y ≥ 95 mm²
2) Cable dimensions above 18.5 kW ≥ 35 mm
200-240
V
-
15
380-480
V
22
30
525-600
V
-
-
-
-
2
and below 22 kW ≤ 10 mm
LineMotor
4.5
2)
4.5
1)
14/24
1)
14/24
2
4.5
4.5
14/24
14/24
2)
1)
1)
DC connec-
tion
3.7
3.7
141430.6
141430.6
BrakeEarthRelay
3.7
3.7
3
3
0.6
0.6
5.2.2. Motor Cables
See section
General Specifications
•Use a screened/armoured motor cable to comply with EMC emission specifications.
•Keep the motor cable as short as possible to reduce the noise level and leakage currents.
•Connect the motor cable screen to both the decoupling plate of the frequency converter and to the metal cabinet of the motor.
•Make the screen connections with the largest possible surface area (cable clamp). This is done by using the supplied installation devices in the
frequency converter.
•Avoid mounting with twisted screen ends (pigtails), which will spoil high frequency screening effects.
•If it is necessary to split the screen to install a motor isolator or motor relay, the screen must be continued with the lowest possible HF impedance.
for correct dimensioning of motor cable cross-section and length.
MG.11.B7.02 - VLT® is a registered Danfoss trademark
79
5
5. How to InstallVLT® HVAC Drive Design Guide
5.2.3. Electrical Installation of Motor Cables
Screening of cables
Avoid installation with twisted screen ends (pigtails). They spoil the screening effect at higher frequencies.
If it is necessary to break the screen to install a motor isolator or motor contactor, the screen must be continued at the lowest possible HF impedance.
Cable length and cross-section
The frequency converter has been tested with a given length of cable and a given cross-section of that cable. If the cross-section is increased, the cable
capacitance - and thus the leakage current - may increase, and the cable length must be reduced correspondingly.
Switching frequency
When frequency converters are used together with Sine-wave filters to reduce the acoustic noise from a motor, the switching frequency must be set
according to the Sine-wave filter instruction in
Aluminium conductors
Aluminium conductors are not recommended. Terminals can accept aluminium conductors but the conductor surface has to be clean and the oxidation
must be removed and sealed by neutral acid free Vaseline grease before the conductor is connected.
Furthermore, the terminal screw must be retightened after two days due to the softness of the aluminium. It is crucial to keep the connection a gas tight
joint, otherwise the aluminium surface will oxidize again.
5.2.4. Removal of Knockouts for Extra Cables
1.Remove cable entry from the frequency converter (Avoiding foreign parts falling into the frequency converter when removing knockouts)
2.Cable entry has to be supported around the knockout you intend to remove.
3.The knockout can now be removed with a strong mandrel and a hammer.
4.Remove burrs from the hole.
5.Mount Cable entry on frequency converter.
Par. 14-01.
5.2.5. Enclosure Knock-outs
Illustration 5.2: Cable entry holes for enclosure B1. The suggested use
of the holes are purely recommendations and other solutions are pos-
sible.
Illustration 5.4: Cable entry holes for enclosure C1. The suggested use
of the holes are purely recommendations and other solutions are pos-
sible.
Illustration 5.3: Cable entry holes for enclosure B2. The suggested use
of the holes are purely recommendations and other solutions are pos-
sible.
80
MG.11.B7.02 - VLT® is a registered Danfoss trademark
Illustration 5.5: Cable entry holes for enclosure C2. The suggested use
of the holes are purely recommendations and other solutions are pos-
sible.
VLT® HVAC Drive Design Guide5. How to Install
5.2.6. Gland/Conduit Entry - IP21 (NEMA 1) and IP54 (NEMA12)
Cables are connected through the gland plate from the bottom. Remove the plate and plan where to place the entry for the glands or conduits. Prepare
holes in the marked area on the drawing.
The gland plate must be fitted to the frequency converter to ensure the specified protection degree, as well as ensuring proper cooling of the unit. If the
gland plate is not mounted, it may trip the unit.
Enclosure D1 + D2
5
Enclosure E1
Cable entries viewed from the bottom of the frequency converter - 1) Mains side 2) Motor side
MG.11.B7.02 - VLT® is a registered Danfoss trademark
81
5. How to InstallVLT® HVAC Drive Design Guide
Enclosure F1
5
Enclosure F2
Enclosure F3
Enclosure F4
F1-F4: Cable entries viewed from the bottom of the frequency converter - 1) Place conduits in marked areas
82
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide5. How to Install
5
Illustration 5.6: Mounting of bottom plate, E1 enclosure.
The bottom plate of the E1 enclosure can be mounted from either in- or outside of the enclosure, allowing flexibility in the installation process, i.e. if
mounted from the bottom the glands and cables can be mounted before the frequency converter is placed on the pedestal.
5.2.7. Connection to Mains and Earthing
NB!
The plug connector for power can be removed.
1.Make sure the frequency converter is properly earthed. Connect to earth connection (terminal 95). Use screw from the accessory bag.
2.Place plug connector 91, 92, 93 from the accessory bag onto the terminals labelled MAINS at the bottom of the frequency converter.
3.Connect mains wires to the mains plug connector.
The earth connection cable cross section must be at least 10 mm2 or 2 rated mains wires terminated separately according to EN 50178.
The mains connection is fitted to the main switch if this is included.
NB!
Check that mains voltage corresponds to the mains voltage of the frequency converter name plate.
IT Mains
Do not connect 400 V frequency converters with RFI-filters to mains supplies with a voltage between phase and earth of more than
440 V.
For IT mains and delta earth (grounded leg), mains voltage may exceed 440 V between phase and earth.
MG.11.B7.02 - VLT® is a registered Danfoss trademark
83
5
5. How to InstallVLT® HVAC Drive Design Guide
Illustration 5.7: Terminals for mains and earthing.
Illustration 5.8: How to connect to mains and earthing with disconnector (A5 enclosure).
84
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide5. How to Install
5.2.8. Mains connection for A2 and A3
5
Illustration 5.9: First mount the two screws on the mounting plate, slide it into place and tighten fully.
Illustration 5.10: When mounting cables, first mount and tighten earth cable.
The earth connection cable cross section must be at least 10 mm2 or 2 rated mains wires terminated separately according to
IEC 61800-5-1
.
EN 50178/
MG.11.B7.02 - VLT® is a registered Danfoss trademark
85
5
5. How to InstallVLT® HVAC Drive Design Guide
Illustration 5.11: Then mount mains plug and tighten wires.
Illustration 5.12: Finally tighten support bracket on mains wires.
86
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide5. How to Install
5.2.9. Mains connection for A5
5
Illustration 5.13: How to connect to mains and earthing without mains disconnect switch. Note that a cable clamp is used.
Illustration 5.14: How to connect to mains and earthing with mains disconnect switch.
MG.11.B7.02 - VLT® is a registered Danfoss trademark
87
5
5. How to InstallVLT® HVAC Drive Design Guide
5.2.10. Mains connection for B1, B2 and B3
130BA720.10
Illustration 5.15: How to connect to mains and earthing for B1 and
B2.
NB!
For correct cable dimensions please see the section General Specifications at the back of this manual.
Illustration 5.16: How to connect to mains and earthing for B3 with RFI.
130BA725.10
Illustration 5.17: How to connect to mains and earthing for B3 without
RFI.
88
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide5. How to Install
5.2.11. Mains connection for B4, C1 and C2
130BA714.10
5
Illustration 5.18: How to connect to mains and earthing for B4.
Illustration 5.19: How to connect to mains and earthing for C1 and C2.
5.2.12. Mains connection for C3 and C4
Illustration 5.20: How to connect C3 to mains and earthing.
5.2.13. Motor Connection
NB!
Motor cable must be screened/armoured. If an unscreened / unarmoured cable is used, some EMC requirements are not complied
with. For more information, see
EMC specifications
130BA718.10
.
130BA719.10
Illustration 5.21: How to connect C4 to mains and earthing.
MG.11.B7.02 - VLT® is a registered Danfoss trademark
89
5
5. How to InstallVLT® HVAC Drive Design Guide
Illustration 5.22: Mounting of decoupling plate.
1.Fasten decoupling plate to the bottom of the frequency converter with screws and washers from the accessory bag.
2.Attach motor cable to terminals 96 (U), 97 (V), 98 (W).
3.Connect to earth connection (terminal 99) on decoupling plate with screws from the accessory bag.
4.Insert terminals 96 (U), 97 (V), 98 (W) and motor cable to terminals labelled MOTOR.
5.Fasten screened cable to decoupling plate with screws and washers from the accessory bag.
All types of three-phase asynchronous standard motors can be connected
to the frequency converter. Normally, small motors are star-connected
(230/400 V, D/Y). Large motors are delta-connected (400/600 V, D/Y).
Refer to the motor name plate for correct connection mode and voltage.
NB!
In motors without phase insulation paper or other insulation reinforcement suitable for operation with voltage supply (such as a fre-
quency converter), fit a Sine-wave filter on the output of the frequency converter.
90
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide5. How to Install
6-wire motor terminal block
High Power Terminal Block Connections
5
Delta configurationStar configuration
High power frequency converters can accept two wires per phase.
No.969798Motor voltage 0-100%
U1V1W1
U1V1W16 wires out of motor, Star-connected
U2, V2, W2 to be interconnected separately
(optional terminal block)
No.99Earth connection
PE
UVW
W2U2V2
of mains voltage.
3 wires out of motor
6 wires out of motor, Delta-connected
5.2.14. Motor connection for A2 and A3
Follow these drawings step by step for connecting the motor to the frequency converter.
MG.11.B7.02 - VLT® is a registered Danfoss trademark
91
5
5. How to InstallVLT® HVAC Drive Design Guide
Illustration 5.23: First terminate the motor earth, then place motor U, V and W wires in plug and tighten.
Illustration 5.24: Mount cable clamp to ensure 360 degree connection between chassis and screen, note the outer insulation of the motor cable is
removed under the clamp.
92
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide5. How to Install
5.2.15. Motor connection for A5
5
Illustration 5.25: First terminate the motor earth, then place motor U, V and W wires in terminal and tighten. Please ensure that the outer insulation
of the motor cable is removed under the EMC clamp.
5.2.16. Motor connection for B1 and B2
Illustration 5.26: First terminate the motor earth, then Place motor U, V and W wires in terminal and tighten. Please ensure that the outer insulation
of the motor cable is removed under the EMC clamp.
MG.11.B7.02 - VLT® is a registered Danfoss trademark
93
5. How to InstallVLT® HVAC Drive Design Guide
5.2.17. Motor connection for B3 and B4
5
130BA726.10
Illustration 5.27: First terminate the motor earth, then Place motor U,
V and W wires in terminal and tighten. Please ensure that the outer
insulation of the motor cable is removed under the EMC clamp.
5.2.18. Motor connection for C1 and C2
130BA721.10
Illustration 5.28: First terminate the motor earth, then Place motor U,
V and W wires in terminal and tighten. Please ensure that the outer
insulation of the motor cable is removed under the EMC clamp.
Illustration 5.29: First terminate the motor earth, then Place motor U, V and W wires in terminal and tighten. Please ensure that the outer insulation
of the motor cable is removed under the EMC clamp.
94
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide5. How to Install
5.2.19. Motor connection for C3 and C4
130BA740.10
Illustration 5.30: First terminate the motor earth, then Place motor U, V and W wires in terminal and tighten. Please ensure that the outer insulation
of the motor cable is removed under the EMC clamp.
5.2.20. Fuses
Branch circuit protection
In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines etc., must be shortcircuit
and overcurrent protected according to the national/international regulations.
Short circuit protection
The frequency converter must be protected against short-circuit to avoid electrical or fire hazard. Danfoss recommends using the fuses mentioned in
tables 5.3 and 5.4 to protect service personnel or other equipment in case of an internal failure in the unit. The frequency converter provides full short
circuit protection in case of a short-circuit on the motor output.
Over-current protection
Provide overload protection to avoid fire hazard due to overheating of the cables in the installation. Over current protection must always be carried out
according to national regulations. The frequency converter is equipped with an internal over current protection that can be used for upstream overload
protection (UL-applications excluded). See par. 4-18 Current
a circuit capable of supplying a maximum of 100,000 A
Non UL compliance
If UL/cUL is not to be complied with, Danfoss recommends using the fuses mentioned in table 5.2, which will ensure compliance with EN50178:
In case of malfunction, not following the recommendation may result in unnecessary damage to the frequency converter.
Limit
in the
VLT HVAC Drive Programming Guide
(symmetrical), 500 V/600 V maximum.
rms
. Fuses must be designed for protection in
5
MG.11.B7.02 - VLT® is a registered Danfoss trademark
P355170M601320221900 A, 700 V120
P400170M601320221900 A, 700 V120
P450170M601320221900A, 700 V120
Table 5.17: E enclosures, 380-480 V
98
Bussmann PN*Danfoss PNRatingLosses (W)
MG.11.B7.02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Design Guide5. How to Install
Size/TypeBussmann JFHR2*SIBA Type RK1FERRAZ-SHAWMUT Type RK1
P355170M5013/170M40172061032.700900 A, 700 V
P400170M5013/170M40172061032.700900 A, 700 V
P450170M60132063032.900900 A, 700 V
P500170M60132063032.900900A, 700 V
P560170M60132063032.900
Table 5.18: E enclosures, 525-600 V
*170M fuses from Bussmann shown, use the -/80 visual indicator, -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and amperage
may be substituted for external use.
*170M fuses from Bussmann shown, use the -/80 visual indicator, -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and amperage
may be substituted for external use.
5.2.21. Access to Control Terminals
All terminals to the control cables are located underneath the terminal cover on the front of the frequency converter. Remove the terminal cover by means
of a screwdriver (see illustration).
5
Illustration 5.31: A1, A2, A3,B3, B4, C3 and C4 enclosures
5.2.22. Control Terminals
Drawing reference numbers:
1.10 pole plug digital I/O.
2.3 pole plug RS485 Bus.
3.6 pole analog I/O.
4.USB Connection.
MG.11.B7.02 - VLT® is a registered Danfoss trademark
Illustration 5.32: A5, B1, B2, C1 and C2 enclosures
99
5
5. How to InstallVLT® HVAC Drive Design Guide
Illustration 5.33: Control terminals (all enclosures)
5.2.23. Electrical Installation, Control Cable Terminals
To mount the cable to the terminal:
1.Strip isolation of 9-10 mm
2.
Insert a screw driver
3.Insert the cable in the adjacent circular hole.
4.Remove the screw driver. The cable is now mounted to the ter-
minal.
To remove the cable from the terminal:
1.
Insert a screw driver
2.Pull out the cable.
1)
Max. 0.4 x 2.5 mm
1)
in the square hole.
1)
in the square hole.
1.
2.
3.
100
MG.11.B7.02 - VLT® is a registered Danfoss trademark
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.