1.1.1 Copyright, Limitation of Liability and Revision Rights1-1
1.1.2 Symbols1-1
1.1.3 Abbreviations1-2
1.1.5 Definitions1-2
1.1.8 Electrical Overview1-7
2 How to Program
2.1 Programming with MCT-10 Setup Software
2.2 Local Control Panel (LCP)
2.3 Menus
2.3.1 Status2-2
2.3.2 Quick Menu2-2
2.3.3 The FC101 Start-up Wizard for Open-loop Applications2-2
2.3.4 Main Menu2-11
2.4 Quick Transfer of Parameter Settings between Multiple Adjustable Frequency
Drives
2.5 Read-out and Programming of Indexed Parameters
1-1
2-1
2-1
2-1
2-2
2-12
2-12
2.6 Initialize the Adjustable Frequency Drive to Default Settings in Two Ways
3 Parameters
3.1 Main Menu - Operation and Display - Group 0
3.1.1 0-0* Basic Settings3-1
3.1.2 0-1* Define and set-up Operations3-2
3.1.3 0-3* LCP Custom Readout3-3
3.1.4 0-4* LCP3-4
3.1.5 0-5* Copy/Save3-4
3.1.6 0-6* Password3-5
3.2 Main Menu - Load and Motor - Group 1
3.2.1 1-0* General Settings3-6
3.2.2 1-10 - 1-13 Motor Selection3-6
3.2.5 1-2* Motor Data3-8
3.3 Main Menu - Brakes - Group 2
3.3.1 2-1* Overvoltage Control3-13
3.4 Main Menu - Reference/Ramps - Group 3
3.4.1 3-0* Reference Limits3-14
2-12
3-1
3-1
3-6
3-13
3-14
3.4.2 3-1* References3-14
3.4.3 3-4* Ramp 13-15
MG18B222 - VLT® is a registered Danfoss trademark
Contents
VLT® HVAC Basic Drive Programming Guide
3.4.4 3-5* Ramp 23-15
3.4.5 3-8* Other Ramps3-16
3.5 Main Menu - Limits/Warnings - Group 4
3.5.1 4-1* Motor Limits3-17
3.5.3 4-5* Adj. Warnings3-17
3.5.4 4-6* Speed Bypass3-18
3.6 Main Menu - Digital In/Out - Group 5
3.6.1 5-0* Digital I/O Mode3-20
3.6.2 5-1* Digital Inputs3-20
3.6.4 5-4* Relays3-26
3.6.6 5-9* Bus Controlled3-30
3.7 Main Menu - Analog In/Out - Group 6
3.7.1 6-0* Analog I/O Mode3-31
3.7.2 6-1* Analog Input 533-31
3.7.3 6-2* Analog Input 543-32
3.7.4 6-7* Analog/Digital Output 453-32
3.7.5 6-9* Analog/Digital Output 423-34
3.8 Main Menu - Communications and Options - Group 8
3.8.1 8-0* General Settings3-36
3-17
3-20
3-31
3-36
3.8.2 8-3* FC Port Settings3-36
3.8.3 8-5* Digital/Bus3-37
3.8.4 8-7* BACnet3-38
3.8.5 8-8* FC Port Diagnostics3-39
3.8.6 8-9* Bus Feedback3-39
3.9 Main Menu - Smart Logic - Group 13
3.9.1 13-** Prog. Features3-40
3.9.2 13-0* SLC Settings3-40
3.9.3 13-1* Comparators3-42
3.9.4 13-2*Timers3-43
3.9.5 13-4* Logic Rules3-43
3.9.6 13-5* States3-46
3.10 Main Menu - Special Functions - Group 14
3.10.1 14-0* Inverter Switching3-49
3.10.2 14-1* >Mains Power On/Off3-49
3.10.3 14-2* Trip Reset3-49
3.10.4 14-4*Energy Optimizing3-50
3-40
3-49
3.10.5 14-5* Environment3-50
3.11 Main Menu - Drive Information - Group 15
MG18B222 - VLT® is a registered Danfoss trademark
3-52
Contents
VLT® HVAC Basic Drive Programming Guide
3.11.1 15-0* Operating Data3-52
3.11.2 15-3* Alarm Log3-52
3.11.3 15-4* Drive Identification3-52
3.12 Main Menu - Data Readouts - Group 16
3.12.1 16-0* General Status3-54
3.12.2 16-1* Motor Status3-54
3.12.3 16-3* Drive Status3-55
3.12.4 16-5* Ref. & Feedb.3-55
3.12.5 16-6* Inputs and Outputs3-55
3.12.6 16-8* Fieldbus & FC Port3-57
3.12.7 16-9* Diagnosis Readouts3-57
3.13 Main Menu - Data Readouts 2 - Group 18
3.13.1 18-1* Fire Mode Log3-58
3.14 Main Menu - Adjustable Frequency Drive Closed-loop - Group 20
3.14.1 20-0* Feedback3-59
3.14.2 20-8* PI Basic Settings3-59
3.14.3 20-9* PI Controller3-59
3.15 Main Menu - Application Functions - Group 22
3.15.1 22-4* Sleep Mode3-60
3.15.2 22-6* Broken Belt Detection3-61
3-54
3-58
3-59
3-60
3.16 Main Menu - Application Functions 2 - Group 24
3.16.1 24-0* Fire Mode3-62
3.16.2 24-1* Drive Bypass3-63
4 Troubleshooting
4.1.2 Alarm Words4-3
4.1.3 Warning Words4-3
4.1.4 Extended Status Words4-4
4.1.5 Fault Messages4-4
5 Parameter Lists
5.1 Parameter Options
5.1.1 Default settings5-1
5.1.2 0-** Operation / Display5-2
5.1.3 1-** Load and Motor5-3
5.1.4 2-** Brakes5-4
5.1.5 3-** Reference/Ramps5-5
5.1.6 4-** Limits/Warnings5-6
3-62
4-1
5-1
5-1
5.1.7 5-** Digital In/Out5-7
MG18B222 - VLT® is a registered Danfoss trademark
Contents
VLT® HVAC Basic Drive Programming Guide
5.1.8 6-** Analog In/Out5-8
5.1.9 8-** Comm. and Options5-9
5.1.10 13-** Smart Logic5-10
5.1.11 14-** Special Functions5-11
5.1.12 15-** Drive Information5-12
5.1.13 16-** Data Readouts5-13
5.1.14 18-** Info & Readouts5-14
5.1.15 20-** Drive Closed Loop5-14
5.1.16 22-** Appl. Functions5-15
5.1.17 24-** Appl. Functions 25-15
6 Index
6-1
MG18B222 - VLT® is a registered Danfoss trademark
Introduction
1 Introduction
VLT® HVAC Basic Drive Programming Guide
11
VLT HVAC Basic Drive
FC 100 Series
Table 1.1
This guide can be used with all VLT
HVAC Basic Drive adjustable
frequency drives with software
version 2.0X.
The actual software version
number can be read from
15-43 Software Version.
Table 1.2
Copyright, Limitation of Liability and
1.1.1
Revision Rights
the use, or the inability to use information contained in
this manual, even if advised of the possibility of such
damages. In particular, Danfoss is not responsible for any
costs, including but not limited to those incurred as a
result of lost profits or revenue, loss or damage of
equipment, loss of computer programs, loss of data, the
costs to substitute these, or any claims by third parties.
Danfoss reserves the right to revise this publication at any
time and to make changes to its contents without prior
notice or any obligation to notify former or present users
of such revisions or changes.
Symbols
1.1.2
Symbols used in this guide.
NOTE!
Indicates something to be noted by the reader.
CAUTION
Indicates a potentially hazardous situation which, if not
avoided, may result in minor or moderate injury or
equipment damage.
This publication contains information proprietary to
Danfoss. By accepting and using this manual, the user
agrees that the information contained herein will be used
solely for operating equipment from Danfoss or equipment
from other vendors provided that such equipment is
intended for communication with Danfoss equipment over
a serial communication link. This publication is protected
under the copyright laws of Denmark and most other
countries.
Danfoss does not warrant that a software program
produced according to the guidelines provided in this
manual will function properly in every physical, hardware
or software environment.
Although Danfoss has tested and reviewed the documentation within this manual, Danfoss makes no warranty or
representation, neither expressed nor implied, with respect
to this documentation, including its quality, performance,
or fitness for a particular purpose.
In no event shall Danfoss be liable for direct, indirect,
special, incidental, or consequential damages arising out of
WARNING
Indicates a potentially hazardous situation which, if not
avoided, could result in death or serious injury.
Indicates default setting
*
Table 1.3
MG18B222 - VLT® is a registered Danfoss trademark1-1
Introduction
VLT® HVAC Basic Drive Programming Guide
11
1.1.3 Abbreviations
Alternating currentAC
American wire gaugeAWG
Ampere/AMPA
Automatic Motor AdaptationAMA
Current limitI
Degrees Celsius
Direct currentDC
Drive DependentD-TYPE
Electro Magnetic CompatibilityEMC
Electronic Thermal RelayETR
Adjustable frequency driveFC
Gramg
HertzHz
Horsepowerhp
KilohertzkHz
Local Control PanelLCP
Meterm
Millihenry InductancemH
MilliamperemA
Millisecondms
Minutemin
Motion Control ToolMCT
NanofaradnF
Newton MetersNm
Nominal motor currentI
Nominal motor frequencyf
Nominal motor powerP
Nominal motor voltageU
Permanent Magnet motorPM motor
Protective Extra Low VoltagePELV
Printed Circuit BoardPCB
Rated Inverter Output CurrentI
Revolutions Per MinuteRPM
Regenerative terminalsRegen
Seconds
Synchronous Motor Speedn
Torque limitT
VoltsV
The maximum output currentI
The rated output current supplied by the
adjustable frequency drive
Table 1.4
LIM
°C
M,N
M,N
M,N
M,N
INV
s
LIM
VLT,MAX
I
VLT,N
1.1.4
Available Literature for VLT HVAC
Basic Drive
-Quick Guide MG18AXYY
-Programming Guide MG18BXYY provides
information on how to program and includes
complete parameter descriptions.
-Design Guide MG18CXYY provides all the
technical information about the adjustable
frequency drive and customer design and
applications.
-PC-based Configuration Tool MCT 10, MG10AXYY
enables the user to configure the adjustable
frequency drive from a Windows™-based PC
environment.
-
Danfoss VLT® Energy Box software at
www.danfoss.com/BusinessAreas/DrivesSolutions
then choose PC Software Download
VLT® Energy Box Software allows energy
consumption comparisons of HVAC fans and
pumps driven by Danfoss drives and alternative
methods of flow control. This tool may be used
to project, as accurately as possible, the costs,
savings, and payback of using Danfoss adjustable
frequency drives on HVAC fans and pumps.
X = Revision number
YY = Language code
Danfoss technical literature is available in print from your
local Danfoss Sales Office or online at:
Rated output current supplied by the Adjustable frequency
drive.
U
VLT, MAX
Maximum output voltage.
Input:
Control command
Start and stop the connected motor by means of LCP and
digital inputs.
Functions are divided into two groups.
Functions in group 1 have higher priority than functions in
group 2.
1-2MG18B222 - VLT® is a registered Danfoss trademark
175ZA078.10
Pull-out
rpm
Torque
Introduction
VLT® HVAC Basic Drive Programming Guide
11
Group 1Reset, Coasting stop, Reset and Coasting stop,
Quick stop, DC braking, Stop and the [OFF] key.
Group 2Start, Latched start, Reversing, Start reversing, Jog
and Freeze output
Table 1.5
Motor:
Motor Running
Torque generated on output shaft and speed from zero
rpm to max. speed on motor.
f
JOG
Motor frequency when the jog function is activated (via
digital terminals).
f
M
Motor frequency.
f
MAX
Maximum motor frequency.
f
MIN
Minimum motor frequency.
f
M,N
Rated motor frequency (nameplate data).
I
M
Motor current (actual).
I
M,N
Rated motor current (nameplate data).
n
M,N
Rated motor speed (nameplate data).
n
s
Synchronous motor speed
2 ×
par
=
. 1 − 23 × 60
par
. 1 − 39
n
s
P
M,N
s
Rated motor power (nameplate data in kW or hp).
T
M,N
Rated torque (motor).
U
M
Instantaneous motor voltage.
U
M,N
Rated motor voltage (nameplate data).
Break-away torque
Figure 1.1
η
VLT
The efficiency of the adjustable frequency drive is defined
as the ratio between the power output and the power
input.
Start-disable command
A stop command belonging to the group 1 control
commands - see this group.
Stop command
See Control commands.
References:
Analog Reference
A signal transmitted to the analog inputs 53 or 54, can be
voltage or current.
Binary Reference
A signal transmitted to the serial communication port.
Preset Reference
A defined preset reference to be set from -100% to +100%
of the reference range. Selection of eight preset references
via the digital terminals.
Ref
MAX
Determines the relationship between the reference input
at 100% full scale value (typically 10 V, 20 mA) and the
resulting reference. The maximum reference value set in
3-03 Maximum Reference.
Ref
MIN
Determines the relationship between the reference input
at 0% value (typically 0 V, 0 mA, 4 mA) and the resulting
reference. The minimum reference value set in
3-02 Minimum Reference.
MG18B222 - VLT® is a registered Danfoss trademark1-3
Introduction
VLT® HVAC Basic Drive Programming Guide
11
Miscellaneous:
Analog Inputs
The analog inputs are used for controlling various
functions of the Adjustable frequency drive.
There are two types of analog inputs:
Current input, 0-20 mA and 4-20 mA
Voltage input, 0-10 V
Analog Outputs
The analog outputs can supply a signal of 0–20 mA, 4–20
mA.
Automatic Motor Adaptation, AMA
AMA algorithm determines the electrical parameters for
the connected motor at standstill.
CTW
Control Word
Digital Inputs
The digital inputs can be used for controlling various
functions of the Adjustable frequency drive.
ETR
Electronic Thermal Relay is a thermal load calculation
based on present load and time. Its purpose is to estimate
the motor or Adjustable frequency drive temperature.
Initializing
If initialization is carried out (14-22 Operation Mode), the
Adjustable frequency drive returns to the default setting.
Intermittent Duty Cycle
An intermittent duty rating refers to a sequence of duty
cycles. Each cycle consists of an on-load and an off-load
period. The operation can be either periodic duty or nonperiodic duty.
LCP
The Local Control Panel makes up a complete interface for
control and programming of the adjustable frequency
drive. The control panel is detachable and can be installed
up to 10 ft [3 m] from the adjustable frequency drive, i.e.,
in a front panel by means of the installation kit option.
lsb
Least significant bit.
msb
Most significant bit.
MCM
Short for Mille Circular Mil, an American measuring unit for
cable cross-sections. 1 MCM = 0.5067 mm2.
Process PI
The PI control maintains the desired speed, pressure,
temperature, etc. by adjusting the output frequency to
match the varying load.
Power Cycle
Switch off line power until the display (LCP) is dark – then
turn power on again.
RCD
Residual Current Device.
Set-up
You can save parameter settings in two set-ups. Change
between the two parameter set-ups and edit one set-up,
while another set-up is active.
Slip Compensation
The adjustable frequency drive compensates for the motor
slip by giving the frequency a supplement that follows the
measured motor load, keeping the motor speed almost
constant.
Slip compensation is default set to off.
Smart Logic Control (SLC)
The SLC is a sequence of user-defined actions executed
when the associated user-defined events are evaluated as
true by the Smart Logic Controller. (Parameter group 13-**
Smart Logic Control (SLC).)
STW
Status Word
Adjustable Frequency Drive Standard Bus
Includes RS-485 bus with FC protocol. See 8-30 Protocol.
Thermistor
A temperature-dependent resistor placed where the
temperature is to be monitored (adjustable frequency drive
or motor).
Trip
A state entered in fault situations, e.g., if the adjustable
frequency drive is subject to an over-temperature or when
the adjustable frequency drive is protecting the motor,
process or mechanism. Restart is prevented until the cause
of the fault has disappeared and the trip state is canceled
by activating reset or, in some cases, by being
programmed to reset automatically. Trip may not be used
for personal safety.
Trip Lock
A state entered in fault situations when the adjustable
frequency drive is protecting itself and requiring physical
intervention, e.g., if the adjustable frequency drive is
subject to a short circuit on the output. A locked trip can
only be canceled by cutting off line power, removing the
cause of the fault, and reconnecting the adjustable
frequency drive. Restart is prevented until the trip state is
canceled by activating reset or, in some cases, by being
programmed to reset automatically. Trip may not be used
for personal safety.
VT Characteristics
Variable torque characteristics used for pumps and fans.
1-4MG18B222 - VLT® is a registered Danfoss trademark
Introduction
VLT® HVAC Basic Drive Programming Guide
11
plus
VVC
If compared with standard voltage/frequency ratio control,
Voltage Vector Control (VVC
plus
) improves the dynamics
and the stability, both when the speed reference is
changed and in relation to the load torque.
Power Factor
The power factor is the relation between I1 and I
3 x U x
I
cos
ϕ
Power factor
=
3 x U x
1
I
RMS
RMS
.
The power factor for 3-phase control:
=
I1 x cos
I
RMS
ϕ1
=
I
RMS
I
1
since cos
ϕ1 = 1
The power factor indicates to what extent the adjustable
frequency drive imposes a load on the line power supply.
The lower the power factor, the higher the I
RMS
for the
same kW [hp] performance.
2
2
I
=
I
RMS
+
1
2
I
+
I
+ .. +
5
7
2
I
n
In addition, a high power factor indicates that the different
harmonic currents are low.
The built-in DC coils in the adjustable frequency drive
produce a high power factor, which minimizes the
imposed load on the line power supply.
Safety Precautions
1.1.6
WARNING
The voltage of the adjustable frequency drive is dangerous
whenever connected to line power. Incorrect installation of
the motor, adjustable frequency drive or serial communication bus may cause death, serious personal injury or
damage to the equipment. Consequently, the instructions
in this manual, as well as national and local rules and
safety regulations, must be complied with.
Safety Regulations
1.The line power supply to the adjustable
frequency drive must be disconnected whenever
repair work is to be carried out. Make sure that
the line power supply has been disconnected and
that the necessary time has elapsed before
removing motor and line power supply plugs.
2.The [OFF] key on the control panel of the
adjustable frequency drive does not disconnect
the line power supply and consequently it must
not be used as a safety switch.
3.The equipment must be properly grounded, the
user must be protected against supply voltage
and the motor must be protected against
overload in accordance with applicable national
and local regulations.
4.The ground leakage current exceeds 3.5 mA.
5.Protection against motor overload is not included
in the factory setting. If this function is desired,
set 1-90 Motor Thermal Protection to data value [4]ETR trip 1 or data value [3] ETR warning 1.
6.Do not remove the plugs for the motor and line
power supply while the adjustable frequency
drive is connected to line power. Make sure that
the line power supply has been disconnected and
that the necessary time has elapsed before
removing motor and line power plugs.
7.Please note that the adjustable frequency drive
has more voltage sources than L1, L2 and L3,
when load sharing (linking of DC intermediate
circuit) or external 24 V DC are installed. Make
sure that all voltage sources have been disconnected and that the necessary time has elapsed
before commencing repair work.
Safety Precautions - Continued
1.1.7
Warning against unintended start
1.The motor can be brought to a stop by means of
digital commands, bus commands, references or
a local stop, while the adjustable frequency drive
is connected to line power. If personal safety
considerations (e.g., risk of personal injury caused
by contact with moving machine parts following
an unintentional start) make it necessary to
ensure that no unintended start occurs, these
stop functions are not sufficient. In such cases,
the line power supply must be disconnected.
2.The motor may start while setting the
parameters. If this means that personal safety
may be compromised (e.g., personal injury caused
by contact with moving machine parts), motor
starting must be prevented, for instance by
secure disconnection of the motor connection.
3.A motor that has been stopped with the line
power supply connected, may start if faults occur
in the electronics of the adjustable frequency
drive, through temporary overload or if a fault in
the power supply grid or motor connection is
remedied. If unintended start must be prevented
for personal safety reasons (e.g., risk of injury
caused by contact with moving machine parts),
the normal stop functions of the adjustable
frequency drive are not sufficient.
MG18B222 - VLT® is a registered Danfoss trademark1-5
Introduction
VLT® HVAC Basic Drive Programming Guide
11
4.Control signals from, or internally within, the
adjustable frequency drive may in rare cases be
activated in error, be delayed or fail to occur
entirely. When used in situations where safety is
critical, these control signals must not be relied
on exclusively.
WARNING
High Voltage
Touching the electrical parts may be fatal - even after the
equipment has been disconnected from line power.
Also make sure that other voltage inputs have been
disconnected, such as load sharing (linkage of DC
intermediate circuit)
Systems where adjustable frequency drives are installed
must, if necessary, be equipped with additional monitoring
and protective devices according to the valid safety
regulations, e.g., law on mechanical tools, regulations for
the prevention of accidents, etc. Modifications on the
adjustable frequency drives by means of the operating
software are allowed.
NOTE!
Hazardous situations shall be identified by the machine
builder/integrator who is responsible for taking necessary
preventive means into consideration. Additional
monitoring and protective devices may be included, always
according to valid national safety regulations, e.g., law on
mechanical tools, regulations for the prevention of
accidents.
Protection Mode
Once a hardware limit on motor current or DC link voltage
is exceeded, the adjustable frequency drive will enter
Protection mode. Protection mode means a change of the
PWM modulation strategy and a low switching frequency
to minimize losses. This continues 10 sec after the last fault
and increases the reliability and the robustness of the
adjustable frequency drive while re-establishing full control
of the motor. Parameter 0-07 Auto DC Braking may cause
PWM when coasted.
1-6MG18B222 - VLT® is a registered Danfoss trademark
L1
L2
L3
3 Phase
power
input
PE
PE
+10Vdc
0-10Vdc-
0-10Vdc-
50 (+10V OUT)
54 (A IN)
53 (A IN)
55 (COM A IN/OUT)
0/4-20 mA
0/4-20 mA
42 0/4-20mA A OUT / DIG OUT
45 0/4-20mA A OUT / DIG OUT
18 (DIGI IN)
19 (DIGI IN)
27 (DIGI IN)
29 (DIGI IN)
12 (+24V OUT)
24V (NPN)
20 (COM D IN)
OV (PNP)
24V (NPN)
OV (PNP)
24V (NPN)
OV (PNP)
24V (NPN)
OV (PNP)
Bus ter.
Bus ter.
RS-485
Interface
RS-485
(N PS-485) 69
(P RS-485) 68
(Com RS-485) 61
(PNP) Source
(NPN) Sink
ON=Terminated
OFF=Unterminated
ON
1 2
240Vac 2A
Not present on all power sizes
Do not connect shield to
61 on 116, 117 and 118 units
01
02
03
relay1
relay2
UDC+
UDC-
Motor
U
V
W
130BB626.10
06
05
04
240Vac 2A
Introduction
1.1.8 Electrical Overview
VLT® HVAC Basic Drive Programming Guide
11
Figure 1.2
NOTE!
Please note there is no access to UDC- and UDC+ on the following units:
IP20 380–480 V 40–125 hp [30–90 kW]
IP20 200–240 V 20–60 hp [15–45 kW]
IP20 525–600 V 3–125 hp [2.2–90 kW]
IP54 380–480 V 30–125 hp [22–90 kW]
MG18B222 - VLT® is a registered Danfoss trademark1-7
Introduction
VLT® HVAC Basic Drive Programming Guide
11
1-8MG18B222 - VLT® is a registered Danfoss trademark
130BB765.11
B
a
c
k
Com.
1-20 Motor Power
[5] 0.37kW - 0.5HP
Setup 1
A
B
1
12
131415
11
11
10
9
8
7
6
5
4
3
2
C
D
Status
Main
Menu
Quick
Menu
Hand
On
OK
Menu
O
Reset
Auto
On
Alarm
Warn.
On
11
How to Program
VLT® HVAC Basic Drive Programming Guide
2 How to Program
2.1 Programming with MCT-10 Setup
Software
The adjustable frequency drive can be programmed from a
PC via RS-485 COM port by installing the MCT-10 Setup
Software. This software can either be ordered using code
number 130B1000 or downloaded from the Danfoss
Website: http://www.danfoss.com/BusinessAreas/DrivesSolutions/Softwaredownload/ Please refer to manual
MG10RXYY.
2.2 Local Control Panel (LCP)
The following instructions are valid for the FC 101 LCP. The
LCP is divided into four functional sections.
A. Alphanumeric display
B. Menu key
C. Navigation keys and LEDs
D. Operation keys and LEDs
Information can be read from the display.
1Parameter number and name.
2Parameter value.
3Set-up number shows the active set-up and the edit set-
up. If the same set-up acts as both the active and edit setup, only that set-up number is shown (factory setting).
When the active and edit set-up differ, both numbers are
shown in the display (Set-up 12). The flashing number
indicates the edit set-up.
4Motor direction is shown to the bottom left of the display
– indicated by a small arrow pointing either clockwise or
counter-clockwise.
5The triangle indicates if the LCP is in status, quick menu or
main menu.
Table 2.1
B. Menu Key
Use the menu key to select between status, quick menu or
main menu.
C. Navigation keys and LEDs
6 Com led: Flashes when bus communication is communi-
cating.
7 Green LED/On: Control section is working.
8 Yellow LED/Warn.: Indicates a warning.
9 Flashing Red LED/Alarm: Indicates an alarm.
10 [Back]: For moving to the previous step or layer in the
navigation structure
11
Arrows [▲] [▼]: For navigating between parameter groups,
parameters and within parameters. Can also be used for
setting local reference.
12 [OK]: For selecting a parameter and for accepting changes to
parameter settings
22
Table 2.2
Figure 2.1
A. Alpha Numeric Display
The LCD display is backlit with two alpha-numeric lines. All
data is displayed on the LCP.
MG18B222 - VLT® is a registered Danfoss trademark2-1
130BB628.10
Select Language
[ 0 ] English
Set-up 1
FC
+24V
DIG IN
DIG IN
DIG IN
DIG IN
COM DIG IN
A OUT / D OUT
A OUT / D OUT
18
19
27
29
42
55
50
53
54
20
12
01
02
03
04
05
06
R2
R1
0-10 V
Reference
Start
+10V
A IN
A IN
COM
130BB674.10
45
+
-
130BB629.10
Press OK to start Wizard
Push Back to skip it
Set-up 1
How to Program
VLT® HVAC Basic Drive Programming Guide
D. Operation keys and LEDs
22
13 [Hand On]: Starts the motor and enables control of the
adjustable frequency drive via the LCP.
NOTE!
2.3.2
Quick Menu
Use the quick setup of the adjustable frequency drive to
program the most common VLT HVAC Basic Drive
functions. The [Quick Menu] consists of:
Terminal 27 Digital Input (5-12 Terminal 27 DigitalInput) has coast inverse as default setting. This
means that [Hand On] will not start the motor if
there is no 24 V to terminal 27. Connect terminal 12
to terminal 27.
14 [Off/Reset]: Stops the motor (off). If in alarm mode the
alarm will be reset.
15 [Auto On]: The adjustable frequency drive is controlled
either via control terminals or serial communication.
Table 2.3
2.3.3 The FC101 Start-up Wizard for Open-
The built-in wizard menu guides the installer through the
Wizard for open-loop applications
•
Closed-loop set-up wizard
•
Motor set-up
•
Changes made
•
loop Applications
set up of the adjustable frequency drive in a clear and
At power-up
At the first power-up, the user is asked to choose the
preferred language. Once selected, this screen will never
be shown again in the following power-ups, but the
language can still be changed in 0-01 Language.
structured manner in order to set up an open-loop
application. An open-loop application is here an
application with a start signal, analog reference (voltage or
current) and optionally also relay signals (but no feedback
signal from the process applied).
Figure 2.2
2.3 Menus
2.3.1 Status
When choosing the [Status] menu it is possible to choose
between the following:
Motor Power (kW) (if 0-03 Regional Settings is set
•
to [1] North America, Motor Power will be shown
in the unit of hp instead of kW), 16-10 Power [kW]
for kW, 16-11 Power [hp] for hp;
Custom Readout 16-09 Custom Readout;
•
Figure 2.3
The wizard will initially be shown after power-up until any
parameter has been changed. The wizard can always be
accessed again through the Quick Menu. Press [OK] to start
the wizard. If [Back] is pressed, the FC 101 will return to
the status screen.
Figure 2.4
2-2MG18B222 - VLT® is a registered Danfoss trademark
130BC401.10
Value
Setup 1
Power kW/50 Hz
Setup 1
Set Motor Speed low Limit
Hz
Setup 1
Set Motor Speed high Limit
Hz
Setup 1
Set Ramp 1 ramp-up time
s
Setup 1
Set Ramp 1 ramp-down Time
s
Setup 1
Active Flying start?
Disable
OK
OK
B
a
c
k
Status
Main
Menu
Quick
Menu
Hand
On
OK
Menu
O
Reset
Auto
On
Alarm
Warn
On
Status Screen
The Wizard can always be
reentered via the Quick Menu!
Power Up Screen
At power up the user is
asked to choose the
prefered language.
Select language
[1] English
0.0 Hz
0.0 kW
Setup 1
Setup 1
Status
Main
Menu
Quick
Menu
Hand
On
OK
Menu
O
Reset
Auto
On
Alarm
Warn
On
Press OK to start Wizard
Press Back to skip it
Setup 1
Status
Main
Menu
Quick
Menu
Hand
On
OK
Menu
O
Reset
Auto
On
Alarm
Warn
On
The next screen will be
the Wizard screen.
Wizard Screen
5
Setup 1
Set Motor Power
7
Setup 1
Set Motor Voltage
8
Setup 1
Set Motor frequency
9
Setup 1
Set Motor current
10
Setup 1
Set Motor nominal speed
11
1
2
if
if
3
17
20
21
22
B
a
c
k
B
a
c
k
B
a
c
k
Select Regional Settings
... the HVAC FC 101 Wizard starts
Setup 1
200-240V/50Hz/Delta
Grid Type
4
Asynchronous Motor
Setup 1
Asynchronous
Select Motor Type
6
Setup 1
Set Motor current
12
Setup 1
Select Motor nominal speed
13
Setup 1
Set Motor Cont. Rated Torque
14
Setup 1
Stator resistance
15
Setup 1
Motor poles
16
Setup 1
Back EMF at 1000 rpm
18
Setup 1
d-axis inductance
19
Setup 1
Set Max Output Frequency
23
24
Setup 1
Setup 1Setup 1
Setup 1
Set T53 low Voltage
V
Set T53 high Voltage
V
Set T53 Low Current
A
Set T53 High Current
A
Current
Voltage
28
29
26
27
Setup 1
Setup 1
Setup 1
Setup 1
Setup 1
Setup 1
Setup 1
Setup 1
Setup 1
AMA Failed
0.0 Hz
0.0 kW
Wizard completed
Press OK to accept
Automatic Motor Adaption
O
Auto Motor Adapt OK
Press OK
Select Function of Relay 2
No function
Select Function of Relay 1
[0] No function
Set Max Reference
Hz
Set Min Reference
Hz
AMA running
-----
AMA failed
Do AMA
(Do not AMA)
AMA OK
30
31
32
33
34
37
38
39
3536
[0]
[0]
[0]
Setup 1
Select T53 Mode
Current
25
[0]
[0]
3.8
A
3000
RPM
5.4
Nm
0.65
Ohms
8
57
V
5
mH
0065
Hz
1.50
kW
0050
V
0050
Hz
04.66
A
1420
RPM
[0]
PM motor
Motor Type = Asynchronous
Motor Type = PM Motor
0000
0050
0003
0003
[0]
[0]
04.66
13.30
0050
0220
0000
0050
How to Program
VLT® HVAC Basic Drive Programming Guide
22
Figure 2.5
MG18B222 - VLT® is a registered Danfoss trademark2-3
How to Program
VLT® HVAC Basic Drive Programming Guide
The FC 101 Start-up Wizard for Open-loop Applications
0.12–110 kW/0.16–150 hpSize relatedEnter motor power from nameplate data
0
Size related
[0] AsynchronSetting the parameter value might change these
Select operating mode for restart upon
reconnection of the drive to AC line voltage after
power-down
parameters:
1-01 Motor Control Principle
1-03 Torque Characteristics
1-14 Damping Gain
1-15 Low Speed Filter Time Const.
1-16 High Speed Filter Time Const.
1-17 Voltage filter time const.
1-20 Motor Power [kW]
1-22 Motor Voltage
1-23 Motor Frequency
1-24 Motor Current
1-25 Motor Nominal Speed
1-26 Motor Cont. Rated Torque
1-30 Stator Resistance (Rs)
1-33 Stator Leakage Reactance (X1)
1-35 Main Reactance (Xh)
1-37 d-axis Inductance (Ld)
1-39 Motor Poles
1-40 Back EMF at 1000 RPM
1-66 Min. Current at Low Speed
1-72 Start Function
1-73 Flying Start
4-19 Max Output Frequency
4-58 Missing Motor Phase Function
2-4MG18B222 - VLT® is a registered Danfoss trademark
How to Program
VLT® HVAC Basic Drive Programming Guide
No & NameRangeDefaultFunction
1-22 Motor Voltage50.0–1,000.0 VSize relatedEnter motor voltage from nameplate data
1-23 Motor Frequency20.0–400.0 HzSize relatedEnter motor frequency from nameplate data
1-24 Motor Current0.01–10,000.00 ASize relatedEnter motor current from nameplate data
1-25 Motor Nominal
Speed
1-26 Motor Cont. Rated
Torque
100.0–9,999.0 RPMSize relatedEnter motor nominal speed from nameplate data
0.1–1,000.0Size relatedThis parameter is available only when 1-10 Motor
Construction Design is set to [1] PM, non-salientSPM.
NOTE!
Changing this parameter will affect settings
of other parameters
1-39 Motor Poles2-1004Enter the number of motor poles
1-40 Back EMF at 1000
RPM
1-73 Flying StartWhen PM is selected, Flying Start is enabled and
1-73 Flying Start[0] Disabled
3-02 Minimum Reference -4,999-4,9990The minimum reference is the lowest value
3-03 Maximum Reference -4,999–4,99950The maximum reference is the lowest obtainable
3-41 Ramp 1 Ramp Up
Time
3-42 Ramp 1 Ramp
Down Time
4-12 Motor Speed Low
Limit [Hz]
4-14 Motor Speed High
Limit [Hz]
4-19 Max Output
Frequency
5-40 Function Relay [0]
Function relay
5-40 Function Relay [1]
Function relay
See 1-29 Automatic Motor Adaption
(AMA)
0.000–99.990Size relatedSet the stator resistance value
0–1000Size relatedEnter the value of the d-axis inductance.
10–9,000Size relatedLine-Line RMS back EMF voltage at 1000 RPM
[1] Enabled
0.05–3,600.0 sSize relatedRamp-up time from 0 to rated 1-23 Motor
0.05–3,600.0 sSize relatedRamp-down time from rated 1-23 Motor
0.0–400 Hz0 HzEnter the minimum limit for low speed
0.0–400 Hz65 HzEnter the maximum limit for high speed
0–400Size relatedEnter the maximum output frequency value
See 5-40 Function RelayAlarmSelect the function to control output relay 1.
See 5-40 Function RelayDrive runningSelect the function to control output relay 2.
OffPerforming an AMA optimizes motor performance.
Obtain the value from the permanent magnet
motor data sheet. The de-axis inductance cannot
be found by performing an AMA.
cannot disable
0
Select [1] Enable to enable the drive to catch a
motor spinning due to line drop-out. Select [0]Disable if this function is not required. When is
enabled 1-71 Start Delay and 1-72 Start Function
have no function. is active in VVC+ mode only.
obtainable by summing all references.
by summing all references.
Frequency if Asynchron motor is selected; ramp-up
time from 0 to 1-25 Motor Nominal Speed if PM
motor is selected
Frequency to 0 if Asynchron motor is selected;
ramp-down time from 1-25 Motor Nominal Speed
to 0 if PM motor is selected
MG18B222 - VLT® is a registered Danfoss trademark2-5
How to Program
VLT® HVAC Basic Drive Programming Guide
No & NameRangeDefaultFunction
22
6-10 Terminal 53 Low
Voltage
6-11 Terminal 53 High
Voltage
6-12 Terminal 53 Low
Current
6-13 Terminal 53 High
Current
6-19 Terminal 53 mode[0] Current
Table 2.4
0–10 V0.07 VEnter the voltage that corresponds to the low
reference value.
0–10 V10 VEnter the voltage that corresponds to the high
reference value.
0-20 mA4Enter the current that corresponds to the low
reference value.
0-20 mA20Enter the current that corresponds to the high
reference value.
1Select if terminal 53 is used for current or voltage
[1] Voltage
input.
2-6MG18B222 - VLT® is a registered Danfoss trademark
6-29 Terminal 54 Mode
[1]
Voltage
6-25 T54 high Feedback
0050
Hz
20-94 PI integral time
0020.00
s
Current
Voltage
This dialog is forced to be set to
[1] Analog input 54
27
28
29
30
31
32
33
34
20-00 Feedback 1 source
[1]
Analog input 54
3-10 Preset reference [0]
0.00
3-03 Max Reference
50.00
3-02 Min Reference
0.00
Asynchronous Motor
1-73 Flying Start
[0]
No
1-22 Motor Voltage
0050
V
1-24 Motor current
04.66
A
1-25 Motor nominal speed
1420
RPM
3-41 Ramp 1 ramp-up time
0003
s
3-42 Ramp1 ramp-down time
0003
s
5
6
7
8
9
18
19
20
21
22
22a
23
24
25
26
35
36
37
38
39
40
0-06 Grid Type
4-12 Motor speed low limit
0016
Hz
4-13 Motor speed high limit
0050
Hz
130BC402.10
1-20 Motor Power
1.10
kW
1-23 Motor frequency
0050
Hz
6-22 T54 Low Current
A
6-24 T54 low Feedback
0016
Hz
6-23 T54 high Current
13.30
A
6-25 T54 high Feedback
0050
0.01
s
20-81 PI Normal/Inverse Control
[0]
Normal
20-83 PI Normal/Inverse Control
0050
Hz
20-93 PI Proportional Gain
00.50
1-29 Automatic Motor Adaption
[0]
O
6-20 T54 low Voltage
0050
V
6-24 T54 low Feedback
0016
Hz
6-21 T54 high Voltage
0220
V
6-26
T54 Filter time const.
1-00 Conguration Mode
[3]
Closed Loop
3
0-03 Regional Settings
[0]
Power kW/50 Hz
1
3-16 Reference Source 2
[0]
No Operation
22b
1-10 Motor Type
[0]
Asynchronous
4
2
[0]
200-240V/50Hz/Delta
1-30 Stator resistance
0.65
Ohms
1-25 Motor nominal speed
3000
RPM
1-24 Motor Current
3.8
A
1-26 Motor Cont. Rated Torque
5.4
Nm
1-37 d-axis inductance(Ld)
5
mH
4-19 Max Ouput Frequency
0065
Hz
1-40 Back EMF at 1000 rpm
57
V
10
11
12
13
14
15
16
17
PM motor
1-39 Motor poles
8
%
04.66
Hz
MotorType = Asynchronous
MotorType = PM Motor
How to Program
Closed-loop Set-up Wizard
VLT® HVAC Basic Drive Programming Guide
22
Figure 2.6
MG18B222 - VLT® is a registered Danfoss trademark2-7
How to Program
VLT® HVAC Basic Drive Programming Guide
Closed-loop Set-up Wizard
22
No & NameRangeDefaultFunction
0-03 Regional Settings[0] International
[1] US
0-06 GridType[0] -[[132] please see start-up
wizard for open-loop
application
1-00 Configuration Mode[0] Open-loop
[3] Closed-loop
1-10 Motor Construction*[0] Motor construction
[1] PM, non-salient SPM
1-20 Motor Power
1-22 Motor Voltage50.0–1,000.0 VSize relatedEnter motor voltage from nameplate data
1-23 Motor Frequency20.0–400.0 HzSize relatedEnter motor frequency from nameplate data
1-24 Motor Current0.0–10,000.00 ASize relatedEnter motor current from nameplate data
1-25 Motor Nominal Speed100.0–9,999.0 RPMSize relatedEnter motor nominal speed from nameplate
1-26 Motor Cont. Rated Torque0.1–1,000.0Size relatedThis parameter is available only when
0.125–150 hp [0.09–110 kW]Size relatedEnter motor power from nameplate data
0
Size selectedSelect operating mode for restart upon
reconnection of the adjustable frequency
drive to AC line voltage after power-down.
0Change this parameter to Closed-loop
[0] AsynchronSetting the parameter value might change
these parameters:
1-01 Motor Control Principle
1-03 Torque Characteristics
1-14 Damping Gain
1-15 Low Speed Filter Time Const.
1-16 High Speed Filter Time Const.
1-17 Voltage filter time const.
1-20 Motor Power [kW]
1-22 Motor Voltage
1-23 Motor Frequency
1-25 Motor Nominal Speed
1-26 Motor Cont. Rated Torque
1-30 Stator Resistance (Rs)
1-33 Stator Leakage Reactance (X1)
1-35 Main Reactance (Xh)
1-37 d-axis Inductance (Ld)
1-39 Motor Poles
1-40 Back EMF at 1000 RPM
1-66 Min. Current at Low Speed
1-72 Start Function
1-73 Flying Start
4-19 Max Output Frequency
4-58 Missing Motor Phase Function
data
1-10 Motor Construction Design is set to [1]PM, non-salient SPM.
NOTE!
Changing this parameter will affect
settings of other parameters
1-29 Automatic Motor Adaption
(AMA)
1-30 Stator Resistance (Rs)0.000–99.990Size relatedSet the stator resistance value
1-37 d-axis Inductance (Ld)0–1000Size relatedEnter the value of the d-axis inductance.
2-8MG18B222 - VLT® is a registered Danfoss trademark
OffPerforming an AMA optimizes motor
performance.
Obtain the value from the permanent magnet
motor data sheet. The de-axis inductance
cannot be found by performing an AMA.
How to Program
VLT® HVAC Basic Drive Programming Guide
No & NameRangeDefaultFunction
1-39 Motor Poles2-1004Enter the number of motor poles
1-40 Back EMF at 1000 RPM10–9,000Size relatedLine-Line RMS back EMF voltage at 1000 RPM
1-73 Flying Start[0] Disabled
[1] Enabled
3-02 Minimum Reference-4,999-4,9990The minimum reference is the lowest value
3-03 Maximum Reference-4,999-4,99950The maximum reference is the highest value
3-10 Preset Reference-100–100%0Enter the setpoint.
3-41 Ramp 1 Ramp Up Time0.05–3,600.0 sSize relatedRamp-up time from 0 to rated 1-23 Motor
3-42 Ramp 1 Ramp Down Time0.05–3,600.0 sSize relatedRamp-down time from rated 1-23 Motor
4-12 Motor Speed Low Limit [Hz]0.0–400 Hz0.0 HzEnter the minimum limit for low speed
4-14 Motor Speed High Limit [Hz]0–400 Hz65 HzEnter the minimum limit for high speed
4-19 Max Output Frequency0–400Size relatedEnter the maximum output frequency value
6-29 Terminal 54 mode[0] Current
[1] Voltage
6-20 Terminal 54 Low Voltage0–10 V0.07 VEnter the voltage that corresponds to the low
6-21 Terminal 54 High Voltage0–10 V10 VEnter the voltage that corresponds to the low
6-22 Terminal 54 Low Current0-20 mA4Enter the current that corresponds to the high
6-23 Terminal 54 High Current0-20 mA20Enter the current that corresponds to the high
6-24 Terminal 54 Low Ref./Feedb.
Value
6-25 Terminal 54 High Ref./Feedb.
Value
6-26 Terminal 54 Filter Time
Constant
20-81 PI Normal/ Inverse Control[0] Normal
20-83 PI Start Speed [Hz]0–200 Hz0Enter the motor speed to be attained as a
20-93 PI Proportional Gain0–100.01Enter the process controller proportional gain.
-4,999-4,9990Enter the feedback value that corresponds to
-4,999–4,99950Enter the feedback value that corresponds to
0–10 s0.01Enter the filter time constant.
[1] Inverse
0
1Select if terminal 54 is used for current or
0
Select [1] Enable to enable the adjustable
frequency drive to catch a spinning motor,
e.g., in fan applications. When PM is selected,
Flying Start is enabled.
obtainable by summing all references.
obtainable by summing all references.
Frequency if Asynchron motor is selected;
ramp-up time from 0 to 1-25 Motor Nominal
Speed if PM motor is selected.
Frequency to 0 if Asynchron motor is selected;
ramp-down time from 1-25 Motor Nominal
Speed to 0 if PM motor is selected.
voltage input
reference value.
high reference value.
reference value.
reference value.
the voltage or current set in 6-20 Terminal 54Low Voltage/6-22 Terminal 54 Low Current
the voltage or current set in 6-21 Terminal 54High Voltage/6-23 Terminal 54 High Current
Select [0] Normal to set the process control to
increase the output speed when the process
error is positive. Select [1] Inverse to reduce
the output speed.
start signal for commencement of PI control.
Quick control is obtained at high amplification. However, if amplification is too great,
the process may become unstable
22
MG18B222 - VLT® is a registered Danfoss trademark2-9
How to Program
VLT® HVAC Basic Drive Programming Guide
No & NameRangeDefaultFunction
22
20-94 PI Integral Time0.1–999.0 s999.0 sEnter the process controller integral time.
Obtain quick control through a short integral
time, though if the integral time is too short,
the process becomes unstable. An excessively
long integral time disables the integral action.
Table 2.5
Motor Set-up
The Quick Menu Motor Set-up guides you through the
needed motor parameters.
No & NameRangeDefaultFunction
0-03 Regional
Settings
0-06 GridType [0] -[132]
1-10 Motor
Construction
1-20 Motor
Power
1-22 Motor
Voltage
1-23 Motor
Frequency
1-24 Motor
Current
1-25 Motor
Nominal
Speed
[0] International
[1] US
please see
start-up wizard
for open-loop
application
*[0] Motor
construction
[1] PM, nonsalient SPM
0.12–110 kW/
0.16–150 hp
50.0–1,000.0 V Size relatedEnter motor
20.0–400.0 HzSize relatedEnter motor
0.01–10,000.00ASize relatedEnter motor
100.0–9,999.0
RPM
0
Size selected Select operating
mode for restart
upon
reconnection of
the drive to AC
line voltage after
power-down
[0]
Asynchron
Size relatedEnter motor
Size relatedEnter motor
power from
nameplate data
voltage from
nameplate data
frequency from
nameplate data
current from
nameplate data
nominal speed
from nameplate
data
No & NameRangeDefaultFunction
1-26 Motor
Cont. Rated
Torque
0.1–1,000.0Size relatedThis parameter is
available only
when 1-10 Motor
Construction
Design is set to
[1] PM, nonsalient SPM.
NOTE!
Changing this
parameter will
affect settings
of other
parameters
0.000–99.990Size relatedSet the stator
resistance value
0–1000Size relatedEnter the value
of the d-axis
inductance.
Obtain the value
from the
permanent
magnet motor
data sheet. The
de-axis
inductance
cannot be found
by performing an
AMA.
2-1004Enter the number
of motor poles
10–9,000Size relatedLine-Line RMS
back EMF voltage
at 1000 RPM
[0] Disabled
[1] Enabled
0Select Enable to
enable the
Adjustable
frequency drive
to catch a
spinning motor
2-10MG18B222 - VLT® is a registered Danfoss trademark
How to Program
VLT® HVAC Basic Drive Programming Guide
No & NameRangeDefaultFunction
3-41 Ramp 1
Ramp Up
Time
3-42 Ramp 1
Ramp Down
Time
4-12 Motor
Speed Low
Limit [Hz]
4-14 Motor
Speed High
Limit [Hz]
4-19 Max
Output
Frequency
Table 2.6
0.05–3,600.0 sSize relatedRamp-up time
from 0 to rated
1-23 Motor
Frequency
0.05–3,600.0 sSize relatedRamp-down time
from rated
1-23 Motor
Frequency to 0
0.0–400 Hz0.0 HzEnter the
minimum limit
for low speed
0.0–400 Hz65Enter the
maximum limit
for high speed
0–400Size relatedEnter the
maximum output
frequency value
Changes Made
Changes Made lists all parameters changed since factory
setting. Only the changed parameters in current edit-setup
are listed in changes made.
If the parameter's value is changed back to the factory
settings from another different value, the parameter will
NOT be listed in Changes Made.
1.Press [Menu] key to enter the Quick Menu until
indicator in display is placed above Quick Menu.
2.
Press [▲] [▼] to select either FC 101 wizard,
closed-loop setup, motor setup or changes made,
then press [OK].
3.
Press [▲] [▼] to browse through the parameters
in the Quick Menu.
4.Press [OK] to select a parameter.
5.
Press [▲] [▼] to change the value of a parameter
setting.
6.Press [OK] to accept the change.
7.Press either [Back] twice to enter “Status”, or
press [Menu] once to enter “Main Menu”.
simplest and quickest access to the typical required
parameters.
The Main Menu accesses all parameters.
1.Press [Menu] key until indicator in display is
placed above “Main Menu”.
2.
Use [▲] [▼] to browse through the parameter
groups.
3.Press [OK] to select a parameter group.
4.
Use [▲] [▼] to browse through the parameters in
the specific group.
5.Press [OK] to select the parameter.
6.
Use [▲] [▼] to set/change the parameter value.
[Back] is used to go one level back.
22
2.3.4
Main Menu
[Main Menu] is used for programming all parameters. The
Main Menu parameters can be accessed immediately
unless a password has been created via 0-60 Main MenuPassword. For the majority of VLT HVAC Basic Drive
applications, it is not necessary to access the Main Menu
parameters but instead the Quick Menu provides the
MG18B222 - VLT® is a registered Danfoss trademark2-11
How to Program
VLT® HVAC Basic Drive Programming Guide
22
2.4 Quick Transfer of Parameter Settings
between Multiple Adjustable Frequency
Drives
Once the set-up of an adjustable frequency drive is
complete, Danfoss recommends that you store the data in
the LCP or on a PC via MCT-10 Setup Software tool.
Data storage in LCP.
WARNING
Stop the motor before performing this operation.
1.
Go to 0-50 LCP Copy
2.Press the [OK] key
3.Select “All to LCP”
4.Press the [OK] key
Connect the LCP to another adjustable frequency drive
and copy the parameter settings to this adjustable
frequency drive as well.
Data transfer from LCP to adjustable frequency drive:
NOTE!
Stop the motor before performing this operation.
1.
Go to 0-50 LCP Copy
2.Press the [OK] key
3.Select “All from LCP”.
4.Press the [OK] key
2.5
Read-out and Programming of Indexed
Parameters
Use as an example.
Choose the parameter, press [OK], and use [▲/▼] to scroll
through the indexed values. To change the parameter
value, select the indexed value and press [OK]. Change the
value by using the up/down keys. Press [OK] to accept the
new setting. Press [Cancel] to abort. Press [Back] to leave
the parameter.
2.6
Initialize the Adjustable Frequency
Drive to Default Settings in Two Ways
4.Cut off the line power supply and wait until the
display turns off.
5.Reconnect the line power supply - the adjustable
frequency drive is now reset. Except the following
parameters.
8-30 Protocol
8-31 Address
8-32 Baud Rate
8-33 Parity / Stop Bits
8-35 Minimum Response Delay
8-36 Maximum Response Delay
8-37 Maximum Inter-char delay
8-70 BACnet Device Instance
8-72 MS/TP Max Masters
8-73 MS/TP Max Info Frames
8-74 "I am" Service
8-75 Intialisation Password
15-00 Operating hours to 15-05 Over Volt's
15-03 Power Up's
15-04 Over Temp's
15-05 Over Volt's
15-30 Alarm Log: Error Code
15-4* Drive identification parameters
1-06 Clockwise Direction
Two-finger initialization:
1.Power off the adjustable frequency drive.
2.Press [OK] and [Menu].
3.Power up the adjustable frequency drive while
still pressing the keys above for 10 s.
4.The adjustable frequency drive is now reset,
except the following parameters:
2-12MG18B222 - VLT® is a registered Danfoss trademark
How to Program
15-00 Operating hours
15-03 Power Up's
15-04 Over Temp's
15-05 Over Volt's
15-4* Drive identification parameters
Initialization of parameters is confirmed by AL80 in the
display after the power cycle.
VLT® HVAC Basic Drive Programming Guide
22
MG18B222 - VLT® is a registered Danfoss trademark2-13
How to Program
VLT® HVAC Basic Drive Programming Guide
22
2-14MG18B222 - VLT® is a registered Danfoss trademark
Parameters
3 Parameters
VLT® HVAC Basic Drive Programming Guide
3.1 Main Menu - Operation and Display Group 0
Parameters related to the fundamental functions of the
adjustable frequency drive, function of the LCP buttons
and configuration of the LCP display.
3.1.1 0-0* Basic Settings
0-01 Language
Option:Function:
Defines the language to be used in the display.
[0]English
[1]Deutsch
[2]Francais
[3]Dansk
[4]Spanish
[5]Italiano
[28]Bras.port
[255] No Text
0-03 Regional Settings
Option:Function:
This parameter cannot be adjusted while the
motor is running. In order to meet the needs
for different default settings in different parts of
the world, 0-03 Regional Settings is implemented
in the adjustable frequency drive. The selected
setting influences the default setting of the
motor nominal frequency.
[0] Interna-
tional
[1] North
America
0-04 Operating State at Power-up
Option:Function:
[0] ResumeResumes operation of the adjustable frequency
Sets default value of 1-23 Motor Frequency [50
Hz].
Sets the default value of 1-23 Motor Frequency
to 60 Hz.
Select the operating mode upon reconnection of
the adjustable frequency drive to AC line voltage
after power-down when operating in Hand (local)
mode.
drive maintaining the same local reference and
the same start/stop condition (applied by [Hand
On]/[Off] on the LCP or Hand Start via a digital
0-04 Operating State at Power-up
Option:Function:
input as before the adjustable frequency drive
was powered down).
[1] Forced
stop,
ref=old
Uses saved reference [1] to stop the adjustable
frequency drive but at the same time retains the
local speed reference in memory prior to powerdown. After AC line voltage is reconnected and
after receiving a start command (using the LCP
[Hand On] button or Hand Start command via a
digital input) the adjustable frequency drive
restarts and operates at the retained speed
reference.
0-06 GridType
Option:Function:
Select the grid type of the supply
voltage/frequency.
NOTE!
Not all choices are supported in
all power sizes.
The IT grid is a line power source
where there are no connections to
ground.
Delta is a line power source where
the secondary part of the
transformer is delta connected and
one phase is connected to ground.
Define and control the individual parameter set-ups. Userdefined parameters and miscellaneous external inputs (e.g.,
bus, LCP, analog/digital inputs, feedback, etc.) control the
functionality of the adjustable frequency drive.
A complete set of all parameters controlling the adjustable
frequency drive is called a set-up. The adjustable frequency
drive contains 2 set-ups, Set-up 1 and Set-up 2.
Furthermore, a fixed set of factory settings can be copied
into one or more set-ups.
Some of the advantages of having more than one set-up
in the adjustable frequency drive are:
Run motor in one set-up (Active Set-up) while
•
updating parameters in another set-up (Edit Setup)
Connect various motors (one at a time) to the
•
adjustable frequency drive. Motor data for various
motors can be placed in different set-ups.
Rapidly change settings of adjustable frequency
•
drive and/or motor, for example, while the motor
is running. Ramp time or preset references) via
bus or digital inputs.
The Active Set-up can be set as Multi Set-up where the
active set-up is selected via input on a digital input
terminal and/or via the bus control word.
0-10 Active Set-up
Option:Function:
Select the set-up in which the adjustable
frequency drive is to operate.
Use 0-51 Set-up Copy to copy a set-up to one or all
other set-ups. To avoid conflicting settings of the
same parameter within two different set-ups, link
the set-ups together using 0-12 Link Setups. Stop
the adjustable frequency drive before switching
between set-ups, where parameters marked ‘not
changeable during operation’ have different
values.
Parameters which are ‘not changeable during
operation’ are marked FALSE in the parameter lists
in 5 Parameter Lists.
[1] Set-up 1 Set-up 1 is active.
[2] Set-up 2 Set-up 2 is active.
[9] Multi
Set-up
Is used for remote selection of set-ups using
digital inputs and the serial communication port.
This set-up uses the settings from 0-12 Link Setups.
0-11 Programming Set-up
Option:Function:
Select the set-up to be edited (i.e.,
programmed) during operation: either the
active set-up or the inactive set-up. The set-up
number being edited is displayed in the LCP
flashing.
[1] Set-up 1
[2] Set-up 2
[9] Active Set-up(i.e., the set-up in which the adjustable
Set-up 1 [1] to Set-up 2 [2] can be edited freely
during operation, independently of the active
set-up.
frequency drive is operating) can also be edited
during operation.
0-12 Link Setups
Option:Function:
The link ensures synchronizing of the “not
changeable during operation” parameter values
enabling shift from one set-up to another during
operation.
If the set-ups are not linked, a change between
them is not possible while the motor is running.
Thus the set-up change does not occur until the
motor is coasted.
[0]Not
linked
Leaves parameters unchanged in both set-ups
and cannot be changed while the motor is
running.
3-2MG18B222 - VLT® is a registered Danfoss trademark
Loading...
+ 92 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.