Installation Instructions
VLT® Decentral Drive FCD 300
Installation Box (175X0318/0320/0329)
1Items Supplied
Depending on the ordering number, the following is supplied:
Installation box, small size with switch (175X0318)
For use with FCD 302-315.
Illustration 1.1 Installation Box, Small Size with Switch (175X0318)
Installation box, small size without switch (175X0329)
For use with FCD 302-315.
NOTICE
See the VLT® Decentral Drive FCD 300 Design Guide for
further information.
2 Safety Instructions
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors, which
can remain charged even when the frequency converter is
not powered. Failure to wait the specified time after power
has been removed before performing service or repair work,
could result in death or serious injury.
1. Stop motor.
2. Disconnect AC mains, permanent magnet type
motors, and remote DC-link power supplies,
including battery back-ups, UPS, and DC-link
connections to other frequency converters.
3. Wait for the capacitors to discharge fully, before
performing any service or repair work. The duration
of waiting time is specified in Table 2.1.
Illustration 1.2 Installation Box, Small Size without Switch
(175X0329)
The functionality and design of the installation box without
switch is identical to the installation box with switch.
Installation box, large size with switch (175X0320)
For use with FCD 322-335.
Illustration 1.3 Installation Box, Large Size with Switch (175X0320)
The dimensions of the boxes are:
Small size: 300 x 192 x 145 mm
•
Large size: 367 x 258 x 154 mm
•
There are 6 plugs on the side of the installation box. The plugs
have the same functionality for all 3 types.
Voltage
[V]
3 x 400 0.55–7.5 4
3 x 400 11–22 15
High voltage can be present even when the warning LED indicator
Table 2.1 Discharge Time
Power Range
[kW]
lights are off.
Minimum waiting
time
(min)
MI04F102 – Rev 2013-11-25
Installation Instructions
VLT® Decentral Drive FCD 300
Installation Box (175X0318/0320/0329)
3Plugs
3.1 Overview
The 6 plugs on the installation box have the following
functionality:
X52 Profibus M12
female
X51 Profibus M12
male
X14 Photocell M8
female
Table 3.1 Plugs
3.2 X1 Mains in M23 Male
General ratings
Pins 1, 2, 3 and 4: 480 V AC, max. 15 A
•
Pins C and D: 30 V DC, max. 3 A
•
Front/screw mounting IP66, UL type 4
•
Tightening torque: 1.5–2.0 Nm
•
Pin Label
1L1
2PE
3L3
4L2
D35
C36
X13 Photocell M8 female
X2 Motor connection M23
(in M25) female
X1 Mains in M23 (in M25)
male
2
Wire mm
/AWG
2.5/14
2.75/18
2.5/14
2.75/18
2
/AWG
Socket Label
1U
4V
3W
2PE
A31A
B31B
C122
D123
Table 3.3 Wire/Connector Assignment for Plug X2
Mating part: Motor X2 (male)
Phoenix order No.: KCX-K0341/XX,XX
XX,XX is the cable length in [m, cm]
Wire mm
3.4 X13/X14 Photocell M8 Female
For non-used connectors. Keep blind plugs installed to
connectors at all times to keep the enclosure tight.
General ratings
30 V DC, max. 1 A
•
Front/screw mounting IP66, UL type 4
•
Tightening torque: 0.1–0.2 Nm
•
Pin Label
1Brown
2White
3Blue
4Black
Table 3.4 Wire/Connector Assignment for Plug X13/X14
Table 3.2 Wire/Connector Assignment for Plug X1
Mating part: Mains X1 (female)
Phoenix order No.: KK-0885/XX,XX
XX,XX is the cable length in [m, cm]
3.3 X2 Motor Connection M23 Female
General ratings
Sockets 1, 2, 3 and 4: 480 V AC, max. 15 A
•
Sockets A and B: 30 V DC, max. 1 A
•
Sockets C and D: 240 V DC, max. 2 A
•
Front/screw mounting IP66, UL type 4
•
Tightening torque: 1.5–2.0 Nm
•
Mating part: Sensor X13 og X14 (male)
Phoenix order No.: SAC-4P-M 8MS/XX,XX-PUR/M8FS 34CP
XX,XX is the cable length in [m, cm]
3.5 X51 Profibus M12 Male
General ratings
30 V DC, max. 1 A
•
Front/screw mounting IP66, UL type 4
•
Tightening torque: 0.2–0.3 Nm
•
Pin Label
1Brown
2White
3Blue
4Black
Table 3.5 Wire/Connector Assignment for Plug X51
Mating part: Profibus X52 and X51 (female/male)
Phoenix order No.: SAC-2P-MSB/ XX,XX-910/FSB SCO CT
XX,XX is the cable length in [m, cm]
2
MI04F102 – Rev 2013-11-25