Danfoss VLT Compact Starter MCD 201, VLT Compact Starter MCD 202, VLT Compact Starter MCD 500 Installation Manual

ENGINEERING TOMORROW
Installation Guide
EtherNet/IP Module
VLT® Compact Starter MCD 201/MCD 202 VLT® Soft Starter MCD 500
Contents
1 Introduction
3
1.1 Purpose of the Manual
3
1.2 Additional Resources
3
1.3 Product Overview
3
1.4 Approvals and Certications
3
1.5 Disposal
3
1.6 Symbols, Abbreviations, and Conventions
4
2 Safety
5
2.1 Qualied Personnel
5
2.2 General Warnings
5
3 Installation
7
3.1 Installation Procedure
7
4 Connection
8
4.1 Soft Starter Connection
8
4.2 Network Connection
9
4.2.1 Ethernet Ports 9
4.2.2 Cables 9
4.2.3 EMC Precautions 9
4.2.4 Network Establishment 9
4.3 Addressing
9
5 Device Conguration
10
5.1 Conguration Overview
10
5.2 On-board Web Server
10
5.3 Ethernet Device Conguration Tool
10
6 Operation
12
6.1 Device Conguration
12
6.2 Scanner Conguration
12
6.2.1 EDS File 12
6.3 LEDs
12
7 Packet Structures
13
7.1 Ensuring Safe and Successful Control
13
7.2 Cyclic Operation
13
7.2.1 Assembly Objects 13
7.2.2 Control Commands 13
7.2.2.1 Receiving Control Data from the Controller 13
Contents Installation Guide
MG17Q102 Danfoss A/S © 05/2017 All rights reserved. 1
7.2.2.2 Control Word (Write-only) 13
7.2.2.3 Command Examples 14
7.2.3 Status Information 14
7.2.3.1 Reading Status Information from the Soft Starter 14
7.2.3.2 Status Word (Read-only) 15
7.2.3.3 Trip Codes 16
7.3 Acyclic Operation
17
7.3.1 Class 0X01 Identity Object 17
7.3.2 Vendor-specic Objects 17
7.3.2.1 Class 100 Objects (Read/Write) 17
7.3.2.2 Class 101 Objects (Read/Write) 18
7.3.2.3 Class 103 Objects (Read-only) 18
7.3.2.4 Class 104 Objects (Read-only) 19
7.3.3 Supported Services for Vendor-specic Objects 19
7.3.3.1 Set Attribute Single 19
7.3.3.2 Get Attribute Single 20
7.3.3.3 Status Codes for Acyclic Services 21
8 Network Design
22
8.1 Star Topology
22
8.2 Line Topology
22
8.3 Ring Topology
22
8.4 Combined Topologies
23
9 Specications
24
Index
25
Contents EtherNet/IP Module
2 Danfoss A/S © 05/2017 All rights reserved. MG17Q102
1 Introduction
1.1 Purpose of the Manual
This installation guide provides information for the instal-
lation of the EtherNet/IP option module for VLT® Compact
Starter MCD 201/MCD 202 and VLT® Soft Starter MCD 500. The installation guide is intended for use by qualied personnel.
Users are assumed to be familiar with:
VLT® soft starters.
EtherNet/IP technology.
PC or PLC that is used as a master in the system.
Read the instructions before installation and ensure that the instructions for safe installation are observed.
VLT® is a registered trademark.
EtherNet/IP is a trademark of ODVA, Inc.
1.2 Additional Resources
Resources available for the soft starter and optional equipment:
The VLT® Compact Starter MCD 200 Operating Instructions provide the necessary information for
getting the soft starter up and running.
The VLT® Soft Starter MCD 500 Operating Guide provides the necessary information for getting the soft starter up and running.
Supplementary publications and manuals are available from Danfoss. See drives.danfoss.com/knowledge-center/ technical-documentation/ for listings.
1.3
Product Overview
1.3.1 Intended Use
This installation guide relates to EtherNet/IP Module for
VLT® soft starters.
The EtherNet/IP interface is designed to communicate with any system complying with the CIP EtherNet/IP standard. EtherNet/IP provides users with the network tools to deploy standard Ethernet technology for manufacturing applications while enabling internet and enterprise connec­tivity.
EtherNet/IP Module is intended for use with:
VLT® Compact Starter MCD 201/MCD 202, 24 V AC/V DC and 110/240 V AC control voltage.
VLT® Soft Starter MCD 500, all models.
NOTICE
The EtherNet/IP Module is NOT suitable for use with the MCD 201/MCD 202 compact starters using 380/440 V AC control voltage.
NOTICE
LOSS OF WARRANTY
The EtherNet/IP Module supports a eld update function for its internal software. This function is for authorized service personnel only. Misuse may cause permanent failure of the module. Unauthorized use voids the product warranty.
The EtherNet/IP Module allows a Danfoss soft starter to connect to an Ethernet network and be controlled or monitored using an Ethernet communication model.
The EtherNet/IP Module operates at the application layer.
Familiarity with Ethernet protocols and networks is required to operate the EtherNet/IP Module successfully. If there are diculties when using this device with third­party products, including PLCs, scanners, and commissioning tools, contact the relevant supplier.
1.4
Approvals and Certications
More approvals and certications are available. For more information, contact a local Danfoss partner.
1.5
Disposal
Do not dispose of equipment containing
electrical components together with
domestic waste.
Collect it separately in accordance with
local and currently valid legislation.
Introduction Installation Guide
MG17Q102 Danfoss A/S © 05/2017 All rights reserved. 3
1 1
1.6 Symbols, Abbreviations, and Conventions
Abbreviation Denition
CIP
Common industrial protocol
DHCP Dynamic host conguration protocol
EMC Electromagnetic compatibility
IP Internet protocol
LCP Local control panel
LED Light-emitting diode
PC Personal computer
PLC Programmable logic controller
Table 1.1 Symbols and Abbreviations
Conventions
Numbered lists indicate procedures. Bullet lists indicate other information and description of illustrations. Italicized text indicates:
Cross-reference.
Link.
Parameter name.
Parameter group name.
Parameter option.
Introduction EtherNet/IP Module
4 Danfoss A/S © 05/2017 All rights reserved. MG17Q102
11
2 Safety
The following symbols are used in this manual:
WARNING
Indicates a potentially hazardous situation that could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that could result in minor or moderate injury. It can also be used to alert against unsafe practices.
NOTICE
Indicates important information, including situations that can result in damage to equipment or property.
2.1 Qualied Personnel
Correct and reliable transport, storage, installation, operation, and maintenance are required for the trouble­free and safe operation of the soft starter. Only qualied personnel are allowed to install or operate this equipment.
Qualied personnel are dened as trained sta, who are authorized to install, commission, and maintain equipment, systems, and circuits in accordance with pertinent laws and regulations. Also, the qualied personnel must be familiar with the instructions and safety measures described in this installation guide.
2.2
General Warnings
WARNING
ELECTRICAL SHOCK HAZARD
VLT® Soft Starter MCD 500 contains dangerous voltages when connected to mains voltage. Only a qualied electrician should carry out the electrical installation. Improper installation of the motor or the soft starter can cause death, serious injury, or equipment failure. Follow the guidelines in this manual and local electrical safety codes. Models MCD5-0360C ~ MCD5-1600C: Treat the busbar and heat sink as live parts whenever the unit has mains voltage connected (including when the soft starter is tripped or waiting for a command).
WARNING
PROPER GROUNDING
Disconnect the soft starter from mains voltage before carrying out repair work. It is the responsibility of the person installing the soft starter to provide proper grounding and branch circuit protection according to local electrical safety codes. Do not connect power factor correction capacitors to the
output of the VLT® Soft Starter MCD 500. If static power factor correction is employed, it must be connected to the supply side of the soft starter.
WARNING
IMMEDIATE START
In auto-on mode, the motor can be controlled remotely (via remote inputs) while the soft starter is connected to mains. MCD5-0021B ~ MCD5-961B: Transportation, mechanical shock, or rough handling may cause the bypass contactor to latch into the On state.
To prevent the motor from starting immediately on rst commissioning or operation after transportation:
Always ensure that the control supply is applied before the power.
Applying control supply before power ensures that the contactor state is initialized.
WARNING
UNINTENDED START
When the soft starter is connected to AC mains, DC supply, or load sharing, the motor can start at any time. Unintended start during programming, service, or repair work can result in death, serious injury, or property damage. The motor can start with an external switch, a eldbus command, an input reference signal from the LCP or LOP, via remote operation using MCT 10 Set-up Software, or after a cleared fault condition.
To prevent unintended motor start:
Press [O/Reset] on the LCP before programming parameters.
Disconnect the soft starter from the mains.
Completely wire and assemble the soft starter, motor, and any driven equipment before connecting the soft starter to AC mains, DC supply, or load sharing.
Safety Installation Guide
MG17Q102 Danfoss A/S © 05/2017 All rights reserved. 5
2 2
WARNING
SAFETY OF PERSONNEL
The soft starter is not a safety device and does not provide electrical isolation or disconnection from the supply.
If isolation is required, the soft starter must be installed with a main contactor.
Do not rely on the start and stop functions for safety of personnel. Faults occurring in the mains supply, the motor connection, or the electronics of the soft starter can cause unintended motor starts or stops.
If faults occur in the electronics of the soft starter, a stopped motor may start. A temporary fault in the supply mains or loss of motor connection can also cause a stopped motor to start.
To provide safety of personnel and equipment, control the isolation device through an external safety system.
NOTICE
Before changing any parameter settings, save the current parameter to a le using MCD PC Software or the Save
User Set function.
NOTICE
Use the autostart feature with caution. Read all the notes related to autostart before operation.
The examples and diagrams in this manual are included solely for illustrative purposes. The information contained in this manual is subject to change at any time and without prior notice. Responsibility or liability is never accepted for direct, indirect, or consequential damage resulting from the use or application of this equipment.
Safety EtherNet/IP Module
6 Danfoss A/S © 05/2017 All rights reserved. MG17Q102
22
3 Installation
3.1 Installation Procedure
CAUTION
EQUIPMENT DAMAGE
If mains and control voltage are applied when installing or removing options/accessories, it may damage the equipment.
To avoid damage:
Remove mains and control voltage from the soft starter before attaching or removing options/accessories.
Installing the EtherNet/IP option:
1. Remove control power and mains supply from the soft starter.
2. Fully pull out the top and bottom retaining clips on the module (A).
3. Line up the module with the communication port slot (B).
4. Push in the top and bottom retaining clips to secure the module to the soft starter (C).
5. Connect Ethernet port 1 or port 2 on the module to the network.
6. Apply control power to the soft starter.
177HA528.13
A
B
C
Illustration 3.1 Installing the EtherNet/IP Option
Remove the module from the soft starter:
1. Remove control power and mains supply from the soft starter.
2. Disconnect all external wiring from the module.
3. Fully pull out the top and bottom retaining clips on the module (A).
4. Pull the module away from the soft starter.
177HA378.12
A
Illustration 3.2 Removing the EtherNet/IP Option
Installation Installation Guide
MG17Q102 Danfoss A/S © 05/2017 All rights reserved. 7
3 3
4 Connection
4.1 Soft Starter Connection
The EtherNet/IP Module is powered from the soft starter.
VLT® Compact Starter MCD 201/MCD 202
For the EtherNet/IP Module to accept eldbus commands, t a link across terminals A1–N2 on the soft starter.
VLT® Soft Starter MCD 500
If the MCD 500 has to be operated in remote mode, input links are required across terminals 17 and 25 to terminal 18. In hand-on mode, links are not required.
NOTICE
FOR MCD 500 ONLY
Control via the eldbus communication network is always enabled in local control mode and can be enabled or
disabled in remote control mode (parameter 3-2 Comms in Remote). See the VLT® Soft Starter MCD 500 Operating Guide for parameter details.
EtherNet/IP Module Connections
MCD 201/202 MCD 500
N2
177HA620.12
1
2
3
A1
17
18
25
177HA621.11
1
2
3
1 A1, N2: Stop input 1 (Auto-on mode)
17, 18: Stop input
25, 18: Reset input
2 EtherNet/IP Module 2 EtherNet/IP Module
3 RJ45 Ethernet ports 3 RJ45 Ethernet ports
Table 4.1 Connection Diagrams
Connection EtherNet/IP Module
8 Danfoss A/S © 05/2017 All rights reserved. MG17Q102
44
4.2 Network Connection
4.2.1 Ethernet Ports
The EtherNet/IP Module has 2 Ethernet ports. If only 1 connection is required, either port can be used.
4.2.2 Cables
Suitable cables for EtherNet/IP Module connection:
Category 5
Category 5e
Category 6
Category 6e
4.2.3 EMC Precautions
To minimize electromagnetic interference, Ethernet cables should be separated from motor and mains cables by 200 mm (7.9 in).
The Ethernet cable must cross the motor and mains cables at an angle of 90°.
1
2
≥ 200 mm
90°
177HA653.10
1 3-phase supply
2 Ethernet cable
Illustration 4.1 Correct Running of Ethernet Cables
4.2.4 Network Establishment
The controller must establish communication directly with each device before the device can participate in the network.
4.3 Addressing
Each device in a network is addressed using a MAC address and an IP address and can be assigned a symbolic name associated with the MAC address.
The factory default is a static IP address (192.168.1.2). The module also supports BootP and DHCP addressing.
The symbolic name is optional and must be congured within the device.
The MAC address is xed within the device and is printed on a label on the front of the module.
ProfiNet MAC: 00-02-A2-25-DC-B3
1 2
TX/RX 2
TX/RX 1
Link 2
Link 1
Error
Status
Power
177HA622.10
Illustration 4.2 MAC ID Location
Connection Installation Guide
MG17Q102 Danfoss A/S © 05/2017 All rights reserved. 9
4 4
5 Device Conguration
5.1 Conguration Overview
The EtherNet/IP Module is congured with a static IP address as default. To avoid IP address conict and to ensure successful employment, connect the module directly to a PC or laptop to congure the IP address before connecting to the network. To congure the IP address, or to enable BootP or DHCP addressing, use the on-board web server.
NOTICE
The error LED ashes whenever the device is receiving power but is not connected to a network. The error LED ashes throughout the conguration process.
5.2 On-board Web Server
Ethernet attributes can be congured directly in the EtherNet/IP Module using the on-board web server.
NOTICE
The web server only accepts connections from within the same subnet domain.
To congure the device using the on-board web server:
1. Attach the module to a soft starter.
2. Connect Ethernet port 1 or port 2 on the module to the network.
3. Apply control power to the soft starter.
4. Start a browser on the PC and enter the device address, followed by /ipcong. The default address for a new EtherNet/IP Module is
192.168.1.2.
177HA640.11
Illustration 5.1 Entering Network Settings
5. Edit the settings as required.
6. Click Submit to save the new settings.
7. If prompted, enter username and password.
7a Username: danfoss
7b Password: danfoss
NOTICE
If an IP address is changed and its record is lost, use the Ethernet Device Conguration Tool to scan the network and identify the module.
NOTICE
If changing the subnet mask, the server is unable to communicate with the module after the new settings are saved.
5.3 Ethernet Device Conguration Tool
If the IP address is unknown, or if the subnet mask of the web server does not match, use the Ethernet Device Conguration Tool to connect to the EtherNet/IP Module.
Changes made via the Ethernet Device Conguration Tool cannot be stored permanently in the module and are lost when control power is cycled. Use the Ethernet Device Conguration Tool to change the IP address settings temporarily. After that, use the new address to connect to the module using the on-board web server to save the settings permanently.
Download the Ethernet Device
Conguration Tool. To install the software, administrator privileges are required on the PC.
Downloading the tool:
1. Go to drives.danfoss.com/downloads/pc-tools/ to nd the tool.
2. Make sure to have administrator privileges on the PC before starting the installation.
3. Accept the End-User License Agreement.
4. Click Yes on the User account control dialog box.
NOTICE
If the PC has a rewall enabled, add the tool to the list of authorized programs.
Device Conguration EtherNet/IP Module
10 Danfoss A/S © 05/2017 All rights reserved. MG17Q102
55
Conguring the device using the Ethernet Device Conguration Tool:
1. Attach the module to a soft starter.
2. Connect Ethernet port 1 or port 2 on the module to the network.
3. Apply control power to the soft starter.
4. Start the Ethernet Device Conguration Tool.
177HA623.10
Illustration 5.2 Starting the Tool
5. Click Search Devices.
5a The software searches for connected
devices.
177HA641.10
Illustration 5.3 The Tool Shows the Connected Devices
6. To set a static IP address, click Congure and select Set IP address.
177HA642.10
Illustration 5.4 Setting a Static IP Address
Device Conguration Installation Guide
MG17Q102 Danfoss A/S © 05/2017 All rights reserved. 11
5 5
6 Operation
The EtherNet/IP Module is conformance tested to ODVA. For successful operation, the scanner must also support all functions and interfaces described in this manual.
6.1 Device Conguration
The EtherNet/IP Module is an Adapter class device and must be managed by a Scanner class device over Ethernet.
6.2 Scanner Conguration
6.2.1 EDS File
Download the EDS le from drives.danfoss.com/services/pc-tools. The EDS le contains all required attributes of the EtherNet/IP Module.
Once the EDS le is loaded, the individual EtherNet/IP Module must be dened.
6.3 LEDs
LED name LED status Description
1 2
TX/RX 2
TX/RX 1
Link 2
Link 1
Error
Status
Power
177HA627.10
Power
O The module is not powered up.
On The module receives power.
Error
O The module is not powered up or does not have an IP address.
Flashing Connection timeout.
On Duplicate IP address.
Status
O The module is not powered up or does not have an IP address.
Flashing The module has obtained an IP address but has not established any network
connections.
On Communication has been established.
Link x
O No network connection.
On Connected to a network.
TX/RX x Flashing Transmitting or receiving data.
Table 6.1 Feedback LEDs
Operation EtherNet/IP Module
12 Danfoss A/S © 05/2017 All rights reserved. MG17Q102
6
7 Packet Structures
7.1 Ensuring Safe and Successful Control
Data written to the EtherNet/IP Module remains in its register until the data is overwritten or the module is reinitialized. The EtherNet/IP Module does not transfer successive duplicate commands to the soft starter.
If the soft starter is started via
eldbus communi­cation but stopped via the LCP or a remote input, an identical start command cannot be used to restart the soft starter.
If the soft starter is controlled via the LCP or the remote inputs (and via eldbus communications), a control command should be immediately followed by a status query to conrm that the command has been actioned.
NOTICE
Functions available only in VLT® Soft Starter MCD 500:
Parameter management
Dual motor control
Digital inputs
Jog
Current measurement in amperes
Power information
Warnings
NOTICE
VLT® Compact Starter MCD 201 open-loop soft starters do not support motor current and motor temperature information.
7.2 Cyclic Operation
This section lists requirements related to cyclic services for the EtherNet/IP Module. The EtherNet/IP Module uses both implicit (I/O) and explicit messaging, with a cyclic trigger (minimum cyclic interval = 1 ms).
7.2.1 Assembly Objects
The EtherNet/IP Module supports the assembly objects listed in Table 7.1.
Assembly instances Description Maximum size Type
104
Originatortarget
2 (4) bytes Integer
154
Targetoriginator
6 (12) bytes Integer
Table 7.1 Assembly Objects
7.2.2 Control Commands
7.2.2.1 Receiving Control Data from the Controller
The EtherNet/IP Module uses output assembly instance 104d in assembly class 0x04 to receive control data from the controller. This instance is the only valid assembly instance.
Byte
Function
1)
Details
0 Control word See chapter 7.2.2.2 Control Word (Write-only)
for details.
1
2 Reserved Must be 0.
3
Table 7.2 Valid Assembly Instance
1) All elds are in little- endian format.
7.2.2.2 Control Word (Write-only)
Use the structure in Table 7.3 to send a control command to the soft starter.
Byte Bit Function
0
0–5 Reser ved Must be 0.
6 Run 0 = Stop command
1 = Start command
7 Reset Changing this bit from 0 to 1 resets a
trip.
1
0–4 Reser ved Must be 0.
5 Motor set
select
0 = Use primary motor set when
starting
1)
1 = Use secondary motor set when
starting
1)
6–7 Reser ved Must be 0.
Table 7.3 Control Word Structure
1) Ensure that the programmable input is not set to motor set select
before using this function.
Packet Structures Installation Guide
MG17Q102 Danfoss A/S © 05/2017 All rights reserved. 13
7 7
7.2.2.3 Command Examples
Byte Value Description
Command: Start a soft starter
0
0b11000000 (0XC0)
or
0b01000000 (0X40)
0bX1000000, where X is 0 or 1 in the reset eld.
Command: Select primary or secondary motor settings
1
0b00000000 (0X0)
or
0b00100000 (0X20)
Select primary motor settings.
Select secondary motor settings.
Command: Reset a soft starter
0
0b11000000 (0XC0)
or
0b10000000 (0X80)
The reset only occurs when the previous reset bit is 0, otherwise the value of 1 is ignored.
Command: Stop a soft starter
0 0bX0000000
Table 7.4 Control Commands
7.2.3 Status Information
7.2.3.1 Reading Status Information from the Soft Starter
The EtherNet/IP Module uses input assembly instance 154d in assembly class 0X04 to send status information to the controller. This instance is the only valid assembly instance.
Byte Function Details
0
Status word
See chapter 7.2.3.2 Status Word (Read-only) for details.
1
2
Reserved
Must be 0.
3
4
Motor current
Measured current is represented as a 32-bit value to 2 decimal places:
0000001 hex = 0.01 A
0000064 hex = 1.00 A
0010D47 hex = 689.35 A
5
6
7
8
Trip code
See chapter 7.2.3.3 Trip Codes.
9
10
Reserved
Must be 0.
11
Table 7.5 Status Information
Packet Structures EtherNet/IP Module
14 Danfoss A/S © 05/2017 All rights reserved. MG17Q102
77
7.2.3.2 Status Word (Read-only)
Use the structure in Table 7.6 to query the status of the soft starter.
Bit Function Details MCD 201 MCD 202 MCD 500
0 Ready 0 = Start or stop command not acceptable
1 = Start or stop command acceptable
1 Control from net 0 = Program mode
1 = Control from net
2 Coasting 0 = Coasting
1 = Enabled
3 Trip 0 = Not tripped
1 = Tripped
4 Reserved Must be 0
5 Reserved Must be 0
6 Reserved Must be 0
7 Warning 0 = No warning
1 = Warning
8 Ramping 0 = Not at full voltage (non-bypassed)
1 = Running (full voltage at the motor)
9 Local/remote 0 = Local control
1 = Remote control
10 Reserved Must be 0
11 On 0 = Unknown, not ready, ready to start, or tripped
1 = Starting, running, stopping, or jogging
12 Reserved Must be 0
13 Reserved Must be 0
14 Reserved Must be 0
15 Temperature limit 0 = Motor operating below normal operating temperature
1 = Motor operating above normal operating temperature
Table 7.6 Status Commands
Packet Structures Installation Guide
MG17Q102 Danfoss A/S © 05/2017 All rights reserved. 15
7 7
7.2.3.3 Trip Codes
The trip code is reported in bytes 2–3 and 17 of the status word.
Trip code Description MCD 201 MCD 202 MCD 500
0 No trip
11 Input A trip
20 Motor overload
21 Heat sink overtemperature
23 L1 phase loss
24 L2 phase loss
25 L3 phase loss
26 Current imbalance
28 Instantaneous overcurrent
29 Undercurrent
50 Power loss
54 Phase sequence
55 Frequency
60 Unsupported option (function not available in inside delta)
61 FLC too high
62 Parameter out of range
70 Miscellaneous, including:
Current read err Lx
ATTENTION! Remove mains volts
Motor connection Tx
Firing fail Px
VZC fail Px
Low control volts
75 Motor thermistor
101 Excess start time
102 Motor connection
103 Shorted SCR
113 Starter communication (between module and soft starter)
114 Network communication (between module and network)
115 L1-T1 shorted
116 L2-T2 shorted
117 L3-T3 shorted
118 Motor 2 overload
119
1)
Time-overcurrent (bypass overload)
121 Battery/clock
122 Thermistor circuit
Table 7.7 Trip Codes
1) For VLT® Soft Starter MCD 500, time-overcurrent protection is only available on internally bypassed models.
Packet Structures EtherNet/IP Module
16 Danfoss A/S © 05/2017 All rights reserved. MG17Q102
77
7.3 Acyclic Operation
This section provides information on objects, instances, and attributes for acyclic operation. It also lists the requirements related to acyclic services for the EtherNet/IP Module.
7.3.1 Class 0X01 Identity Object
The EtherNet/IP Module supports the attributes for identity objects listed in Table 7.8.
Attribute Function Description
1 Vendor Supported
2 Device type The attribute value is 12d
3 Product code Supported
4 Revision: Major,
minor
Revision value set in the EDS le
5 Status Status of the netIC module
6 Serial number Serial number of the netIC
module
7 Product name Supported
Table 7.8 Identity Object Attributes
7.3.2 Vendor-specic Objects
The EtherNet/IP Module supports vendor-specic class objects 100, 101, 103, and 104.
7.3.2.1 Class 100 Objects (Read/Write)
Object name Class Instance Attribute
Motor full load current 100 101 100
Locked rotor time 100 102 100
Start mode 100 103 100
Current limit 100 104 100
Initial current 100 105 100
Start ramp time 100 106 100
Kickstart level 100 107 100
Kickstart time 100 108 100
Excess start time 100 109 100
Stop mode 100 110 100
Stop time 100 111 100
Adaptive control gain 100 112 100
Adaptive start prole 100 113 100
Adaptive stop prole 100 114 100
Brake torque 100 115 100
Brake time 100 116 100
Phase sequence 100 117 100
Current imbalance 100 118 100
Current imbalance delay 100 119 100
Undercurrent 100 120 100
Undercurrent delay 100 121 100
Object name Class Instance Attribute
Instantaneous overcurrent 100 122 100
Instantaneous overcurrent delay 100 123 100
Frequency check 100 124 100
Frequency variation 100 125 100
Frequency delay 100 126 100
Restart delay 100 127 100
Motor temperature check 100 128 100
Local/remote 100 129 100
Comms in remote 100 130 100
Input A function 100 131 100
Input A name 100 132 100
Input A trip 100 133 100
Input A trip delay 100 134 100
Input A initial delay 100 135 100
Remote reset logic 100 136 100
Relay A function 100 137 100
Relay A on delay 100 138 100
Relay A o delay 100 139 100
Relay B function 100 140 100
Relay B on delay 100 141 100
Relay B o delay 100 142 100
Relay C function 100 143 100
Relay C on delay 100 144 100
Relay C o delay 100 145 100
Low current ag 100 146 100
High current ag 100 147 100
Motor temperature ag 100 148 100
Analog output A 100 149 100
Analog A scale 100 150 100
Analog A maximum adjustment 100 151 100
Analog A minimum adjustment 100 152 100
Auto-start type 100 153 100
Auto-start time 100 154 100
Auto-stop type 100 155 100
Auto-stop time 100 156 100
Auto-reset action 100 157 100
Maximum resets 100 158 100
Reset delay groups A&B 100 159 100
Reset delay group C 100 160 100
Motor FLC-2 100 161 100
Locked rotor time-2 100 162 100
Start mode-2 100 163 100
Current limit-2 100 164 100
Initial current-2 100 165 100
Start ramp-2 100 166 100
Kickstart level-2 100 167 100
Kickstart time-2 100 168 100
Excess start time-2 100 169 100
Stop mode-2 100 170 100
Stop time-2 100 171 100
Adaptive control gain-2 100 172 100
Adaptive start prole-2 100 173 100
Adaptive stop prole-2 100 174 100
Packet Structures Installation Guide
MG17Q102 Danfoss A/S © 05/2017 All rights reserved. 17
7 7
Object name Class Instance Attribute
Brake torque-2 100 175 100
Brake time-2 100 176 100
Language 100 177 100
User screen - top left 100 178 100
User screen - top right 100 179 100
User screen - bottom left 100 180 100
User screen - bottom right 100 181 100
Graph timebase 100 182 100
Graph maximum adjustment 100 183 100
Graph minimum adjustment 100 184 100
Mains reference voltage 100 185 100
Access code 100 186 100
Adjustment lock 100 187 100
Emergency run 100 188 100
Current calibration 100 189 100
Main contactor time 100 190 100
Bypass contactor time 100 191 100
Motor connection 100 192 100
Jog torque 100 193 100
Motor overload 100 194 100
Current imbalance 100 195 100
Undercurrent 100 196 100
Instantaneous overcurrent 100 197 100
Frequency 100 198 100
Heat sink overtemperature 100 199 100
Table 7.9 Class 100 Objects
7.3.2.2 Class 101 Objects (Read/Write)
Object name Class Instance Attribute
Excess start time 101 100 100
Input A trip 101 101 100
Motor thermistor 101 102 100
Starter communication 101 103 100
Network communication 101 104 100
Battery/clock 101 105 100
Low control volts 101 106 100
Comms timeout 101 107 100
Tracking gain 101 108 100
Tracking gain-2 101 109 100
Frequency detect 101 110 100
Bypass protection 101 111 100
Pedestal detect 101 112 100
Table 7.10 Class 101 Objects
7.3.2.3 Class 103 Objects (Read-only)
Object name Class Instance Attribute
Binary protocol version 103 100 100
Product type code 103 101 100
Minor software version 103 102 100
Major software version 103 103 100
Soft starter model 103 104 100
Parameter changed 103 105 100
Num parameter 103 106 100
Parameter value 103 107 100
Access type 103 108 100
Starter state 103 109 100
Warning 103 110 100
Initialized 103 111 100
Reserved 103 112 100
Parameters have changed 103 113 100
Phase sequence 103 114 100
Trip/warning code 103 115 100
Current 103 116 100
Current % of FLC 103 117 100
Motor 1 temperature 103 118 100
Motor 2 temperature 103 119 100
Power ( W) 103 120 100
Power scale 103 121 100
% power factor 103 122 100
Voltage (refers to mains reference
voltage)
103 123 100
Phase 1 current 103 124 100
Phase 2 current 103 125 100
Phase 3 current 103 126 100
Phase 1 voltage (refers to mains
reference voltage)
103 127 100
Phase 2 voltage (refers to mains
reference voltage)
103 128 100
Phase 3 voltage (refers to mains
reference voltage)
103 129 100
Minor revision 103 130 100
Major revision 103 131 100
Table 7.11 Class 103 Objects
Packet Structures EtherNet/IP Module
18 Danfoss A/S © 05/2017 All rights reserved. MG17Q102
77
7.3.2.4 Class 104 Objects (Read-only)
Object name Class Instance Attribute
Major software version 104 101 100
Minor software version 104 102 100
Major software version 104 103 100
Minor software version 104 104 100
Major software version 104 105 100
Minor software version 104 106 100
Major software version 104 107 100
Minor software version 104 108 100
Model 104 109 100
Control variant 104 110 100
Backplane variant 104 111 100
Actual motor current 104 112 100
Variant high byte 104 113 100
Customer 104 114 100
Table 7.12 Class 104 Objects
7.3.3 Supported Services for Vendor­specic Objects
This section describes the operational instructions to carry out acyclic services on class objects 100, 101, 103, and 104.
The EtherNet/IP Module supports the services for vendor- specic objects in Table 7.13.
Service code Function Description
0x01 Get attribute all Only supported for class 0x01
identity object
0x10 Set attribute single Supported
0x0E Get attribute single Supported
Table 7.13 Supported Services
7.3.3.1 Set Attribute Single
To set an attribute, use the service code 0x10 (set attribute single). For details on returned status codes, see
chapter 7.3.3.3 Status Codes for Acyclic Services. Illustration 7.1 shows the successful writing of parameter 1-01 Motor Full Load Current (Class 100, Instance 101).
NOTICE
Class and service codes are written in hexadecimal values, while instance is in decimal values.
177HA681.11
Illustration 7.1 Example: Setting the Value of Class 0x64
Instance 101 - Successful
Writing to a parameter that does not exist (or is read-only) results in an error.
Illustration 7.2 shows the example of an attempt to write to a non-existing parameter (Class 101, Instance 113).
177HA682.11
Illustration 7.2 Example: Setting the Value of Class 0x65
Instance 113 - Error
Packet Structures Installation Guide
MG17Q102 Danfoss A/S © 05/2017 All rights reserved. 19
7 7
7.3.3.2 Get Attribute Single
To get an attribute, use the service code 0x0E (get attribute single). For details on returned status codes, see
chapter 7.3.3.3 Status Codes for Acyclic Services. Illustration 7.3 shows the successful reading of parameter 1-09 Excess Start Time (Class 100, Instance 109).
NOTICE
Class and service codes are written in hexadecimal values, while instance is in decimal values.
177HA679.11
Illustration 7.3 Example: Retrieving the Value of Class 0x64,
Instance 109 - Successful
Reading a parameter that does not exist results in an error. Illustration 7.4 shows the example of an attempt to read a non-existing parameter (Class 101, Instance 113).
177HA680.11
Illustration 7.4 Example: Retrieving the Value of Class 0x65,
Instance 113 - Error
Packet Structures EtherNet/IP Module
20 Danfoss A/S © 05/2017 All rights reserved. MG17Q102
77
7.3.3.3 Status Codes for Acyclic Services
Status
code
Status name Comments
0x00 Success This code is returned after successful execution of the service, that is
When the register mapped for service Get attribute single is successfully read.
When the register mapped for service Set attribute single is successfully set.
0x03 Invalid parameter value
0x05 Path destination unknown The mapped register does not exist.
0x08 Service not supported The requested service is not available for this Object class/instance.
0x09 Invalid attribute value This code only applies to the service Set attribute single. It is returned if the value is out of range
for the mapped register.
0x0E Attribute not settable This code only applies to the service Set attribute single. It is returned if the mapped register is
read-only.
0x14 Attribute not supported The attribute specied in the request is not supported.
0x16 Object does not exist The object specied does not exist in the device.
Table 7.14 Status Codes, Get/Set Attribute Single
Packet Structures Installation Guide
MG17Q102 Danfoss A/S © 05/2017 All rights reserved. 21
7 7
8 Network Design
The EtherNet/IP Module supports star, line, and ring topologies.
8.1 Star Topology
In a star network, all controllers and devices connect to a central network switch.
177HA628.10
Illustration 8.1 Star Network Topology
8.2 Line Topology
In a line network, the controller connects directly to 1 port of the
rst EtherNet/IP Module. The 2nd Ethernet port of the EtherNet/IP Module connects to another module, which in turn connects to another module until all devices are connected.
177HA629.10
Illustration 8.2 Line Network Topology
NOTICE
The EtherNet/IP Module has an integrated switch to allow data to pass through in line topology. The EtherNet/IP Module must be receiving control power from the soft starter for the switch to operate.
NOTICE
If the connection between 2 devices is interrupted, the controller cannot communicate with devices after the interruption point.
NOTICE
Each connection adds a delay to communication with the next module. The maximum number of devices in a line network is 32. Exceeding this number may reduce the reliability of the network.
8.3 Ring Topology
In a ring topology network, the controller connects to the 1st EtherNet/IP Module via a network switch. The 2
nd
Ethernet port of the EtherNet/IP Module connects to another module, which in turn connects to another module until all devices are connected. The nal module connects back to the switch.
The EtherNet/IP Module supports beacon-based ring node
conguration.
177HA630.10
Illustration 8.3 Ring Network Topology
NOTICE
The network switch must support loss of line detection.
Network Design EtherNet/IP Module
22 Danfoss A/S © 05/2017 All rights reserved. MG17Q102
88
8.4 Combined Topologies
A single network can include both star and line components.
177HA631.10
Illustration 8.4 Combined Star/Line Network Topology
Network Design Installation Guide
MG17Q102 Danfoss A/S © 05/2017 All rights reserved. 23
8 8
9 Specications
Enclosure Dimensions, W x H x D [mm (in)] 40 x 166 x 90 (1.6 x 6.5 x 3.5) Weight 250 g (8.8 Oz) Protection IP20
Mounting Spring-action plastic mounting clips 2
Connections Soft starter 6-way pin assembly Contacts Gold ash Networks RJ45
Settings IP address BootP, automatically assigned, congurable Device name Congurable
Network Link speed 10 Mbps, 100 Mbps (auto-detect) Full duplex Auto crossover
Power Consumption (steady state, maximum) 35 mA at 24 V DC Reverse polarity protected Galvanically isolated
Certication
RCM IEC 60947-4-2 CE IEC 60947-4-2 ODVA EtherNet/IP conformance tested
Environmental Operating temperature -10 to +60 °C (14–140 °F), above 40 °C (104 °F) with derating Storage temperature -25 to +60 °C (-13 to +140 °F) Humidity 5–95% relative humidity Pollution degree Pollution degree 3 Vibration IEC 60068-2-6
Specications EtherNet/IP Module
24 Danfoss A/S © 05/2017 All rights reserved. MG17Q102
99
Index
A
Abbreviations........................................................................................... 4
Acyclic service........................................................................................ 17
Additional resources.............................................................................. 3
Approvals................................................................................................... 3
Assembly class................................................................................ 13, 14
Assembly instance............................................................................... 14
Assembly object.................................................................................... 13
Auto-on mode.......................................................................................... 5
B
Busbar......................................................................................................... 5
C
Cable
category................................................................................................. 9
Ethernet cable..................................................................................... 9
Capacitors
Power factor correction capacitor................................................ 5
Certications............................................................................................. 3
Class object............................................................................................. 17
Commands
Control.......................................................................................... 13, 14
Start................................................................................................ 13, 15
Status.................................................................................................... 15
Stop................................................................................................ 13, 15
Connections........................................................................................... 24
Contactors
Bypass contactor................................................................................ 5
Main contactor.................................................................................... 6
Control command......................................................................... 13, 14
Control word.......................................................................................... 13
Control word structure....................................................................... 13
Conventions.............................................................................................. 4
Cyclic service.......................................................................................... 13
D
Dimensions............................................................................................. 24
E
Electromagnetic interference............................................................. 9
Ethernet attribute................................................................................. 10
H
Heat sink..................................................................................................... 5
I
Identity object....................................................................................... 17
Inputs
Remote................................................................................................... 5
Installing EtherNet/IP option.............................................................. 7
Intended use............................................................................................. 3
IP address.............................................................................. 9, 10, 12, 24
IP address conict................................................................................. 10
L
LED
Description......................................................................................... 12
LED........................................................................................................... 4
Name.................................................................................................... 12
Status.................................................................................................... 12
M
MAC address............................................................................................. 9
Motor
connection............................................................................................ 6
N
Network
Auto crossover.................................................................................. 24
Full duplex.......................................................................................... 24
Line........................................................................................................ 22
Link speed........................................................................................... 24
Ring....................................................................................................... 22
Star........................................................................................................ 22
Q
Qualied personnel........................................................................... 3, 5
R
Removing EtherNet/IP Option........................................................... 7
Reset mode............................................................................................... 8
S
Start command............................................................................... 13, 15
Status command................................................................................... 15
Status word............................................................................................. 14
Stop command............................................................................... 13, 15
Subnet mask........................................................................................... 10
Supply..................................................................................................... 5, 6
Symbols...................................................................................................... 4
T
Terminals
A1............................................................................................................. 8
N2............................................................................................................. 8
Index Installation Guide
MG17Q102 Danfoss A/S © 05/2017 All rights reserved. 25
U
Unintended start..................................................................................... 5
W
Weight...................................................................................................... 24
Index EtherNet/IP Module
26 Danfoss A/S © 05/2017 All rights reserved. MG17Q102
Index Installation Guide
MG17Q102 Danfoss A/S © 05/2017 All rights reserved. 27
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Danfoss A/S Ulsnaes 1 DK-6300 Graasten vlt-drives.danfoss.com
*MG17Q102*
175R1168 MG17Q102 05/2017
Loading...