Danfoss VLT Center Winder MCO 352 Operating Instructions Manual

VLT® Center Winder MCO 352 Contents
Contents
1 How to Read these Operating Instructions
How to Read These Operating Instructions 3 Additional Literature for VLT AutomationDrive, MCO 305 and MCT 10 Motion Con-
trol Tool Approvals 3 Symbols 3 Abbreviations 4
2 Safety Instructions and General Warnings
High Voltage Warning 5 Safety Instructions 5 Before commencing repair work 5 Avoid Unintended Start 5 Safe Stop of VLT AutomationDrive FC302 6 General Warning 6
3 Introduction to Center Winder Controller
MCO 352 Center Winder Controller 7 Additional Features 8
3
3
5
7
System Requirements 9
VLT AutomationDrive Terminals 11 Center Winder Option Terminals 12 Digital and Analog I/Os 13 Read-only Application Parameters 25
5 Center Winder Calibration
Frequency Converter Checkout 27 Preset Winder Function Parameters 28 Winder Scaling Factor Calibration – Open loop Speed Adjustments 29 Check Inputs 30 Calibration of Diameter Measurement Signal 30 Check Tension Correction Direction 31 Winder Closed Loop Calibration 31
6 Troubleshooting
11
27
33
7 Appendix
Center Winder Settings 35 MCO Basic Settings 36
Index
MG.33.T1.02 - VLT® is a registered Danfoss trademark
35
37
1
1
1 How to Read these Operating Instructions VLT® Center Winder MCO 352
2
MG.33.T1.02 - VLT® is a registered Danfoss trademark
VLT® Center Winder MCO 352 1 How to Read these Operating Instructions
1 How to Read these Operating Instructions
1
1.1.1 How to Read These Operating Instructions
These Operating Instructions will help you get started, program, and troubleshoot your Center Winder Option. Please read these operating instructions in full and, in order to be able to work with the system safely and professionally, particularly observe t h e hi n t s and cautionary remarks.
Chapter How to Read these Operating Instructions introduces the manual and informs you about the approvals, symbols, and abbreviations used in this literature.
Chapter Safety Instructions and General Warnings entails instructions on how to handle the Center Winder Controller correctly.
Chapter Introduction to Center Winder Controller informs you in general about center winders and different methods of rewinding and unwinding.
Chapter How to Ins tall informs you how to start up the Center Winder Option. This section includes the description of the terminals and the parameters.
Chapter Center Winder Calibration informs how to calibrate the wi nder. Detailed instructions on how to proceed can be found in this section.
Chapter Troubleshooting assists you in solving problems that may occur when installing and using the Cente r Winder Co ntrolle r.
Chapter Appendix provides information about para meters in clearl y arranged lists. P lease see t he Parame ter Ref erence in th e MCO 305 De sign Guide for more details.
1.2.1 Additional Literature for VLT AutomationDrive, MCO 305 and MCT 10 Motion Control Tool
The MCO 305 Operating Instructions provide the necessary information for build-in, set-up, and optimize the controller. The VLT AutomationDrive FC 300 Operating Instructions provide the necessary information for getting the drive up and running. The VLT AutomationDrive FC 300 Design Guide entails all technical information about the driv e and customer design and applications. The VLT AutomationDrive FC 300 MCT 10 Operating Instructions provide information for installation and use of the software on a PC.
Danfoss Drives technical literature is also available online at www.danfoss.com/drives.
1.3.1 Approvals
1.4.1 Symbols
Symbols used in this Operating Instructions.
NB!
Indicates something to be noted by the reader.
Indicates a general warning.
MG.33.T1.02 - VLT® is a registered Danfoss trademark
3
1
1 How to Read these Operating Instructions VLT® Center Winder MCO 352
Indicates a high-voltage warning.
Indicates default setting
1.5.1 Abbreviations
Automatic Motor Adaptation AMA Build-up Ratio BUR Direct Current DC Frequency Converter FC Local Control Panel LCP Milliampere mA Millisecond ms Minute min Motion Control Option MCO Motion Control Tool MCT Parameter par. Proportional Integral Derivative Control PID Pulses per Revolution PPR Revolutions per Minute RPM Second s Tension limit d etection TLD Volts V Quad Counts qc
4
MG.33.T1.02 - VLT® is a registered Danfoss trademark
VLT® Center Winder MCO 352 2 Safety Instructions and General Warnings
2 Safety Instructions and General Warnings
VLT Center Winder MCO352
Operating Instructions Software version: 1.xx
These Operating Instructions can be used for the VLT Center Winder MCO352 with all FC 300 frequency converters with software version 4.9x. The software version of FC 300 can be read in parameter 15-43.
2.2.1 High Voltage Warning
The voltage of the VLT AutomationDrive is dangerous whenever the conver ter is connecte d to ma ins. Incorrect fitting of the motor or the VLT Automa­tionDrive may cause damage to the equipment, serious injury or death. Consequently, it is essential to comply with the instructions in this manual as well as local and national rules and safety regulations.
2
2.2.2 Safety Instructions
Make sure the VLT AutomationDrive is properly connected to earth.
Do not remove mains plugs or motor plugs while the VLT AutomationDrive is connected to mains.
Protect users against supply voltage.
Protect the motor against overloading according to national and local regulations.
Motor overload protection is not included in the default settings. To add this function, set par. 1-90
warning
.
For the North American market: ETR functions provide class 20 motor overload protection, in accordance with NEC.
The earth leakage current exceeds 3.5 mA.
The [OFF] key is not a safety switch. It does not disconnect the VLT AutomationDrive from mains.
Motor thermal protection
2.2.3 Before commencing repair work
1. Disconnect VLT AutomationDrive from mains.
2. Disconnect DC bus terminals 88 and 89.
3. Wait at least 4 minutes.
4. Remove motor plugs.
to value
ETR trip
or
ETR
2.2.4 Avoid Unintended Start
While VLT AutomationDrive is connected to mains, the motor can be started/stopped using digital commands, bus commands, references or via the LCP.
Disconnect the VLT AutomationDrive from mains whenever personal safety considerations make it necessary to avoid unintended start.
To avoid unintended start, always activate the [OFF] key before chan ging parameters. Un less terminal 37 is t urned off, an electronic f ault, temporary overload, a fault in the mains supply, or lost motor connect i on may cause a stopped motor to start.
MG.33.T1.02 - VLT® is a registered Danfoss trademark
5
2
2 Safety Instructions and General Warnings VLT® Center Winder MCO 352
2.2.5 Safe Stop of VLT AutomationDrive FC302
The VLT AutomationDrive FC 302 can perform the Designated Safety Function Uncontrolled Sto pping by removal of power (as defined by draft IEC 61800-5-2) or Stop Category 0 (as defined in EN 60204-1). I t is designed and approved suitable for the requirements of Safety Category 3 in EN 954-1. This functionality is called Safe St op. In orde r to inst all an d use t he Saf e Sto p func tion in ac corda nc e with th e requ ire ments of Safety Ca tegory 3 in EN 954-1, the related information and instructions of the VLT AutomationDrive FC 300 Design Guide MG.33.BX.YY must be followed! The information and instructions of the Operating Instructions are not sufficient for a correct and safe use of the Safe Stop functionality!
2.2.6 General Warning
WARNING: Touching the electrical parts may be fatal – even after the equipment has been disconnected from mains. Also make sure that all voltage inputs have been disconnected, such as load-sharing (linkage of DC intermediate circuit), as well as the motor connection for kinetic back-up. Using VLT AutomationDrive FC 300 wait at least 15 minutes.
6
MG.33.T1.02 - VLT® is a registered Danfoss trademark
VLT® Center Winder MCO 352 3 Introduction to Center Winder Controller
3 Introduction to Center Winder Controller
3.1.1 MCO 352 Center Winder Controller
The MCO 352 Center Winder Controller uses the speed winder method with a diameter calculation and either a load cell or dancer feedback. Below is a simplified block diagram of a tension controlled winder system. The system would be identical if a dancer were used except that the Taper Function block would have a 0/4-20 mA output used to load the dancer air cylinder proportional to the tapered tension se t point. The drive is fed an open loop speed reference based on the calculated diameter of the roll. This si gnal is summed wit h a signal gene rated by a PID a mplifier comp aring the actual tension feedback with a tapered tension set point. The ta pered tension set point is actually the tension set point modified based on the roll diameter a nd the taper set point. Taper generally reduces the tension set point hyperbolically with a change in diamete r. The PID ampli fier output is also reduced with increasing diameter since the same change in reference will have a larger surface speed change as the roll increases in diameter . Ide a lly , th e op en l o op reference signal is scaled at core so that the surface speed of the core matc hes line spe ed. The diamet er value is calcul ated by the ratio of line spee d verse winder speed.
3
Roll diameter
This calculation needs to be updated fairly quickly since the roll can change diameter very quickly when near the core. If the true diameter changes faster than the diameter is calculated, the open loop reference speed will lag too far behind the re quired speed and the tension PID w il l ne ed to make u p to o much of the difference.
=
core diameter
Line speed
(
Winder
speed
)
The Tension PID updates every 30 ms and should be updated at least 3 times faster than the diameter calculation. This is because the tension PID block must be allowed to stabilize syst em tension before a new diameter is calculated, since the calculated diameter is used by both the open-loop ref ere nce and as an input to the tension PID block.
MG.33.T1.02 - VLT® is a registered Danfoss trademark
7
3
3 Introduction to Center Winder Controller VLT® Center Winder MCO 352
3.1.2 Additional Features
Several features have been included to increase the overall stability of the winder and to increase control and monitoring of the windi ng process.
Acceleration Feed-Forward: The Winder block diagram includes an acceleration feed-forward function that allows a shift in the tension/taper set point based on changes in line speed. This provides a tension boost during initial acceleration to help compensate for system inertia.
Tension-Taper Set-Point Ramp: The tapered tension set point generator will integrate any changes to the tension or taper set points over multiple program scans. A parameter is provided to increase or decrease response time.
Diameter Calculator Limi ter: The diameter calculator incl udes a similar integration tech nique. A maximum rate of dia meter change can be adjusted by parameter. In addition, the calculated diameter is restricted from moving in the wrong direction to only 20 % of the rate applied to the expected change in diameter. For example, if the station is rewinding a roll, the diamet er is not expected to reduce in diameter.
Diameter Calculator Minimum Speed: There is also a minimum speed requirement to enable the diameter calculator. At low speeds, the line and winder speeds may not have enough resolution to accurately calculate diameter. A parameter is provided to define a minimum line speed required for the diameter calculator to function. Until that speed is reached, the diameter value will not change.
Programmable Analog Inputs: The VLT AutomationDrive has two analog inputs. Inputs 53 and 54 are analog inputs with a voltage range of ±10 VDC or a current range of 0/4-20mA. Use DIP-switch S201/S202 to select configuration. The source of the tension and taper set-points can be adjusted by either analog input or parameter setting. The tension feedback and initial diameter measurement can only use analog inputs. Parameters are provided to select the source of each input. Care must be taken not to program a single input for more than one function.
Initial Diameter Measurement: In many winding applications there are very few variations in starting core diameter or initial roll size. A choice of three programmable starting diameters can be programme d and logically selected. For applications where the starting diameter can vary regularly, the Winder will allow the initial diameter to be measured through an analog input signal. Scaling parameters are provided to set the analog level at core and at full roll. This function assumes a linear change in the diameter measurement signal.
End of Roll Detection: An output is provided to indicate a diameter limit. For rewinding applications, the diameter limit occurs when the calculated diameter exceeds a set limit. For unwinding applications, the diameter limit occurs when the calculated diameter is less than the set limit. The station will continue to run after a diameter limit is detected. This output can be used to stop the line for a roll change.
Tension Limit Detector: The Winder includes a tension limit detection (TLD) feature. This feature allows the Win der to trip if a lo w-tension or high-tension feedback exists for a period of time. The trip delay includes a normal running delay as well as a secondary starting dela y.
8
MG.33.T1.02 - VLT® is a registered Danfoss trademark
VLT® Center Winder MCO 352 3 Introduction to Center Winder Controller
3.2.1 System Requirements
The center winder system has some minimum requirements for proper operation.
Frequency converter: VLT AutomationDrive with VLT Center Winder MCO 352. It is also recommended that the drive have dynamic braking option capabilities to allow a quick stop of a large roll.
Winder motor: The motor needs to be inverter duty with a wide speed range (>100:1). The motor should be geared or belted so tha t top m otor speed at core does not exceed 4500 RPM. Generally, the motor maximum constant horsepower speed wil l be t he l imiting factor.
Winder Encoder: The winder encoder needs to be mounted on the winder motor. The encoder must have a differential, quadrature TTL/5VDC output. The encoder PPR should be selected such that the channel frequency is as close to 400 kHz at the winder motor top speed.
Line Encoder: The line speed encoder output circu itry needs to be the same as the winde r encoder. Again, the encoder PPR should selecte d such that the channel frequency is as close to 400 kHz at the maximum line speed.
Tension Feedback: The tension feedback is required from either a load cell or dancer. If load cells are used they need to be calibrated for a either a 0-20 mA or 0-10 V signal from zero to maximum tension. If a dancer is used the calibration should be 0-20mA/0-10V from bottom to top of the dancer movement.
Logic Inputs: The digital inputs for tension on, over/under etc. are 24 VDC, sinking inputs. The drive has a 24VDC/200mA supply available if dry contacts are used. Logic commands can also be sent to the drive serial port. Note that a third party HMI/operator display such as EXOR or Red Lion can be used in place of the digital inputs. It is possible to serially access logic parameters through the VLT AutomationDrive USB or RS485 port.
Tension and Taper set-points: The tension and taper set-points are available on the display of the drive as parameters and can also be accessed serially through the VLT AutomationDrive USB or RS485 port. These set points can also be set usin g any unused 0-20mA/0-10VDC drive input, using an analog signal or potentiometer
3
Maximum Winder Motor speed Tension Loop Scan Time 30 ms TLD Time Resolution 25 ms Quick Stop Scan time 1 ms Coast Scan Time <1 ms Tension Loop Response Time 25 ms Line encoder frequency 100 kHz - 410 kHz Winder Encoder frequency 100 kHz – 410 kHz Winder Speed resolution ±16384 qc counts @ 4500 RPM Digital inputs 24 VDC, sinking Digital outputs 24 VDC, sourcing Analog Tension & taper set points 0-10 VDC, 0-20 mADC, 1000 count resolution Load cell or dancer feedback 0-10 VDC, 0-20 mADC, 1000 count resolution
4500 RPM
MG.33.T1.02 - VLT® is a registered Danfoss trademark
9
4
4 How to Install VLT® Center Winder MCO 352
10
MG.33.T1.02 - VLT® is a registered Danfoss trademark
VLT® Center Winder MCO 352 4 How to Install
4How to Install
4.1.1 VLT AutomationDrive Terminals
The VLT AutomationDrive control card contains input and output logic terminals used by the Winder Option. The Winder Option does not assign a function to all of the inputs and outputs on the control card. The terminals required for proper Winder operation are discussed in this manual. See the VLT AutomationDrive Operating Instructions for further details.
Analog Inputs
53 Multifunction inpu t 1 54 Multifunction inpu t 2 55 A/I common
Inputs
27 Quick Stop 37 Safe Stop
Relay 1
Running on tension
4
Relay 2
Ready
Analog Outputs
42 Taper Tension Setpoint
Supply Voltage
50 10 V DC max. load 15 mA
MG.33.T1.02 - VLT® is a registered Danfoss trademark
11
4
4 How to Install VLT® Center Winder MCO 352
4.1.2 Center Winder Option Terminals
The figure below shows the five green terminal str ips on the MC O 305 Op tion Card. The 24V supply on the digit al input and outp ut terminal strips are internally connected to the VLT AutomationDrive +24V supply available at terminals 12 & 13. The COM is connected to VLT AutomationDrive terminal
39. An external 24 VDC power supply can be used. See the MCO 305 Instruction Manual for details on setting MCO Supplied by external 24 VDC (parameter 33-85). The isolated 5V/400mA and 8V/250mA encoder supply is generated on the MCO 305 Card from the 24 V power supply.
X55
is always used for winder/unwinder speed
X56
is always used for line speed
X57 Digital Inputs
I1 Over/under winding I2 Winder jog reverse I3 Winder jog forward I4 Partial roll select I5 Tension on/off (reset) I6 Material select I7 Core select I8 Diameter reset
X59 Digital Outputs
O1 End of roll indicator O2 TLD indicator O3 Running on tension O4 Ready
12
MG.33.T1.02 - VLT® is a registered Danfoss trademark
VLT® Center Winder MCO 352 4 How to Install
4.2 Digital and Analog I/Os
4.2.1 MCO 352 I/O
X57/1 Input MCO352 Over/Under
Option: Function:
Determines whether the winder will operate for over or under winding. The motor direction will need to change depending on whether the material is wrappi ng over or under the wi nder core. The di­rection selected will also affect the jog directions.
NB!
This input is scanned only when tension is OFF.
X57/2 Input MCO352 Winder Jog Reverse
Option: Function:
Jogs winder in the reverse winding direction at the speed pro grammed in par. 19-07 (Winder Jo g Speed).
4
NB!
This input is scanned only when tension is OFF.
X57/3 Input MCO352 Winder Jog Forward
Option: Function:
Jogs winder in Forward winding direction at the speed programme d in par. 19-07 (Winder Jog Speed).
NB!
This input is scanned only when tension is OFF.
X57/4 Input MCO352 Partial Roll Select
Option: Function:
Selects new setting in parameter 19-04 as the preset starting diameter when the Diameter Reset (Input 8) is energized, rather than using one of the two preset core diameters. If the initial diameter is to be measured by an analog signal, this input must be held ON along with the correct setting in parameters 19-13 to 19-16.
NB!
This input is scanned only when tension is OFF.
MG.33.T1.02 - VLT® is a registered Danfoss trademark
13
4
4 How to Install VLT® Center Winder MCO 352
X57/5 Input MCO352 Tension On/Off (Reset)
Option: Function:
Turns the tension controller ON and OF F. This input should be en ergized while th e line is at zero speed. The core will be released when this input i s not energized. This input is also used to reset fault conditions.
X57/6 Input MCO352 Material Select
Option: Function:
Selects the Material Type (PAPER/POLY). Different material types such as paper verses poly require different Tension loop PID settings and Speed loop proportional gain settings. Changing this input toggles the values in parameters 19-41 to 19-50. If the PID parameter values are changed this input must be switch to initiate saving the new values.
NB!
This input is scanned only when tension is OFF and when the material selection is to be made by digital input ( see par. 19-23).
X57/7 Input MCO352 Core Select
Option: Function:
Selects one of two preset core sizes set in parameters 19-05 and 19-06. Core 1 = OFF, Core 2 = ON. This input is checked when the Diamet er Reset (I nput 8) i n energized and the partial rol l selec t (Input 4) is not energized. If unwinding, Core 2 can be used as an alternate initial roll diameter, but Core 1 must always be set for the smallest core diameter used.
NB!
This input is scanned only when tension is OFF.
X57/8 Input MCO352 Diameter Reset
Option: Function:
Resets diameter to a new value. If the New Diameter Set (Input 4) is energized, the partial core diameter value set in parameter 19-04 is used, otherwise the diamet er is reset to core1 or core2 values based on Core Select (Input 7).
NB!
This input is scanned only when tension is OFF.
4.2.2 VLT I/O
Input 27 Quick Stop
Option: Function:
Terminal 27 must be closed for the drive to run. If this input is opened while running, the frequency converter will ramp to a stop at a rate set by the Quick Stop Deceleration time (parameter 3-81).
14
MG.33.T1.02 - VLT® is a registered Danfoss trademark
VLT® Center Winder MCO 352 4 How to Install
Input 37 Safe Stop
Option: Function:
Terminal 37 must be closed for the frequency converter to run. If this input is opened while running the frequency converter will coast to a stop.
Output O1 End of Roll Indicator
Option: Function:
This output turns ON to indicate that the diameter has reached the value programmed in parameter 19-12. This output turns OFF when Diameter is reset (Input 8) to a value in normal operating range.
Output O2 TLD Indicator
Option: Function:
This output is turned ON when the Tension Limit Detector has sensed that tension has been out of range as set in parameters 19-08 and 19-09 for the number of scans set in parameter 19-10. A Tension Limit results in a Winder fault. Turning the tension OFF resets this fault and the output.
4
Output O3 Running on Tension
Option: Function:
This output is turned ON when the winder is regulating tension. The output is turned OFF when tension is switched off or if there is a station fault. Turning the tension OFF resets this fault and the output.
Output O4 Ready
Option: Function:
This output is turned ON when the station is ready to run. The output turns OFF if there is a TLD fault, an FC Alarm, an MCO 305 Error, Commanded Quick Stop, or Commanded Coast. Note: Outputs 5-8 are not used.
Relay 01 Running on Tension
Option: Function:
This relay output (01, 02, 03) is energized when the winder is regulating tension. The relay output is de-energized when tension is switched off or if there is a station fault.
NB!
Parameter 5-40 must be set for MCO controlled [51] for this function to work as described.
Relay 02 Ready
Option: Function:
This relay output (04, 05, 06) is energized when the station is ready to run. The relay will de-energize on a TLD fault, an FC Alarm, an MCO 305 Error, Quick Stop, or Coast.
MG.33.T1.02 - VLT® is a registered Danfoss trademark
15
4 How to Install VLT® Center Winder MCO 352
NB!
Parameter 5-40 must be set for MCO controlled (51) for this function to work as described.
4.2.3 Analog Inputs
Parameters 19-14, 19-19 to 19-21 allow setting the two analog inputs from the VLT AutomationDrive for any of the following.
4
•Tension Set Point
•Taper Set Point
Tension Feedback
Initial Diameter measurement
Input 53 Multi-function Input 1
Option: Function:
This analog input functions according to the setting of parameter 19-19 to 19-21. Use DIP-switch S201 to select a current (0-20 mA) or a voltage (-10 V to 10 V) configuration.
Input 54 Multi-function Input 2
Option: Function:
This analog input functions according to the setting of parameter 19-19 – 19-21. Use DIP-switch S201 to select a current (0-20mA) or a voltage (-10 V to 10 V) configuration.
Terminal 55 Analog Input Common
Option: Function:
This terminal is the common for the two analog inputs 53/54.
Terminal 50 Analog Input +10V Out
Option: Function:
This terminal is a supply of +10V/30 mA for the analog inp ut s.
Output 42 Tapered Tension Set-Point
Option: Function:
When a Dancer system is used, the calculated Tapered Tension Set Point should control the loading of the dancer air cylinder. This 0/4-20mA output can be used as input for the I-P transducer regu­lating the load on the dancer air cylinder. Parameter 6-50 must be set for either OPTION 0-20 mA or OPTION 4-20 mA.
NB!
If using a dancer, the Taper set point will have no affect if this output is not used to control the dancer air cylinder.
Terminal 39 Analog Output Common
Option: Function:
This terminal is used as a common for the analog output signals.
16
MG.33.T1.02 - VLT® is a registered Danfoss trademark
VLT® Center Winder MCO 352 4 How to Install
4.3.1 Parameters
19-01 Winder Mode Selection
Option: Function:
Sets the station as either a rewinder or unwinder. [0] * Rewinder [1] Unwinder
19-02 Tension Set-Point
Range: Function:
0 [0-1000]
1000 = 100.0% of full tension. Full tension is the point at which the load ce ll or dancer produces a 20 mA or 10 V signal.
Sets the desired running tension. Note that the taper setting will affect the actual tension on the
web. If a dancer system is used, this value sets the dancer running position which would no rmally
be 500 or center of movement. This parameter is only active if par. 19-19 is set to 0.
19-03 Taper Set-Point
Range: Function:
0 [-1100 – 1100] The Taper set-point is used to change the tension set-point as the diameter increases. The result
of the taper function is called the tapered tension set-point. The tapered tension set-point is always
equal to the tension set-point at core. This parameter is only active if parameter 19-20 is set to a
value of 0. A value of 0 = no taper or the tapered tension set-point will always be equal to the
tension set-point. A value of 1000 is 100.0 % taper or each time the diameter doubles from core
the tapered tension set-point will be decreased to 50 % of the previous value. Negative tapers are
also possible.
4
NB!
Taper is not required in unwinding applications. For unwinding applications, leave this parameter set to 0.
19-04 Partial Roll Diameter Value
Range: Function:
5000 [5000 – 100000]
100,000 = 100 % of full roll. Example: If drive has been set-up for a full roll dia¬meter of 40 inches and the roll loaded on rewind = 10 inches, then the value entered into this parameter would be
10
× 100, 000 = 25, 000
40
MG.33.T1.02 - VLT® is a registered Danfoss trademark
17
4
4 How to Install VLT® Center Winder MCO 352
This parameter is intended to preset the diameter when a partial roll is loa ded on the rew ind er. If Input 4 is ON when the diameter is reset with Input 8, the diameter will be preset to the value programmed in this parameter. For unwinding applications, this parameter can be used to set the full roll diameter.
19-05 Core1 Diameter
Range: Function:
5000* [5000 – 100000]
NB!
Note: Parameter 19-05 must be less than parameter 19-06.
19-06 Core2 Diameter
Range: Function:
5000* [5000 – 100000]
100000 = 100 % of full roll, see parameter 19-04.
This parameter is programmed with the main core value to be used on the winder. This parameter must be set for the smallest core diameter for both rewind and unwind applications.
100000 = 100 % of full roll, see Parameter 19-04.
This parameter allows programming a secondary core diameter if rewinding or a secondary full roll diameter if unwinding.
NB!
Parameter 19-05 must be less than parameter 19-06.
19-07 Winder Jog Speed
Range: Function:
0%* [0 – 100%]
NB!
Diameter is not taken into account to determine surface jo g speed.
Winder jog speed 100 = 100 % of the speed set in parameter 3-03 (MAX REFERENCE RPM).
This parameter sets the winder jog speed percentage. This speed is used for both forward and reverse jogging. The jog ramp is fixed at 4 seconds.
19-08 TLD Low Limit
Range: Function:
0* [-200 – 2000]
1000 = 100.0 % tension.
18
This parameter is the low limit for the Tension Limit Detector.
NB!
Setting the value to -200 will disable the low tension limit trip.
MG.33.T1.02 - VLT® is a registered Danfoss trademark
VLT® Center Winder MCO 352 4 How to Install
NB!
If the tension detection reaches the TLD Low Limit for more than TLD Timer (par. 19-10), output 2 is turned on and a trip is forced.
19-09 TLD High Limit
Range: Function:
0* [0 – 2200]
1000 = 100.0 % tension.
This parameter is the high limit for the Tension Limit Detector.
4
NB!
Setting the value to 2200 will disable the high tension limit trip.
NB!
If the tension detection reaches the TLD High Limit for more than TLD Timer (par. 19-10), output 2 is turned on and a trip is forced.
19-10 TLD Timer
Range: Function:
1* [1 – 200]
Each program scan is approx 25 ms.
Sets the number of consecutive program scans that the tension must exceed the high or low tension
limit before the Tension Limit Output will be energized and the station coasts to a stop. This function
is only active when tension is on.
19-11 TLD on Delay
Range: Function:
0* [-500 – 0]
Each program scan is approx 25 ms.
When tension is first turned on, the tension limit timer can be preset to a negative value to allow
time for the winder to stabilize web tension. As soon as the tension moves within the low and high
tension limits, the TLD function begins operating normally. This function can be useful during a quick
machine start with a slack web. This function is only active when tension is on.
19-12 Diameter Limit Detector
Range: Function:
0* [-100 – 100000]
100,000 = 100 % of full roll
When the calculated roll diameter reaches the set diameter, digital output 1 will turn ON to indicate
the end of the roll. This indicates a full roll when rewinding and an empty roll when unwinding.
NB!
The station will not stop automatically when the end of roll is detected.
MG.33.T1.02 - VLT® is a registered Danfoss trademark
19
4
4 How to Install VLT® Center Winder MCO 352
19-13 Initial Diameter Measurement
Option: Function:
It is possible to connect a roll diameter sensor to one of the frequency converter's a nalog inputs. This signal can be used to have the controller use a measured initial diameter, rather than a diameter size set by parameter. This is particularly useful in applications where non-uniform roll sizes are the
norm. [0] * Set diameter when diameter reset Parameters 19-04 to 19-06 set the diameter when the diameter is reset. [1] Set diameter based on analog signal The frequency converter sets the diameter based on an analog signal. The diameter can only be
reset when the tension is OFF.
19-14 Diameter Measurement Input
Option: Function:
This parameter sets the analog input used for diameter meas u rement. [1] Input 53 (0-10 VDC or 0-20 mA) [2] Input 54 (0-10 VDC or 0-20 mA)
19-15 Reading at Core
Range: Function:
0* [-1100 – 1100]
If a signal of 1.50 V results from measuring the smallest core, set this parameter to 150.
This parameter sets the analog input signal reading at the smallest core used. The value needs to
be multiplied by 100 to allow maximum resolution.
19-16 Reading at Full Roll
Range: Function:
0 [-1111 – 2111]
If a signal of 9.50 V results from measuring the full roll, set this parameter to 950.
This parameter sets the analog input signal reading at the large st roll size use d. The value needs
to be multiplied by 100 to allow maximum resolution.
19-19 Tension Set-Point Input
Option: Function:
This parameter sets the source of the tension set-point. [0] * Parameter 19-02 [1] Input 53 (0-10 VDC or 0-20 mA) [2] Input 54 (0-10 VDC or 0-20 mA)
19-20 Taper Set-Point Input
Option: Function:
This parameter sets the source of the taper set-point. [0] * Parameter 19-03 [1] Input 53 (0-10VDC or 0-20mA) [2] Input 54 (0-10VDC or 0-20mA)
19-21 Tension Feedback Input
Option: Function:
Sets analog input used for tension feedback. [1] * Input 53 (0-10 VDC or 0-20 mA) [2] Input 54 (0-10 VDC or 0-20 mA)
20
MG.33.T1.02 - VLT® is a registered Danfoss trademark
VLT® Center Winder MCO 352 4 How to Install
19-22 Tension Feedback Type
Option: Function:
Selects type of tension feedback device. [0] * Load cell [1] Dancer
19-23 Command Source
Option: Function:
Determines if the digital inputs 1-8 are to be active or parameters 19-61 through 19-68 are used
for these functions. When a third party displ ay is used to control these functions, changing a pa-
rameter is the most efficient method. [1] * Par. 19-61 to 19-68 for controlling Entered for the parameters 19-61 through 19-68 to control the functions. [2] Digital input control Entered for digital input control.
19-24 Line Speed Scale
Range: Function:
200* [200 – 18000]
Display value:
par
. 19 − 24 −
(
max. Line encoder
50
)
Hz
× 4
4
Scales line speed for 100,000 counts at max speed. These counts can be read in parameter 19-96 .
19-25 Speed Match Scale
Range: Function:
500* [500 – 10000] Matches surface speeds of line and winder at core while running line at 100 % speed.
19-26 Winder Speed Scale
Range: Function:
200* [200 – 18000]
Display value:
(
par
. 19 − 26 −
Scales winder speed for 100,000 counts at max speed. These counts can be read in par. 19-95.
max. Winder encoder
50
)
Hz
× 4
19-27 Diameter Accel Rate
Range: Function:
1* [1 – 50] Sets amount of changes allowed for the diameter in each program scan. Thi s setting depends on
maximum material thickness and max line speed at core. The diameter change is scaled based on
100,000 = 100%.
Description of display value (calculation example):
Max. core speed
Material thickness = 0.01 inches
Roll diameter = 25 inches
Scan time = 25 ms
Counts
= (10
Scan
Max. counts
scan
= 10
= 10
rev
)(
s
0.01
rev
s
rev
inch
100000
)(
25
counts
inches
)(
25
scan
ms
)
NB!
If the diameter can vary from the selected reset value, a larger value will allow the calculator diameter to move more quickly to the correct value.
MG.33.T1.02 - VLT® is a registered Danfoss trademark
21
4
4 How to Install VLT® Center Winder MCO 352
19-28 Tapered Tension Accel Rate
Range: Function:
1* [1 – 10]
19-29 Diameter Calculator Minimum Speed
Range: Function:
500* [500 – 200000]
19-30 Line Acceleration Feed-Forward
Range: Function:
0* [ -20000 – 20000]
A value of 1 means a maximum taper tension set point change of 0.1 % of full scale is possible each program scan time.
Sets the amount the Taper and Tension Set-Points can vary each scan period. This function ramps the tapered tension set-point to the preset value when the user changes either the tension or taper set-points. This ensures stability during step changes in set-points.
100,000 = 100 % line speed
Sets minimum line speed to be achieved before the diameter calculator will be activated. At low line speeds, the resolution of the line and w inder speed will be too l ow to accurately calculate the d i­ameter.
The tension PID output is summed with the change per scan of line speed multiplied by this factor.
PID output
+
(
Line speed
)
×
1000
(
par
. 19 − 30
)
Helps compensate for tension changes caused by line speed acceleration and deceleration.
19-31 Velocity Sampling Time (ms)
Range: Function:
50* [50 – 500]
The speed values are averaged over the sampling time.
Sets sampling time for both line speed and winder speed.
19-40 Tension PID Limit
Range: Function:
0* [0 – 200000]
16,384 = 100 %
Sets maximum Tension PID loop output that can be added to the open lo op speed re ference. The value is normally set to limit the contribution of the tension PID loop to 10 % of the maximum reference speed.
19-41 PID Profiles
Range: Function:
0* [0 – 10000]
A value of 10,000 = fully profiled.
Allows scaling the tension loop PID output to compensate for roll diameter. Ideally, the output from the tension loop PID amplifier is halved each time the di ameter doubles, this is con sidered fully profiled. In some cases it might be desirable to be less than fully profiled which would give over compensation as the diameter increases.
22
MG.33.T1.02 - VLT® is a registered Danfoss trademark
VLT® Center Winder MCO 352 4 How to Install
4
19-42 PID Proportional Gain
Range: Function:
0* [0 – 5000] Sets proportional gain for tension loop PID amplifier.
19-43 PID Derivative Time
Range: Function:
0* [0 – 1000]
0 = OFF
Sets derivative time for tension loop PID amplifier.
19-44 PID Integral Time
Range: Function:
10* [10 – 20100]
>20000 = OFF
Sets Integral time for tension loop PID amplifier.
19-45 PID Integral Limit
Range: Function:
0* [0 – 100000] Sets limit for the integral part in the tension loop PID amplifier.
19-47 PID Der. Gain Limit
Range: Function:
1000* [1000 – 50000] Sets limit for derivation gain in tension loop PID amplifier.
19-48 PID Anti Wind-Up
Option: Function:
Activates Anti Wind-up in tension loop PID amplifier. [0] * Anti Wind-Up disabled [1] Anti Wind-Up enabled
19-49 Speed Loop Prop Min.
Range: Function:
0* [0 – 10000]
A value of 100 used in parameter 19-49 or 19-50 will be transl ated to 0.100 in parameter 7-02.
Speed Loop Prop Gain used at core diameter. The valu e used for the speed loop proportional gain
(Par. 7-02) is modified as the roll diameter changes. Parameters 19-49 and 19-50 are the minimum
and maximum values determined at core and full roll. They can be different for each material select
by parameter or digital input. As the diameter inc reases, the actual speed loop prop ga in will be
calculated and written to the associated parameter (7-02).
MG.33.T1.02 - VLT® is a registered Danfoss trademark
23
4
4 How to Install VLT® Center Winder MCO 352
19-50 Speed Loop Pro Max.
Range: Function:
0 [0 – 10000]
19-51 Save Speed Prop Values
Option: Function:
[0] * No function [1] Initiates saving Initiates the save. The value will return to 0 after the save has completed. This function can only
19-61 Over Under Winding
Option: Function:
[0] * Selects over winding [1] Selects under winding
A value of 100 used in parameter 19-49 or 19-50 wil l be translated to 0.100 in param eter 7-02.
Speed Loop Prop Gain used at full roll diameter. More information see parameter 19-49.
Allows saving speed proportional gain values and tension PID values in memory. The values should be saved after completing changes to parameters 19-41 – 19-50. The values are automatically stored when a different material is selected.
be used when tension if OFF.
Parameter 19-61 - 19-68 can replace the digital Inputs 1-8 when parameter 19-23 is programmed to 1. When this is the case the digital inputs are not used and their functions are transferred to parameter 19-61 through 19-68. These parameters act just the same as if they were the digital inputs with values of 0 and 1.
19-62 Winder Jog Reverse
Option: Function:
See Parameter 19-61. [0] * No function [1] Selects winder jog reverse
19-63 Winder Jog Forward
Option: Function:
See Parameter 19-61. [0] * No function [1] Selects winder jog forward
19-64 New Diameter Select
Option: Function:
See Parameter 19-61. [0] * No function [1] Preset diameter to programmed val-
ue in par. 19-04
Diameter is preset to the value programmed in parameter 19-04 when parameter 19-68 is changed
to 1.
19-65 Tension On/Off
Option: Function:
See Parameter 19-61. [0] * Turns tension off [1] Turns tension on
24
MG.33.T1.02 - VLT® is a registered Danfoss trademark
VLT® Center Winder MCO 352 4 How to Install
19-66 Material Select
Range: Function:
1* [1-9] See Parameter 19-61.
There is a possibility of 9 material types. Each material type has its own set of parameters 19-41 to 19-50. These parameters will display the stor ed values for the material number selected. Any changes to these parameter values are not saved permanently until the material type is changed to a new value while the tension is off.
19-67 Core Select
Option: Function:
See Parameter 19-61. The core select parameter is used in conjunction with the diameter reset. When a new roll is started,
it is important to reset the diameter to the proper core value. [0] * Setting 1 [1] Setting 2
19-68 Diameter Reset
Option: Function:
See Parameter 19-61.
1 resets the diameter to either core 1 or 2 or the partial diameter depending on parameters 19-64
and 19-67. Parameter 19-68 will be reset to a value of zero when tension is turned on. The ta ble
below shows what the diameter will be set to base on the state of parameters 19-64 and 19-67. [0] * Core 1 [1] Core 2
4
Par 19-64 Par 19-67 DIAMETER 0 0 Par 19-06 (Core 2) 0 1 Par 19-05 (Core 1) 1 0 Par 19-04 (Partial core) 1 1 Par 19-04 (Partial core)
4.4.1 Read-only Application Parameters
Parameters 19-92 to 19-99 are special read-only parameters. They can be monitored on LCP lines 1 to 3 as controlled by parameters 0-20 – 0-24. Looking at the values shown in parameters 19-92 –19-99 will not allow dy namic monitoring. Whe n setting parameters 0-20 – 0-24, the read-outs are selected as user parameter 19-92 – 19-99.
19-92 Winder Software Version
Option: Function:
This is a read only parameter indicating the Winder program software version.
19-93 Winder Error Status
Option: Function:
This parameter indicates the error status of the Winder Option. Several different conditions can be
detected.
NO ALARM [0] TENSION LIMIT DETECTED [1] FC ALARM [2] MCO305 ERROR [3] QSTOP [4] LOCAL MODE [5]
Turning the tension off resets all fault conditions while in remote mode.
MG.33.T1.02 - VLT® is a registered Danfoss trademark
25
4
4 How to Install VLT® Center Winder MCO 352
19-94 Program Loop Scan Time
Option: Function:
Read only parameter used to display the time[ms] per program loop scan.
19-95 Winder Speed Counts
Option: Function:
Read only parameter used to display the winder speed counts. 100000 counts = 100 % winder speed.
19-96 Line Speed Counts
Option: Function:
Read only parameter used to display the line speed counts. 100000 counts = 100 % line speed.
19-97 Diameter Size
Option: Function:
Read only parameter used to display the diameter of the roll. 100000 counts = 100 % diameter.
19-98 Tapered Tension Set-Point
Option: Function:
Read only parameter used to display the Tapered tension set point 1000 = 100.0% tension.
19-99 Tension Feedback
Option: Function:
Read-only parameter used to display the actual tension feedback. A reading of 1000 = 100.0 % of the 20 mA, or 10 V signal from the load cells or dancer.
26
MG.33.T1.02 - VLT® is a registered Danfoss trademark
VLT® Center Winder MCO 352 5 Center Winder Calibration
5 Center Winder Calibration
5.1.1 Frequency Converter Checkout
The VLT AutomationDrive frequency converter should be checked out before installing the Winder software.
1. Ensure proper wiring
2. Power-up the drive.
3. Perform an Automatic Motor Adaptation (AMA) after programming motor nameplate information (parameters 1-20 to 1-26). Inputs 27 and 37 should be turned ON. Use the [Hand On], [Off] and [Reset] keys for local mode control.
4. Determine max speed of winder (RPM) and program into parameter 3-03. Calculate the actual maximum winder speed at the smallest core and set par. 3-03 for 10 % higher than that value. This value cannot exceed 4,500 RPM.
5. Insure that the winder motor encoder is rated for the maximum RPM used. Enter the winder motor encoder resolution ( PPR) into parameter 32-01.
6. It is suggested that the ramp times be increased for initial testing. Set parameters 3-41 and 3-42 to a few seconds. These settings will be changed later.
7. Determine proper encoder wiring. Set the local reference = 100 RPM. Use the [Hand On] and [Off] keys for local mode control. Check that the motor runs stable at 100 RPM. If the drive indicates a Warning 12 Torq ue Limit or Alarm 61 Tracki ng error while attempting to run at low speed, the encoder is most likely wired backwards. Swap the A and A’ leads and test again. The direction the motor rotates is the f orward direction . This direction can be reversed by removing power and swapping two motor phases and swapping the A and A’ encoder leads.
8. Tune the speed loop PID: The VLT AutomationDrive will run in a Speed Closed-Loop Mode (par. 1-00). The speed loop PID values (par. 7-00 – 7-08) need to be set to allow stable operation at all speeds and loads. It is expected that the speed proportional gain will need to be increased at larger roll diameters. The goal of this te st is to determine an integr al value (par. 7-03) that works well under all conditions and fi nd the proportional gain values (par. 7-02) that work best at core and at full roll.
a. Running the motor in local mode is the simplest way to test changes in PID settings. Experienced MCO users may choose to use the APOSS
program Testrun function. If using the Testrun function, program for the encoder used return the drive to remote mode and reset the ramp times (par. 3-41 and 3-42) to 0.05 s. Turn the MCO BANDWIDTH to 0 and use the feed forward velocity factor only for each test-run. This will show turn off the closed-loop positioning controller and show the response and stability of the FC 300 drive speed PID control.
b. Begin running with an empty core. Adjust the parameters 7-02 and 7-03 for the best performance at low and high speeds. Use the local reference
to adjust the speed if not using Testrun. Note the proportional setting.
c. Now place a full roll on the winder. Adjust the parameters 7-02 and 7-03 for the best performa nce at low and high speed. Again note the
proportional setting. If any others settings were changed, repeat test with core only and this time only change proportional setting to the value that was used before at core.
d. Once the values for core and full roll are found, set them into the parameter 19-49 (core) and 19-50 (full roll). A value of 0.100 used in parameter
7-02 has to be set to 100 in parameter 19-49 or 19-50. The proportional gain values for the intermediate diameters are calculated internally in the Center Winder option program. Parameter 19 -49 = min. speed prop ga in (core prop) Parameter 19-50 = max. speed prop gain (full roll prop)
5
NB!
Note that there may be a need to modify these settings for different materials or roll widths. The Winder Option will allow unique speed Proportional values as well as the Tension PID values for each of up to nine materials.
NB!
Parameters 19-41 to 19-50 must be saved with parameter 19-51.
NB!
If parameter 19-96 is negative, encoder channels A and B have to be switched.
MG.33.T1.02 - VLT® is a registered Danfoss trademark
27
5
5 Center Winder Calibration VLT® Center Winder MCO 352
5.1.2 Preset Winder Function Parameters
NB!
The following procedure assum es that di gi tal inpu t cont ro l wi ll be used. If serial control will be used, issue logic commands by writing values to the appropriate parameter (19-61 – 19-68).
Par. Function Range Value to preset to
3-41 Ramp-up Time 1 0.01 – 3600.00 s 0.05 s 3-42 Ramp-down Time 1 0.01 – 3600.00 s 0.05 s 19-01 Winder Mode 0 – 1 Set according to application 19-02 Tension Set Point 0 – 1000 0 19-03 Taper Set Point -1100 – 1100 0 19-04 Partial roll diameter value 5000 – 100000 Calculate if used 19-05 Smallest core to be used 5000 – 100000 Calculate Calculate if used 19-06 Secondary core 5000 – 100000 5 19-07 Winder jog speed % 0 – 100 -200 19-08 TLD Low Limit -200 – 2000 2200 19-09 TLD High Limit 0 – 2200 200 19-10 TLD Out of Range Timer 1 – 200 19-11 TLD Timer Start Value -500 – 0 -200 19-12 Full Roll Detector -100 – 100000 100000 for rewind, 0 for unwind 19-13 Initial Diameter Measurement 0 – 1 Set based on application 19-14 Diameter Measurement Input 1 – 2 Set based on application 19-15 Reading at Core x 100 -1100 – 1100 Will Be Determined if used 19-16 Reading at Full Roll x 100 -1111 – 2111 Will Be Determined if used 19-19 Tension Setpoint Input 0 – 2 Set according to application 19-20 Taper Setpoint Input 0 – 2 Set acco rding to application 19-21 Tension Feedback Input 1 – 2 Set according to application 19-22 Tension Feedback Type 0 – 1 Set according to application 19-23 Discrete Functions Source 1 – 2 2 19-24 Line Speed 200 – 18000 Will Be Determined 19-25 Scale Speed 500 – 10000 Will Be Determined 19-26 Match Winder Speed 200 – 18000 Will Be Determined 19-27 Scale Diameter Change Rate 1 – 50 20 19-28 Tapered Tension Change Rate 1 – 10 2 19-29 Diameter Calculator Minimum Speed 500 – 200000 500 19-30 Acceleration Feed-Forward -20000 – 20000 0 19-31 Velocity Sampling Time (ms) 50 – 500 50 19-40 PID Limit 0 – 200000 0 19-41 PID Profiles 0 – 10000 19-42 PID Proportional Gain 0 – 5000 19-43 PID Derivative Time 0 – 1000 19-44 PID Integral Time 10 – 20100 19-45 PID Integral Limit 0 – 100000 19-47 PID Der. Gain Max 1000 – 50000 19-48 PID Anti Wind-Up 0 – 1 19-49 Speed Loop Prop Min. 0 – 10000 19-50 Speed Loop Prop Max. 0 – 10000 19-51 Save Values 0 – 1
28
MG.33.T1.02 - VLT® is a registered Danfoss trademark
VLT® Center Winder MCO 352 5 Center Winder Calibration
5.1.3 Winder Scaling Factor Calibration – Open loop Speed Adjustments
The procedure for setting the next three scaling parameters requires that the machine is able to run the line without material. If this is not possible, empirical calculations can be performed.
1. Set parameter 19-24 “Line Speed Scale”
Place the smallest empty core on the winder station.
Issue a Tension-ON command to the Winder. This will require an input at terminals 27, 37, and I5.
Run the line up to max speed.
Adjust Line Speed Scale parameter 19-24 so that Displayed Line Speed Counts displayed on the LCP indicates 100,000 counts.
If the values are negative, turn the line off, power-down the drive and re-wire the line spee d encoder A and A’ leads.
Re-test after changing encoder wiring.
Empirical calculation: The Line Speed Scaling factor can be calculated according to this formula
(
Par
. 19 24 =
The maximum pulse frequency (Hz) can be found if the encoder resolu tions in pulses-per-revolu tion (PPR) and maximum enc oder speed in RPM are known.
rpm
Hz
=
60
2. Set parameters 19-25 “Speed Match” & 19-26 “Winder Speed Scale”
Verify that the smallest core size (parameter 19-05) has been programmed correctly. The value entered is a percentage of the 100,000 full roll value. For example, if using a 20 inch full roll with a 3.75 inches core,
Par
Open Input 7 “CORE SELECT”
Open Input 4 “PARTIAL ROLL DIAMETER”
Momentarily close Input 8 “DIAMETER RESET” Confirm that the displayed Diameter is the value set in parameter 19-05.
•Close Input 5TENSION ON
Return to maximum line speed to again obtain 100,000 line speed encoder counts. The winder should begin running along with the line speed encoder.
Adjust parameter 19-25 “Speed Match” so that core surface speed matches the surface speed of the main line section.
Empirical calculation: Assuming that parameter 3-03 is set to 110 % of the maximum winder speed required at maximum line speed, this will result
in a 90 % reference signal to the Winder drive. The value 16384 (4000Hex) is a scaled value representing 100 % reference.
Max. Line encoder pulse frequency
ppr
×
. 19 05 =
3.75 20
50
× 100, 000 = 18, 750
)
× 4
5
Par
. 19 25 =
Remaining at maximum line speed, adjust parameter 19-26 “Winder Speed Scale” so that Winder Speed reads from the LCP reads 100,000 counts.
Empirical calculation: The winder encoder pulse frequency will need to be calculated for operation at maximum line speed on the smallest core.
Par
. 19 26 =
Turn line off so line encoder is zero.
Open Input 5 “TENSION OFF”.
Enable the diameter calculator by reducing the setting of parameter 19-29 to 500.
Close Input 5 “TENSION ON” and re-start the line. If the scaling parameters are set correctly, the diameter should remain very close to the core diameter value.
Stop the line and open Input 5 “TENSION OFF”.
16384 × 0, 9 ×
(
max. winder encoder pulse frequency
100, 000
par
. 19 − 05
50
)
× 4
MG.33.T1.02 - VLT® is a registered Danfoss trademark
29
5
5 Center Winder Calibration VLT® Center Winder MCO 352
5.1.4 Check Inputs
1. Check Input 3 “Winder Jog Forward”:
Close Input 3. The winder should jog in the forward (over) direction.
Open Input 3.
The jog speed can be adjusted in parameter 19-07.
2. Check Input 2 “Winder Jog Reverse”:
Close Input 2. The winder should jog in the reverse (under) direction.
Open Input 2 “Jog Reverse”.
The jog speed can be adjusted in parameter 19-07.
3. Check Input 1 “Over/Unde r Wind”:
•Close Input 1Over /Under Wind.
Close Input 3 winder should jog in the under direction.
Open Input 3 “Jog Forward”.
Open Input 1 “Over /Under Wind”.
5.1.5 Calibration of Diameter Measurement Signal
1. Parameter 19-13 should be set to 1 to enable this feature.
2. Mount the smallest core used on the winder.
3. Set the LCP to display the signal at the analog input selected in parameter 19-14.
4. Close Input 4 “Partial Roll Diameter”.
5. Close Input 8 “Diameter Reset”.
6. Record the voltage or current input value resulting from core diameter.
7. Multiply the value by 100 and enter into parameter 19-15.
8. Set the LCP to dis play Diameter.
9. Mount a full roll or simulate a full-roll.
10. Increase the value of parameter 19-15 until the displayed Diameter is as close to 100,000 as possible.
11. The displayed Diameter should now sweep from the core diameter to the full-roll di ameter (100,000) as the analog input moves through its full range.
12. Open Inputs 4 and 8 unless the Diameter will always be initially measured.
30
MG.33.T1.02 - VLT® is a registered Danfoss trademark
VLT® Center Winder MCO 352 5 Center Winder Calibration
5.1.6 Check Tension Correction Direction
1. Make sure that the taper and tension set points are set to zero. With no web, the tension should be at zero as well.
2. Close Input 5 “Tension ON”
3. Increase PID limit parameter 19-40 to 5000.
4. The Winder should not be moving since Tension PID values are set to zero.
5. Run the line at some slow speed, the Winder should follow at slow speed.
6. Increase Proportional Gain parameter 19-42 to 50.
7. Increase the Tension Set Point 20% through the input means selected in parameter 19-19.
8. If rewinding, the Winder should increase in speed. If the station is used as an unwinder, the speed should decrease. If there is no change in speed, increase par 19-42 until a speed change is noticeable.
9. Applied load to load cells or dancer to indic ate a tension feedback over 20 % (200). The Wi nder should decrease in speed if rewinding an d increase in speed if unwinding.
10. Stop the line.
11. Open Input 5 “Tension off”
5.1.7 Winder Closed Loop Calibration
5
1. Web up the machine.
2. Verify the starting diameter:
- If rewinding with an empty core, the value set in parameter 19-05 should be the starting diameter. Open Input 4 “Partial Core” and Input 7 “Core Select.”
- If starting with a partial roll or if unwinding, the diameter value should be measured and the percentage of 100,000 calculated. This value should be entered into parameter 19-04. Close Input I4.
- Reset the diameter with Input I8. (If using the initial diameter measurement function, no special action is required.)
3. Close Input 5 “Tension ON”.
4. Set the Tension Set Poi nt to a proper tensi on for the material be ing used. If using a d ancer, set the tensi on set point to 500, which represents the mid-point dancer position.
5. Increase tension proportional gain parameter 19-42 unti l the winder starts to develop tension. Continue to increase un til the displayed Tapered Tension Set Point matches the LCP displ ayed Tension Feedback. Note proportional gain value. Continue to increase u ntil winder becomes unstable when a tension disturbance is introduced by pushing on the web. Note this value and set the proportional gain between these two values.
6. Slowly increase line speed to about 10 % of max. Adjust the integral time parameter 19-44 until tension is stable.
7. Slowly increase line speed to max speed. Fine-tune parameters 19-43 – 19-47 for stable tension.
8. Adjust par 19-30 “Acceleration Feed-Forward” so that tension remains stable during acceleration or deceleration. This adjustment should be optimized when line ramps are set to minimum values required.
9. Check that the displayed Diameter is changing with the roll diameter.
10. If the Tension Limit Detection (TLD) is to be used, determine appropriate settings for parameters 19-08 to 19-11.
11. Determine desired setting for parameter 19-12, End-of-roll output.
12. Ensure tuning is appropriate from core to full roll. If tension regulation changes with roll diameter, adjust the PID profiler parameter 19-41. A higher setting will result in a reduction of PID ou t put at larger roll diameters.
13. If various materials are run on the winder, repea t steps 5 through 9 with all addition al material types or widths. Input 6 is provided to allow switching between two different material types or nine material types if using parameter 19-66.
MG.33.T1.02 - VLT® is a registered Danfoss trademark
31
6
6 Troubleshooting VLT® Center Winder MCO 352
32
MG.33.T1.02 - VLT® is a registered Danfoss trademark
VLT® Center Winder MCO 352 6 Troubleshooting
6 Troubleshooting
Parameter 19-93 indicates the error status of the Center Winder Controller. Several different conditions can be detected.
NO ALARM [0] TENSION LIMIT DETECTED [1] FC ALARM [2] MCO305 ERROR [3] QSTOP [4] LOCAL MODE [5]
Table 6.1: Center winder error, par. 19-93
Turning the tension off resets all fault conditions while in remote mode. All messages are shown in the LCP display of the FC 300 in short and in the APOSS software in plain text.
You can find brief information on the error messages in the table or detailed information in the following section.
6
The tables contain the messages in numerical order. Letters following a % sign represent variables which can be used in plain text at the corresponding locations
Error no Error Text Description
103 Illegal axis num. Axes not in system 105 Error not reset Error not cleared 106 Home not done Failed to move to HOME position 107 Home vel. zero Home was executed with Home Velocity set to zero 108 Position error Position error 109 Index not found Index pulse (encoder) not found 110 Unknown cmm. Unknow command 111 SW end limit Software end limit activated 112 Unknown param. Illegal parameter number 113 FC not enabled FC 300 is not ready but the PID controller is active 114 Too many loops Too many nested loops 115 Par. save failed Parameter save failed 116 Param. memory Parameters in memory are corrupted 117 Progr. memory Programs in memory are corrupted 118 Reset by CPU Reset by CPU 119 User abort User abort 125 HW end limit HQ end limit activated 149 Too many inter. Too many interrupt functions 150 No ext. 24V External supply is missing 151 Too many gosub Too many nested GOSUB commands 152 Too many return Too many RETURN commands 154 D. out overload Digital Output overloaded 155 LINK failed LINKGPAR command failed 162 Memory error Error in veryfying; EEPROM: address % defect 170 Array size (DIM) Error in DIM command 171 Array too small Attempt was made to cross array bounds 179 Waitndx timeout Timeout while waiting for index 184 Too many ontime Too many time interrupts 187 Out of memory No more room for variables 190 Memory locked The program memory is write-protected 191 Illegal cam array Curve array wrong 192 Encoder error Encoder error 199 Internal MCO fault Internal MCO fault
MG.33.T1.02 - VLT® is a registered Danfoss trademark
33
7
7 Appendix VLT® Center Winder MCO 352
34
MG.33.T1.02 - VLT® is a registered Danfoss trademark
VLT® Center Winder MCO 352 7 Appendix
7 Appendix
7.1.1 Center Winder Settings
Par. No. Parameter Description Default Value Changes Dur­Basic Winder Settings
19-01 19-02 Tension Set-Point 0 TRUE - - ­19-03 Taper Set-Point 0 TRUE - - ­19-04 Partial Roll Diameter Value 5000 TRUE - - ­19-05 Smallest Core Used 5000 TRUE - - ­19-06 Secondary Core 5000 TRUE - - ­19-07 Winder Jog Speed 0 TRUE - - ­19-08 TLD Low Limit 0 TRUE - - ­19-09 TLD High Limit 0 TRUE - - ­19-10 TLD Out of Range Timer 1 TRUE - - ­19-11 TLD Timer Start Value 0 TRUE - - ­19-12 End of Roll Detector 0 TRUE - - ­19-13 Initial Diameter Measurement [0] Set diameter when
19-14 Diameter Measurement Input [1] Input 53 TRUE - - ­19-15 Reading at Core 0 TRUE - - ­19-16 Reading at Full Roll 0 TRUE - - ­19-19 Tension Set-Point Input [0] Par. 19-02 TRUE - - ­19-20 Taper Set-Point Input [0] Par. 19-03 TRUE - - ­19-21 Tension Feedback Input [1] Input 53 TRUE - - ­19-22 Tension Feedback Type [0] Load cell TRUE - - ­19-23 Discrete Functions Source [1] Par. 19-61 to 19-68 TRUE - - ­19-24 Line Speed Scale 200 TRUE - - ­19-25 Speed Match Scale 500 TRUE - - ­19-26 Winder Speed Scale 200 TRUE - - ­19-27 Diameter Change Rate 1 TRUE - - ­19-28 Tapered Tension Change Rate 1 TRUE - - ­19-29 Diameter Calculator Minimum Speed 500 TRUE - - ­19-30 Line Acceleration Feed-Forward 0 TRUE - - ­19-31 Tension PID Settings 19-40 19-41 PID Effect Verses Diameter 0 TRUE - - ­19-42 PID Proportional Gain 0 TRUE - - ­19-43 PID Derivative Time 0 TRUE - - ­19-44 PID Integral Time 10 TRUE - - ­19-45 PID Integral Limit 0 TRUE - - ­19-47 PID Der. Gain Limit 1000 TRUE - - ­19-48 PID Anti Wind-up [0] Anti Wind-up disa-
19-49 Speed Loop Prop Min. 0 TRUE - - ­19-50 Speed Loop Prop Max. 0 TRUE - - ­19-51 19-6* Command Parameters 19-61 19-62 Winder Jog Reverse [0] No Function TRUE 19-63 Winder Jog Forward [0] No Function TRUE 19-64 New Diameter Select [0] No Function TRUE 19-65 Tension On/Off [0] Turns tension off TRUE 19-66 Mat Select 1 TRUE 19-67 Core Select [0] Core 1 TRUE 19-68 Diameter Reset [0] Core 1 TRUE 19-9* Read Only Application Parameters 19-92 Winder Software Version - read only No 0 Int32 19-93 Winder Error Status - read only No 0 Int32 19-94 Program Loop Scan Time - read only No 0 Int32 19-95 Winder Speed Counts - read only No 0 Int32 19-96 Line Speed Counts - read only No 0 Int32 19-97 Diameter Size - read only No 0 Int32 19-98 Tapered Tension Set-Point - read only No 0 Int32 19-99 Tension Feedback - read only No 0 Int32
Winder Mode Selection [0] Rewinder TRUE - - -
diameter reset
Velocity Sampling Time (ms) 50 TRUE - - -
Tension PID Maximum Contribution 0 TRUE - - -
bled
Save Speed Prop Values [0] No Function TRUE - - -
Over Under Winding [0] Over Winding TRUE
ing Operation
TRUE - - -
TRUE - - -
4 set-up Conversion
Index
Type
7
MG.33.T1.02 - VLT® is a registered Danfoss trademark
35
7 Appendix VLT® Center Winder MCO 352
7.1.2 MCO Basic Settings
7
Par. No. Pa rameter Description Default Value Changes Dur­32-0* Encoder 2 - Slave
32-00 32-01 Incremental Resolution 1024 PPR TRUE 1set-up Uint32 32-02 Absolute Protocol [0] None TRUE 1set-up Uint8 32-03 Absolute Resolution 8192 PPR TRUE 1set-up Uint32 32-05 Absolute Encoder Data Length 25 Bit TRUE 1set-up Uint8 32-06 Absolute Encoder Clock Frequency 262.000 kHz TRUE 1set-up Uint32 32-07 Absolute Encoder Clock Generation [1] On TRUE 1set-up Uint8 32-08 Absolute Encoder Cable Length 0 TRUE 1set-up Uint16 32-09 Encoder Monitoring [0] Off TRUE 1set-up Uint8 32-10 Rotational Direction [1] No action TRUE 1set-up Uint8 32-11 User Unit Denominator 1 TRUE 1set-up Uint32 32-12 User Unit Numerator 1 TRUE 1set-up Uint32 32-3* Encoder 1 - Master 32-30 Incremental Signal Type [1] RS42 2 TRUE 1set-up Uint8 32-31 Incremental Resolution 1024 PPR TRUE 1set-up Uint32 32-32 Absolute Protocol [0] None TRUE 1set-up Uint8 32-33 Absolute Resolution 8192 PPR TRUE 1set-up Uint32 32-35 Absolute Encoder Data Length 25 Bit TRUE 1set-up Uint8 32-36 Absolute Encoder Clock Frequency 262.000 kHz TRUE 1set-up Uint32 32-37 Absolute Encoder Clock Generation [1] On TRUE 1set-up Uint8 32-38 Absolute Encoder Cable Length 0 TRUE 1set-up Uint16 32-39 Encoder Monitoring [0] Off TRUE 1set-up Uint8 32-40 32-5* Feedback Source 32-50 32-6* PID Controller 32-60 32-61 Derivative Value for PID Control 0 TRUE 1-setup 0 Uint32 32-62 Integral Factor 0 TRUE 1-setup 0 Uint32 32-63 Limit Value for Integral Sum 1000 TRUE 1-setup 0 Uint16 32-64 PID Bandwidth 1000 TRUE 1-setup 0 Uint16 32-65 Velocity Feed-forward 0 TRUE 1-setup 0 Uint32 32-66 Acceleration Feed-forward 0% TRUE 1-setup 0 Uint32 32-67 Maximum Tolerated Position Error 20000 qc TRUE 1-setup Uint32 32-68 Reverse Behavior for Slave [0] Reversing TRUE 1-setup Uint8 32-69 Sampling Time for PID Control 1 ms TRUE 1-setup Uint16 32-70 Scan Time for Profile Generator [1] 1 ms TRUE 1-setup Uint8 32-71 Size of the Control Window (Activation) 0 qc TRUE 1-setup Uint32 32-72 32-8* Velocity & Acceleration 32-80 32-81 Shortest Ramp 1000 ms TRUE All set-ups Uint32 32-82 Ramp Type 0 TRUE All set-ups Uint8 32-83 Velocity Resolution 100 TRUE All set-ups Uint16 32-84 Default Velocity 50 TRUE All set-ups Uint16 32-85 Default Acceleration 50 TRUE All set-ups Uint16
Encoder Type [1] RS422 TRUE 1set-up Uint8
Encoder Termination [1] On TRUE 1set-up Uint8
Source Slave [2] Enc2 TRUE 1-setup
Proportional Factor 30 TRUE 1-setup 0 Uint32
Size of the Control Window (Deactivation) 0 qc TRUE 1-setup Uint32
Maximum Velocity (Encoder) 1500 RPM TRUE All set-ups Uint32
ing Operation
4 set-up Conversion In-
dex
Type
36
MG.33.T1.02 - VLT® is a registered Danfoss trademark
VLT® Center Winder MCO 352 Index
Index
A
Abbreviations 4 Acceleration Feed-forward 8, 22, 28, 31, 35 Additional Features 8 Analog Inputs 16, 20 Analog Inputs 8, 16 Analog Output 16 Application Parameters 25 Approvals 3 Approvals 3
B
Basic Winder Settings 35 Block Diagram 7, 8
C
Calibratio 9 Calibration 3, 29, 30, 31 Check Inputs 30 Check Tension Correction Direction 31 Commencing Repair Work 5
D
Dancer Feedback 7, 9 Diameter Calculato r 29 Diameter Calculato r 8, 22, 28, 35 Diameter Measurement Si gn al 8 Diameter Measurement Si gn al 30 Digital Inputs 9, 21 Digital Inputs 24 Digital Inputs 9 Digital Output 19 Digital Outputs 9
E
End Of Roll Detection 8
F
Frequency Converter Chec kout 27
G
General Warning 6 General Warnings 3
H
High Voltage Warning 5 How To Read 3
I
Initial Diameter Measurement 8, 31 Initial Diameter Measurement 16 Initial Diameter Measurement 20, 28, 35
L
Limiter 8 Literature 3 Literature 3
MG.33.T1.02 - VLT® is a registered Danfoss trademark
37
Index VLT® Center Winder MCO 352
M
Mco Basic Settings 36 Minimum Speed 8, 22, 28, 35
O
Open Loop Speed Adjustments 29
P
Preset Winder Function Parameters 28
R
Relay Output 15
S
Safe Stop Of Vlt Automationdrive Fc302 6 Safety Instructions 3, 5 Symbols 3 Symbols 3 System Requirements 9
T
Tension And Taper Set-points 8 Tension And Taper Set-points 9 Tension Limit Detector 8, 15, 18, 19 Tension-taper Set-point Ramp 8 Terminals 3, 5, 29
U
Unintended Start 5
V
Vlt Automationdrive Terminals 11
W
Winder Closed Loop 31 Winder Scaling Factor 29
38
MG.33.T1.02 - VLT® is a registered Danfoss trademark
Loading...