Danfoss VLT Brook Crompton Motor FCM 300 Design Manual

MAKING MODERN LIVING POSSIBLE
Design Guide
VLT® Brook Crompton Motor FCM 300
www.danfoss.com/drives
Contents
Contents
VLT® DriveMotor FCM Series
1 Introduction
1.1.1 Software Version 4
1.1.5 Safety Regulations 5
1.1.6 Warning against Unintended Start 5
1.3.1 Integration of Frequency Converter and Motor 6
1.4.1 Ordering Form 7
1.4.2 Product Range 8
1.4.3 Ordering 9
1.4.4 PC Software Tools 9
1.4.5 Ordering info for Frames and Flanges 10
1.4.6 Ordering Info for Inverter Box Position and Drain Hole Position 10
2 Installation
2.1.1 FCM 305-375 for 3 Phases, 380-480 V 11
2.1.2 General Technical Data 12
2.1.3 Tightening Torques 15
2.1.4 Maximum Cable Cross Section 15
2.1.5 Screw Sizes 16
11
2.1.6 Protection 16
2.2 Description of the Motor
2.2.1 Handling the FC Motor 18
2.2.2 Bearings 18
2.2.3 Output shafts 19
2.2.4 Dimensions 19
2.2.5 Installation of the FC Motor 21
2.2.6 Alignment 22
2.2.7 Bolt Torques 22
2.2.8 Maintenance 22
2.2.9 FCM 300 Thermal Protection 23
2.3.1 Service Plug Kit (175N2546) 23
2.3.2 Plug Kit (175N2545) 25
2.3.3 Remote Mounting Kit (175N0160) 25
2.3.5 Potentiometer Option (177N0011) 26
2.3.6 Local Operation Pad (LOP) (175N0128) IP65 26
3 Programming
17
28
3.1.1 Control Panel (175NO131) 28
3.1.2 LCP Installation 28
3.1.3 LCP Functions 28
3.1.4 Display 28
MG03BA02 - VLT® is a registered Danfoss trademark 1
Contents
VLT® DriveMotor FCM Series
3.1.5 LEDs 29
3.1.6 Control Keys 29
3.1.7 Control Key Functions 29
3.1.8 Display Read-out State 30
3.1.9 Display Mode 30
3.1.10 Display Mode - Selection of Read-out State 30
3.1.11 Quick Menu Mode Versus Menu Mode 31
3.1.12 Quick Setup via Quick Menu 32
3.1.13 Parameter Selection 32
3.1.14 Menu Mode 32
3.1.15 Parameter Groups 32
3.1.16 Changing Data 33
3.1.17 Changing a Text Value 33
3.1.18 Infinitely Variable Change of Numeric Data Value 33
3.1.19 Menu Structure 34
3.1.20 Parameter Group 0-** Operation/Display 36
3.2.1 Parameter Group 1-** Load/Motor 40
3.6.1 Serial Bus 60
3.6.2 Telegram Communication 60
3.6.3 Telegram Build-up 61
3.6.4 Databytes 61
3.6.5 Control Word According to Fieldbus Profile Standard 63
3.7.1 Parameter Group 5-** Serial Communication 69
3.8.1 Parameter Group 6-** Technical Functions 74
4 All about FCM 300
4.1.1 Galvanic Isolation (PELV) 77
4.1.2 Earth Leakage Current 77
4.1.3 Extreme Running Conditions 78
4.1.4 Acoustic Noise 78
4.1.5 Balance 78
4.1.6 Thermal Protection and Derating 78
4.1.7 Derating for Ambient Temperature 79
77
4.1.8 Derating for Air Pressure 79
4.1.9 Derating for Running at Low Speed 79
4.1.10 Derating for High Switching Frequency 79
4.1.11 Vibration and Shock 80
4.1.12 Air Humidity 80
4.1.13 UL Standard 80
4.1.14 Efficiency 80
4.1.15 Mains Supply Interference/Harmonics 81
2 MG03BA02 - VLT® is a registered Danfoss trademark
Contents
VLT® DriveMotor FCM Series
4.1.16 Power Factor 82
4.1.17 What is CE Labelling? 82
4.1.18 The Machinery Directive (98/37/EEC) 82
4.1.19 The Low-voltage Directive (73/23/EEC) 82
4.1.20 The EMC Directive (89/336/EEC) 82
4.1.21 What is Covered? 82
4.1.22 Danfoss FCM 300 Series Motor and CE Labelling 83
4.1.23 Compliance with EMC Directive 89/336/EEC 83
4.1.24 EMC Standards 83
4.1.25 Aggressive Environments 84
4.2.1 List of Warnings and Alarms 84
4.2.2 What if the Motor does not Start? 85
4.2.3 Warnings 86
4.2.4 Warning Word, Extended Status Word and Alarm Word 88
4.3 List of Parameters
Index
89
95
MG03BA02 - VLT® is a registered Danfoss trademark 3
Introduction
VLT® DriveMotor FCM Series
1
1 Introduction
1.1 Safety
1.1.1 Software Version
FCM 300 Series
Design Guide
Software version: 3.1x
This Design Guide can be used for all FCM 300 Series frequency converters with software version 3.1x. The software version number can be seen from parameter 624 Software version no.
Table 1.1
Disposal Instruction
1.1.2
Equipment containing electrical components may not be disposed of together with domestic waste. It must be separately collected with electrical and electronic waste according to local and currently valid legislation.
Table 1.2
1.1.4 General warnings
NOTICE
All operations must be carried out by appropriately trained personnel. Use all lifting facilities provided e.g. both lifting points if fitted or single lifting point if fitted*. Vertical lifting - Prevent uncontrolled rotation. Lift machine - Do not lift other equipment with motor lifting points only. Before installation check for fan cover damage, shaft damage, foot/mounting damage, and loose fasteners. Check nameplate details. Ensure level mounting surface, balanced mounting, not misaligned. Gaskets, and/or sealants, and guards must be correctly fitted. Correct belt tension.
Please observe derating rules, see 4.1 Special Conditions.
*Note: maximum hand lift is 20 kg below shoulder, but above ground level. Max. gross weights:
Frame size 80: 15 kg
-
Frame size 90 & 100: 30 kg
-
Frame size 112: 45 kg
-
Frame size 132: 80 kg
-
Symbols
1.1.3
The following symbols are used in this Design Guide and require special attention.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
NOTICE
Indicates highlighted information that should be regarded with attention to avoid mistakes or operate equipment at less than optimal performance.
WARNING
The voltage on the FC motor is dangerous when the motor is connected to mains. Incorrect installation of the FC motor may lead to material damage or serious injury, or it may be fatal. Consequently, the instructions in this manual as well as national and local rules and safety regulations must be complied with. Touching the electrical parts may be fatal, even after the mains supply has been disconnected. Wait at least 4 minutes.
- Installation must be fused and isolated correctly.
- Covers and cable entries must be fitted.
WARNING
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
4 MG03BA02 - VLT® is a registered Danfoss trademark
By altitudes above 2 km, please contact Danfoss Drives regarding PELV.
175NA161.10
Promotion
All
users
X = version number YY = language
Misc.
Quick Setup
MG.03.FX.YY
Design
Guide
MG03BXYY
PROFIBUS-
Manual
MG.03.EX.YY
Brochure
MB.03.CX.YY
Articles
MZ.03.AX.YY
MCT 10 Setup
Software Manual
MG10RXYY
Data sheet
MD.03.AX.YY
Introduction
VLT® DriveMotor FCM Series
NOTICE
It is the user's or certified electrician's responsibility to ensure correct earthing and protection in accordance with applicable national and local requirements and standards.
1.1.5 Safety Regulations
The VLT DriveMotor (FC motor) must be discon-
nected from mains if repair work is to be carried out. Check that the mains supply has been discon­nected and that the necessary time has passed (4 minutes).
Correct protective earthing of the equipment
must be established, the user must be protected against supply voltage, and the motor must be protected against overload in accordance with applicable national and local regulations. Use of RCD's (ELCB relays) is described in 4.1.2 Earth Leakage Current .
The earth leakage currents are higher than 3.5
mA. This means that the FC motor requires a fixed, permanent installation as well as reinforced protective earthing.
If personal safety considerations make it necessary to ensure that no unintended start occurs, these stop functions are not sufficient.
While parameters are being changed, the motor
may start. A motor that has been stopped may start if faults
occur in the electronics of the FC motor, or if a temporary overload or a fault in the mains supply ceases.
1.2 Introduction
Specific technical publications on the FCM 300 series:
Design Guide:
Quick Setup:
Table 1.3
Gives all required information for design purposes, and gives a good insight into the product concept, product range, technical data, control, programming, etc.
Helps the users to quickly get their FCM 300 Series motor unit installed and running. The Quick Setup is always delivered with the unit.
1
1
Warning against Unintended Start
1.1.6
The motor can be brought to a stop by means of
digital commands, bus commands, or references, while the frequency converter is connected to mains.
Illustration 1.1 Available literature for FCM 300 Series
For further information on the FCM 300 Series, contact the local Danfoss supplier.
MG03BA02 - VLT® is a registered Danfoss trademark 5
Proc.
Fieldbus
Danfoss MCT 10 setup Software
PLC
Proc.
175NA009.13
1
Introduction
1.3 Product Concept
VLT® DriveMotor FCM Series
1.3.1 Integration of Frequency Converter and Motor
The Danfoss VLT frequency converter integrated onto the asynchronous motor gives infinite speed control in one unit.
The VLT DriveMotor FCM 300 Series is a very compact alternative to the ordinary solution with VLT frequency converter and motor as separate units. The frequency converter is attached instead of the motor terminal box, and it is no higher than the standard terminal box, nor wider or longer than the motor (see 2.2.4 Dimensions ).
Installation is extremely easy. Panel space is not a problem. There is no need for special details on wiring to meet the EMC directive, since motor cables are not necessary. The only connections are mains and control connections.
Factory-set adaption between frequency converter and motor gives precise and energy efficient control in addition to eliminating pre-setting on site.
The FC motor can be used in stand alone Systems with traditional control signals, such as start/stop signals, speed references and closed loop process control or in multiple drive Systems with control signals distributed by a field bus.
Combination of fieldbus and traditional control signals and closed loop PID control is possible.
Illustration 1.2 Control Structures
6 MG03BA02 - VLT® is a registered Danfoss trademark
175NA121.14
B2
BC
Inverter position
Motor drain hole position
D
0
1
2
3
Introduction
VLT® DriveMotor FCM Series
1.4 Selection of FC motor, FCM 300
1.4.1 Ordering Form
1
1
Illustration 1.3
MG03BA02 - VLT® is a registered Danfoss trademark 7
Introduction
VLT® DriveMotor FCM Series
1
1.4.2 Product Range
VLT DriveMotor FCM 300 Series, 2/4 poled motors
Type Motor output Mains supply
FCM 305 0.55 kW FCM 307 0.75 kW FCM 311 1.1 kW FCM 315 1.5 kW FCM 322 2.2 kW FCM 330 3.0 kW FCM 340 4.0 kW FCM 355 5.5 kW FCM 375 7.5 kW
Table 1.4 Power Size
Each type in the product range is available in different versions:
Inverter versions
Power size: (See Table 1.4)
Application
P: Process
S: Sensorless (special pump OEM)
Mains voltage:
T4: 380-480 V three phase supply
Enclosure
C55: IP55
C66: IP66
Hardware variant:
ST: Standard
RFI filter
R1: Compliance with class 1A
R2: Compliance with class 1B
Display connector
3 phase 380-480 V
Number of poles
2: 2 pole motor
4: 4 pole motor
Motor data
B2: IE2 high efficiency motor
BC: IE2 high efficiency motor/cast iron
Motor mounting option
B03: Foot mounting
B05: B5 flange
B14: B14 face
B34: Foot and B14 face
B35: Foot and B5 flange
Motor flange code (Regarding standard flange size and available flange sizes, see 1.4.5 Ordering info for Frames and Flanges).
000: Foot mounting only
085: 85 mm
100: 100 mm
115: 115 mm
130: 130 mm
165: 165 mm
215: 215 mm
265: 265 mm
300: 300 mm
Motor cooling method
1: Shaft mounted fan
Inverter position
D: Standard on top
Motor drain hole position (see 1.4.6 Ordering Info for Inverter Box Position and Drain Hole Position)
0: No drain hole
1: Opposite inverter box both ends (drive/non
drive) 2: 90° inverter box right
3: 90° inverter box left
D0: No display plug able connector
Fieldbus
F00: No fieldbus
F10: Profibus DPV1 3 MB
F12: Profibus DPV1 12 MB
Motor thermistor
X: No motor thermistor
8 MG03BA02 - VLT® is a registered Danfoss trademark
175NA162.10
Introduction
1.4.3 Ordering
VLT® DriveMotor FCM Series
1.4.4
PC Software Tools
1
1
Take a copy of the ordering form, see 1.4.1 Ordering Form. Fill in and post or fax your order to the nearest branch office of the Danfoss sales organisation. On the basis of your order, the FCM 300 Series motor is given a type code.
The ordering form for the basic unit must always be completed. When the type code is written, always state the characters of the basic string (1-34). Together with the order confirmation the customer receives an 8-figure code number to be used when reordering.
Danfoss PC software for serial communication, MCT 10 All FCM 300 Series units have an RS 485 port as standard, which enables them to communicate e.g. with a PC. A programme entitled MCT 10 is available for this purpose (see 1.4.4 PC Software Tools ).
Ordering numbers, MCT 10 Use code number 130B1000 for ordering the CD containing MCT 10 Set-up Software.
Accessories for the FC motor A Local Operation Pad (LOP) for local set point and start/ stop is available for the FC motor. The LOP is IP 65 enclosed. A Local Control Panel (LCP 2) which makes up a complete interface for operation, programming and monitoring of the FC motor is also available.
PC Software - MCT 10
All frequency converters are equipped with a serial communication port. Danfoss provides a PC tool for communication between PC and frequency converter, VLT Motion Control Tool MCT 10 Set-up Software.
MCT 10 Set-up Software
MCT 10 has been designed as an easy to use interactive tool for setting parameters in our frequency converters. The MCT 10 Set-up Software will be useful for:
Planning a communication network off-line. MCT
10 contains a complete frequency converter database
Commissioning frequency converters on line
Saving settings for all frequency converters
Replacing a drive in a network
Expanding an existing network
Future developed drives will be supported
The MCT 10 Set-up Software Modules
The following modules are included in the software package:
Ordering numbers, accessories
Local Operation Pad incl. cable (LOP) Local Control Panel (LCP 2) 175N0131 Remote mounting kit (LCP 2) 175N0160 Plug kit (LCP 2) 175N2545 Cable for plug kit (LCP 2) 175N0162 Cable (direct mounting) (LCP 2) 175N0165 Service plug kit (LCP 2) 175N2546 Potentiometer option 177N0011
Table 1.5
175N0128
Illustration 1.4
MG03BA02 - VLT® is a registered Danfoss trademark 9
ISA
ISA
2
3
1
ISA ISA
1
ISA
1
175NA125.11
Introduction
VLT® DriveMotor FCM Series
1
1.4.5 Ordering info for Frames and Flanges
Frame sizes and the corresponding flange sizes for different mounting versions
Type
FCM 305 80
FCM 307 80
FCM 311 90
FCM 315 90
FCM 322 100
FCM 330 100
FCM 340 112
FCM 355 132
FCM 375 132
S: Available as standard shaft A: Available as an alternative with specially elongated shaft to provide standard shaft for frame B: Available as an alternative with standard shaft for frame, requiring no modification
Motor frame size
4 pole
Mounting version
B5/B35 165 115/130 B14/B34 100 75/85/115/130 B5/B35 165 115/130 B14/B34 100 75/85/115/130 B5/B35 165 110/115/130 215 B14/B34 115 85/100/130/165 B5/B35 165 110/115/130 215 B14/B34 115 85/100/130/165 B5/B35 215 165 B14/B34 130 165 85/100/115 B5/B35 215 165 B14/B34 130 165 85/100/115 B5/B35 215 165 B14/B34 130 165 85/100/115 B5/B35 265 215 B14/B34 165 215 B5/B35 265 215 B14/B34 165 215
Flange size, standard
(S) [mm]
alternatives (A) [mm]
Flange size,
Flange size,
alternatives (B) [mm]
Table 1.6
Ordering Info for Inverter Box Position and Drain Hole Position
1.4.6
Inverter box position, always top mounted. All drain holes are mounted with screw and washer, IP 66 if not opened.
1: Drain holes opposite inverter side, both drive end and non drive end. 2/3: Drain holes 90° to inverter, both drive end and non drive end.
Illustration 1.5
10 MG03BA02 - VLT® is a registered Danfoss trademark
Installation
VLT® DriveMotor FCM Series
2 Installation
2.1 Technical Data
2.1.1 FCM 305-375 for 3 Phases, 380-480 V
2 2
FCM Motor output [HP] 0.75 1.0 1.5 2.0 3.0 4.0 5.0 7.5 10.0 [kW] 0.55 0.75 1.1 1.5 2.2 3.0 4.0 5.5 7.5 Motor torque 2 pole [Nm] 4 pole [Nm] Frame size [mm] 80 80 90 90 100 100 112 132 132 DriveMotor Weight [kg] Drive Weight [kg] 2.2 2.2 2.8 2.8 4.1 4.2 6.4 10.4 10.4 Input current [A] 380 V 2 p 1.5 1.8 2.3 3.4 4.5 5.0 8.0 12.0 15.0 380 V 4 p 1.4 1.7 2.5 3.3 4.7 6.4 8.0 11.0 15.5 480 V 2 p 1.2 1.4 1.8 2.7 3.6 4.0 6.3 9.5 11.9 480 V 4 p 1.1 1.3 2.0 2.6 3.7 5.1 6.3 8.7 12.3 Efficiency at nom. speed 2 pole 73.4 75.3 77.5 79.0 81.3 82.7 83.8 85.1 86.2 4 pole 75.9 77.5 79.3 80.5 82.4 83.6 84.6 85.8 86.7 Power terminals [AWG] 10 10 10 10 10 10 10 6 6 [mm2] Gland sizes 3xM20x1.5 3xM20x1.5 3xM20x1.5 3xM20x1.5 3xM20x1.5 3xM20x1.5 3xM20x1.5 1xM25x1.5/
Max. prefuse UL4) [A] IEC4) [A]
1)
At 400 V 3000 r/min
2)
At 400 V 1500 r/min
3)
2 pole motor - B3
4)
Type gG prefuses must be used. To maintain UL/cUL, use prefuses of the type Bussmann KTS-R 500 V or Ferraz Shawmut, ATMR Class C (max. 30 A). The fuses must be placed for protection in a circuit that is capable of supplying a maximum of 100,000 amps RMS (symmetrical), 500 V maximum.
1)
2)
3)
305 307 311 315 322 330 340 355 375
1.8 2.4 3.5 4.8 7.0 9.5 12.6 17.5 24.0
3.5 4.8 7.0 9.6 14.0 19.1 25.4 35.0 48.0
11 13 17 20 26 28 37 56 61
4 4 4 4 4 4 4 10 10
2xM20x1.5
10 10 10 10 10 15 15 25 25 25 25 25 25 25 25 25 25 25
1xM25x1.5/
2xM20x1.5
Table 2.1
MG03BA02 - VLT® is a registered Danfoss trademark 11
Installation
VLT® DriveMotor FCM Series
2.1.2 General Technical Data
Mains supply, TT, TN and IT* (L1, L2, L3)
22
Supply voltage 380-480 V units 3x380/400/415/440/460/480 V ±10% Supply frequency 50/60 Hz Max. imbalance of supply voltage ±2% of rated supply voltage Power factor / cos max. 0.9/1.0 at rated load No. of switching operations on supply input L1, L2, L3 approx. 1 time/2 min
*) Not valid for RFI class 1B units
Torque characteristics Starting torque/overload torque 160% for 1 min Continuous torque see above
Control card, digital/pulse inputs Number of programmable digital inputs 4 Terminal nos. X101-2, -3, -4, -5 Voltage level 0-24 V DC (PNP positive logics) Voltage level, logic 0 <5 V DC Voltage level, logic 1 >10 V DC Maximum voltage on input 28 V DC Input resistance, R Scanning time 20 mses
i
approx. 2 kΩ
Control card, pulse input No. of programmable pulse inputs 1 Terminal nos. X101-3 Max. frequency on terminal 3, open collector/push pull 24 V 8 kHz/70 kHz Resolution 10 bit Accuracy (0.1-1 kHz), terminal 3 Max. error: 0.5% of full scale Accuracy (1-12 kHz), terminal 3 Max. error: 0.1% of full scale
Control card, analogue inputs No. of programmable analogue voltage inputs 1 Terminal nos. X101-2 Voltage level 0-10 V DC (scalable) Input resistance, R No. of programmable analogue current inputs 1 Terminal no. X101-1 Current range 0 - 20 mA (scalable) Input resistance, R Resolution 9 bit Accuracy on input Max. error 1% of full scale Scanning time 20 ms.
Control card, digital/pulse and analogue outputs No. of programmable digital and analogue outputs 1 Terminal nos. X101-9 Voltage level at digital output/load 0 - 24 V DC/25 mA Current at analogue output 0 - 20 mA Maximum load to frame (terminal 8) at analogue output Accuracy of analogue output Max. error: 1.5% of full scale Resolution on analogue output. 8 bit
i
i
approx. 10 kΩ
approx. 300 Ω
R
500 Ω
LOAD
Relay output No. of programmable relay outputs 1 Terminal number (resistive and inductive load) 1-3 (break), 1-2 (make) Max. terminal load (AC1) on 1-3, 1-2 250 V AC, 2A, 500 VA
12 MG03BA02 - VLT® is a registered Danfoss trademark
Installation
Max. terminal load (DC1) (IEC 947) on 1-3, 1-2 25 V DC, 3A/50 V DC, 1.5 A , 75 W Min. terminal load (AC/DC) on 1-3, 1-2 control card 24 V DC, 10 mA/24 V AC, 100 mA
Rated values for up to 300,000 operations (at inductive loads the number of operations is reduced by 50%)
Control card, RS 485 serial communication Terminal nos. X100-1, -2
Control characteristics (frequency converter)
Frequency range Resolution on output frequency 0.1% System response time Max. 40 ms. Speed accuracy (open loop, CT mode, 4 P motor driven in speed range 150-1500 rPm) ±15 rpm
Externals
Enclosure Vibration test 1 g Max. relative humidity 95% for storage/transport/operation Ambient temperature Max. 40° C (24-hour average max. 35° C)
See 4.1.7 Derating for Ambient Temperature
Min. ambient temperature in full operation 0°C Min. ambient temperature at reduced performance -10° C Temperature during storage/transport -25-+65/70° C Max. altitude above sea level 1000 m
See 4.1.8 Derating for Air Pressure
EMC standards applied, Emission EN 61000-6-3/EN 6100-6-4, EN 61800-3, EN 55011, EN 55014 EMC standards applied, Immunity Safety standards applied, EN 60146, EN 50178, EN 60204, UL508
VLT® DriveMotor FCM Series
0-132 Hz
See 4.1 Special Conditions for frequency range for IP 66 motors at the end of this section.
IP 55 (IP65, IP66)
See 4.1 Special Conditions for frequency range for IP 66 motors at the end of this section.
EN 61000-6-2, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6,
ENV 50204
2 2
NOTICE
The normal IP 66 solution is only intended for speed up to maximum 3000 rpm. If higher speed is needed, notify when ordering.
MG03BA02 - VLT® is a registered Danfoss trademark 13
Installation
VLT® DriveMotor FCM Series
22
Illustration 2.1 Key Diagram for FCM 300 Series
Terminal No. Function Example
1 Analogue input (0-20 mA) Feedback signal 2 Analogue (0-10 V)/digital input 2 Speed reference 3 Digital input (or pulse) 3 Reset 4 Digital input (or precise stop) 4 Start 5 Digital input (other) 5 Jog (fixed speed) 6 24 V DC supply for digital inputs (max. 150 mA) 7 10 V DC supply for potentiometer (max. 15 mA) 8 0 V for terminals 1-7 and 9 9 Analogue (0-20 mA)/digital output Fault indication
Table 2.2 X101: Terminal Block for Analogue/Digital Control Signals
Reset to be closed short time for resetting fault trips
-
Start to be closed for changing to run mode
-
Jog will run at fixed speed while closed (10 Hz)
-
Speed reference (0-10 V) determines speed while in run mode
-
Table 2.3 Connection Diagram - Factory Setting
14 MG03BA02 - VLT® is a registered Danfoss trademark
Installation
Terminal No. Function
1-2 Make (normally open) 1-3 Brake (normally closed)
Table 2.4 X102: Terminal Block for Relay Output
VLT® DriveMotor FCM Series
2 2
NOTICE
See parameter 323 (relay output) for programming of relay output.
LED 300-304
LED 300 (red): Fault trip LED 301 (yellow): Warning LED 302 (green): Power on
Terminal No. Function
1 P RS 485 For connection to 2 N RS 485 3 5 V DC Supply for RS 485 4 0 V DC
Table 2.5 X100: Terminal Block for Data Communication
Cover (lid) screws 25.6-31lb-in (3-3.5 Nm) Plastic cable entrance plugs 19.5 lb-in (2.2 Nm) L1, L2, L3 (AC Line) screws (FCM 305-340) 5-7 lb-in (0.5-0.6 Nm) L1, L2, L3 (AC Line) screws (FCM 355-375) 15 lb-in (1.2-1.5 Nm) Earth Ground 30.1 lb-in (3.4 Nm)
Table 2.6
bus or PC
bus
LED 303-304: Communication
For PROFIBUS versions, refer to the manual MG90AXYY.
2.1.3 Tightening Torques
Terminal screws require a max 2.5 mm flat-blade screwdriver. AC Line screws require an 8 mm flat-blade screwdriver. Lid screws, earth ground and cable clamp screws all require T-20 Torx or flat-blade screwdriver (max. tightening speed 300 RPM).
Maximum Cable Cross Section
2.1.4
Note
Use °60 C copper wire or better
Max size AC Line cable (FCM 305-340) 10 4.0 Max size AC Line cable (FCM 355-375) 6 10 Max size control cable 16 1.5 Max size serial communication cable 16 1.5 Earth Ground 6 10
Table 2.7
MG03BA02 - VLT® is a registered Danfoss trademark 15
AWG
mm
2
Installation
VLT® DriveMotor FCM Series
2.1.5 Screw Sizes
Cover (lid) screws M5
22
Earth Ground and Cable Clamp screws (FCM 305-340): M4 Earth Ground and Cable Clamp screws (FCM 355-375) M5
Table 2.8
2.1.6 Protection
If a mains phase is missing, the inverter will cut
Thermal overload protection of motor and
electronics. Monitoring of the intermediate circuit voltage
ensures that the inverter cuts out if the intermediate circuit voltage gets too high or too low.
out when a load is placed on the motor.
Illustration 2.2 Terminal Arrangement (for Installation see Quick Setup, MG03AXYY)
16 MG03BA02 - VLT® is a registered Danfoss trademark
175NA163.10
Installation
2.2 Description of the Motor
The FC motor consists of the following parts:
VLT® DriveMotor FCM Series
2 2
Illustration 2.3
Item Description Item Description
1 Flinger (when fitted) 16 Bearing circlip 2 Drive and oilseal 17 Fan 3 Endshield fixing bolt 18 Fan cover 4 Drive and end endshield 19 Fan cover screw and washer 5 Preload washer 20 Screwed bung 6 Bearing 21 O-ring 7 Shaft key 22 ISM box 8 Rotor assembly 23 Cable strap 9 Stator assembly with or without fee 24 Cable strap screws 10 Connector block 25 ISM box lid 11 Gasket 26 Torx screw 12 Detachable feet 27 Washer 13 Foot fixing bolt and washer 28 Face endshield 14 Bearing retention circlip 29 Flange endshield 15 Non-drive endshield
Table 2.9
MG03BA02 - VLT® is a registered Danfoss trademark 17
Installation
VLT® DriveMotor FCM Series
2.2.1 Handling the FC Motor
Handling and lifting of VLT DriveMotors (FC motors) must
22
only be undertaken by qualified personnel. Full product documentation and operating instructions must be available together with tools and equipment necessary for safe working practice. Eyebolts and/or lifting trunnions supplied with the FC motor are designed to support only the weight of the FC motor, not the weight of the FC motor and any aucillary equipment attached to it. Be absolutely sure that cranes, jacks, slings and lifting beams are capable of carrying the weight of equipment to be
Bearings
2.2.2
The standard solution is fixed bearing in the drive side of the motor (shaft output side). To avoid static indention, the storage area should be vibration free. Where exposure to some vibration is unavoidable, the shaft should be locked. Bearings may be fitted with a shaft locking device which should be kept in place during storage. Shafts should be rotated by hand, one quarter of a revolution, at weekly intervals. Bearings are despatched from the works fully charged with lithium
based grease. lifted. Where an eyebolt is provided with the motor, this should be screwed down until its shoulder is firmly against the face of the stator frame to be lifted.
FCM type Approx. weight [kg]
FCM 305 11 FCM 307 13 FCM 307 17 FCM 315 20 FCM 322 26 FCM 330 28 FCM 340 37 FCM 355 56 FCM 375 61
Frame size Lubrication type Temperature range
80-132 Esso unirex N3 -30°C to + 140°C
Table 2.11 Lubrication
Table 2.10 Weight
Maximum hours bearing life (Lna) expected at 80° C bearing temp. x 103 hours.
FCM
305-315
355-375 Lna bearing life is the adjusted, L10 life rating, taking account of: -Reliability -Material improvement -Lubrication conditions.
Table 2.12 Bearing Life
FCM Bearings Oil seals - Bore x O/D x width in mm
Drive end Non-drive end Drive end Non-drive end
305-307 6204ZZ 6003ZZ 20x30x7 17x28x6 311-315 6205ZZ 6003ZZ 25x35x7 17x28x6 322-330 6206ZZ 6005ZZ 30x42x7 25x37x7 340 6206ZZ 6005ZZ 30x42x7 25x37x7 355-375 6208ZZ 6005ZZ 40x52x7 25x37x7
Table 2.13 Standard Bearing References and Oil Seals
Horiz. Vert. Horiz. Vert.
30 30 30 30322-340
3000 min
-1
1500 min
-1
18 MG03BA02 - VLT® is a registered Danfoss trademark
Installation
VLT® DriveMotor FCM Series
2.2.3 Output shafts
Output shafts are produced from 35/40 Ton (460/540 MN/m2) tensile steel. Drive end shafts are provided with a tapped hole to DIN332 Form D and a closed profile keyway as standard.
Balance
All motors are dynamically balanced, to ISO 8821with key convention to IEC 60034-14.
2.2.4
Dimensions
2 2
FCM 2 pole 4 pole
305 0.00082 0.0019 307 0.00082 0.0027 311 0.00090 0.0022 315 0.0011 0.0030 322 0.0024 0.0042 330 0.0028 0.0050 340 0.0053 0.0091 355 0.0072 0.0143 375 0.0097 0.0190
Table 2.14 Inertia
J [kgm2]
General FCM 305 307 311 315 322 330 340 355 375 Frame size 80 80 90 90 100 100 112 132 132 A [mm] 125 125 140 140 160 160 190 216 216 B [mm] 125 125 140 140 140 140 178 C [mm] 50 50 56 56 63 63 70 89 89 H [mm] 80 80 90 90 100 100 112 132 132 K [mm] 10 10 10 10 12 12 12 12 12 AA [mm] 27 27 28 28 28 28 35 38 38 AB [mm] 157 157 164 164 184 184 218 242 242 BB [mm] 127 127 150 150 170 170 170 208 208 BC [mm] 13.5 13.5 L [mm] 278 278 322 322 368 368 382 484.5 AC [mm] 160 160 178 178 199 199 215 255 255 HD [mm] 219.5 219.5 238 238 264 264 292 334 334 EB [mm] 1.5 1.5 2.5 2.5 6 6 6 6 6 FCL [mm] 206 206 230 230 256 256 286 357.5 357.5 FCW [mm] 141 141 158 158 176 176 196 242.5 242.5
Table 2.15 Foot Mounting - B3
1)
2 pole motor = 37.5. 2)2 pole motor = 53
1)
12.5
MG03BA02 - VLT® is a registered Danfoss trademark 19
12.5
1)
15 15 15 53 15
484.5
2)
Installation
VLT® DriveMotor FCM Series
22
FCM 305 307 311 315 322 330 340 355 375 Frame size 80 80 90 90 100 100 112 132 132 D [mm] 19 19 24 24 28 28 28 38 38 E [mm] 40 40 50 50 60 60 60 80 80 ED [mm] 32 32 40 40 50 50 50 70 70 ED1 [mm] 4 4 5 5 5 5 5 5 5 DH M6x16 M6x16 M8x19 M8x19 M10x22 M10x22 M10x22 M12x28 M12x28 F [mm] 6 6 8 8 8 8 8 10 10 G [mm] 15.5 15.5 20 20 24 24 24 33 33
Table 2.16 Shaft Drive End
B5 FCM Frame size 48 56 63 71 80 90 100 112 132 IEC Ref. FF85 FF100 FF115 FF130 FF165 FF165 FF215 FF215 FF265 DIN Ref. A105 A120 A140 A160 A200 A200 A250 A250 A300 C [mm] 50 56 63 70 89 M [mm] 85 100 115 130 165 165 215 215 265 N [mm] 70 80 95 110 130 130 180 180 230 P [mm] 105 120 140 160 200 200 250 250 300 S [mm] 10 10 12 12 14.5 14.5 14.5 T [mm] 3 3.5 3.5 3.5 4 4 4 LA [MM] 7 7 12 10 12 12 12
305/307 311/315 322/330 340 355/375
Table 2.17 Flange Mounting - B5, B35, (B3+B5)
20 MG03BA02 - VLT® is a registered Danfoss trademark
Installation
B14 FCM 305/307 311/315 322/330 340 355/375 Frame size 56 63 71 80 90 100 112 132 IEC Ref. FT65 FT75 FT85 FT100 FT115 FT130 FT130 FT165 DIN Ref. C80 C90 C105 C120 C140 C160 C160 C2OO C [mm] 50 56 63 70 89 M [mm] 65 75 85 100 115 130 130 165 N [mm] 50 60 70 80 95 110 110 130 P [mm] 80 90 105 120 140 160 164 200 S [mm] M5 M6 M6 M8 M8 M8 M10 T [mm] 2.5 2.5 3 3 3.5 3.5 3.5 LA [MM] 9 9 9 9 8.5 13 13 Max. the B14 flange
8.5 11 11 11.5 15 15.5 17
VLT® DriveMotor FCM Series
2 2
Table 2.18 Face Mounting - B14, B34 (B3+B14)
Installation of the FC Motor
2.2.5
Illustration 2.4
FC motors must be installed with adequate access for routine maintenance. A minimum of 0.75 m of working space around the motor is recommended. Adequate space around the motor, particularly at the fan inlet (50 mm), is also necessary to facilitate airflow. Where several FC motors are installed in close proximity, care must be taken to ensure that there is no recirculation of exhausted warm air. Foundations must be solid, rigid and level.
NOTICE
Electrical installation
Do not remove the top foil inside the inverter part, as
this is a part of the protective arrangements.
MG03BA02 - VLT® is a registered Danfoss trademark 21
Installation
VLT® DriveMotor FCM Series
Fitting pinions, pulleys and couplings.
These should be bored to our standard limits and fitted on the shaft with a screwing motion. Attention must be paid
22
to correct guarding of all moving parts.
2.2.6 Alignment
When the application calls for direct coupling, the shafts
NOTICE
Tapping of fittings onto the FC motor shaft, with a
must be correctly aligned in all three planes. Bad
alignment can be a major source of noise and vibration.
hammer or mallet, causes bearing damage. This results in an increase in bearing noise and a significant reduction in bearing life.
Allowance must be made for shaft endfloat and thermal
expansion in both axial and vertical planes. It is preferable
to use flexible drive couplings.
NOTICE
Max. the B14 flange, see 2.2.4 Dimensions .
Horizontal shaft Vertical shaft
Shaft up Shaft down
Type Poles Load towards
motor
W-DA80
W-DA90
W-DA100
W-DA112
W-DA132
2 339 539 321 565 362 521 774 4 303 503 283 530 330 583 729 2 444 684 421 716 476 661 915 4 398 638 366 682 442 606 854 2 781 1101 743 1159 839 1063 1295 4 710 1030 655 1107 787 975 1215 2 768 1088 715 1170 850 1035 1295 4 690 1010 612 1131 811 932 1202 2 1355 1707 1266 1838 1486 1618 2114 4 1253 1605 1130 1779 1427 1482 2068
Load away
from motor
Load towards
motor
Load away
from motor
Load up Load
down
Maximum
permissible radial
load at the end of
shaft (horizontal
mounting)
Table 2.19 Maximum Permissible External Axial and Radial Loads in Newtons
Bolt Torques
2.2.7
Remove the fan cover and ensure that all air inlet holes
are completely free. Clean any dirt and obstructions from Endshields and lid should be secured with the bolt sizes
and torques detailed in Table 2.20.
FCM Type Frame size Bolt diameter Nm. Torque
305-307 80 M5 5 311-315 90 M5 5 322-330 100 M6 (taptite) 8-10 340 112 M6 (taptite) 8-10 355-375 132 M8 (taptite) 29 LID screws torque: 2.2-2.4 Nm
Table 2.20 Endshield Fixing Bolt Torques
Maintenance
2.2.8
behind the fan and along the ribs of the frame, and
between the motor and inverter part.
Periodic maintenance of motor part
Routine cleaning of the FC motor
1. Remove the inverter part, the fan cover and the fan which is keyed to the shaft extension. Loosen and remove bearing cover screws and endshield bolts/studs. The endshields should then be eased off their spigots.
2. The rotor can now be carefully withdrawn from the stator, taking care not to damage the stator bore and both stator and rotor windings.
3. Having dismantled the motor, maintenance can be carried out to remove all dirt. For this purpose, the use of an air line supplying dry compressed air under comparatively low pressure is best, as a high velocity air-stream can force dirt
22 MG03BA02 - VLT® is a registered Danfoss trademark
Installation
VLT® DriveMotor FCM Series
into the spaces between the windings and insulation, etc. Grease-removing solvents can cause damage to impregnating varnish or insulation
4. The FC-motor should be re-assembled in the reverse order from dismantling, remembering to ease endshields onto bearings and spigots. DO NOT USE FORCE.
5. Before starting, check that the rotor revolves freely. Ensure that the electrical connections are correct.
6. Refit any pulley, coupling, sprocket etc. which has been removed, being particularly careful to ensure correct alignment with the driven part, as misalignment will lead to ultimate bearing trouble and shaft breakage.
7. When replacing screws and bolts, care should be taken to use only those with the requisite quality and tensile strength recommended by the manufacturer. These must also be of identical thread form and screw/bolt length (see Table 2.24).
FCM 300 Thermal Protection
2.2.9
The thermal protection of FC and motor is covered in the following way:
Overload situations are handled by the calculated
electrical load (I 2X t). Missing ventilation and high ambient
temperature is handled by the temperature measurement. The derating for low speed (due to missing ventilation) is not incorporated in the electrical load calculation but taken care of by the temperature measurement. Forced ventilation is thus automatically covered.
Electrical load
The current is measured in the DC link and the estimated load is calculated. The level of the electrical load is set at an output torque of 105%. Above that level a counter is increased, below the level it is decreased. The counter starts at zero. When the counter reaches 100, the unit trips. At 98 the warning indication goes on (LED and status word).
Load
0% - 60 s 20% - 100 s 40% - 150 s 60% - 200 s 80% - 250 s 105% 900 s (if over 105%) 300 s (if under 105%) 120% 550 s ­140% 210 s ­160% 60 s ­>165% 20 s -
At full AC brake (parameter 400) a load > 165% is simulated => 20 s to trip.
The value can be read in parameter 527. (LCP:FC thermal).
The temperature measurement is sensing the temperature within the electronics box.
At warning level Warning indication goes on (LED and status word) and the unit might trip if the temperature doesn't sink back below warning level within 15 minutes. If the function TEMP.DEP.SW is activated in parameter 412, the switching frequency is decreased gradually down to 2 kHz attempting to decrease the temperature.
Trip level Immediate trip and alarm indication (LED and status word).
The value can be read in parameter 537 (LCP: Heat sink temp.).
The temperature levels seem to be high, but due to a local heating of the sensor the practical levels of the inside air temperature are approx. 10° C lower.
2.3
Time from 0 to 100 Time from 100 to 0
Table 2.21
Local Control
2.3.1 Service Plug Kit (175N2546)
Purpose
To run LCP2 and PROFIBUS at the same time. The service plug can be used with FCM 300 of serial number 03Gxxx and software version as from 2.03. Used together with cable for plug kit 175N0162.
2 2
MG03BA02 - VLT® is a registered Danfoss trademark 23
Installation
VLT® DriveMotor FCM Series
22
Illustration 2.5
24 MG03BA02 - VLT® is a registered Danfoss trademark
Installation
VLT® DriveMotor FCM Series
2.3.2 Plug Kit (175N2545)
Purpose
To make a plugable connection between LCP 2 and FCM
300. Used together with cable for plug kit 175N0162.
Illustration 2.6
2.3.4
Remote Mounting Kit Cont.
Illustration 2.8
2 2
Remote Mounting Kit (175N0160)
2.3.3
Illustration 2.7 Connections
Colour of wire/ Terminal X100/ D-sub pin
yellow 1 8
green 2 9
red 3 2
blue 4 3
Illustration 2.9
Table 2.22
MG03BA02 - VLT® is a registered Danfoss trademark 25
Installation
VLT® DriveMotor FCM Series
2.3.5 Potentiometer Option (177N0011)
Option to control the reference by means of a potenti-
22
ometer. The option is mounted instead of a cable bracket. The potentiometer is operated by removing the blind plug to set the desired reference, and then mount the blind plug again.
Illustration 2.10
Illustration 2.12 Local Operation Panel (LOP) 175N0128 IP 65
Colour of wire Terminal on X101
White 2 (analog input) Red 8 (0 V) Black 7 (+10 V)
Table 2.23
Local Operation Pad (LOP)
2.3.6 (175N0128) IP65
Illustration 2.11
Colour of wire Terminal Function
White 2 Reference Brown 3 Reset Purple* or Grey 4 Green 5 Red 6 +24 V Yellow 7 +10 V Blue 8 Ground * Can be orange in some cables
See Illustration 2.11
Illustration 2.13 Fixture for LOP 175N2717 (included in 175N0128)
Table 2.24 Wiring
26 MG03BA02 - VLT® is a registered Danfoss trademark
Installation
Functions/settings Key I (Start) Key II (Start)
Default - Dual speed operation (connect purple wire):
No changes to factory setting.
Function 2 - Dual mode operation (connect purple wire):
Select desired modes of operation in Setups 1 and 2 (use para. 4-6) Parameter 335 = 18 (select Setup)
Function 3 - Dual direction operation (connect grey wire):
Parameter 335 = 10 (start reversing) Parameter 200 = 1 (both directions)
Table 2.25
*If no reset is required, do not connect the brown wire
**or set parameter 213
VLT® DriveMotor FCM Series
Run on set reference (+/-)
Run with Setup 1 Run with Setup 2 Stop (and reset* - if trip)
Run forward Run reverse Stop (and reset* - if trip)
Run on 10 Hz** jog speed
NOTICE
After fitting, cut off or isolate excess wire.
Use the [+[/[-] keys to set reference
Key (Stop)
Stop (and reset* - if trip)
2 2
At power up the unit will always be in stop mode. Set reference will be stored during power down. If permanent start mode is desired, connect terminal 6 to terminal 4 and do not connect purple/grey wire to terminal 4. This means the stop function on LOP is disabled.
MG03BA02 - VLT® is a registered Danfoss trademark 27
Programming
3 Programming
VLT® DriveMotor FCM Series
33
3.1 Parameters
3.1.1 Control Panel (175NO131)
The FC motor optionally features a Local Control Panel­LCP 2 which makes up a complete interface for operation and monitoring of the FC motor. IP 65 on front.
3.1.2 LCP Installation
The LCP 2 is connected to the terminal X100, 1-4 (see separate instruction MI03AXYY).
1.
Service Plug Kit (175N2546) (see 2.3.1 Service Plug Kit (175N2546)) and cable 175N0162
2.
Plug kit (175N2545) (see 2.3.2 Plug Kit (175N2545)) and cable 175N0162
3.
Remote mounting kit (175N0160) (see 2.3.4 Remote Mounting Kit Cont.)
LCP Functions
3.1.3
The functions of the control panel can be divided into three groups:
Display
Keys for changing program parameters
Keys for local operation
All data are indicated by means of a 4-line alphanumeric display, which in normal operation is able show 4 measurements and 3 operating conditions continuously. During programming, all the information required for quick, effective parameter Set-up of the FC motor will be displayed. As a supplement to the display, there are three LEDs for voltage, warning and alarm. All program parameters of the FC motor can be changed immediately from the control panel, unless this function has been blocked via parameter 018.
Illustration 3.1
Display
3.1.4
The LCD display is back lit and has a total of 4 alpha­numeric lines together with a box that shows the direction of rotation (arrow) and the chosen Set-up as well as the Set-up in which programming is taking place if that is the case.
Illustration 3.2
28 MG03BA02 - VLT® is a registered Danfoss trademark
Loading...
+ 72 hidden pages