Danfoss VLT® Brake Resistors MCE 101 are optimised for:
VLT® Micro Drive FC 51
•
VLT® HVAC Drive FC 102
•
VLT® AQUA Drive FC 202
•
VLT® AutomationDrive FC 300
•
VLT® AutomationDrive FC 360
•
VLT® Decentral Drive FCD 302
•
VLT® 2800
•
General versions for horizontal and vertical applications are
available.
The Design Guide provides the information required to
select and plan installation of the right brake resistor for
an application:
Selection of the correct brake resistor
•
Pre-installation considerations
•
Programming.
•
As an alternative to using a brake resistor, other braking
methods can be applied depending on the braking profile
of the application, see chapter 7 Special Conditions.
1.2
Conformity
Table 1.1 Approval
1) See Table 9.2 and Table 9.4 for UL conformity.
What is CE Conformity and Labelling
The purpose of CE labelling is to avoid technical trade
obstacles within EFTA and the EU. The EU has introduced
the CE label as a simple way of showing whether a
product complies with the relevant EU directives. The CE
label says nothing about the specifications or quality of
the product. Brake resistors are regulated by the following
EU directive:
The low-voltage directive (2006/95/EC)
Brake resistors must be CE labelled in accordance with the
low-voltage directive of December 12, 2006. The directive
applies to all electrical equipment and appliances used in
the 50-1000 V AC and the 75-1500 V DC voltage ranges.
Danfoss CE-labels in accordance with the directive and
issues a declaration of conformity upon request.
1.3
Safety Precautions
1)
Additional technical literature is also available online at
When in use, the brake resistor surface temperature
rises. DO NOT touch the brake resistor during operation.
WARNING
Never work on a brake resistor in operation.
NOTICE
Never attempt to repair a defective brake resistor.
1.4 Disposal
Equipment containing electrical components
may not be disposed of together with
domestic waste.
It must be separately collected with electrical
and electronic waste according to local and
currently valid legislation.
When the speed reference of a frequency converter is
reduced, the motor acts as a generator and the frequency
converter brakes. When a motor acts as a generator, it
supplies energy to the frequency converter which is
collected in the DC link. The function of the brake resistor
is to provide a load on the DC link during braking, thereby
ensuring that the braking power is absorbed by the brake
resistor.
If a brake resistor is not used, the DC-link voltage of the
frequency converter continues to increase, until disconnecting for protection. The advantage of using a brake
resistor is that it enables braking of a heavy load quickly,
e.g. on a conveyor belt.
The brake resistors in this series are all external
components. Therefore, the brake resistor does not form
an integral part of the frequency converter.
The external brake resistor provides the following
advantages:
The resistor time cycle can be selected as
•
required.
The heat developed during braking can be
•
conveyed beyond the panel cabinet to allow the
energy to be used.
The electronic components do not overheat, even
•
when the brake resistor is overloaded.
The brake resistor series is suitable for Danfoss frequency
converters
VLT® Micro Drive FC 51
•
VLT® HVAC Drive FC 102
•
VLT® AQUA Drive FC 202
•
VLT® AutomationDrive FC 300
•
VLT® AutomationDrive FC 360
•
VLT® Decentral Drive FCD 302
•
VLT® 2800
•
.
2.2.1 How to Select
The Danfoss brake resistor range consists of 2 groups:
Brake resistors for horizontal loads (conveyors,
•
trolleys, gantry cranes, etc.), see Illustration 2.1;
Brake resistors for vertical loads (cranes, hoists,
•
elevators), see Illustration 2.2.
Illustration 2.1 Horizontal Loads
Illustration 2.2 Vertical Loads
The brake resistor range is intended to cover the general
braking requirements for horizontal and vertical brake
applications.
To select the best brake resistor for an application, refer to
chapter 8.1 Selection Flow Chart. The flow chart links to
further information, either selection tables or calculations
of inertia or duty cycle.
To cater for both the horizontal and vertical ranges, 3
types of brake resistors are available:
The flat-pack brake resistor is an anodized aluminiumhoused resistor suitable for wall mounting or on a
footprint or an L-profile bracket. The L-profile bracket is
used for rear mounting. The brake resistor is designed for
high pulse loads of up to 40 times the nominal load and is
therefore suitable for both vertical and horizontal
applications. The enclosure protection is IP54 or IP65.
Illustration 2.5 CBR-V-DT IP21
Illustration 2.3 Flat-pack IP54
Aluminium-housed Compact Brake
2.3.2
Resistor
The compact brake resistor is housed in aluminium profiles
with pre-mounted brackets for wall mounting. It is
designed for high pulse loads of up to 60 times the
nominal load and is therefore used for both horizontal and
vertical loads. The enclosure protection class is either IP21,
IP54 or IP65. The brake resistor IP classes IP21 and IP65 are
equipped with a connection box containing cable glands
and cable connection to the resistor and the temperature
switch. IP54 versions have fixed unscreened cables.
Illustration 2.6 CBR-V-BT IP65
2.4 Steel Grid Brake Resistors
The steel grid brake resistor is steel grid housed and
consists of multiple elements. This brake resistor is suitable
for pulse loads between 10 and 20 times the nominal load,
suitable for frequent braking applications such as cranes,
hoists and elevators. It is supplied in an IP20 enclosure
with cable glands and has a built-in temperature switch.
The brake resistors are cooled by natural convection, and
the specified minimum clearances must be observed to
ensure efficient ventilation. The ventilation must be
efficient enough to dispatch the regenerative power in the
brake resistor.
NOTICE
When installing the brake resistor, ensure all precautions
are in place to avoid the risk of overloading. Overloading
can lead to a fire hazard due to the heat generated in
the brake resistor.
The brake resistor is very hot during or after braking.
The brake resistor must be located in a secure
environment to avoid fire risk.
Mount the brake resistor free of any combustible
•
materials at a well ventilated location.
The MCE 101 brake resistors product type 9xx
•
contain a built-in temperature switch (for
overtemperature protection purposes. See
chapter 3.3 Protective Functions).
Vertical Mounting, IP54
For minimum clearances for vertical mounting for all
aluminium-housed compact and flat-pack brake resistors,
see Illustration 3.1 and Illustration 3.2.
33
Aluminium-housed Compact Brake
3.1.1
Resistors and Flat-pack Brake
Resistors
The aluminium-housed compact and flat-pack brake
resistors are designed for vertical mounting for optimum
cooling performance. However, horizontal mounting is
possible for both flat-pack and compact brake resistors.
Derating with 20% is required when mounting the
compact brake resistors horizontally. No derating for flatpacks are required. The enclosure protection of the IP21
types is reduced to IP20 when mounted horizontally.
NOTICE
All resistors are cooled by natural convection. To ensure
sufficient airflow and cooling, follow minimum clearance
in Illustration 3.1 to Illustration 3.8.
Illustration 3.1 Vertical Mounting, IP54
Versions with Fixed Cables
For minimum clearances for horizontal mounting for all
aluminium-housed compact and flat-pack brake resistors,
IP54 versions (versions with fixed cables), see Illustration 3.4
(side view).
33
Illustration 3.4 Horizontal mounting, IP54
Versions with Fixed Cables
Vertical mounting, IP21 and IP65
For minimum clearances for vertical mounting for all
aluminium-housed compact brake resistors, see
Illustration 3.5 and Illustration 3.6.
Illustration 3.2 Vertical Mounting, IP54
Versions with Fixed Cables
Horizontal mounting, IP54
For minimum clearances for horizontal mounting for all
aluminium-housed compact and flat-pack brake resistors,
see Illustration 3.3 (top view).
Illustration 3.3 Horizontal mounting, IP54
Versions with Fixed Cables
Illustration 3.5 Vertical Mounting, IP21 and IP65
Versions with Connection Box
For minimum clearances for horizontal mounting for all
aluminium housed compact brake resistors, see
Illustration 3.8 (side view).
33
Illustration 3.8 Horizontal Mounting, IP21 and IP65
Versions with Connection Box
Orientation, compact and flat-pack brake resistors
Illustration 3.6 Vertical Mounting, IP21 and IP65
Versions with Connection Box
Horizontal mounting, IP21 and IP65
For minimum clearances for horizontal mounting for all
aluminium-housed compact brake resistors, see
Illustration 3.7 (top view).
Illustration 3.7 Horizontal Mounting, IP21 and IP65
Versions with Connection Box
Illustration 3.9 Orientation of Compact and Flat-pack Brake
Resistors
Derating with 20% is required when mounting the
compact brake resistors horizontally. The enclosure
protection of the IP21 types is reduced to IP20 when
mounted horizontally.
The steel grid brake resistors are designed for horizontal
mounting only.
33
NOTICE
All resistors are cooled by natural convection. To ensure
sufficient airflow and cooling, follow minimum
clearances in Illustration 3.10 and Table 3.3.
Illustration 3.10 Minimum Clearances of all Steel Grid Brake
Resistors - Top View
Illustration 3.12 Orientation of Steel Grid Brake Resistors
Illustration 3.11 Minimum Clearances of all Steel Grid Brake
Resistors - Side View
The footprint bracket is an accessory used for mounting
flat-pack brake resistors.
Use the footprint bracket to mount the brake resistor at
the rear of the frequency converter. Once mounted, the
combined brake resistor and frequency converter occupy
the same space in the cabinet as the frequency converter
alone.
For mechanical dimensions for footprint brackets, see
chapter 9.8.2 Mounting Brackets: Footprint.
L profile brackets
The L profile bracket is an accessory used for mounting
flat-pack brake resistors. The L profile brackets support
both horizontally and vertically mounting on a fixed
surface optimising the required footprint.
The following EMC precautions are recommended to
achieve interference-free operation of fieldbus cable(s) and
33
digital and analog inputs and outputs.
NOTICE
To comply with EMC emission specifications, screened/
armoured cables are recommended.
NOTICE
Observe relevant national and local regulations, for
example regarding protective earth connection. Keep the
fieldbus cable(s) away from motor and brake resistor
cables to avoid coupling of high frequency noise from one
cable to another. Normally, a distance of 200 mm (8
inches) is sufficient, but keeping the greatest possible
distance between the cables is recommended, especially
where cables run in parallel over long distances. When
crossing is unavoidable, the fieldbus cable(s) must cross
motor and brake resistor cables at an angle of 90°, see
Illustration 3.15.
Cables General: All cabling must comply with national
and local regulations on cable cross-sections and
ambient temperature.
See Table 3.3 for recommended temperature ratings for all
cables and conductors connected to the brake resistor as
ground connection, thermal switch and brake power.
IP classRecommended cables
IP20
IP21
IP54
IP65
Table 3.3 Cable Temperature Ratings
1) For ground connection
How to connect more than one resistor
Star parallel connection to ensure load is shared evenly
between 2 or more resistors.
≥80 °C
≥80 °C
≥90 °C
≥90 °C
1)
Illustration 3.15 Cable Routing
Illustration 3.16 Connection of Several Brake Resistors
To reduce the electrical noise from the wires between the
brake resistor and the frequency converter, twist the wires.
For enhanced EMC performance a metal screen can be
used.
Illustration 3.17 Twisted Cables
Brake Cable
3.2.3
Max. length: 20 m shielded cable.
Automatic restart after enabling of the temperature
switch:
Select coast inverse for the selected digital input.
Prevent automatic restart:
Select latched start for the selected digital input.
NOTICE
Coast does not terminate the brake function.
Example 1
33
Ensure the connection cable to the brake resistor is
shielded. Connect the shielding to the conductive back
plate of the frequency converter and to the brake resistor
metal cabinet, using cable clamps.
3.3
Protective Functions
3.3.1 Overtemperature Protection
The Danfoss brake resistor MCE 101 is equipped with a
galvanic isolated temperature switch (PELV) that is closed
under normal operating conditions and open if the brake
resistor is overheated.
NOTICE
Use the temperature switch as overtemperature
protection feature to prevent damage of the brake
resistor caused by overtemperature. To prevent damage
to the brake resistor, perform an immediate stop or a
ramp down.
There are several ways the temperature switch can be
used:
The temperature switch as digital input to frequency
converter
Example 1
1.Connect terminal T1 of the brake resistor to the
frequency converter terminal 12 or 13.
2.Connect terminal T2 of the brake resistor to a
digital input e.g. terminal 18.
Illustration 3.18 Temperature Switch in Brake Resistor
NOTICE
The temperature switch as input to the frequency
converter cannot be considered a primary safety
function.
In case of a malfunction in the brake IGBT, the frequency
converter and brake resistor are only protected by
disconnecting the mains supply to the frequency
converter. The temperature switch must be connected
disabling the mains supply to the frequency converter by
a contactor preventing dangerous overtemperatures.
The temperature switch disabling the mains supply to
3.3.2
Brake Resistor and Brake IGBT
VLT by a contactor
Example 2
1.Connect the brake resistor built-in thermal switch
as controlling an input contactor. In this example,
the thermal switch within the brake resistor is
33
connected in series with the thermal switch
within the motor.
2.Connect start and stop push buttons in series
with the thermal switches.
3.Connect to a contactor in the mains supply in
front of the frequency converter.
Thermal overheating in brake resistor or motor disables
the mains supply to the frequency converter.
Example 2
Brake resistor power monitor
In addition, the brake power monitor function makes it
possible to read out the momentary power and the mean
power for a selected time period. The brake can also
monitor the power energising and make sure it does not
exceed a limit selected in parameter 2-12 Brake Power Limit(kW). In 2-13 Brake Power Monitoring, select the function to
carry out when the power transmitted to the brake resistor
exceeds the limit set in parameter 2-12 Brake Power Limit(kW).
NOTICE
Monitoring the brake power does not fulfil a safety
function. The brake resistor circuit is not ground leakage
protected.
The brake is protected against short-circuiting of the brake
resistor, and the brake transistor is monitored to ensure
that short-circuiting of the transistor is detected. Use a
relay or digital output to protect the brake resistor against
overloading in the event of a fault in the frequency
converter, see chapter 3.3.1 Overtemperature Protection.
Illustration 3.19 Temperature Switch in both Motor and Brake
Resistor disabling Mains Supply by an Input Contactor
Thermo relay disabling the brake resistor
Example 3
Calculate the brake current (I
thermo relay
) setting of the
temperature switch as follows:
P
I
thermo relay
brake resistor max
=
R
br
Rbr is the current brake resistor value calculated in
chapter 4.1.2 Calculation of Brake Resistor Resistance.
Look up the brake current setting of the thermo relay for
Danfoss brake resistors in chapter 8 Selection Guide.
Overvoltage control (OVC) can be selected as an alternative
brake function in parameter 2-17 Over-voltage Control. If the
DC-link voltage increases, this function is active for all
units. The function ensures that a trip can be avoided. This
is done by increasing the output frequency to limit the
voltage from the DC link. It is a useful function, e.g. if the
ramp-down time is too short since tripping of the
frequency converter is avoided. In this situation the rampdown time is extended.
To ensure the optimal selection of brake resistor for a
given application, its inertia and braking profile
calculations are required.
This chapter explains the calculations required to obtain
values for optimal selection of brake resistor for a given
application.
4.1.1 Brake Set-up
The following sections use expressions and abbreviations
related to the brake set-up in Illustration 4.1.
Udc is the voltage, where the brake is activated. The FCseries brake function is settled depending on the mains
supply.
DC-link Voltage (Udc), FC 51
Size [V]Brake active
[V]
FC 51 1x200-240390410410
FC 51 3x200-240390410410
FC 51 3x380-480,
1.5-4.0 kW
FC 51 3x380-480,
5.5-15 kW
FC 51 3x380-480,
18.5-22 kW
Table 4.1 DC-link Voltage (Udc), FC 51
1) Adjustable with 2-14 Brake Voltage Reduce
770800800
705-770
770800800
1)
Warning
before cut
out [V]
800800
Cut out
(trip) [V]
DC-link Voltage (Udc), FC 102
Brake
Size [V]
FC 102 3x200-240390405410
FC 102 3x380-480778810820
FC 102 3x525-600
FC 102 3x525-600
FC 102 3x525-690109911091130
1)
2)
active
[V DC]
943965975
109911091130
High
voltage
warning
[V DC]
Over
voltage
alarm
[V DC]
44
Table 4.2 DC-link Voltage (Udc), FC 102
1) Enclosure types A, B, C
2) Enclosure types D, E, F
Illustration 4.1 Brake Set-up
Calculation of Brake Resistor
4.1.2
Resistance
To prevent the frequency converter from cutting out for
protection when the motor brakes, select resistor values on
the basis of the peak braking power and the intermediate
circuit voltage:
2
Udc
R
=
br
P
peak
Ω
The brake resistor performance depends on the DC-link
voltage (Udc).
FC 202 3x200-240390405410
FC 202 3x380-480778810820
FC 202 3x525-600
FC 202 3x525-600
FC 202 3x525-690109911091130
Table 4.3 DC-link Voltage (Udc), FC 202
1) Enclosure types A, B, C
2) Enclosure types D, E, F
1)
2)
active
[V DC]
943965975
109911091130
High
voltage
warning
[V DC]
Over
voltage
alarm
[V DC]
P
[W]
P
peak
P
avg
T
p
T
b
t [s]
175ZA094.13
System IntegrationDesign Guide
DC-link Voltage (Udc), FC 301/FC 302
Use the brake resistance R
, to ensure that the frequency
rec
converter is able to brake at the highest braking torque
High
voltage
warning
[V DC]
Size [V]
FC 301 3x200-240
FC 301 3x200-240
Brake
active
[V DC]
1)
2)
365405410
390405410
FC 302 3x200-240390405410
44
FC 301 3x380-480
FC 301 3x380-480
FC 302 3x380-500
FC 302 3x380-500
FC 302 3x525-600
FC 302 3x525-600
1)
2)
3)
4)
3)
4)
728810820
778810820
810840855
810828855
943965975
109911091130
FC 302 3x525-690109911091130
Table 4.4 DC-link Voltage (Udc), FC 301/FC 302
1) Enclosure type A
2) Enclosure types B, C
3) Enclosure types A, B, C
4) Enclosure types D, E, F
DC-link Voltage (Udc), FC 360
1)
High
voltage
warning
[V DC]
800800
800800
Size [V]
FC 360 3x380-480,
0.37-22 kW
FC 360 3x380-480, 30-75
kW
Brake
active
[V DC]
700-770
N/A
2)
Over
voltage
alarm
[V DC]
Over
voltage
alarm
[V DC]
(M
) (e.g. 160%). The formula is written as:
br(%)
2
U
x 100
R
Ω =
η
η
rec
motor
VLT
P
motor
is typically at 0.90
is typically at 0.98
x
dc
M
x η
br
%
VLT
x η
motor
When a higher brake resistor resistance is selected, 160%/
150%/110% braking torque cannot be obtained, and there
is a risk that the frequency converter cuts out of DC-Link
overvoltage for protection.
For braking at lower torque, for example 80% torque, it is
possible to install a brake resistor with lower power rating.
Calculate size using the formula for calculating R
Calculation of Braking Power
4.1.3
rec
.
When calculating the braking power, ensure that the brake
resistor is scaled for the average power as well as the peak
power.
The average power is determined by the process
•
period time, i.e. the length of the braking time in
relation to the process period time.
The peak power is determined by the braking
•
torque, which means that as braking progresses,
the brake resistor must be able to dissipate the
energy input.
Illustration 4.2 shows the relation between the average
Illustration 4.2 Relation between Average Power and Peak
Power
ω Start
ω Stop
∆t
∆ω/∆t
175ZA863.11
System Integration
Design Guide
4.1.4 Calculation of the Brake Resistor Peak
Power
P
the motor shaft. Calculate P
P
P
when the motor brakes.
P
the efficiencies of the motor and the frequency converter.
Calculate P
P
When the brake resistor recommended by Danfoss is
selected (R
chapter 8 Selection Guide, the brake resistor is certain to
provide a braking torque of 160%/150%/110% on the
motor shaft.
is the peak power by which the motor brakes on
peak, mec
as follows:
peak, mec
=
P
×
M
peak, mec
is the braking power dissipated to the brake resistor
peak
is lower than P
peak
=
peak
motor
peak,mec
as follows:
peak
P
×
M
motor
) on the basis of the tables in
rec
BR %
×
W
BR %
since the power is reduced by
η
×
η
W
VLT
motor
Danfoss offers brake resistors with a duty-cycle of max.
10% and 40%. If a 10% duty-cycle is applied, the brake
resistors are able to absorb P
for 10% of the period
peak
time. The remaining 90% of the period time is used on
deflecting excess heat.
Calculate the average power with 10% duty-cycle as
follows:
P
=
P
avg
peak
× 10 %
W
Calculate the average power with 40% duty-cycle as
follows:
P
=
P
avg
peak
× 40 %
W
The calculations apply to intermittent braking using a
period time of 30 s.
NOTICE
Exceeding the specified intermittent braking period time
may result in overheating the resistor.
44
Calculation of the Brake Resistor
4.1.5
Average Power
The average power is determined by the length of the
braking time in relation to the process period time.
When the kinetic energy (Eb) transferred to the resistor in
each braking sequence is known (see chapter 6.1 ConveyorBelt and chapter 6.2 Centrifuge), calculate the average
power of the brake resistor as follows:
E
avg
b
=
W
T
p
T
× 100
b
%
T
p
Tp = process period time in s
Tb = braking time in s
P
Tp = period time in s, see Illustration 4.2.
When the kinetic energy transferred to the resistor in each
braking sequence is not known, calculate the average
power on the basis of the process period time and the
braking time.
Calculate the duty-cycle for the braking sequence as
follows:
Duty cycle =
where
4.1.6 Braking of Inertia
When braking high inertia values on the motor shaft, base
the brake resistor values on the inertia, Δω, Δt, see
Illustration 4.3.
Illustration 4.3 Braking of High Inertia
Δt is determined by the ramp-down time.
NOTICE
The ramp-down time goes from the rated motor
frequency to 0 Hz.
Resistor brake is only functional in
frequency converters with integrated
dynamic brake. An external resistor must
be connected.
Resistor Brake
The resistor brake limits voltage in the
intermediate circuit when the motor acts as
generator. Without brake resistor, the frequency
converter eventually trips.
The resistor brake consumes surplus energy
resulting from motor braking. A frequency
converter with brake, stops a motor faster than
without a brake, which is used in many
applications. Requires connection of external
brake resistor.
An alternative to the resistor brake is the AC
brake.
AC Brake
The AC brake consumes surplus energy by
creating power loss in the motor.
It is important to keep in mind that an increase
in power loss causes motor temperature to rise.
* OffNo brake function.
[0]
[1]Resistor
Brake
[2]AC BrakeAC brake is active.
Resistor brake is active.
5.2
Parameters for VLT® HVAC Drive FC 102
and VLT® AQUA Drive FC 202
2-02 DC Braking Time
Range:Function:
10 s* [0 - 60 s] Set the duration of the DC braking current set
in 2-01 DC Brake Current, once activated.
2-03 DC Brake Cut In Speed [RPM]
Range:Function:
Size
related*
[ 0 - 0
RPM]
Set the DC brake cut-in speed to
activate the DC braking current set in
2-01 DC Brake Current, upon a stop
command.
When 1-10 Motor Construction is set to
[1] PM non-salient SPM this value is
limited to 0 RPM (OFF)
NOTICE
Parameter 2-03 DC Brake Cut In Speed [RPM] does nothave effect when 1-10 Motor Construction=[1] PM, nonsalient SPM.
2-04 DC Brake Cut In Speed [Hz]
Range:Function:
Size related* [ 0 - 1000.0
Hz]
Set the DC brake cut-in speed for
activation of the DC braking
current set in 2-01 DC BrakeCurrent, upon a stop command.
NOTICE
Parameter 2-04 DC Brake Cut In Speed [Hz] has no effect
when 1-10 Motor Construction[1] PM, non-salient SPM.
Available selections depend on 1-10 Motor
Construction:
[0] Asynchron:
[0] Off
•
[1] Resistor brake
•
[2] AC brake
•
[1] PM non-salient:
[0] Off
•
[1] Resistor brake
•
[0] OffNo brake resistor installed.
[1] Resistor
brake
[2] AC brake AC Brake only works in Compressor Torque mode
Brake resistor incorporated in the system, for
dissipation of surplus brake energy as heat.
Connecting a brake resistor allows a higher DClink voltage during braking (generating
operation). The resistor brake function is only
active in frequency converters with an integral
dynamic brake.
in 1-03 Torque Characteristics.
2-11 Brake Resistor (ohm)
Range:Function:
Size
related*
[ 5.00 -
65535.00
Ohm]
Set the brake resistor value in Ω. This
value is used for monitoring the power
to the brake resistor in 2-13 Brake PowerMonitoring. This parameter is only active
in frequency converters with an integral
dynamic brake.
Use this parameter for values without
decimals. For a selection with 2 decimals,
use parameter 30-81 Brake Resistor (ohm).
2-12 Brake Power Limit (kW)
Range:Function:
Size
related*
[ 0.001 -
2000.000
kW]
Parameter 2-12 Brake Power Limit (kW) is
the expected average power dissipated in
the brake resistor over the time period
selected within 2-13 Brake PowerMonitoring. It is used as the monitoring
limit for 16-33 Brake Energy /2 min and
thereby specifies when a warning/alarm is
to be given.
To calculate parameter 2-12 Brake PowerLimit (kW), the following formula can be
used.
2
U
V×tbrs
P
br,avg
P
br,avg
the brake resistor, Rbr is the resistance of
the brake resistor. tbr is the active
breaking time within the 120 s period, Tbr.
br
W
=
RbrΩ×Tbrs
is the average power dissipated in
2-12 Brake Power Limit (kW)
Range:Function:
Ubr is the DC voltage where the brake
resistor is active.
NOTICE
If values are unknown, or if Tbr is
different from 120 s, the practical
approach is to run the brake
application, readout 16-33 BrakeEnergy /2 min and then enter this
+20% in 2-12 Brake Power Limit(kW).
2-13 Brake Power Monitoring
Option:Function:
This parameter is only active in frequency
converters with an integral dynamic brake.
This parameter enables monitoring of the
power to the brake resistor. The power is
calculated on the basis of the resistance
(parameter 2-11 Brake Resistor (ohm)), the
DC-link voltage, and the resistor duty time.
The time periode can be selected in this
parameter.
The functions are as follows:
Off:
•
Brake power monitoring disabled.
Default setting.
Warning (time period):
•
Activates a warning on the display
when the power transmitted over
the selected time period exceeds
100% of the monitoring limit
(parameter 2-12 Brake Power Limit(kW)). The warning disappears
when the transmitted power falls
below 80% of the monitoring limit.
Trip (time period);
•
Trips frequency converter and
displays an alarm when the
calculated power exceeds 100% of
the monitoring limit.
Warning & trip (time period):
•
Activates both of the above,
including warning, trip and alarm.
* DisabledBrake power monitoring disabled.
[0]
[1]Warning 120s Warning based on 120 s time periode.
[2]Trip 120sTrip based on 120 s time periode.
[3]Warning &
trip 120s
[4]Warning 30sWarning based on 30 s time periode.
[5]Trip 30sTrip based on 30s time periode
trip 30s
[7]Warning 60sWarning based on 60 s time periode.
[8]Trip 60sTrip based on 60 s time periode.
[9]Warning &
trip 60s
[10] Warning 300s Warning based on 300 s time periode.
[11] Trip 300sTrip based on 300 s time periode.
[12] Warning &
55
trip 300s
[13] Warning 600s Warning based on 600s time periode.
[14] Trip 600sTrip based on 600 s time periode.
[15] Warning &
trip 600s
Warning and trip based on 30 s time
periode.
Warning and trip based on 60 s time
periode.
Warning and trip based on 300 s time
periode.
Warning and trip based on 600 s time
periode.
If power monitoring is disabled or Warning is selected, the
brake function remains active, even if the monitoring limit
is exceeded. This may lead to thermal overload of the
resistor. It is also possible to generate a warning via a
relay/digital outputs. The measuring accuracy of the power
monitoring depends on the accuracy of the resistance of
2-15 Brake Check
Option:Function:
[2] TripMonitors for a short-circuit or disconnection of
the brake resistor, or a short-circuit of the brake
IGBT. If a fault occurs, the frequency converter
cuts out while displaying an alarm (trip locked).
[3] Stop and
trip
[4] AC brake Monitors for a short-circuit or disconnection of
Monitors for a short-circuit or disconnection of
the brake resistor, or a short-circuit of the brake
IGBT. If a fault occurs, the frequency converter
ramps down to coast and then trips. A trip lock
alarm is displayed.
the brake resistor, or a short-circuit of the brake
IGBT. If a fault occurs, the frequency converter
performs a controlled ramp-down.
NOTICE
Remove a warning arising in connection with [0] Off or
[1] Warning by cycling the mains supply. The fault must
be corrected first. For [0] Off or [1] Warning, the
frequency converter keeps running even if a fault is
located.
the resistor (better than ±20%).
2-15 Brake Check
Option:Function:
Select type of test and monitoring function to
check the connection to the brake resistor, or
whether a brake resistor is present, and then
display a warning or an alarm in the event of a
fault. The brake resistor disconnection function is
tested during power-up. However, the brake
IGBT test is performed when there is no braking.
A warning or trip disconnects the brake function.
The testing sequence is as follows:
1.The DC-link ripple amplitude is
measured for 300 ms without braking.
2.The DC-link ripple amplitude is
measured for 300 ms with the brake
turned on.
3.If the DC-link ripple amplitude while
braking is lower than the DC-link ripple
amplitude before braking +1%. Brake
check failed, return a warning or alarm.
4.If the DC-link ripple amplitude while
braking is higher than the DC-link
ripple amplitude before braking +1%.
Brake check OK.
OffMonitors brake resistor and brake IGBT for a
[0]
*
[1] WarningMonitors brake resistor and brake IGBT for a
short-circuit during operation. If a short-circuit
occurs, a warning appears.
short-circuit, and runs a test for brake resistor
disconnection during power-up.
2-16 AC brake Max. Current
Range:Function:
100 %* [ 0 - 1000.0%]Enter the maximum permissible current
when using AC brake to avoid
overheating of motor windings. The AC
brake function is available in Flux mode
only.
NOTICE
Parameter 2-16 AC brake Max. Current has no effect when
1-10 Motor Construction=[1] PM, non-salient SPM.
2-17 Over-voltage Control
Option:Function:
[0]DisabledNo OVC required.
[2] *EnabledActivates OVC.
NOTICE
Parameter 2-17 Over-voltage Control has no effect when
1-10 Motor Construction[1] PM, non-salient SPM.
NOTICE
The ramp time is automatically adjusted to avoid
tripping of the frequency converter.
0 kW* [0 - 10000 kW] View the brake power transmitted to an
external brake resistor, stated as an
instantaneous value.
16-33 Brake Energy /2 min
Range:Function:
0 kW* [0 - 10000
kW]
View the brake power transmitted to an
external brake resistor. The mean power is
calculated on an average level based on
the selected time period within 2-13 BrakePower Monitoring.
30-81 Brake Resistor (ohm)
Range:Function:
Size
related*
[ 0.01 -
65535.00 Ohm]
Set the brake resistor value in Ω
with 2 decimals. This value is used
for monitoring the power to the
brake resistor in 2-13 Brake PowerMonitoring.
5.3
Parameters for VLT® AutomationDrive
FC 301/FC 302 and ® Decentral Drive
FCD 302
2-02 DC Braking Time
Range:Function:
10 s* [0 - 60 s] Set the duration of the DC braking current set
in 2-01 DC Brake Current, once activated.
2-03 DC Brake Cut In Speed [RPM]
Range:Function:
Size related* [ 0 - 60000
RPM]
2-04 DC Brake Cut In Speed [Hz]
Range:Function:
Size related* [ 0 - 1000.0
Hz]
Set the DC brake cut-in speed for
activation of the DC braking
current set in 2-01 DC BrakeCurrent, upon a stop command.
Set the DC brake cut-in speed for
activation of the DC braking
current set in 2-01 DC BrakeCurrent, upon a stop command.
55
NOTICE
Parameter 2-04 DC Brake Cut In Speed [Hz] has no effect
when 1-10 Motor Construction[1] PM, non-salient SPM.
2-10 Brake Function
Option:Function:
[0] OffNo brake resistor is installed.
[1] Resistor
brake
[2] AC brake Is selected to improve braking without using a
A brake resistor is incorporated in the system, for
dissipation of surplus brake energy as heat.
Connecting a brake resistor allows a higher DClink voltage during braking (generating operation).
The resistor brake function is only active in
frequency converters with an integral dynamic
brake.
brake resistor. This parameter controls an
overmagnetisation of the motor when running
with a generatoric load. This function can improve
the OVC-function. Increasing the electrical losses
in the motor allows the OVC function to increase
the braking torque without exceeding the over
voltage limit.
NOTICE
The AC brake is not as efficient as dynamic
braking with resistor.
AC brake is for VVC+ mode in both open
and closed loop.
Set the brake resistor value in Ω. This
value is used for monitoring the power
to the brake resistor in 2-13 Brake PowerMonitoring. This parameter is only active
in frequency converters with an integral
dynamic brake.
Use this parameter for values without
decimals. For a selection with 2 decimals,
use parameter 30-81 Brake Resistor (ohm).
Range:Function:
Size
related*
[ 0.001 -
2000.000
kW]
Parameter 2-12 Brake Power Limit (kW) is
the expected average power dissipated in
the brake resistor over the time period
selected within 2-13 Brake PowerMonitoring. It is used as the monitoring
limit for 16-33 Brake Energy /2 min and
thereby specifies when a warning/alarm is
to be given.
To calculate parameter 2-12 Brake PowerLimit (kW), the following formula can be
used.
2
U
V×tbrs
P
br,avg
P
br,avg
the brake resistor, Rbr is the resistance of
the brake resistor. tbr is the active
breaking time within the 120 s period, Tbr.
Ubr is the DC voltage where the brake
resistor is active.
br
W
=
RbrΩ×Tbrs
is the average power dissipated in
NOTICE
If values are unknown, or if Tbr is
different from 120 s, the practical
approach is to run the brake
application, readout 16-33 BrakeEnergy /2 min and then enter this
+20% in 2-12 Brake Power Limit(kW).
2-13 Brake Power Monitoring
Option:Function:
This parameter is only active in frequency
converters with an integral dynamic brake.
This parameter enables monitoring of the
power to the brake resistor. The power is
calculated on the basis of the resistance
(parameter 2-11 Brake Resistor (ohm)), the
DC-link voltage, and the resistor duty time.
The time periode can be selected in this
parameter.
The functions are as follows:
2-13 Brake Power Monitoring
Option:Function:
Off:
•
Brake power monitoring disabled.
Default setting.
Warning (time period):
•
Activates a warning on the display
when the power transmitted over
the selected time period exceeds
100% of the monitoring limit
(parameter 2-12 Brake Power Limit(kW)). The warning disappears
when the transmitted power falls
below 80% of the monitoring limit.
Trip (time period);
•
Trips frequency converter and
displays an alarm when the
calculated power exceeds 100% of
the monitoring limit.
Warning & trip (time period):
•
Activates both of the above,
including warning, trip and alarm.
[0] * DisabledBrake power monitoring disabled.
[1]Warning 120s Warning based on 120 s time periode.
[2]Trip 120sTrip based on 120 s time periode.
[3]Warning &
trip 120s
[4]Warning 30sWarning based on 30 s time periode.
[5]Trip 30sTrip based on 30s time periode
[6]Warning &
trip 30s
[7]Warning 60sWarning based on 60 s time periode.
[8]Trip 60sTrip based on 60 s time periode.
[9]Warning &
trip 60s
[10] Warning 300s Warning based on 300 s time periode.
[11] Trip 300sTrip based on 300 s time periode.
[12] Warning &
trip 300s
[13] Warning 600s Warning based on 600s time periode.
[14] Trip 600sTrip based on 600 s time periode.
[15] Warning &
trip 600s
Warning and trip based on 120 s time
periode.
Warning and trip based on 30 s time
periode.
Warning and trip based on 60 s time
periode.
Warning and trip based on 300 s time
periode.
Warning and trip based on 600 s time
periode.
If power monitoring is disabled or Warning is selected, the
brake function remains active, even if the monitoring limit
is exceeded. This may lead to thermal overload of the
resistor. It is also possible to generate a warning via a
relay/digital outputs. The measuring accuracy of the power
monitoring depends on the accuracy of the resistance of
the resistor (better than ±20%).
Parameter 2-15 Brake Check is only active in
frequency converters with an integral dynamic
brake.
Select type of test and monitoring function to
check the connection to the brake resistor, or
whether a brake resistor is present, and then
display a warning or an alarm in the event of a
fault.
NOTICE
The brake resistor disconnection function
is tested during power-up. However, the
brake IGBT test is performed when there is
no braking. A warning or trip disconnects
the brake function.
The testing sequence is as follows:
1.The DC-link ripple amplitude is
measured for 300 ms without braking.
2.The DC-link ripple amplitude is
measured for 300 ms with the brake
turned on.
3.If the DC-link ripple amplitude while
braking is lower than the DC-link ripple
amplitude before braking + 1%: Brake
check has failed by returning a warning
or alarm.
4.If the DC-link ripple amplitude while
braking is higher than the DC-link ripple
amplitude before braking + 1%: Brake
check is OK.
OffMonitors brake resistor and brake IGBT for a
[0]
*
[1] WarningMonitors brake resistor and brake IGBT for a
[2] TripMonitors for a short-circuit or disconnection of
[3] Stop and
trip
[4] AC brake Monitors for a short-circuit or disconnection of
short-circuit during operation. If a short-circuit
occurs, warning 25 appears.
short-circuit, and runs a test for brake resistor
disconnection during power-up.
the brake resistor, or a short-circuit of the brake
IGBT. If a fault occurs, the frequency converter
cuts out while displaying an alarm (trip locked).
Monitors for a short-circuit or disconnection of
the brake resistor, or a short-circuit of the brake
IGBT. If a fault occurs, the frequency converter
ramps down to coast and then trips. A trip lock
alarm is displayed (e.g. warning 25, 27 or 28).
the brake resistor, or a short-circuit of the brake
IGBT. If a fault occurs, the frequency converter
performs a controlled ramp-down. This option is
available for FC 302 only.
2-15 Brake Check
Option:Function:
[5] Trip Lock
NOTICE
Remove a warning arising in connection with [0] Off or
[1] Warning by cycling the mains supply. The fault must
be corrected first. For [0] Off or [1] Warning, the
frequency converter keeps running even if a fault is
located.
2-16 AC brake Max. Current
Range:Function:
100 %* [ 0 - 1000.0 %] Enter the maximum permissible current
when using AC brake to avoid
overheating of motor windings.
NOTICE
Parameter 2-16 AC brake Max. Current has no effect when
1-10 Motor Construction[1] PM, non salient SPM.
2-17 Over-voltage Control
Option:Function:
Overvoltage control (OVC) reduces the risk
of the frequency converter tripping due to
an overvoltage on the DC-link caused by
generative power from the load.
[0] * DisabledNo OVC required.
[1]Enabled (not
at stop)
[2]EnabledActivates OVC.
Activates OVC except when using a stop
signal to stop the frequency converter.
NOTICE
Do not enable OVC in hoisting applications.
2-18 Brake Check Condition
Range:Function:
[0] * At Power UpBrake check is performed at power
up.
[1]After Coast Situations Brake check is performed after coast
situations.
16-32 Brake Energy /s
Range:Function:
0 kW* [0 - 10000 kW] View the brake power transmitted to an
external brake resistor, stated as an
instantaneous value.
View the brake power transmitted to an
external brake resistor. The mean power is
calculated on an average level based on
the selected time period within 2-13 BrakePower Monitoring.
30-81 Brake Resistor (ohm)
Range:Function:
Size
55
related*
[ 0.01 -
65535.00
Ohm]
Set the brake resistor value in Ω. This
value is used for monitoring the
power to the brake resistor in
2-13 Brake Power Monitoring. This
parameter is only active in frequency
converters with an integral dynamic
brake.
5.4
Parameters for VLT® AutomationDrive
FC 360
2-10 Brake Function
Option:Function:
[0]*OffNo brake resistor is installed.
[1]Resistor
brake
[2]AC brake Improves braking without using a brake resistor.
A brake resistor is incorporated in the system for
dissipation of surplus brake energy as heat.
Connecting a brake resistor allows a higher DClink voltage during braking (generating
operation). The brake resistor function is only
active in frequency converters with an integral
dynamic brake.
This parameter controls an overmagnetisation of
the motor when running with a generatoric load.
This function can improve the OVC-function.
Increasing the electrical losses in the motor
allows the OVC-function to increase braking
torque without exceeding the voltage limit.
NOTICE
The AC brake is not as efficient as
dynamic braking with resistor.
AC brake is for VVC+ mode in both open
and closed loop.
2-11 Brake Resistor (ohm)
Range:Function:
Size
related*
[ 0 65535
Ohm]
Set the brake resistor value in Ω. This
value is used for monitoring the power to
the brake resistor. Parameter 2-11 BrakeResistor (ohm) is only active in frequency
converters with an integral dynamic brake.
Use this parameter for values without
decimals.
2-12 Brake Power Limit (kW)
Range:Function:
Size
related*
[0.001
- 2000
kW]
Parameter 2-12 Brake Power Limit (kW) is the
expected average power dissipated in the
brake resistor over a period of 120 s. It is
used as the monitoring limit for 16-33 BrakeEnergy /2 min and thereby specifies when a
warning/alarm is to be given.
To calculate parameter 2-12 Brake PowerLimit (kW), the following formula can be
used.
brake resistor. tbr is the active breaking time
within the 120 s period, Tbr.
Ubr is the DC voltage where the brake
resistor is active. This depends on the unit
as follows:
T4 units: 778 V
NOTICE
If Rbr is not known or if Tbr is different
from 120 s, the practical approach is
to run the brake application, readout
16-33 Brake Energy /2 min and then
enter this + 20% in 2-12 Brake PowerLimit (kW).
2-16 AC Brake, Max current
Range:Function:
100 %* [0 - 160%]Enter the maximum permissible current
when using AC brake to avoid overheating
of motor windings.
NOTICE
Parameter 2-16 AC Brake, Max current
has no effect when 1-10 Motor
Construction is set to [1] PM, nonsalient SPM.
2-17 Over-voltage Control
Option:Function:
Overvoltage control (OVC) reduces the risk of
the frequency converter tripping due to an
overvoltage on the DC-link caused by
generative power from the load.
[0] * DisabledNo OVC required.
[1]Enabled
(not at
stop)
[2]EnabledActivates OVC
Activates OVC except when using a stop signal
to stop the frequency converter.
WARNING
Do NOT enable OVC in hoisting
applications.
5.5
Parameters for VLT® 2800
126 DC brake time
Range:Function:
10 sec* [0 - 60 sec.] The DC brake time is set at which
parameter 132 DC brake voltage is to be
active.
127 DC brake cut-in frequency
Range:Function:
0.00 OFF* [0.0 (OFF) par. 202]
Set the DC brake cut-in frequency at
which the DC brake is to be
activated in connection with a stop
command.
132 DC brake voltage
Range:Function:
0%* [0 - 100% of
max. DC
brake
voltage]
Set the DC brake voltage to be activated at
stop when the DC brake frequency set in
parameter 127 DC brake cut-in frequency is
reached, or if DC braking inverse is active via
a digital input or via serial communication.
Subsequently, the DC brake voltage is active
for the time set in parameter 126 DC braketime.
400 Brake function
Option:Function:
[0] Off
[1] Resistor
brake
[4] AC brake
[5] Load
sharing
Select [1] Resistor brake if the frequency
converter has an integral brake transistor, and a
brake resistor is connected to terminals 81, 82.
A higher DC-link voltage is permitted during
braking (generated operation) when a brake
resistor is connected.
Select [4] AC brake to improve braking without
using brake resistors. Note that [4] AC brake is
not as effective as [1] Resistor brake.
NOTICE
Disconnected and reconnect mains voltage to activate a
change of selection.
Set the voltage by which the level for
resistor braking is reduced. It is only
active when [1] Resistor is selected in
parameter 400 Brake function.
NOTICE
The greater the reduction value, the faster the reaction
to a generator overload. Should only be used if there are
problems with overvoltage in the DC-link voltage.
Illustration 6.1 shows the relation between the braking
power and the acceleration/braking of a conveyor belt.
Note:
The motor power during braking is negative,
•
since the torque on the motor shaft is negative.
The motor power is time-dependent.
•
The braking power (the power to be dissipated to the
brake resistor) corresponds almost exactly to the negative
motor power plus losses in the motor and the frequency
converter.
Kinetic energy (E) in conveyor belt + motor:
E
= 0. 5 × m ×
where
m = mass with linear movement [kg]
v = speed of mass with linear movement [m/s]
j = inertia of motor and gear box [kgm2]
ω = motor speed [rad/s]
2
v
+ 0 .5 × j × ω
2
Ws
Insert:
n
× 2π
ω
=
60
The result is:
E
= 0 .5×
b
2
m v
+ 0 .0055×
2
j
×
n
−0 .052× n ×
M
×
η
Ws
f
M
66
n
ω
= motor speed =
× 2π
60
rad /
s
This formula is also expressed as follows:
E
= 0. 50 × m ×
2
v
+ 0 .0055 × j ×
n2Ws
However, not all of the energy is dissipated in the brake
resistor. The friction of the conveyor belt and the power
loss of the motor also contribute to the braking function.
So, the formula for energy dissipation (Eb) to the brake
resistor is as follows: