This manual provides information on how to design and
implement center winder control and positioning control
applications with FC 360 frequency converters. It does not
cover general design, installation and commissioning of
the frequency converter.
VLT® is a registered trademark.
Prerequisites
The manual is intended for use by qualified personnel who
are familiar with the functions of VLT® AutomationDrive FC
360 and have hands-on experience with installing and
commissioning FC 360 frequency converters. The
frequency converter should be installed and commissioned
according to the FC 360 Quick Guide. Users of this manual
should have the Quick Guide at hand for reference.
1.2 Additional Resources
Additional resources are available to understand frequency
converter functions and programming.
VLT® AutomationDrive FC 360 Quick Guide,
•
provides information required to install and
commission the frequency converter.
VLT® AutomationDrive FC 360 Design Guide,
•
provides detailed information about the design
and applications of the frequency converter.
VLT® AutomationDrive FC 360 Programming Guide,
•
provides information on how to programme and
includes complete parameter descriptions.
Contact the local Danfoss supplier for the printed
documentation.
1.3
Document and Software Version
This manual is regularly reviewed and updated. All
suggestions for improvement are welcome. Table 1.1 shows
the document version and the corresponding software
version.
In the frequency converter, read the software version in
15-43 Software Version.
1.4
Abbreviations and Conventions
ACAlternating current
AEOAutomatic energy optimisation
ACPApplication control processor
AWGAmerican wire gauge
AMAAutomatic motor adaptation
°C
DCDirect current
EEPROM
EMCElectromagnetic compatibility
EMIElectromagnetic interference
ETRElectronic thermal relay
f
M,N
FCFrequency converter
IPIngress protection
I
LIM
I
INV
I
M,N
I
VLT,MAX
I
VLT,N
L
d
LCPLocal control panel
MCPMotor control processor
N.A.Not applicable
P
M,N
PCBPrinted circuit board
PEProtective earth
PELVProtective extra low voltage
PWMPulse width modulated
R
s
RegenRegenerative terminals
RPMRevolutions per minute
RFIRadio frequency interference
SCRSilicon controlled rectifier
SMPSSwitch mode power supply
T
Current limit
Rated inverter output current
Nominal motor current
Maximum output current
Rated output current supplied by the
frequency converter
d-axis inductance
Indicates a potentially hazardous situation that could
result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that could
result in minor or moderate injury. It can also be used to
alert against unsafe practices.
NOTICE
Indicates important information, including situations that
can result in damage to equipment or property.
2.2 Qualified Personnel
WARNING
UNINTENDED START
When the frequency converter is connected to AC mains,
DC supply, or load sharing, the motor may start at any
time. Unintended start during programming, service, or
repair work can result in death, serious injury, or
property damage. The motor can start via an external
switch, a serial bus command, an input reference signal
from the LCP, or after a cleared fault condition.
To prevent unintended motor start:
Disconnect the frequency converter from the
•
mains.
Press [Off/Reset] on the LCP before
•
programming parameters.
Fully wire and assembly the frequency
•
converter, motor, and any driven equipment
before connecting the frequency converter to
AC mains, DC supply, or load sharing.
Correct and reliable transport, storage, installation,
operation, and maintenance are required for the troublefree and safe operation of the frequency converter. Only
qualified personnel are allowed to install or operate this
equipment.
Qualified personnel are defined as trained staff, who are
authorised to install, commission, and maintain equipment,
systems, and circuits in accordance with pertinent laws and
regulations. Additionally, the personnel must be familiar
with the instructions and safety measures described in this
manual.
2.3
Safety Precautions
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when
connected to AC mains input, DC supply, or load sharing.
Failure to perform installation, start-up, and maintenance
by qualified personnel can result in death or serious
injury.
Installation, start-up, and maintenance must be
•
performed by qualified personnel only.
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors,
which can remain charged even when the frequency
converter is not powered. Failure to wait the specified
time after power has been removed before performing
service or repair work, could result in death or serious
injury.
1.Stop the motor.
2.Disconnect AC mains, permanent magnet type
motors, and remote DC-link power supplies,
including battery back-ups, UPS, and DC-link
connections to other frequency converters.
3.Wait for the capacitors to discharge fully, before
performing any service or repair work. The
duration of waiting time is specified in
Table 2.1.
Minimum waiting time (minutes)
Voltage [V]
415
380–4800.37–7.5 kW11–75 kW
High voltage may be present even when the warning LEDs are
off.
Leakage currents exceed 3.5 mA. Failure to ground the
frequency converter properly can result in death or
serious injury.
Ensure the correct grounding of the equipment
•
by a certified electrical installer.
WARNING
EQUIPMENT HAZARD
Contact with rotating shafts and electrical equipment
can result in death or serious injury.
Ensure that only trained and qualified
•
personnel perform installation, start up, and
maintenance.
Ensure that electrical work conforms to national
•
and local electrical codes.
Follow the procedures in this document.
•
22
CAUTION
INTERNAL FAILURE HAZARD
An internal failure in the frequency converter can result
in serious injury, when the frequency converter is not
properly closed.
Ensure that all safety covers are in place and
•
securely fastened before applying power.
NOTICE
HIGH ALTITUDES
For installation at altitudes above 2000 m, contact
Danfoss regarding PELV.
NOTICE
Use on Isolated Mains
For details about the use of the frequency converter on
isolated mains, refer to section RFI Switch in the DesignGuide.
Follow the recommendations regarding the installation
on IT-mains. Use relevant monitoring devices for ITmains to avoid damage.
Center winders are widely used in the processing of
materials such as cloth, plastics, paper, and sheet metal.
Center winder control is to maintain a stable tension on
the line or web of the material during the winding process.
The center winder control in FC 360 uses a speed-based method with tension feedback. The tension feedback is provided
by either a load cell or a dancer. Illustration 3.1 shows the control diagram of a center winder system.
Instable tension may cause physical deformities of the
material. Because the diameter of the roll changes
constantly, the winding or unwinding speed must be
adapted to maintain a stable tension.
Control principle
Illustration 3.1 Control Diagram of a Center Winder System
The center winder control calculates the roll diameter and feed the frequency converter with an open-loop speed reference.
A PID amplifier compares the actual tension feedback with the tapered tension setpoint, and generates a speed signal
based on the error. The speed signal is aggregated with the speed reference signal to determine the actual winder speed.
Roll diameter
This calculation needs to be performed fast, because the diameter of the roll changes faster when the roll is near the core. If
the actual diameter changes faster than the diameter is calculated, the open-loop reference speed lags too far behind the
required speed, and the tension PID will need to make up too much of the difference.
The tension PID updates every 16 ms. The calculated diameter is used by both the open-loop reference and as an input to
the tension PID.
The tapered tension setpoint is the tension setpoint modified based on the roll diameter and the taper setpoint. Taper
generally reduces the tension setpoint hyperbolically with a change in diameter. The PID amplifier output decreases as the
diameter increases, because the same change in reference will have a larger surface speed change as the roll increases in
diameter. Ideally, the open-loop reference signal is scaled at core so that the surface speed of the core matches line speed.
The diameter value is calculated based on the equation below.
An encoder on the feed-roll or lead-roll motor provides the line speed. An encoder on the winder motor provides the motor
speed. The winder speed is the current motor speed multiplies the gear ratio.
Illustration 3.2 shows the control diagram for center winder applications with FC 360 frequency converters. The amplitude of
accommodation depends on the change of diameter and the difference between tension feedback and tension setpoint.
33
Illustration 3.2 Center Winder Control with FC 360
The frequency converter adjusts the operation of the winder based on the states of a roll, such as ready-to-run, end-of-roll,
running-on-tension-loop and tension-over-limit. For example, a frequency converter can stop winding for a roll change.
The frequency converter can be controlled through either digital inputs or PROFIBUS.
Features
3.1.1
The following features are provided to increase the overall
stability of the winder, and improve the control and
monitoring of the winding process.
•
Acceleration feed-forward: This function allows a
shift in the tension/taper setpoint based on
changes in line speed. It provides a tension boost
•
during initial acceleration to help compensate for
system inertia.
Tension-taper setpoint ramp: The tapered tension
setpoint generator integrates any changes to the
scans. A parameter is provided to increase or
decrease response time.
Diameter calculator minimum speed: There is also
•
a minimum speed requirement to enable the
diameter calculator. At low speeds, the line and
winder speeds may not have enough resolution
to accurately calculate diameter. A parameter is
provided to define a minimum line speed
required for the diameter calculator to function.
Until that speed is reached, the diameter value
will not change.
are analog inputs with a voltage range of 0–10 V
DC or a current range of 0/4–20 mA. Use
6-19 Terminal 53 mode and 6-29 Terminal 54 mode
to configure the inputs. The source of the tension
and taper setpoints can be adjusted by either
33
analog inputs or parameter setting. Only analog
inputs can be used for tension feedback and
initial diameter measurement. Use parameters to
select the source of each input. Do not program
a single input for more than one functions.
Initial diameter measurement: 3 starting
•
diameters can be set and logically selected. For
applications where the starting diameter changes
regularly, the winder allows the initial diameter to
be measured through an analog input signal.
Scaling parameters are provided to set the analog
level at core and at full roll. This function
assumes a linear change in the diameter
measurement signal.
End-of-roll detection: The frequency converter
•
generates an output to indicate a preset diameter
limit is met. This output can be used to stop
winding for a roll change.
Tension limit detector: The winder includes a
•
tension limit detection (TLD) feature. This feature
allows the winding machine to trip if a lowtension or high-tension feedback exists for a
period of time. The trip delay includes a normal
running delay as well as a secondary starting
delay.
3.2 Application Requirements
For the center winder system to operate properly, the
following requirements must be met:
Winder motor
•
The motor needs to be frequency converter duty
with a wide speed range (>100:1). The motor
should be geared or belted so that top motor
speed at core does not exceed 4500 RPM.
Generally, the maximum constant-horsepower
speed of the motor is the limiting factor.
Tension feedback
•
The tension feedback is provided from either a
load cell or a dancer. If a load cell is used, it
needs to be calibrated for a either a 0-20 mA or
0-10 V signal for 0 to maximum tension. If a
dancer is used, the calibration should be 0–20
mA/0–10 V for bottom-to-top of the dancer
movement.
Logic inputs
•
Digital inputs are used as signals for statuses
such as tension-on, over-tension, or undertension. They are 24 V DC sinking inputs, and
only necessary when used for controlling. The
frequency converter has a 24 V DC/200 mA
supply available if dry contacts are used. It is
possible to access logic parameters through
PROFIBUS.
Tension and taper setpoints
•
The tension and taper setpoints are available on
the display of the local control panel (LCP) as
parameters. They can also be set using 0–20 mA
or 0–10 V DC input, or via PROFIBUS.
ParameterValue or range
Maximum winder motor
speed
Tension loop control cycle16 ms
TLD time resolution25 ms
Quick stop scan time1 ms
Coast scan time<1 ms
MCB 102 frequency100–410000 Hz
24 V encoder frequency4–32000 kHz
Digital inputs24 V DC, sinking
Analog tension and taper
setpoints
Load cell or dancer feedback 0–10 V DC, 0–20 mA DC
Table 3.1 Recommended Parameter Settings
Line speed
Create or simulate a line speed signal of winder mode.
Ensure that 18-83 Line Speed shows the correct feedforward speed, which is a positive value. Otherwise check
wiring and the parameters in parameter group 17.
Winder speed
Have the motor run in the direction of winding mode.
Confirm that parameter 16-05 Main Actual Value [%] shows
the correct motor speed, which is a positive value.
Tension feedback
Create or simulate a tension on the web. Confirms that
18-86 Tension Feedback shows the correct tension value.
Otherwise check parameters 6-10 to 6-29.
run the winding machine without material to the
maximum speed.
Confirm that the diameter remains very close to
•
the core diameter value. Otherwise recalculate
the value of parameter 37-46 Winder Speed MatchScale.
To set this parameter, the winding machine must run
without material. If this is not possible, empirical
calculations must be performed first. Set the winder speed
match scale parameter by completing the steps below:
1.Mount the smallest empty core on the winding
machine.
2.
Ensure that the core size (parameter 37-24 Core1Diameter) is set correctly. The value entered is a
percentage of the full roll value. For example, if
using a 20 inch full roll with a 3.75 inch core,
3.Use core1 diameter as preset diameter and set
parameter parameter 37-59 Diameter Reset to [1]On. Confirms that parameter 19-97 is the value
set in parameter 37-24 Core1 Diameter.
4.
Set parameter 37-57 Tension On/Off to [1] On and
initiate a start signal.
5.
Adjust parameter parameter 37-46 Winder SpeedMatch Scale to make sure core surface speed
matches the surface speed of the main line
selection.
Empirical calculation is performed as follows:
Parameter 37-46 Winder Speed Match
Scale=Parameter 37-24 Core1 Diameter/lead roll diameter
To use DI for logic control, set parameter 37-40 Center
Winder Cmd Src to [2] Digital input control, and select
functions in the corresponding DI input (parameters 5-10
to 5-16).
Using DI for logic control
There are 6 logic commands that can be sent via
•
digital inputs:
Core diameter source.
-
Select a new diameter.
-
Reset the diameter.
-
Center winder jog forward.
-
Center winder tension on.
-
Empirical calculation is performed as follows:
Parameter 37-46 Winder Speed Match
Scale=parameter 37-24 Core1 Diameter/lead roll diameter
Tightening the slack web
•
1.Give an appropriate jog speed by
setting parameter 37-26 Winder JogSpeed.
2.
Set parameter 37-57 Tension On/Off to [0]Off.
3.
Set parameter 37-54 Winder Jog Reverse
or parameter 37-55 Winder Jog Forward
to 1 until the slack web is tightened.
Setting up starting diameter
•
If the winding machine starts with an empty core,
set the value in parameter 37-24 Core1 Diameter
to the starting diameter value.
If the winding machine starts with a partial roll or
unwinding, measure the diameter value and enter
the value in parameter 37-23 Partial Roll DiameterValue. Select the partial roll diameter as the
starting diameter.
Protecting the system from over-tension
•
Set parameter 37-27 TLD Low Limit and
parameter 37-28 TLD High Limit to applicable
values, so that the frequency converter stops if
tension is out of the range defined in these 2
parameters.
3.3
Wiring and Control Process
Wiring
1.Connect the load cell or dancer to analog input
53.
2.Connect the line encoder to MCB 102.
3.Connect the winding machine encoder to 24 V
encoder interface (digital inputs 12, 20, 32, 33).
4.Connect digital output 29 to the winding
machine as end-of-roll signal source.
5.Connect digital output 27 to the winding
machine as TLD-indicator signal source.
6.Connect digital output 45 to the winding
machine as ready-to-run signal source.
7.If a dancer is used, connect analog output 42 to
the winding machine as tapered-tension-setpoint
signal source.
Control process
Wind up the machine, starting with an empty
•
core.
Set up parameters as shown in Table 3.2. The
•
values in the table serve as examples only. Actual
settings may differ and should be based on
actual application situations.
Tighten the slack web until the tension is within
•
the valid range defined in parameter 37-27 TLD
Low Limit and parameter 37-28 TLD High Limit.
Refer to chapter 3.2.1 Application Requirements for
information about how to tighten a slack web.