Danfoss VLT AutomationDrive FC 302 with Connectors Installation Instructions Manual

NOTICE
VLT® AutomationDrive FC 302 with connectors is NOT UL approved.
The ETR functionality is not guaranteed.
General rating: Enclosure IP55.
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors, which can remain charged even when the frequency converter is not powered. Failure to wait the specified time after power has been removed before performing service or repair work, could result in death or serious injury.
1. Stop the motor.
2. Disconnect AC mains, permanent magnet type motors and remote DC-link power supplies, including battery back-ups, UPS, and DC-link connections to other frequency converters.
3. Wait for the capacitors to discharge fully, before performing any service or repair work. The duration of waiting time is specified in Table 2.1.
Voltage
[V]
Power range
[kW]
Minimum waiting
time (minutes)
3x400 0.55–7.5 4
High voltage can be present even when the warning LED indicator
lights are off.
Table 2.1 Discharge Time
3Items Supplied
Depending on the ordering number, the following is supplied:
FC 302 with connectors - 2 motor connectors (134N3195)
Illustration 3.1 2 Motor Connectors
Installation Instructions
VLT® AutomationDrive FC 302 with Connectors
Danfoss A/S © Rev. 06/2014 All rights reserved. MI04G102
FC 302 with connectors - 4 motor connectors (134N3196)
Illustration 3.2 4 Motor Connectors
FC 302 with connectors - side view
Illustration 3.3 Side View
For overall dimensions, refer to the VLT® AutomationDrive FC 302 Design Guide.
NOTICE
See the VLT® AutomationDrive FC 302 Design Guide for further information.
4 Connectors
4.1 Overview
The frequency converter has 7 connectors plus 2 or 4 motor connectors
Label Connector Description
X1 Mains Mains in M23 (in M25) Male
X2.1-X2.4 Motor Motor connection M23 Female
X51 PROFIBUS - Male PROFIBUS M12
X52
PROFIBUS -
Female PROFIBUS M12
X11-X14 I/O box connector Phoenix I/O box
Table 4.1 Connectors
4.2 X1- Mains M23 (in M25) Male
General ratings
Pins 1, 2, 3 and 4: 480 V AC, maximum 15 A
Pins C and D: 30 V DC, maximum 3 A
Tightening torque: 1.5–2.0 Nm
Pin Label Connected to frequency
converter wiring schematic
Min. wire
[mm
2
]
1L1 91 (T1) 2.5
4L2 92 (T2) 2.5
3L3 93 (T3) 2.5
2PE 95 (PE) 2.5
D 0 V DC 35 2.75
C 24 V DC 36 2.75
Table 4.2 Wire/Connector Assignment for Plug X1
Mating part: Mains X1 (female) Phoenix order number.: KK-0885/XX,XX
Installation Instructions VLT® AutomationDrive FC 302 with Connectors
2
Danfoss A/S © Rev. 06/2014 All rights reserved. MI04G102