Danfoss VLT AutomationDrive Fact sheet

Page 1
VLT® AutomationDrive
The premier, globally supported drive concept for exceptional control of motor driven applications.
Designed for variable speed con­trol of all asynchronous motors and permanent magnet motors, on any in­dustrial machine or production line, a VLT® AutomationDrive helps its owner save energy, increase exibility, and optimize processes.
Flexible and expandable
Built on a exible, modular design concept the AutomationDrive is packed with standard, industry features out of the box. These can be expanded with plug-and-play options with additional features, positioning control, eldbuses, safety functions such as STO, SS1, SLS, SMS and SSM, motor protection and more.
Robust and safe
VLT AutomationDrives are proven performers in all industrial environ­ments and grid voltages, including 690V. Enclosures are available up
to IP 66 (depending on model), and integrated DC chokes and RFI lters in all models protect installations by minimizing harmonic distortion and electromagnetic interferences. All drives are fully tested at the factory before they are shipped.
Easy to set up and operate via the user-friendly graphical control panel, a VLT AutomationDrive only requires little maintenance once in operation. The result is an market leading control solution that provides a fast return on investment and a highly competitive cost of ownership.
Power range
3 x 200 – 240 V ..................... 0.25 – 37 kW
3 x 380 – 480/500 V ......... 0.37 – 800 kW
3 x 525 – 600 V .............. 0.75 kW – 75 kW
3 x 525 – 690 V .............. 1.1 kW – 1.2 MW
Normal overload ..........1.5 kW – 1.4 MW
98%
Energy efficiency
Optmize processes while reducing energy costs. Versatile, flexible, configurable and built to last.
Feature Benet
Reliable Maximum uptime
Ambient temperature 50° C without derating Less need for cooling or oversizing Available in IP 00, 20, 21, 54, 55
and 66 enclosures Resistant to wear and tear Low lifetime cost Back-channel cooling for frame D, E and F Prolonged lifetime of electronics
User-friendly Saves commissioning and operating cost
Plug-and-Play technology Easy upgrade and changeover Awarded control panel User-friendly Intuitive VLT® interface Saves time Pluggable cage clamp connectors Easy connection Exchangeable languages User-friendly
Intelligent
Intelligent warning systems Warning before controlled stop Smart Logic Control Reduces need for PLC capacity Advanced plug-in features Easy commissioning
Safe stop
STO: Safe Torque O (IEC 61800-5-2)
Intelligent heat management Intelligent heat management
Enclosures for all environments
Safety cat. 3, PL d (ISO 13849-1), Stop cat. 0 (EN 60204-1)
SIL 2 (IEC 61508) SIL CL 2 (IEC 62061)
Facts about our products
Page 2
Fieldbus options
n VLT® PROFIBUS DP MCA 101 n VLT® DeviceNet MCA 104 n VLT® CanOpen MCA 105 n VLT® Probus Converter MCA 113 n VLT® Probus Converter MCA 114 n VLT® PROFINET MCA 120 n VLT® Ethernet/IP MCA 121 n VLT® Modbus TCP MCA 122 n VLT® POWERLINK MCA 123 n VLT® EtherCAT MCA 124 n VLT® DeviceNet Converter MCA 194
I/O and feedback options
n VLT® General Purpose I/O MCB 101 n VLT® Encoder Input MCB 102 n VLT® Resolver Input MCB 103 n VLT® Relay Card MCB 105 n VLT® 24 V External Supply MCB 107 n VLT® Extended Relay Card MCB 113 n VLT® Sensor Input MCB 114
Safety options
n VLT® Safe PLC I/O MCB 108 n VLT® PTC Thermistor Card MCB 112 n VLT® Safe Option MCB 140 Series n VLT® Safe Option MCB 150 Series
Motion Control Options
n VLT® Motion Control Option
MCO 305
n VLT® Synchronizing Controller
MCO 350
n VLT® Position Controller MCO 351 n VLT® Center Winder MCO 352
Power options
n VLT® Brake resistors MCE 101 n VLT® Sine-Wave Filters MCC 101 n VLT® dU/dt Filters MCC 102 n VLT® Common Mode Filter MCC 105 n VLT® Advanced Harmonic Filters
AHF 005/010
Other accessories
n
IP 21/NEMA 1 Kit (convert IP 20 to IP 21)
n PROFIBUS adapter n Sub-D9 Connector n Decoupling plate for
eldbus cables
n USB connection cable to PC n Panel Through option n LCP panel mounting kit
Specications
Mains supply (L1, L2, L3)
Supply voltage
Supply frequency 50/60 Hz True Power Factor (λ) 0.92 nominal at rated load Displacement Power Factor (cos φ) near unity (> 0.98) Switching on input supply L1, L2, L3 Maximum 2 times/min.
Output data (U, V, W)
Output voltage 0–100% of supply voltage
Output frequency
Switching on output Unlimited Ramp times 1–3600 sec.
Note: 160% current can be provided for 1 minute. Higher overload rating is achieved by oversizing the drive.
Digital inputs
Programmable digital inputs FC 301: 4 (5) / FC 302: 4 (6) Logic PNP or NPN Voltage level 0–24 VDC
Note: One/two digital inputs can be programmed as digital output for FC 301/FC 302.
Analogue input
Analogue inputs 2 Modes Voltage or current
Voltage level
Current level
Pulse/encoder inputs
Programmable pulse/encoder inputs FC 301: 1 / FC 302: 2 Voltage level 0 – 24 V DC (PNP positive logic)
Digital output*
Programmable digital/pulse outputs FC 301: 1 / FC 302: 2 Voltage level at digital/frequency output 0 – 24 V
Analogue output*
Programmable analogue outputs 1 Current range 0/4–20 mA
Relay outputs*
Programmable relay outputs FC 301: 1 / FC 302: 2
Cable lengths
Max. motor cable lengths
*More analogue and digital inputs/outputs can be added with options.
n Mounting brackets n Mains disconnect option n USB Extension n Interbus gateway MCA 110 n Option Adapter n RCMB20/RCMB35 Leakage Current
Monitor Module
Brake chopper (IGBT) option
Limits the load on the intermediate circuit in the case the motor acts as a generator.
200 – 240 V ±10% FC 301: 380 – 480 V ±10% FC 302: 380 – 500 V ±10%, 525 – 600 V ±10% 525 – 690 V ±10%
FC 301: 0.2 – 590 Hz (0.25 – 75 kW) FC 302: 0 – 590 Hz (0.25 – 75 kW) 0 – 590 Hz (90 – 1200 kW) 0 – 300 Hz (Flux mode)
FC 301: 0 to +10 V FC 302: -10 to +10 V (scaleable)
0/4 to 20 mA (scaleable)
FC 301: 50 m / FC 302: 150 m
(screened/armoured)
FC 301: 75 m / FC 302: 300 m
(unscreened/unarmoured)
High power options
n
Emergency stop with Safety Relay
n
Safety Stop with Safety Relay
n
RFI Filters
n
NAMUR terminals
n
Residual Current Device
n
Insulation Resistance Monitor
n
Mains shielding
n
Regen terminals
Please see the VLT® High Power Drive Selection Guide for the complete range of options.
Danfoss VLT Drives, Ulsnaes 1, DK-6300 Graasten, Denmark, Tel. +45 74 88 22 22, Fax +45 74 65 25 80 www.danfoss.com/drives • E-mail: info@danfoss.com
DKDD.PFP.301.A3.02 VLT® is a trademark of Danfoss A/S Produced by PE-MMSC 2014.09