IP 66/Type 4x enclosed
VLT® drives up to 90 kW
IP 66/Type 4x enclosed VLT® frequency converters cover the range from 0.25 to 90 kW,
allowing for mounting near the motor in harsh environments.
Perfect
match for:
– Installation in wash-down
areas
– Pump stations
– Rooftop condenser fans
(if protected against icing)
VLT® AutomationDrive, VLT® HVAC
Drive and VLT® AQUA Drive come in
IP 66/Type 4x versions covering 0.25
to 90 kW (normal overload).
IP 66/Type 4x drives are suitable for
installation in wash-down areas in
food & beverage plants, as well as outdoor in wastewater plants or on
rooftop airhandling units. The drives
are built to withstand harsh cleaning
agents and corrosive air.
IP 66/Type 4x drives can be installed
directly at the processing equipment
without the need for protective cover.
Feature Benet
All cast aluminium parts are powder coated
with a strong epoxy coating
All screws are stainless Less maintenance
Fan designed to withstand corrosion Reliable operation
– Can be installed near the motor
– Built in EMC lter
Reliable Maximum up-time
Robust single enclosure Maintenance free
Unique cooling concept with no ambient
air ow over electronics
Max. ambient temperature 50˚ C
without derating
User friendly Save commissioning and operating cost
Easy installation
Watertight USB plug can be mounted
in the bottom
All cast aluminium parts are powder
coated with a strong epoxy coating.
The corrosion resistance has been
successfully tested with commonly
used cleaning detergents. Protection
against corrosive gasses complies
with to IEC 60721-3-3 level 3C3.
Power range
3 x 200 – 240 V:.................... 0.25 – 45 kW
3 x 380 – 500 V:.................... 0.37 – 90 kW
With 110% overload torque
(normal overload)
3 x 380 – 600 V:.................... 0.37 – 75 kW
With 160/150% overload torque
(High overload)
– Excellent protection against corrosion
connected with aggressive cleaning agents
used in the food and beverage industry
– No need for expensive cover
or IP 66/Type 4x cabinet in stainless steel
– Facilitate modular plant design
– Short motor cables
Problem-free operation in harsh environments
No external cooling or oversizing necessary
– Reduced assembly time
– Less installation cost
Set-up via VLT® Motion Control Tool MCT 10
possible without opening the drive
www.danfoss.com/drives
Stainless steel back plate
For open mounting – like on a frame –
a stainless steel back plate is available
to guide the air from the fan through
the rear heatsink.
Watertight USB plug
A watertight USB plug is available for
mounting in a gland hole in the bottom of the drive. With this plug it is
possible to commission the drive via
the VLT® Motion Control Tool MCT 10
without opening the drive
PC software tools
MCT 10
n Ideal for commissioning and
servicing the drive
MCT 31
n Harmonics calculations tool
Free download from
http://Drives.Danfoss.com
Specications
Mains supply (L1, L2, L3)
Supply voltage
Supply frequency 50/60 Hz
Displacement Power Factor (cos φ) near unity (> 0.98)
Switching on input supply L1, L2, L3 1–2 times/min.
Output data (U, V, W)
Output voltage 0–100% of supply
Switching on output Unlimited
Ramp times 1–3600 sec.
Closed loop 0–132 Hz
Digital inputs
Programmable digital inputs 6*
Logic PNP or NPN
Voltage level 0–24 VDC
* Two of the inputs can be used as digital outputs.
Analogue reference inputs
Analogue inputs 2
Modes Voltage or current
Voltage level –10 to +10 V (scaleable)
Current level 0/4 to 20 mA (scaleable)
Pulse inputs
Programmable pulse inputs 2
Voltage level 0–24 VDC (PNP positive logic)
Pulse input accuracy (0.1–110 kHz)
* Two of the digital inputs can be used for pulse inputs.
Analogue output
Programmable analogue outputs 1
Current range at analogue output 0/4–20 mA
Relay outputs
Programmable relay outputs 2 (240 VAC, 2 A and 400 VAC, 2 A)
Approvals
Norske Veritas, CCl
Fieldbus communication
FC Protocol, N2 Metasys, FLN Apogee, Modbus RTU, Modbus TCP, LonWorks, BACnet, DeviceNet,
Probus, CanOpen, Ethernet and Pronet (available June 2009)
Temperature
Ambient temperature Up to 55˚C
200-240 V ±10%, 380-500 V ±10%,
525-600 V ±10%
Cabinet sizes
Power range [kW] (200–240 V)
(HO/NO) (380–600 V)
Enclosure name A4 A5 B1 B2 C1 C2
Height 390 420 481 651 680 770
Width 200 242 242 242 308 370
Depth 175 200 260 260 310 335
0.25–2.2
0.37–4.0
0.25–3.7
0.37–7.5
5.5–7.5/11
11–15/18
11/15
18/22–22/30
15/18–22/30
30/37–45/55
30/37–37/45
55/75–75/90
For outdoor installations:
The drive must be installed under a
suitable cover to protect from direct
exposure to sun, snow and ice.
Danfoss VLT Drives, Ulsnaes 1, DK-6300 Graasten, Denmark, Tel. +45 74 88 22 22, Fax +45 74 65 25 80
www.danfoss.com/drives • E-mail: info@danfoss.com
DKDD.PFO.400.A2.02 VLT® is a trademark of Danfoss A/S Produced by PE-MMSC 2014.09