Danfoss VACON OPTEA, VACON OPTE9 User guide

User Guide
VACON® OPTEA/OPTE9 Ethernet Board
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
Contents
1
1.1
Purpose of the Manual 10
Additional Resources 10
1.2
Manual and Software Version 10
1.3
1.4
Type Approvals and Certications 11
1.5
Trademarks 11
1.6
Product Overview 12
1.6.1
Ethernet Networks with VACON® AC drives 12
1.6.2
Fieldbus Protocols 12
1.6.2.1
1.6.2.2
1.6.2.3
Redundancy Protocols 17
1.6.3
Modbus TCP/Modbus UDP 12
PROFINET I/O 16
EtherNet/IP 17
Contents
1.6.3.1
1.6.3.2
1.6.3.3
1.6.3.4
1.6.4
PROFINET Shared Device (OPTEA) 23
1.6.5
Address Conict Detection (ACD) 24
1.6.6
Technical Data 24
1.6.7
VACON® PC Tools 24
1.7
AC Drive Support 25
1.7.1
VACON® OPTEA Advanced Dual Port Ethernet Drive Support 25
1.7.2
VACON® OPTE9 Dual Port Ethernet Drive Support 25
1.8
Symbols and Abbreviations 26
2
Safety 29
2.1
Safety Symbols 29
2.2
Danger and Warnings 29
2.3
Cautions and Notices 30
Rapid Spanning Tree Protocol (RSTP) 17
Media Redundancy Protocol (MRP) 19
Device Level Ring (DLR) 20
PROFINET System Redundancy (OPTEA) 22
2.4
Grounding 32
3
Commissioning 34
3.1
Before Commissioning 34
3.1.1
Installing VACON® PC Tools 34
3.1.2
Downloading Fieldbus Option Firmware 34
3.1.3
Downloading Function Blocks for PLC 34
BC346130105092EN-US-000101/DPD01583 | 3Danfoss A/S © 2020.06
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
3.2
Commissioning with VACON® PC tools 35
3.2.1
Updating Fieldbus Firmware with VACON® Loader 35
3.2.2
Updating Firmware over Ethernet with VACON® Loader 36
3.2.3
Conguring with VACON® NCIPCong 39
3.2.4
Setting the Drive Parameters 40
3.2.4.1
3.2.4.2
3.3
OPTCx Emulation Mode (OPTEA) 43
4
Control Interface and Communication 46
4.1
Ethernet Communication Overview 46
4.2
Fieldbus Option Board Communication Modes 46
4.2.1
Requirements for Communication Modes 46
4.2.2
Fieldbus Communication Mode Features and Limitations 47
4.2.3
Normal Fieldbus Communication 47
Setting the Drive Parameters with VACON® NCDrive 40
Setting the Drive Parameters with VACON® Live 42
Contents
4.2.4
Fast Fieldbus Communication 48
4.2.5
Fast Safety Fieldbus Communication 49
4.2.6
Normal Extended Mode 49
4.3
Drive Control with Modbus TCP/UDP 49
4.3.1
Modbus Communication Overview 49
4.3.2
Quick Setup for Modbus Connection 49
4.3.3
Data Addresses and Modbus Memory Map 49
4.3.4
Coil Registers 50
4.3.5
Resettable Trip Counters 50
4.3.6
Input Discrete Registers 51
4.3.7
Input Registers 51
4.3.8
Holding Registers 51
4.3.8.1
4.3.8.2
4.3.8.3
4.3.8.4
VACON® Application IDs 52
FB Process Data In 52
FB Process Data Out 54
ID Map 55
4.3.8.5
4.3.8.6
4.3.8.7
4.3.8.8
4.3.8.9
4.3.8.10
4.3.8.11
Operation Day Counter 56
Resettable Operation Day Counter 57
Energy Counter 57
Resettable Energy Counter 58
Fault History 59
Fault History with 16-bit Error Codes 59
Reset Fault History 59
BC346130105092EN-US-000101/DPD015834 | Danfoss A/S © 2020.06
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
4.4
Contents
4.3.8.12
4.3.9
Connection Timeout in Modbus Communication 60
4.3.10
Example Messages 61
4.3.10.1
4.3.10.2
4.3.10.3
Drive Control with PROFINET 63
4.4.1
PROFINET Communication Overview 63
4.4.2
Quick Setup for PROFINET Connection 64
4.4.3
PROFIdrive 4.1 Prole Overview 64
4.4.4
PROFIdrive 4.1 State Machine 64
4.4.5
Telegram Types 66
4.4.5.1
4.4.5.2
Reset Fault with Time Stamps 59
Write Process Data 61
Read Process Data 62
Exception Response 63
Standard Telegram 1 and Variants 67
VACON®-specic Telegram 1 and Variants 68
4.4.5.3
4.4.5.4
4.4.5.5
4.4.5.6
4.4.5.7
4.4.6
Telegram Building Blocks 74
4.4.6.1
4.4.6.2
4.4.6.3
4.4.6.4
4.4.7
PROFIdrive Signal Numbers 77
4.4.8
User-specic Record Data 80
4.4.9
Connection Timeout in PROFINET 80
4.4.10
Examples with Siemens Controller 81
4.4.10.1
4.4.10.2
VACON®-specic Telegram 2 and Variants 69
VACON®-specic Telegram 3 and Variants 70
VACON®-specic Telegram 4 and Variants 71
VACON®-specic Telegram 5 and Variants 72
VACON®-specic Telegram Vendor PPO and Variants 72
PROFIdrive 4.1 Control Word (STW1) 74
PROFIdrive 4.1 Status Word (ZSW1) 75
Setpoint Value 76
Actual Speed Value 77
Conguring with Step 7 81
Conguring with TIA Portal 90
4.4.10.3
4.5
PROFIsafe (OPTEA) 102
4.5.1
Introduction to PROFIsafe 102
4.5.2
PROFIdrive on PROFIsafe 103
4.6
Drive Control with EtherNet/IP 103
4.6.1
EtherNet/IP Communication Overview 103
4.6.2
Quick Setup for EtherNet/IP Connection 104
4.6.3
AC/DC Drive Prole 105
Conguring with SIMATIC PDM 97
BC346130105092EN-US-000101/DPD01583 | 5Danfoss A/S © 2020.06
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
4.6.4
EDS File 105
4.6.5
CIP Objects 105
4.6.5.1
4.6.5.2
4.6.5.3
4.6.5.4
4.6.5.5
4.6.5.6
4.6.5.7
4.6.5.8
4.6.5.9
4.6.6
Vendor-specic Objects 126
4.6.6.1
4.6.6.2
Identity Object, Class 0x01 105
Message Router Object, Class 0x02 108
Connection Manager Object, Class 0x06 109
TCP/IP Interface Object, Class 0xF5 110
Ethernet Link Object, Class 0xF6 115
Assembly Object, Class 0x04 118
Motor Data Object, Class 0x28 119
Control Supervisor Object, Class 0x29 120
AC/DC Drive Object, Class 0x2A 123
Vendor Parameters Object, Class 0xA0 126
Assembly Instance Selector Object, Class 0xBE 127
Contents
4.6.6.3
4.6.6.4
4.6.7
Supported Assembly Instances Overview 132
4.6.8
CIP I/O Assembly Instances for AC/DC Drive 133
4.6.8.1
4.6.8.2
4.6.9
Vendor-specic I/O Assembly Instances 137
4.6.9.1
4.6.9.2
4.6.10
Mapping of Standard Output Assemblies onto VACON® Data 149
4.6.11
Mapping of VACON® Data onto Standard Input Assemblies 150
4.6.12
Special Assembly Instances 150
4.6.13
Connection Timeout in EtherNet/IP Communication 150
4.7
VACON® Process Data Description 151
4.7.1
Control Word Overview 151
4.7.2
Status Word Overview 155
Motor Control Mode Object, Class 0xA1 129
Fault History Object, class 0xA2 131
CIP Output Instances 135
CIP Input Instances 136
Vendor Output Instances 137
Vendor Input Instances 143
4.7.3
Control and Status Word Monitoring Values 158
4.7.4
Speed Reference and Actual Speed 159
4.7.5
Process Data 159
4.7.6
Fieldbus Process Data 159
4.8
Time Synchronization 162
4.8.1
System Time Update with ID 2551 162
4.8.2
Simple Network Time Protocol (SNTP) 162
BC346130105092EN-US-000101/DPD015836 | Danfoss A/S © 2020.06
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
5
Parameter Access 163
Parameter Access with PROFINET 163
5.1
5.1.1
Parameter Access Sequence 163
Parameter Requests 163
5.1.2
5.1.2.1
5.1.2.2
5.1.2.3
5.1.3
Parameter Responses 165
5.1.3.1
5.1.3.2
5.1.3.3
5.1.3.4
5.1.3.5
5.1.3.6
Request Header 164
Parameter Address 164
Parameter Value 165
Error Response 166
PROFIdrive 4.1 Error Classes and Codes 166
PROFIdrive Parameter Access Errors 167
Response Header 169
Parameter Values 169
Parameter Description Elements 169
Contents
Drive Parameter Access Using Application ID 170
5.1.4
5.1.5
PROFINET Parameters 170
5.1.5.1
5.1.5.2
5.1.5.3
5.1.6
Parameter Channel Examples 173
5.1.6.1
5.1.6.2
5.1.6.3
5.1.6.4
5.1.6.5
5.1.6.6
5.2
Parameter Access with EtherNet/IP 179
5.2.1
Explicit Messaging 179
5.2.2
List of Data Types 179
5.2.3
General CIP Error Codes 180
PROFIdrive Parameters 170
Vendor-specic PROFIdrive Parameters 171
Safety Parameters 173
Request First Element of PNU964 Value 174
Request All Elements of Parameter PNU964 175
Request the Value of Parameter ID 103 176
Change the Value of Drive Parameter ID 103 (Successful) 176
Change the Value of Drive Parameter ID 103 (Unsuccessful) 177
Change the Values of Multiple Drive Parameters (ID 103 and ID 104) 178
5.2.4
Connection Manager Object Error Codes 181
5.2.5
Supported CIP and Vendor Objects 182
6
Parameters 184
6.1
Option Board Parameters 184
6.1.1
Comm. Protocol 186
6.1.2
Comm. Timeout 186
6.1.3
Mode/Emulation 187
BC346130105092EN-US-000101/DPD01583 | 7Danfoss A/S © 2020.06
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
6.2
Contents
6.1.4
IP Address Mode 187
6.1.5
Speed and Duplex 188
6.1.6
IP Port Filtering 188
6.1.7
EIP Output Instance 189
6.1.8
EIP Input Instance 189
6.1.9
EIP Product Code Oset 189
6.1.10
Modbus Unit Identier 189
6.1.11
PNIO Name of Station 190
6.1.12
SNTP Mode 190
6.1.13
SNTP IP Address 190
6.1.14
SNTP Port 190
6.1.15
Time Interval 190
6.1.16
Time Oset 190
AC Drive Parameters 191
6.2.1
AC Drive Parameters for Fieldbus Control and Reference Selection 191
6.2.2
Protocol-related ID Reading and Writing 191
6.2.3
Fieldbus Parameters for VACON® 100 Family Standard Application 191
6.2.4
Fieldbus Parameters for VACON® 20 Standard Application 192
6.2.5
Fieldbus Parameters for VACON® 20 X Multipurpose Application 192
6.2.6
Fieldbus Parameters for VACON® NXP Multipurpose Application 192
6.2.7
Torque Control Parameterization 193
6.3
VACON® NXP System Software Parameters for Application Developers 193
6.3.1
System Software Variables for Selecting Communication Modes 194
6.3.2
System Software Variables for Monitoring Supported Communication Modes 194
6.3.3
System Software Variables for Selecting the Input Process Data Slot 194
7
Monitoring Values 195
7.1
Option Board Monitoring Values 195
7.1.1
MAC Address 197
7.1.2
Media Redundancy 197
7.1.3
System Redundancy (OPTEA) 198
7.1.4
SNTP Status 198
7.1.5
SNTP Server IP 198
7.1.6
Last Update Time 198
7.2
Monitoring Values of Control and Status Words 198
8
Fault Tracing 200
8.1
LED Indications on VACON® OPTEA/OPTE9 Option Boards 200
8.2
LED Indications with EtherNet/IP 201
BC346130105092EN-US-000101/DPD015838 | Danfoss A/S © 2020.06
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
8.3
8.4
8.5
8.6
8.7
8.8
Contents
PROFINET Alarm System 203
Fault Handling 205
Gathering Diagnostic Data 205
Typical Fault Conditions 205
Other Fault Conditions 206
Fieldbus Fault Codes 207
BC346130105092EN-US-000101/DPD01583 | 9Danfoss A/S © 2020.06
•••••
• NOTE! Download the English and French product manuals with applicable safety, warning and caution information from https://
www.danfoss.com/en/service-and-support/.
REMARQUE Vous pouvez télécharger les versions anglaise et française des manuels produit contenant l'ensemble des informa­tions de sécurité, avertissements et mises en garde applicables sur le site https://www.danfoss.com/en/service-and-support/.
Manual version
New features
Firmware version
DPD01583C (for OPTE9)
EtherNet/IP protocol
Ethernet ring support (RSTP)
Address Conict Detection (ACD)
V004 (OPTE9)
DPD01583D (for OPTE9)
Media Redundancy Protocol (MRP)
Simple Network Management Protocol (SNMP)
LLDP-MIB, LLDP-EXT-DOT3-MIB, LLDP-EXT-PNO-MIB
EDD les SIMATIC PDM
V006 (OPTE9)
DPD01583E (for OPTE9)
Fast communication modes in VACON® NXP
PROFINET Alarms.
V007 (OPTE9)
DPD01583F (for OPTE9)
Simple Network Time Protocol (SNTP).
Fast MRP support veried
V008 (OPTE9)
Device Level Ring (DLR)
V009 (OPTE9)
DPD01583G (for OPTEA/OPTE9)
PROFINET + PROFIsafe for VACON® NXP
V001 (OP­TEA)
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
Introduction
1 Introduction
1.1 Purpose of the Manual
The EtherNet/IP user guide provides information about conguring the system, controlling the drive, accessing parameters, pro­gramming, troubleshooting, and some typical application examples.
The user guide is intended for use by qualied personnel, who are familiar with the VACON® drives, EtherNet/IP technology, and with the PC or PLC that is used as a master in the system.
Read the instructions before commissioning and programming and follow the procedures in this manual.
1.2 Additional Resources
Resources available for the drive and optional equipment are:
VACON® Ethernet Installation Guide provides the necessary information to install the option board to the AC drive.
The Operating Guide of the AC drive provides the necessary information to get the drive up and running.
The Application Guide of the AC drive provides more details on working with parameters and many application examples.
Supplementary publications and manuals are available from drives.danfoss.com/knowledge-center/technical-documentation/. For US and Canadian markets:
1.3 Manual and Software Version
This manual is regularly reviewed and updated. All suggestions for improvement are welcome. The original language of this manual is English.
Table 1: Manual and Software Version
BC346130105092EN-US-000101 / DPD0158310 | Danfoss A/S © | 2020.06
Manual version
New features
Firmware version
Support for all features supported by OPTE9 board including EtherNet/IP and Modbus TCP/UDP protocols
Improved emulation mode with OPTCP, OPTCQ, and OPTCI boards when installed to VA­CON® NXP
PROFINET System Redundancy "S2"
V002 (OP­TEA)
DPD01583H (for OPTEA/OPTE9)
The structure of the manual updated. Installation information removed (see VACON
®
Ethernet Installation Guide).
Support for 32-bit process data items with VACON® 100 family AC drives.
V003 (OP­TEA)
Shared Device
V005 (OP­TEA)
089
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
1.4 Type Approvals and Certications
The following list is a selection of possible type approvals and certications for Danfoss drives:
Introduction
N O T I C E
The specic approvals and certication for the drive are on the nameplate of the drive. For more information, contact the local
Danfoss oce or partner.
1.5 Trademarks
EtherNet/IP© is a trademark of ODVA, Inc.
License for LWIP
Copyright (c) 2001, 2002 Swedish Institute of Computer Science. All rights reserved.
BC346130105092EN-US-000101 / DPD01583 | 11Danfoss A/S © 2020.06
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
Redistribution and use in source and binary forms, with or without modication, are permitted provided that the following condi­tions are met:
1. Redistributions of source code must retain the above copyright notice, this list of conditions and the following disclaimer.
2. Redistributions in binary form must reproduce the above copyright notice, this list of conditions and the following disclaimer in the documentation and/or other materials provided with the distribution.
3. The name of the author may not be used to endorse or promote products derived from this software without specic prior writ­ten permission.
THIS SOFTWARE IS PROVIDED BY THE AUTHOR “AS IS” AND ANY EXPRESS OR IMPLIED WARRANTIES, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED. IN NO EVENT SHALL THE AUTHOR BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY, OR CONSEQUENTIAL DAMAGES (IN­CLUDING, BUT NOT LIMITED TO, PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSI­NESS INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY OUT OF THE USE OF THIS SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE
Introduction
1.6 Product Overview
1.6.1 Ethernet Networks with VACON® AC drives
The VACON® AC drives can be connected to the Ethernet networks using the VACON® OPTEA Advanced Dual Port Ethernet eldbus option board (OPTEA), or the VACON® OPTE9 Dual Port Ethernet eldbus option board (OPTE9).
OPTEA supports all the features described in this manual. Features that are not supported by OPTE9, are marked with extra (OPTEA) on the title.
The option boards support PROFINET I/O, EtherNet/IP, Modbus TCP, and Modbus UDP eldbus protocols. In addition, the Advanced Dual Port Ethernet board (OPTEA) supports PROFINET I/O with PROFIsafe when the OPTBL/OPTBM/OPTBN option board is also in­stalled. OPTEA also supports advanced features such as PROFINET System Redundancy "S2".
OPTEA can be used alone as PROFINET I/O device. However, PROFIsafe always requires OPTBL/OPTBM/OPTBN option board and VA­CON® NXP control, too.
The drives can be daisy chained by utilizing two Ethernet ports. The following network topologies are supported. See details in Ethernet Board Installation Guide.
Star
Daisy chain
Ring
Every appliance connected to an Ethernet network has two identiers: a MAC address and an IP address. The MAC address (Address format: xx:xx:xx:xx:xx:xx) is unique for each appliance and cannot be changed. The MAC address of the Ethernet board can be found on the sticker attached to the board.
In a local network, the user can dene the IP addresses as long as all the units connected to the network are given the same network portion of the address. Overlapping IP addresses cause conicts between appliances. For more information about setting IP ad­dresses, see 3.2.3 Conguring with VACON® NCIPCong, 3.2.4.1 Setting the Drive Parameters with VACON® NCDrive, or 3.2.4.2 Set-
ting the Drive Parameters with VACON® Live.
1.6.2 Fieldbus Protocols
1.6.2.1 Modbus TCP/Modbus UDP
Modbus is a communication protocol developed by Modicon systems. In simple terms, it is a way of sending information between electronic devices. The device requesting the information is called the Modbus Master (or the Client in Modbus TCP/UDP) and the devices supplying information are Modbus Slaves (in Modbus TCP/UDP servers).
In a standard Modbus network, there is one Master and up to 247 Slaves, each with a unique Slave Address from 1 to 247. The Master can also write information to the Slaves. Modbus is typically used to transmit signals from instrumentation and control devi­ces back to the main controller or data gathering system.
The Modbus communication interface is built around messages. The format of these Modbus messages is independent of the type of physical interface used.
The same protocol can be used regardless of the connection type. Because of it, Modbus gives the possibility to upgrade easily the hardware structure of an industrial network, without the need for large changes in the software. A device can also communicate with several Modbus nodes at once, even if they are connected with dierent interface types. There is no need to use a dierent protocol for every connection.
BC346130105092EN-US-000101 / DPD0158312 | Danfoss A/S © | 2020.06
Master´s message
Slave response
Start
Address
Function
Data
CRC
End
Start
Address
Function
Data
CRC
End
e30bh904.10
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
Illustration 1: Basic Structure of Modbus Frame
Introduction
On simple interfaces like RS485, the Modbus messages are sent in plain form over the network. In this case, the network is dedicated to Modbus. When using more versatile network systems like TCP/IP over Ethernet, the Modbus messages are embedded in packets with the format necessary for the physical interface. In that case Modbus and other types of connections can co-exist at the same physical interface at the same time. Although the main Modbus message structure is peer-to-peer, Modbus is able to function on both point-to-point and multidrop networks.
Each Modbus message has the same structure. Four basic elements are present in each message. The sequence of these elements is the same for all messages, to make it easy to parse the content of the Modbus message. In the Modbus network, the master always starts the conversation. A Modbus master sends a message and depending on the contents of the message, a slave reacts to it. There can be more than one master in a Modbus network. Addressing in the message header is used to dene which device must respond to a message. If the address eld does not match their own address, all other nodes on the Modbus network ignore the message.
Modbus UDP vs TCP
In addition to TCP, the option boards also support UDP (from OPTE9 rmware version V006). We recommend using UDP when read­ing and writing rapidly and repetitively (cyclically) same data as with process data. Use TCP for single operations, like service data (for example, reading or writing parameter values).
The main dierence between UDP and TCP is that when using TCP, the receiver must acknowledge every Modbus frame (see Illustra-
tion 2). It adds extra trac to the network and more load to the system (PLC and drives) because software must follow sent frames
to make sure that they have reached their destination.
BC346130105092EN-US-000101 / DPD01583 | 13Danfoss A/S © 2020.06
Modbus TCP Communication
PLC
Open
Connection
Communicate
Communicate
Close
Connection
Drive
TCP, SYN
TCP, SYN, ACK
TCP, ACK
Modbus Query
Modbus Query
Modbus Response, TCP, ACK
TCP, ACK
TCP, ACK
TCP, ACK
TCP, ACK
TCP, FIN, ACK
Modbus UDP Communication
PLC Drive
Modbus Query
Modbus Response
Modbus Query
e30bh930.10
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
Introduction
Illustration 2: Modbus TCP and UDP Communication Comparison
Another dierence between TCP and UDP is that UDP is connectionless. TCP connections are always opened with TCP SYN messag­es and closed with TCP FIN or TCP RST. With UDP, the rst packet is already a Modbus query. The option board treats IP address and port combination as a connection. If port changes, it is considered as a new connection or as a second connection if both stay ac­tive.
When using UDP, it is not guaranteed that the sent frame reaches is destination. PLC must follow the Modbus requests by using the Modbus transaction id-eld. It actually must do it also when using TCP. If PLC does not receive response in time from drive in UDP connection, it must send the query again. When using TCP, the TCP/IP stack keeps resending the request until receiver has acknowl­edged it (see Illustration 3). If PLC sends new queries during this time, some of them can not be sent to network (by TCP/IP stack) until previous sent package(s) has been acknowledged. It can cause small packet storms when the connection is resumed between PLC and drive (See Illustration 4).
BC346130105092EN-US-000101 / DPD0158314 | Danfoss A/S © | 2020.06
Modbus TCP Communication
PLC Drive
Modbus Query (1)
Modbus Query (2)
Modbus Response (1), TCP, ACK
Modbus Response (2), TCP, ACK
TCP, ACK
TCP retransmission, Modbus Query (2)
TCP retransmission, Modbus Query (2)
Normal communication continues
Packet lost, no response
Packet lost, no response
Modbus Query (1)
Modbus Response (1)
Modbus Response (4)
Modbus Query (2)
Modbus Query (3)
Modbus Query (4)
Packet lost, no response
Packet lost, no response
Normal communication continues
Modbus UDP Communication
PLC Drive
e30bh931.10
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
Introduction
Illustration 3: Modbus TCP and UDP Communication Errors Comparison
BC346130105092EN-US-000101 / DPD01583 | 15Danfoss A/S © 2020.06
e30bh932.10
Modbus TCP Communication
PLC Drive
Modbus Modbus
TCP
stack
TCP
stack
Modbus Query (1)
Modbus Query (2)
Modbus Query (3)
Modbus Query (4)
Modbus Query
(1,2,3)
Modbus Query (4)
Modbus Response (1,2,3)
Modbus Response (4)
TCP Modbus Query
TCP, ACK
TCP, ACK
TCP, ACK
TCP, ACK
TCP, Modbus Response (1,2,3)
TCP, Modbus Response (4)
TCP, Modbus Query (4)
Retransmission
Modbus Query (1,2,3)
Retransmission Modbus Query (1,2,3)
Retransmission
Modbus Query (1,2)
Retransmission
Modbus Query (1)
Modbus
Response (1,2,3)
Modbus
Response (4)
Normal communication continues
Packet lost
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
Introduction
Illustration 4: Modbus TCP Retransmissions
Losing one packet is not a fatal because the same request can be sent again after timeout. In TCP, the packages always reach their destination but if network congestion causes retransmissions, those packages contain most likely old data or instructions when they reach their destination.
1.6.2.2 PROFINET I/O
PROFINET is the Ethernet-based automation standard of PROFIBUS International for the implementation of an integrated and con­sistent automation solution based on Industrial Ethernet. PROFINET supports the integration of simple distributed eld devices and time-critical applications in (switched) Ethernet communication. It also supports the integration of component-based distributed automation systems for vertical and horizontal integration of networks.
The option boards implement the following features:
PROFINET I/O version 2.4
PROFINET RT
Conformance class B (PA)
Highest netload class (class III)
Standard diagnosis for VACON® AC drive faults and alarms
The Advanced Dual Port Ethernet option board (OPTEA) implements also
BC346130105092EN-US-000101 / DPD0158316 | Danfoss A/S © | 2020.06
PLC
Managed switch with RSTP support
DRIVE
OPTE9-1
DRIVE
...
OPTE9-2
DRIVE
OPTE9-3
DRIVE
OPTE9-8
1 2
DP AP
3 4 5 6 7 8
Power
e30bh922.10
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
PROFINET system redundancy (S2)
PROFIsafe over PROFINET
OPTCP-emulation (OPTCx) mode when installed to VACON® NXP
Shared Device
Introduction
1.6.2.3 EtherNet/IP
The EtherNet/IP© is an industrial Ethernet network solution available for manufacturing automation. The CIP© (Common Industrial Protocol) encompasses a comprehensive suite of messages and services for various manufacturing automation applications, includ­ing control, safety, synchronization, motion, conguration, and information. The CIP provides users with a unied communication architecture throughout the manufacturing enterprise.
More information on the EtherNet/IP can be found at http://www.odva.org.
1.6.3 Redundancy Protocols
1.6.3.1 Rapid Spanning Tree Protocol (RSTP)
To use the RSTP protocol, add a managed Ethernet switch that supports the RSTP protocol. If a single link is broken, the RSTP switch notices it and start sending data from the PLC to both directions eectively creating two daisy chains. When the link has been re­paired, the switch notices it, too, and reverts to normal operating mode. Compared to the star topology, the ring topology adds more network trac to almost all drives. Damage to two cables always creates an isolated subnetwork.
In the RSTP conguration, one of the ports in the switch is "Designated Port" (DP) and the other "Alternative Port" (AP). When the network is functioning properly, the trac ows through the designated port. Only the BPDU (Bridge Protocol Data Unit) packets are transferred through the AP port. The BPDU packets are used by the switch to determine if the network is working properly. If it detects that the BPDU packets do not go through the ring, it changes the alternative port to a second designated port. Now the switch sends packets to both directions in the broken ring (see Illustration 6).
Each designated port has a list of MAC addresses which are behind that port. Only frames directed to the device in the MAC list are forwarded into that designated port. The broadcast and multicast frames are sent to all designated ports.
Illustration 5: Ring Topology
In the example below, the Ethernet communication is interrupted to device number 3 and other devices after that when the link is broken. The Fieldbus communication maybe faulted when the link is broken, but when the switch enables the second designated port, the connections can be reopened. In the RSTP protocol, it generally takes few seconds before the second designated port is activated. The time depends on the BPDU exchange cycle, which is 2 seconds by default.
BC346130105092EN-US-000101 / DPD01583 | 17Danfoss A/S © 2020.06
PLC
Managed switch with RSTP support
DRIVE
OPTE9-1
DRIVE
...
OPTE9-2
DRIVE
OPTE9-3
DRIVE
OPTE9-8
1 2
DP DP
3 4 5 6 7 8
Power
e30bh923.10
e30bh924.10
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
Introduction
Illustration 6: Ring Topology: Error in Network
NOTE! The switch itself in Ethernet boards does not implement the RSTP protocol, so the network always needs a third party switch
to support it.
NOTE! Do not use RSTP together with PROFIsafe. Recovery time in RSTP network can be several seconds, and recovery time in STP network can be several tens of seconds. To compensate the recovery time, the PROFIsafe watchdog time must be set long enough so that slow recovery time of RSTP network can be tolerated. However, for example, in Siemens TIA portal, the longest PROFIsafe watchdog time setting is 1920 ms, and it is too short for RSTP.
Conguration Example
The screenshots (
Illustration 7, Illustration 8) show one example of conguring the RSTP in the switch (in this case an EtherWAN
switch). Port two is the designated port and port one is the alternative port. The PLC was connected to port nine (the laptop taking the screenshots was in port 16). When conguring your switch, refer to the manual of the switch manufacturer.
Illustration 7: EtherWAN Switch RSTP Conguration Example
BC346130105092EN-US-000101 / DPD0158318 | Danfoss A/S © | 2020.06
e30bh925.10
OPTE9-1
...
OPTE9-2 OPTE9-3 OPTE9-8
1
2
2
e30bh927.10
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
Illustration 8: EtherWAN Switch RSTP Conguration Example - Port Settings
Introduction
1.6.3.2 Media Redundancy Protocol (MRP)
The MRP is designed to react deterministically on a cable failure. It makes it suitable to be used in process automation. One of the nodes in the network has the role of Media Redundancy Master (MRM), which observes and controls the ring topology to react to network faults. Usually this device is PLC or network switch.
Other nodes in the network are called Media Redundancy Clients (MRC), and they react on received conguration frames from the MRM and can detect link changes on its ring ports. OPTEA and OPTE9 boards support only MRC functionality.
The MRM and MRC have two ring ports, which take one of the following states:
DISABLED - All frames are dropped
BLOCKING - All frames are dropped, except the following frames:
-
MRP frames (for example, MRP_test and MRP_TopologyChange)
-
Frames specied to pass ports in "Discarding" state, for example, LLDP frames
FORWARDING - All frames are forwarded according to normal behavior
The MRM sends MRP_Test frames in a congured time period to monitor the state of the ring topology. If the MRM receives its own MRP_Test frames (network is closed), one of the ring ports is set to FORWARDING state and the other to BLOCKED state (see Illustra-
tion 9). If the MRM does not receive the MRP_Test frames (network is open), it sets both of its ring ports to FORWARDING state (see Illustration 10).
The following gure shows an example of an MRP network, where the PLC acts as an MRM. The dotted line shows Blocked connec­tion.
Illustration 9: MRP Ring: Closed Network
BC346130105092EN-US-000101 / DPD01583 | 19Danfoss A/S © 2020.06
1
PLC/MRM
2
Drive/MRC
OPTE9-1
...
OPTE9-2 OPTE9-3 OPTE9-8
e30bh928.10
1
2
2
1
PLC/MRM
2
Drive/MRC
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
Introduction
In the example below, the Ethernet communication is interrupted to device number 3 and other devices after that when the link is broken.
Illustration 10: MRP Ring: Error in Network
NOTE! MRP (as MRC) can only be used when PROFINET is the selected protocol. MRP is available in all versions of OPTEA board and
in OPTE9 since V006 rmware.
MRP Recovery Times and Fast MRP
MRP can be congured to send test frames with dierent time periods, depending on the maximum allowed recovery time for the network. These times are set as the guaranteed time for a network of 50 nodes to recover from a ring error.
Typically, in PROFINET systems the recovery time is dened as 200 ms. However, the MRP specication allows for recovery times of 500, 200, 30, and 10 ms. OPTEA and OPTE9 boards can be used in systems with the lowest recovery time of 10 ms. It is often called “Fast MRP”.
When using MRP in a PROFINET network, the recommendation is to set the watchdog time of each device in the ring to the maxi­mum recovery time, usually 200 ms. It guarantees that a cable failure does not interrupt the eldbus connection.
1.6.3.3 Device Level Ring (DLR)
Device Level Ring (DLR) protocol provides a way to detect, manage, and recover from faults in a ring-based network. It supports a single-ring topology. Multiple or overlapping rings are not supported. Other features include "Sign on process" used to identify all ring participants, and "Neighbor check process" which allows nodes to check the health of their adjacent nodes.
One device acts as a ring supervisor, monitoring the state of the ring while other devices act as DLR nodes. Only one device can act as an active supervisor, although back-up supervisors are possible. Nodes can be divided into Beacon- and Announce-based nodes depending on which frames the nodes process. OPTEA and OPTE9 boards support Announce-based functionality.
DLR nodes have three states:
IDLE_STATE: indicating linear topology for non-supervisor nodes
FAULT_STATE: initial state for enabled ring supervisor, or when ring fault has been detected
NORMAL_STATE: normal function in ring topology mode
The active ring supervisor sends Beacon frames from both its ring ports once per beacon interval (400 μs by default) to monitor the state of the ring. It also sends an Announce frame once per s. If the Beacon frames are received back at the supervisor, one of its ports is set to blocking and the other to forwarding state (Illustration 11). Only the following packets are processed from the blocked port:
BC346130105092EN-US-000101 / DPD0158320 | Danfoss A/S © | 2020.06
e30bh975.10
1
2 2
3
3
4
4
OPTE9-1 OPTE9-2
OPTE9-3 OPTE9-4
1
Ring Supervisor
2
DLR Node
3
Beacon
4
Announce
OPTE9-1 OPTE9-2
OPTE9-3 OPTE9-4
e30bh976.10
2
3
3
2
1
1
Active Ring Supervisor
2
DLR Node
3
Link Status
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
Beacon frames from self and other supervisors
Link_Status/Neighbor_Status frames
Neighbor_Check request or response and Sign_On frames
Illustration 11: DLR Ring: Network Conguration when Ring is Closed (NORMAL_STATE)
Introduction
If a network error occurs to DLR-capable nodes, the nodes send Link_Status frames to inform the ring supervisor immediately which port(s) have a failure (Illustration 12).
Illustration 12: DLR Ring: Failure in Network
A Link_Status frame triggers an error response in active ring supervisor, which unblocks trac on its previously blocked port (Illus-
tration 13). If there is an uncommon failure (for example, if a cable breaks between two non-DLR capable devices), the error is no-
ticed from Beacon timeout value, and not from Link_Status frames. Therefore, a recovery in a network with non-DLR capable devices can take longer.
BC346130105092EN-US-000101 / DPD01583 | 21Danfoss A/S © 2020.06
OPTE9-1 OPTE9-2
OPTE9-3 OPTE9-4
1
2 2
e30bh977.10
1
Active Ring Supervisor
2
DLR Node
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
Illustration 13: DLR Ring: Network Conguration after Failure (FAULT_STATE)
Introduction
The ring recovers after Beacon frames again are received from both of the active ring supervisors ring ports. Ring recovers back to its original state (Illustration 11).
NOTE! DLR is active only when EtherNet/IP is the selected protocol. DLR is available since V002 rmware for OPTEA and since V009 rmware for OPTE9 board.
DLR Recovery Times
DLR allows setting of the beacon interval and the beacon timeout values, with lower beacon interval providing faster ring recovery performance. With default values (400 μs interval and 1960 μs timeout), DLR can reach much faster ring recovery times than, for example, Media Redundancy Protocol. Typically, these times are around 3 ms for Beacon-based and 4 ms for Announce-based no­des.
When using DLR, we recommend that the watchdog time is set to a value greater than 4 ms. It ensures that a properly congured ring network recovers from a network failure within the watchdog time.
1.6.3.4 PROFINET System Redundancy (OPTEA)
Redundancy is a requirement in process automation systems for high availability and reduced production downtimes. PROFINET System Redundancy provides a solution to build a system with redundant PN controllers, devices, and communication.
PROFINET System Redundancy fullls among others the following requirements:
Highly reliable communication
Short take over time
Bumpless I/O data during fault recovery
Monitoring of the back-up connection
System redundancy implements two redundant PN controllers, one working as primary and other as back-up. These controllers can be connected via a redundant network to PN devices. It is, however, not mandatory as system redundancy has dierent levels which are independent from each other. Thus, PN controller, Ethernet media, and PN device can have dierent redundancy congurations.
BC346130105092EN-US-000101 / DPD0158322 | Danfoss A/S © | 2020.06
1
2
3
45
e30bh978.10
1
Primary
2
Back-up
3
Redundant network
4
Device with redundant connectivity
5
Device with singular connectivity
Host
NAP IO
IOC
PROFINET
SR-ARa
Single NAP
S2
SR-ARb
IOC
Host
e30bh979.10
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
Illustration 14: System Redundancy Overview
Introduction
OPTEA supports "S2" level of System Redundancy and Media Redundancy Protocol (MRP) for redundant connectivity. S2 uses a single PROFINET interface (NAP = Network Access Point), and two SR-ARs (System Redundancy Application Relations =
connections), one to each PN controller. Redundant PN controllers have parallel access to an SR PN device, but only one AR acts as a primary (SR-ARa) and the other is back-up (SR-ARb).
Illustration 15: NAP S2, Connected to 2 IOCs
In case the primary AR fails, the IOC initiates a switch for the back-up SR-AR to become primary. This switchover cannot take longer than the Redundancy Data Hold Time (RDHT) congured by the IOC. During the transition, the input data is hold and the output data frozen to ensure a bumpless transition. OPTEA does not create a fault during this time when a back-up connection is available. A fault is created after this time elapses and no Primary is available.
NOTE! System Redundancy is available in OPTEA version V002 or later and requires the use of GSDML le dated 21.06.2018 or later.
1.6.4 PROFINET Shared Device (OPTEA)
OPTEA supports Shared Device feature where multiple PLCs can connect to same device. PLC A can connect to PROFIdrive module and PLC B can connect to PROFIsafe module. It is also possible to have System Redundancy connections (two PLCs) and PROFIsafe from third PLC at the same time.
This kind of setup generates up to three times more Ethernet trac than connecting with single PLC, so consider the cycle times and number of devices in the system. Connections to multiple PROFIdrive or PROFIsafe modules are not supported.
BC346130105092EN-US-000101 / DPD01583 | 23Danfoss A/S © 2020.06
Technical item or function
Technical data
General
Board name
OPTEA/OPTE9
Ethernet connections
Interface
Two RJ-45 connectors
Transfer cable
Shielded Twisted Pair (STP) CAT5e
(1)
Communications
Speed
10 / 100 Mb
Duplex
half / full
Default IP-address
By default the board is in DHCP mode.
Protocol
Modbus TCP, Modbus UDP, Pronet I/O, EtherNet/IP
Environment
Ambient operating temperature
-10°C…50° C
Storing temperature
-40°C…70° C
Humidity
<95%, no condensation allowed
Altitude
Maximum 1000 m
Vibration
0.5 G at 9…200 Hz
Safety
Fullls EN 50178 standard
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
Shared device feature also enables adding of PROFIsafe to existing systems. Notice that PROFIsafe has its own conguration require­ments (see 4.5 PROFIsafe (OPTEA)).
Introduction
1.6.5 Address Conict Detection (ACD)
The OPTEA and OPTE9 option boards implement ACD algorithm (IETF RFC 5227). The implementation includes requirements from the EtherNet/IP protocol.
The ACD algorithm tries to detect actively if another device is using the IP address in the same network. The ACD sends 4 ARP re­quest packets when the Ethernet interface of the device activates, or when its IP address changes.
ACD prevents the use of the Ethernet interface until the ARP probing nishes. This delays the start-up of eldbus protocols about 1 s. During the delay or after it, the ACD passively checks incoming ARP messages for use of the IP address of the device.
If another device with the same IP address is detected, the ACD tries to defend its IP address with a single ARP message. If the other device with the same IP address also supports ACD, it must stop using the address. If it does not, the ACD closes the Ethernet con­nection and indicates the situation with LEDs. This is done according the "DefendWithPolicyB". Other policies are not supported.
If the eldbus protocol has been active, it can activate a eldbus fault (depends on the eldbus and drive application conguration).
1.6.6 Technical Data
Table 2: OPTEA/OPTE9 Option Board Technical Data
1
For connecting the eldbus Ethernet boards, use only Ethernet cables that meet at least the requirements of category 5 (CAT5) according to EN
50173 or ISO/IEC 11801.
1.6.7 VACON® PC Tools
With VACON® PC tools, it is possible to do following operations for OPTEA/OPTE9 Ethernet board:
Update rmware into OPTEA/OPTE9 board (with VACON® Loader), see
Set parameters for OPTEA/OPTE9 Ethernet board (with VACON® NCDrive or VACON® Live), see 3.2.4.1 Setting the Drive Parame-
ters with VACON® NCDrive and 3.2.4.2 Setting the Drive Parameters with VACON® Live
Read monitor values of OPTEA/OPTE9 Ethernet board (with VACON® NCDrive or VACON® Live)
For instructions on downloading and installing the tools, see 3.1.1 Installing VACON® PC Tools. The following table describes what PC tools are supported in each AC drive type.
3.2.1 Updating Fieldbus Firmware with VACON® Loader
BC346130105092EN-US-000101 / DPD0158324 | Danfoss A/S © | 2020.06
Tool
VACON® 100 family
VACON® NXS/NXP
VACON® 20 family
VACON® Loader
Serial
(1)
Serial
(1)
Serial
(1)
VACON® Live
Serial
(1)
, Ethernet
(2)
-
Serial
(1)
VACON® NCIPCong
Ethernet
(2)
Ethernet
(2)
Ethernet
(2)
VACON® NCDrive
-
Ethernet
(2)
-
VACON® NCLoad
Not supported; use VACON® Loader.
AC drive
Slots
From AC drive software version on
From OPTEA software version on
VACON® NXP
D, E
NXP00002V196
V001
VACON® NXS
D, E
NXS00002V184
V003
VACON® 100 INDUSTRIAL
and 100 X
D, E
FW0072V028
V002
VACON® 100 FLOW
D, E
FW0159V018
V002
AC Drive
From AC drive software version on
VACON® NXP
NXP00002V197
VACON® 100 INDUSTRIAL and 100 X
FW0072V028
VACON® 100 FLOW
FW0159V018
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
Table 3: The Supported PC Tools with Dierent AC Drives
1
The connection type "serial" is a direct serial connection to the AC drive.
2
The connection type "Ethernet" is an Ethernet connection, for example, VACON® 100 family built-in Ethernet interface, or a connection via OPTEA/
OPTE9 Dual Port Ethernet option board.
Introduction
1.7 AC Drive Support
1.7.1 VACON® OPTEA Advanced Dual Port Ethernet Drive Support
The VACON® OPTEA Advanced Dual Port Ethernet option board can be used with the following VACON® AC drives. Option board can be used for PROFINET with PROFIsafe communication in slot E, when OPTBL/OPTBM/OPTBN is installed to slot D. If PROFIsafe is not used, then OPTEA can be installed to slot D too.
Table 4: OPTEA-supported AC Drives and Slots
VACON® 100 Family Support
The VACON® 100 family AC drives are supported from the OPTEA rmware version V002. The process data in VACON® 100 family AC drives is 32 bit. PROFIsafe features are supported only in VACON® NXP drives.
EtherNet/IP and Modbus TCP/UDP Support
Support for EtherNet/IP, Modbus TCP/UDP, and other features which were in OPTE9, were added to OPTEA rmware V002. Table below shows required minimum AC drive rmware version.
Table 5: Required Minimum AC Drive Firmware Versions
1.7.2 VACON® OPTE9 Dual Port Ethernet Drive Support
The VACON® OPTE9 Dual Port Ethernet option board can be used with the following VACON® AC drives.
BC346130105092EN-US-000101 / DPD01583 | 25Danfoss A/S © 2020.06
AC drive
Slots
From AC drive software version on
From OPTE9 software version on
VACON® NXP
D, E
NXP00002V188
V001
VACON® NXS
D, E
NXS00002V179
V001
VACON® 100 INDUSTRIAL and 100 X
D, E
FW0072V018
V003
VACON® 100 FLOW
D, E
FW0159V012
V003
VACON® 20
-
FW0107V011
V002
VACON® 20 X and CP
-
FW0117V007
V002
AC Drive
From AC drive SW version on
VACON® NXP
NXP00002V191
VACON® NXS
NXS00002V181
VACON® 100 INDUSTRIAL and 100 X
FW0072V018
VACON® 100 FLOW
FW0159V012
VACON® 20
FW0107V012
VACON® 20 X and CP
FW0117V009
Abbreviation
Denition
ACD
Address Conict Detection
ARP
Address Resolution Protocol
CIP
Common Industrial Protocol
CRC
Cyclic Redundancy Check is an error-detecting code commonly used in eldbusses to detect accidental changes to raw data.
CW
Control word
DCP
Discovery and Basic Conguration Protocol
DHCP
Dynamic Host Conguration Protocol is used for dynamical resolving of network conguration parameters like an IP address.
DLR
Device Level Ring
DU
Data unit
EDD
Electronic Device Description
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
Table 6: OPTE9-supported AC Drives and Slots
VACON® 100 Family Support
The VACON® 100 family AC drives are supported from the OPTE9 rmware version V003. The process data in VACON® 100 family AC drives is 32 bit.
EtherNet/IP and Modbus TCP/UDP Support
EtherNet/IP protocol was added to OPTE9 rmware version V004. The following table shows required minimum AC drive rmware version.
Table 7: Required Minimum AC Drive Firmware Versions
Introduction
1.8 Symbols and Abbreviations
Table 8: Symbols and Abbreviations
BC346130105092EN-US-000101 / DPD0158326 | Danfoss A/S © | 2020.06
Abbreviation
Denition
EDS
Electronic Data Sheet
EMC
Electromagnetic compatibility
FB
Fieldbus
FD
Full Duplex
GSDML
General Station Description Markup Language
GW
Gateway
HD
Half Duplex
HI
Upper 8/16 bits in a 16/32-bit value.
LED
Light emitting diode
LLDP
Link Layer Discovery Protocol
LO
Lower 8/16 bits in a 16/32-bit value.
MIB
Management Information Base
Modbus TCP / Modbus UDP
Simple and vendor-neutral communication protocol intended for monitoring and controlling of eld devi­ces.
MRC
Media Ring Client
MRM
Media Ring Master
MRP
Media Ring Protocol
NSOLL
Sollwert (German for reference value)
NIST
Istwert (German for actual value)
PC
Personal computer
PDI
Process Data In
PDO
Process Data Out
PHY(X)
Ethernet physical interface X, where X shows the number of interfaces
PLC
Programmable logic controller
PNU
Parameter number
PPO
Process parameter object
PROFINET I/O
PROFINET is a standard for industrial automation in Ethernet network. PROFINET I/O describes the ex­change of data between controllers and eld devices.
RDHT
Redundancy Data Hold Time
RPM
Revolutions per minute
RSTP
Rapid Spanning Tree Protocol
SNMP
Simple Network Management Protocol
SNTP
Simple Network Time Protocol
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
Introduction
BC346130105092EN-US-000101 / DPD01583 | 27Danfoss A/S © 2020.06
Abbreviation
Denition
STW1
Steuerwort 1 (German for control word 1)
SW
Status word
TCP
Transmission Control Layer provides reliable, ordered, and error-checked delivery of data streams between computers that are connected to a local area network.
UTC
Coordinated Universal Time
ZSW1
Zustandwort 1 (German for status word 1)
Type name
Bit size
Explanation
INT88Signed short integer
UINT8
8
Unsigned short integer
INT16
16
Signed integer
UINT16
16
Unsigned integer
INT32
32
Signed long integer
UINT32
32
Unsigned long integer
FLOAT32
32
32-bit oating point
STRING3
24
3 byte string
STRING5
40
5 byte string
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
Table 9: Data Types
Introduction
BC346130105092EN-US-000101 / DPD0158328 | Danfoss A/S © | 2020.06
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
2 Safety
2.1 Safety Symbols
The following symbols are used in this manual:
D A N G E R
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
W A R N I N G
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
C A U T I O N
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
N O T I C E
Indicates information considered important, but not hazard-related (for example, messages relating to property damage).
Safety
2.2 Danger and Warnings
D A N G E R
SHOCK HAZARD FROM POWER UNIT COMPONENTS
The power unit components are live when the drive is connected to mains. A contact with this voltage can lead to death or seri-
ous injury.
Do not touch the components of the power unit when the drive is connected to mains. Before connecting the drive to mains,
-
make sure that the covers of the drive are closed.
D A N G E R
SHOCK HAZARD FROM TERMINALS
The motor terminals U, V, W, the brake resistor terminals, or the DC terminals are live when the drive is connected to mains, also
when the motor does not operate. A contact with this voltage can lead to death or serious injury.
Do not touch the motor terminals U, V, W, the brake resistor terminals, or the DC terminals when the drive is connected to
-
mains. Before connecting the drive to mains, make sure that the covers of the drive are closed.
D A N G E R
SHOCK HAZARD FROM DC LINK OR EXTERNAL SOURCE
The terminal connections and the components of the drive can be live 5 minutes after the drive is disconnected from the mains
and the motor has stopped. Also the load side of the drive can generate voltage. A contact with this voltage can lead to death or
serious injury.
Before doing electrical work on the drive:
-
Disconnect the drive from the mains and make sure that the motor has stopped. Lock out and tag out the power source to the drive. Make sure that no external source generates unintended voltage during work. Wait 5 minutes before opening the cabinet door or the cover of the AC drive. Use a measuring device to make sure that there is no voltage.
BC346130105092EN-US-000101 / DPD01583 | 29Danfoss A/S © 2020.06
VACON® OPTEA/OPTE9 Ethernet Board
User Guide
Safety
W A R N I N G
SHOCK HAZARD FROM CONTROL TERMINALS
The control terminals can have a dangerous voltage also when the drive is disconnected from mains. A contact with this voltage
can lead to injury.
Make sure that there is no voltage in the control terminals before touching the control terminals.
-
W A R N I N G
ACCIDENTAL MOTOR START
When there is a power-up, a power break, or a fault reset, the motor starts immediately if the start signal is active, unless the pulse
control for Start/Stop logic is selected. If the parameters, the applications or the software change, the I/O functions (including the
start inputs) can change. If you activate the auto reset function, the motor starts automatically after an automatic fault reset. See
the Application Guide. Failure to ensure that the motor, system, and any attached equipment are ready for start can result in
personal injury or equipment damage.
Disconnect the motor from the drive if an accidental start can be dangerous. Make sure that the equipment is safe to operate
-
under any condition.
W A R N I N G
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the drive properly can result in death or serious injury.
Ensure the correct grounding of the equipment by a certied electrical installer.
-
W A R N I N G
SHOCK HAZARD FROM PE CONDUCTOR
The drive can cause a DC current in the PE conductor. Failure to use a residual current-operated protective (RCD) device Type B or
a residual current-operated monitoring (RCM) device can lead to the RCD not providing the intended protection and therefore
can result in death or serious injury.
Use a type B RCD or RCM device on the mains side of the drive.
-
2.3 Cautions and Notices
C A U T I O N
DAMAGE TO THE AC DRIVE FROM INCORRECT MEASUREMENTS
Doing measurements on the AC drive when it is connected to mains can damage the drive.
Do not do measurements when the AC drive is connected to mains.
-
C A U T I O N
DAMAGE TO THE AC DRIVE FROM INCORRECT SPARE PARTS
Using spare parts that are not from the manufacturer can damage the drive.
Do not use spare parts that are not from the manufacturer.
-
C A U T I O N
DAMAGE TO THE AC DRIVE FROM INSUFFICIENT GROUNDING
Not using a grounding conductor can damage the drive.
Make sure that the AC drive is always grounded with a grounding conductor that is connected to the grounding terminal
-
that is identied with the PE symbol.
BC346130105092EN-US-000101 / DPD0158330 | Danfoss A/S © | 2020.06
Loading...
+ 182 hidden pages