Danfoss VACON NXP GRID CONVERTER Application guide

VACON® NXP

AC DRIVES

GRID CONVERTER APPLICATION MANUAL

ARFIFF03

arfiff03 Grid Converter

VACON® · 3

 

 

 

 

 

 

Table of contents

 

 

 

 

Document: DPD01599C

 

 

 

 

Software code: ARFIFF03V164

 

 

 

 

Version release date: 31.5.2021

1.

General ....................................................................................................................................

 

8

 

1.1

AFE Control...............................................................................................................................

8

 

1.2

Island (Static Power Supply)....................................................................................................

8

 

1.3

Micro Grid..................................................................................................................................

9

 

1.4

Shaft Generator ......................................................................................................................

10

 

1.5

Acronyms ................................................................................................................................

11

 

1.6

Compatibility issues in parameters between versions........................................................

12

2.

Quick start and operation principles .....................................................................................

13

 

2.1

Quick start instructions..........................................................................................................

13

 

2.2

In case of parallel AFE: ..........................................................................................................

13

 

2.3

Pre-Charging of DC ................................................................................................................

15

 

2.4

Main circuit breaker control (MCB).......................................................................................

16

 

2.5

Start Sequence .......................................................................................................................

17

 

2.6

Stop sequence ........................................................................................................................

18

 

2.7

afe mode; Start Stop timing diagram....................................................................................

19

 

2.8

Operation principle: Droop Speed Control Mode .................................................................

20

 

2.9

Operation principle: Isochronous Speed Control Mode.......................................................

20

 

2.10

Voltage compensation............................................................................................................

21

 

2.11

OPT-D7....................................................................................................................................

22

 

2.12

Master Follower .....................................................................................................................

23

 

 

2.12.1

General .......................................................................................................................

23

 

 

2.12.2 Grid Converter Standard master follower................................................................

23

 

 

2.12.3

Grid Converter DriveSynch........................................................................................

23

 

 

2.12.4

Grid Converter D2-Synch...........................................................................................

23

3.

Control I/O .............................................................................................................................

 

25

 

3.1

Slot A and Slot B terminals....................................................................................................

25

 

3.2

Terminal To Function (TTF) ...................................................................................................

25

 

3.3

Defining inputs and outputs...................................................................................................

26

 

3.4

Defining a terminal in NCDrive..............................................................................................

27

4.

Monitoring signals .................................................................................................................

28

 

4.1

Monitoring value tables..........................................................................................................

28

 

 

4.1.1

Monitoring values 1....................................................................................................

28

 

 

4.1.2

Monitoring values 2....................................................................................................

29

 

 

4.1.3

Fieldbus monitoring values.......................................................................................

29

 

 

4.1.4

I/O monitoring values.................................................................................................

30

 

 

4.1.5

Master/Follower.........................................................................................................

30

 

 

4.1.6

Licence key activation................................................................................................

30

 

 

4.1.7

Line Monitoring ..........................................................................................................

30

 

 

4.1.8

Active Limits ...............................................................................................................

31

 

 

4.1.9

PI Power Controller ...................................................................................................

31

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

Classified as Public

4 · VACON®

arfiff03 Grid Converter

 

 

 

4.2 Description of monitoring values ..........................................................................................

32

 

 

4.2.1

Monitoring 1 values....................................................................................................

32

 

 

4.2.2

Monitoring 2 values....................................................................................................

35

 

 

4.2.3

Fieldbus monitoring values.......................................................................................

37

 

 

4.2.4

I/O monitoring values.................................................................................................

43

 

 

4.2.5

Master Follower .........................................................................................................

44

 

 

4.2.5.1

Currents ...................................................................................................................

45

 

 

4.2.5.2

Statuses ....................................................................................................................

46

 

 

4.2.6

Activation status.........................................................................................................

47

 

 

4.2.7

Line Monitoring ..........................................................................................................

48

 

 

4.2.8

Active Limits ...............................................................................................................

48

 

 

4.2.9

PI Power Controller ...................................................................................................

48

5.

Parameter list

........................................................................................................................

49

 

5.1

Basic parameters ...................................................................................................................

49

 

5.2

Reference ................................................................................................................handling

49

 

 

5.2.1

DC .................................................................................................Reference Tuning

50

 

 

5.2.2 Power .................................................................................../ Frequency reference

50

 

 

5.2.3 PID ...................................................................................Power Controller for AFE

50

 

 

5.2.4

Reactive ....................................................................................................Reference

51

 

 

5.2.5

AC .................................................................................................voltage reference

52

 

5.3

Ramp control ..........................................................................................................................

52

 

5.4

Input signals ...........................................................................................................................

52

 

 

5.4.1

Basic .............................................................................................................settings

52

 

 

5.4.2

Digital ..............................................................................................................inputs

53

 

 

5.4.3

Analogue ........................................................................................................input 1

54

 

 

5.4.4

Analogue ........................................................................................................input 2

54

 

 

5.4.5

Analogue ........................................................................................................input 3

54

 

 

5.4.6

Analogue ........................................................................................................input 4

55

 

5.5

Output signals.........................................................................................................................

55

 

 

5.5.1

Digital .................................................................................................output signals

55

 

 

5.5.2

Delayed ..............................................................................................................DO 1

56

 

 

5.5.3

Delayed ..............................................................................................................DO 2

56

 

 

5.5.4

Analogue ......................................................................................................output 1

57

 

 

5.5.5

Analogue ......................................................................................................output 2

58

 

 

5.5.6

Analogue ......................................................................................................output 3

59

 

 

5.5.7

Options........................................................................................................................

59

 

5.6

Limit settings..........................................................................................................................

60

 

 

5.6.1

Current ...............................................................................................................limit

60

 

 

5.6.2

Power .................................................................................................................limit

60

 

 

5.6.3

Frequency ..........................................................................................................limit

60

 

 

5.6.4

Micro ...................................................................................................................Grid

60

 

 

5.6.5

DC ...................................................................................................................voltage

61

 

5.7

Drive control ...........................................................................................................................

61

 

 

5.7.1

AFE .................................................................................................................control

61

 

 

5.7.2

Identification...............................................................................................................

62

 

 

5.7.3

Active .................................................................................................Compensation

62

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

Classified as Public

arfiff03 Grid Converter

VACON® · 5

 

 

 

 

 

5.8

Master/Follower .....................................................................................................................

62

 

5.9

Protections..............................................................................................................................

63

 

 

5.9.1

General .......................................................................................................................

63

 

 

5.9.2

Temperature Sensor Protections .............................................................................

64

 

 

5.9.3

Earth fault...................................................................................................................

64

 

 

5.9.4

Fieldbus fault..............................................................................................................

64

 

 

5.9.5

External fault..............................................................................................................

65

 

 

5.9.6

Grid voltage D7 ...........................................................................................................

65

 

 

5.9.7

Grid frequency ............................................................................................................

65

 

 

5.9.8

Voltage ........................................................................................................................

65

 

 

5.9.9

Over Load....................................................................................................................

66

 

 

5.9.10

D7 Protections............................................................................................................

66

 

 

5.9.11

Cooling protection......................................................................................................

66

 

 

5.9.12

Extra............................................................................................................................

66

 

5.10

Fieldbus...................................................................................................................................

67

 

5.11

Micro Grid................................................................................................................................

69

 

 

5.11.1

Free Select .................................................................................................................

69

 

5.12

Synchronisation to external grid ...........................................................................................

70

 

5.13

Reserved .................................................................................................................................

70

 

5.14

ID control functions................................................................................................................

71

 

 

5.14.1

Value control ..............................................................................................................

71

 

 

5.14.2

DIN ID control 1..........................................................................................................

71

 

 

5.14.3

DIN ID control 2..........................................................................................................

71

 

 

5.14.4

DIN ID control 3..........................................................................................................

72

 

 

5.14.5

DIN ID control 4..........................................................................................................

72

 

 

5.14.6

Signal Fault function..................................................................................................

72

 

 

5.14.7

ID Controlled Digital Output 1 ...................................................................................

72

 

 

5.14.8

ID Controlled Digital Output 1 ...................................................................................

72

 

5.15

Auto reset................................................................................................................................

73

 

5.16

Grid voltage PI ........................................................................................................................

73

 

5.17

Keypad control (M3) ...............................................................................................................

73

 

5.18

System menu (M6)..................................................................................................................

73

 

5.19

Expander boards (M7) ............................................................................................................

73

6.

Description of parameters.....................................................................................................

74

 

6.1

Basic parameters ...................................................................................................................

74

 

 

6.1.1

Transformer parameters ..........................................................................................

76

 

6.2

Reference handling ................................................................................................................

77

 

 

6.2.1

DC Reference Tuning .................................................................................................

78

 

 

6.2.2

Power / Frequency reference ...................................................................................

79

 

 

6.2.3

PID Power Controller.................................................................................................

82

 

 

6.2.4

Reactive Current Reference......................................................................................

83

 

 

6.2.5

AC Voltage Reference ................................................................................................

84

 

6.3

Ramp control ..........................................................................................................................

86

 

6.4

Input signals ...........................................................................................................................

88

 

 

6.4.1

Basic settings .............................................................................................................

88

 

 

6.4.2

Digital input signals ...................................................................................................

89

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

Classified as Public

6 · VACON®

arfiff03 Grid Converter

 

 

 

6.4.2.1 Synchronization to external grid ...............................................................................

91

 

6.4.2.2

Forced control place .................................................................................................

93

 

6.4.3

Analogue inputs 1-4...................................................................................................

95

 

6.4.3.1 Analogue input to any parameter .............................................................................

97

6.5

Output signals.........................................................................................................................

98

 

6.5.1

Digital output signals.................................................................................................

98

 

6.5.1.1 Fieldbus digital inputs connection.............................................................................

99

 

6.5.2

Delayed digital output 1 & 2 ....................................................................................

100

 

6.5.3

Analogue output 1 & 2 & 3.......................................................................................

102

 

6.5.4

Options......................................................................................................................

105

6.6

Limit settings........................................................................................................................

107

 

6.6.1

Current limits ...........................................................................................................

107

 

6.6.2

Power limits..............................................................................................................

111

 

6.6.3

Frequency limits.......................................................................................................

112

 

6.6.4

Micro Grid limits.......................................................................................................

113

 

6.6.5

DC voltage regulators ..............................................................................................

114

6.7

Drive control .........................................................................................................................

116

 

6.7.1

AFE Control ..............................................................................................................

121

 

6.7.2

Identification.............................................................................................................

122

 

6.7.3

Active Compensation ...............................................................................................

122

6.8

Master Follower ...................................................................................................................

123

6.9

Protections............................................................................................................................

125

 

6.9.1

General settings .......................................................................................................

125

 

6.9.2

Temperature Sensor Protections ...........................................................................

129

 

6.9.2.1

Individual channel monitoring ................................................................................

131

 

6.9.3

Earth fault.................................................................................................................

132

 

6.9.4

Fieldbus ....................................................................................................................

133

 

6.9.5

External fault............................................................................................................

133

 

6.9.6

Grid voltage D7 .........................................................................................................

133

 

6.9.7

Grid frequency ..........................................................................................................

135

 

6.9.8

Supply voltage ..........................................................................................................

136

 

6.9.9

Over Load Protection ...............................................................................................

138

 

6.9.10

D7 protections ..........................................................................................................

139

 

6.9.11

Cooling protection....................................................................................................

140

 

6.9.12

Extra..........................................................................................................................

141

6.10

Fieldbus.................................................................................................................................

 

142

6.11

Micro Grid (uGrid).................................................................................................................

145

 

6.11.1.1

Generator Simulation ...........................................................................................

147

 

6.11.1.2 AFE operation mode selection..............................................................................

148

6.12

Synch to external grid ..........................................................................................................

149

6.13

Reserved

...............................................................................................................................

150

6.14

ID functions...........................................................................................................................

151

 

6.14.1

Value control ............................................................................................................

151

 

6.14.2

DIN ID control...........................................................................................................

153

 

6.14.3

Signal Fault Function...............................................................................................

154

 

6.14.4

ID Controlled Digital Output ....................................................................................

155

6.15

Auto Reset.............................................................................................................................

156

6.16

Grid voltage PI controller.....................................................................................................

157

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

Classified as Public

arfiff03 Grid Converter

VACON® · 7

 

 

 

 

 

 

 

6.16.1

Grid voltage PI OPT-D7 limits .................................................................................

157

7.

Keypad control parameters .................................................................................................

158

8.

FB Status and control in detail ............................................................................................

159

 

8.1

FB DC Reference ..................................................................................................................

159

 

8.2

State machine: Basic............................................................................................................

160

 

 

8.2.1

FB Control Word Basic ............................................................................................

160

 

8.3

State Machine: Standard......................................................................................................

161

 

 

8.3.1

Control Word: Standard...........................................................................................

161

 

8.4

State machine: Vacon AFE 1 ................................................................................................

162

 

 

8.4.1

Control Word: Vacon AFE 1 .....................................................................................

162

 

8.5

State machine: Vacon AFE 2 ................................................................................................

163

 

 

8.5.1

Control Word: Vacon AFE 2 Profile (3)....................................................................

163

 

8.6

FB Status Word.....................................................................................................................

165

 

8.7

FB Micro Grid Control Word 1 ID1700.................................................................................

167

9.

Problem solving ...................................................................................................................

168

10.

Commissioning ....................................................................................................................

169

 

10.1

Open loop voltage compensation ........................................................................................

169

 

 

10.1.1

Parameters affect ....................................................................................................

169

 

 

10.1.2

No load tuning ..........................................................................................................

169

 

 

10.1.3

Tuning on the fly.......................................................................................................

169

 

 

10.1.4

Tuning with load bank..............................................................................................

170

 

 

10.1.5

Tuning against strong grid ......................................................................................

170

 

 

10.1.6

Closed Loop Voltage Control ...................................................................................

170

11.

Fault codes

..........................................................................................................................

171

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

Classified as Public

8 · VACON®

arfiff03 Grid Converter

 

 

1. General

This application is not kept backwards compatible. See chapter Compatibility issues before you update the application. The Grid Converter application is used to make AC grids with a possibility to operate in parallel with other power sources. The Grid Converter application has 3 different operation modes:

-Standard AFE mode.

-Island mode.

-Micro Grid mode.

1.1AFE Control

AFE function keeps constant DC voltage. AFE mode transfers power between DC and AC. AFE cannot create grid by itself, it needs to be connected to existing grid.

 

MCB Control

 

Q2

 

G1

Filter

U2

 

 

U1

 

UDC

~

=

Figure 1.

1.2Island (Static Power Supply)

Island mode generates constant voltage and frequency. In island mode DC Voltage is not controlled.

Island mode cannot operate in parallel with other power sources in AC side, because the drive will not balance reactive or active power with other power sources.

DC voltage level needs to be considered to have correct voltage on AC side in different load situations, considering voltage losses in LCL filter and in transformer.

D7

=

~

T1

MCB Control

U3 Filter U4 D Y U5

Q1

T2

U4 = Transf. GC Side

U5 = Transf. Grid Side

Figure 2.

S1

<![if ! IE]>

<![endif]>Grid

1

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

Classified as Public

 

arfiff03 Grid Converter

VACON® · 9

 

 

1.3Micro Grid

Micro Grid mode controls the grid voltage and frequency. It functions like an ordinary generator. Micro Grid mode does not control DC Voltage.

With the help of voltage droop and frequency droop, more than one Micro Grid and/or Generators can work together.

D7

=

~

D7

=

~

 

 

T1

 

 

 

MCB Control

 

 

 

 

U3

 

U4

 

U5

 

Filter

 

D

Y

 

 

 

S1

 

 

 

 

Q1

 

 

 

 

T2

 

 

 

U4 = Transf. GC Side

 

 

 

U5 = Transf. Grid Side

 

 

 

 

 

 

Q2

 

 

 

 

G1

 

 

T1

 

 

 

MCB Control

 

 

 

 

U3

U4

 

U5

 

Filter

D

Y

Q1

S1

 

 

 

 

 

T2

 

 

 

U4 = Transf. GC Side

 

 

U5 = Transf. Grid Side

 

Figure 3.

<![if ! IE]>

<![endif]>Ship Grid

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

1

Classified as Public

 

10 · VACON®

arfiff03 Grid Converter

 

 

1.4Shaft Generator

The shaft generator is a system where the generator is connected to the main engine shaft that also runs the main propulsion. The disadvantage is that the main engine must run at nominal speed even if full power to the propeller is not necessary.

With the shaft generator system power goes through the drives. One converts power from the generator to DC link, and the other makes a ship grid with constant 50 Hz or 60 Hz, thus there is no direct connection to the generator. The main engine can run at a more efficient speed without changing grid frequency.

One drive operates as an AFE on the generator side and the other operates on Island mode or Micro Grid mode on the grid side.

-The start command to generator side drive.

-Both drives can make DC charging if powered by +24 Vdc.

-When DC is at an 80% of nominal, the generator side and the grid side breakers close.

-The generator side AFE is started to boost DC first.

-The grid side Grid Converter is started and will synchronise to grid.

-The drives take power from the bypass, and the PMS opens the SG contactor.

-You can decrease the speed of the main diesel engine to be more economical.

NOTE! If it is necessary to have these systems in parallel, the system bus communication is reserved for parallel Micro Grid units on the grid side. The control must be arranged separately for each drive.

SG

 

 

Q4

MCB Control

UDC

 

U2 ~

Q2

 

 

 

Filter

 

 

U5

=

D7

=

~

G1

 

 

 

 

 

G2

 

 

T3

 

 

 

 

 

 

 

<![if ! IE]>

<![endif]>Grid

Auxilliary loads

 

 

 

 

 

 

 

including single

 

 

 

 

 

 

 

 

MCB Control

T1

 

 

 

 

<![if ! IE]>

<![endif]>Ship

phase loads

U3

 

 

 

 

Q1

Q3

 

 

Filter

 

D

Y

 

 

 

 

 

 

 

 

T2

 

 

 

 

ST

BT

Figure 4.

1

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

Classified as Public

 

arfiff03 Grid Converter

VACON® · 11

 

 

1.5Acronyms

AC

=

Alternating Current

AI

=

Analogue Input

AIO

=

All-In-One Applications

AM

=

Asynchronous Motor

ASIC

=

Application Specific Integrated Circuit

CL

=

Closed Loop

DC

=

Direct Current

DI

=

Digital Input

DO

=

Digital Output

DS

=

DriveSynch

FB

=

Field Bus

FFT

=

Function To Terminal

FW

=

Firmware

FWP

=

Field Weakening Point

FWPV

=

Field Weakening Point Voltage

GE

=

Greater or Equal

HW

=

Hardware

I/f

=

Current / Frequency

Id

=

Magnetization Current

IGBT

=

Insulated Gate Bipolar Transistor

INV

=

Inversion

Iq

=

Torque Producing Current

LT

=

Less Than

MF

=

Master-Follower

OL

=

Open Loop

PID

=

Proportional Integral Derivative

PM

=

Permanent Magnet

PMSM

=

Permanent Magnet Synchronous Motor

PU

=

Per Unit

RO

=

Relay Output

RS

=

Reset Set

SB

=

System Bus

Sep.Ex SM

=

Separately Excitated Synchronous Motor

SM

=

Synchronous Machine

SPC

=

Speed Control

SQS

=

Sfe Quick Stop

SR

=

Set Reset

SRM

=

Synchronous Reluctance Motor

SS1

=

Safe Stop 1

STO

=

Safe Torque Off

SW

=

Software

TC

=

Torque Control

TC

=

Time Constant

TTF

=

Terminal To Function

U/f

=

Voltage / Frequency

UV

=

Under Voltage

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

1

Classified as Public

 

12 · VACON®

arfiff03 Grid Converter

 

 

1.6Compatibility issues in parameters between versions

Update Note 1: This application parameters are not kept backwards compatible if new features or improvements would be difficult to implement by doing so. Read this change note and chapter “Compatibility issues in parameters between versions” from manual before updating the application.

Update Note 2: It’s recommended to use compare function for parameter changes when updating application, especially in cases when version number change is considerably high.

Application is constantly developed; this includes changing parameter default values, and if parameters are directly downloaded to drive improved default values may be lost.

Update Note 3: If OPT-D7 PI voltage control is needed in uGrid mode, do not use versions V082 or V083.

V092

Major Compatibility Issue: P2.1.7 System Nom. DC is initialized to unit nominal DC value.

500 Vac unit: 675 Vdc

690 Vac unit: 931 Vdc

o When the transformer ratio was other than 1:1: MCB closing limit and DC-Link Voltage reference values were based on grid voltage after transformer. This was causing reference handling problems when given AC values were in range of different voltage class unit.

o DC Voltage Reference in AFE mode is based always to System Nom DC parameter.

V089

oCompatibility Issue: Voltage MotPot is adjusting now field weakening point voltage. Units have been changed from [V] to [%]. This enables more accurate adjustment and adjustment rate.

V087

oMinor Compatibility Issue: FB Actual Speed signal changed to use Filtered DC-Link Voltage signal (ID1108) instead of unfiltered DC Voltage signal.

V081

o Compatibility Issue: Parameters “PID Activation” and “FreqScaleMinAO” had same ID1807. “FreqScaleMinAO” DI changed to ID1809.

o Major Compatibility Issue: Fieldbus State Machine o See full details from latest manual.

o Not Used -> Basic, As in Fieldbus manual

oStandard –> NEW Standard, Application level state machine, this was Basic in earlier versions than V081 i.e. as in Fieldbus manual.

oFB Status and FB Control word modified to be more suitable for AFE use, following idea of ProfiDrive standard.

V080

oMinor compatibility issue: Monitoring and parameter values unified with other premium drive applications.

V128

oMinor compatibility issue: P2.7.8 Control Options2 B1 is no longer available, this has been replaced with P2.9.1.15 FaultWarnIndicat parameter.

1

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

Classified as Public

 

arfiff03 Grid Converter

VACON® · 13

 

 

2. Quick start and operation principles

NOTE! Before you start the commissioning, read the safety instructions in the user manual of your product.

To use the Island, Micro Grid, or Shaft generator operation, you need a licence key. The AFE mode is available without a licence.

This application requires an NXP3 control board VB761 or newer.

The control place (P3.1) of the Micro Grid drive is Keypad as a default.

The basic I/O configuration of the Grid Converter drive consists of OPT-A1, OPT-A2, and OPT-D7 option boards. The basic I/O configuration is described in Table 1.

OPT-D7 is required when the Grid Converter unit is needed to start with zero power to the grid. If grid frequency is not monitored with OPT-D7, the unit may go generator side or directly to full power because different reference frequency and grid frequency.

The Grid Converter is utilised by using AFE hardware with special software. An external LC(L)-filter and charging circuit is needed. This unit is selected when low harmonics are required. The principle connection of AFE drive has been described in Figure 5.

The external 24 Vdc is recommended for control board(s). It enables the setting of parameters even when the power unit itself is not powered. This is important also when software updates are made. Some default I/O configuration of the application can cause unexpected DO operation. When the control board is powered, the drive can give information from the status of the system if, for example, the drive I/O is used for an overall system monitoring.

The external 24 Vdc is required for the drives in cases where the start command starts the control board-controlled precharging operation.

2.1Quick start instructions

1.Connect the unit according to the Figure 5.

2.Power up the control unit with 24 Vdc.

3.Set the basic parameters (G2.1)

4.Check that the digital input parameters (G2.4.2) have been set according to the connections.

5.Change the control place according to the system requirements.

6.Charge the unit.

2.2In case of parallel AFE:

1.Set P2.1.5 Parallel AFE to Yes. This will also set DC Drooping to 3.00% (Default).

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

2

Classified as Public

 

14 · VACON®

arfiff03 Grid Converter

 

 

Figure 5. Connection

2

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

Classified as Public

 

arfiff03 Grid Converter

VACON® · 15

 

 

2.3Pre-Charging of DC

This AFE application has its own charging control, P2.5.1.13 DC Charge (24 Vdc required for control board) and charging protection in case the external charging cannot get DC voltage to required level within set time P2.9.1.6 Charge Max Time (provided that the DC Voltage reaches the under voltage fault level).

The charging function is activated when P2.5.1.13 DC Charge is A.1 or higher. When the control place is IO, Keypad or NCDrive, charging is started from the start command.

Charging is not started if:

-Drive is in fault state.

-P2.4.2.26 Enable CB Close is FALSE

-P2.4.2.8 Run Enable is FALSE

-P2.4.2.19 Quick Stop is FALSE

Charging is also stopped if above conditions occur during charging or if the start command is removed.

For fieldbus control, charging is started with B0 of FB Control Word on the supporting FB profiles. Charging is also stopped if B0 goes low. Also MCB is opened if already closed.

DC Charge (F80) is given if 85 % of DC Nominal is not reached within P2.9.1.6 Charge Max Time and charging is stopped.

DC Charging is stopped when the drive receives feedback from P2.4.2.4 MCB Feedback.

NOTE! Use suitably sized DC Charging resistor. To select the correct size, check Pulse loadability for time duration set in for Max Charge Time parameter.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

2

Classified as Public

 

16 · VACON®

arfiff03 Grid Converter

 

 

2.4Main circuit breaker control (MCB)

The Grid Converter application controls the circuit breaker of the system with the relay output RO2. When the DC bus is charged, the MCB will be closed. The status of the MCB is monitored via a digital input. The digital input used for monitoring is selected with parameter P2.3.1.3. Faults can be set to open the MCB by selecting a response to a fault to be 3=Fault, DC OFF.

An external charging circuit is necessary to charge the DC bus but drive can control this circuit if 24 Vdc is provided for the control board.

Closing limit is 85% of the nominal DC Voltage.

Opening limit is 75% of the nominal DC Voltage.

Nominal DC Voltage = Grid Nom Voltage (P2.1.1) * 1.35.

Over Current (F1), Hardware IGBT (F31) and Software IGBT (F41) faults will open MCB immediately to protect the drive.

NOTE! The MCB feedback is necessary for the correct operation of the Grid Converter application.

NOTE! Only the drive controls its own MCB. If additional interlocks or opening commands are needed, these commands must go through the drive.

NOTE! UPS may be needed during short circuit situation to keep MCB closed if control voltage is taken from the grid where the short circuit occurs.

NOTE! Missing feedback signal prevent drive going to ready state. MCB Feedback can be monitored from Status Word B10.

NOTE! If feedback is not used there will be three second forced delay on internally generated MCB feedback signal. MCB Feedback can be monitored from Status Word B10.

2

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

Classified as Public

 

arfiff03 Grid Converter

VACON® · 17

 

 

2.5Start Sequence

 

Start

 

 

Ready to switch

 

 

on

 

 

Charge

Fault

 

Reset

 

DC-Link

 

 

NO

DC-Link

 

 

> 85 %

 

YES

Close Main

Contactor

Main Contactor

NO

MCC Fault

 

 

Closed

 

 

 

 

 

 

 

 

 

Run Enable

NO

YES

Ready To Run

Start Signal

NO

YES

Synchronize with mains

 

NO

Line Synch Fault

 

Synch OK

 

 

 

 

 

F10

 

 

 

 

 

 

 

 

 

 

YES

Running

Figure 6. AFE start sequence

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

2

Classified as Public

 

18 · VACON®

arfiff03 Grid Converter

 

 

2.6Stop sequence

Modulating

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MCB Closed

 

 

 

F64 A4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

No

 

 

 

 

 

 

 

 

 

 

 

 

F64 A2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stop Request

 

 

 

MCB Closed

 

 

 

(If DC > 85 %)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Delayed)

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Open MCB

No

Yes

Stop Modulation

(If Run State)

Open MCB

Yes

MCB Closed F64 A3

(Delayed)

No

End

Figure 7. Stop sequence

2

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

Classified as Public

 

arfiff03 Grid Converter

VACON® · 19

 

 

2.7afe mode; Start Stop timing diagram

<![if ! IE]>

<![endif]>P. Start Delay

Stable DC

MCB Close level

DC Voltage

FB CW.B00

Control in

FB Control

FB CW.B03

IO Start

Contro in

IO Control

IO MCB Open

Command

Charge Control

MCB Close Control

MCB Feedback

Ready

Run

Above example when “Standard” state machine is used. With “Basic” state machine operation is like in IO Control.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

2

Classified as Public

 

20 · VACON®

arfiff03 Grid Converter

 

 

2.8Operation principle: Droop Speed Control Mode

When the power demand increases, all generators on the grid allow frequency to droop. This will balance the load between all the generators on the grid. Then the power management system gives all generators a command to increase frequency so that the grid frequency is maintained at its nominal value.

When the load is reducing on the grid, the frequency of the generators will increase, and the power management system gives a command to decrease frequency.

Freq.

Change

 

 

 

 

 

52,0 Hz

+4%

 

 

 

 

 

51,5 Hz

+3%

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

r

 

 

51,0 Hz

+2%

 

 

oopi

 

 

 

<![if ! IE]>

<![endif]>Loading

 

ng

 

 

 

 

 

 

 

50,5 Hz

+1%

<![if ! IE]>

<![endif]>-loading

 

 

 

 

 

 

 

Related

 

 

 

<![if ! IE]>

<![endif]>Un

 

 

Load

50,0 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25%

50%

75%

100%

49,5 Hz

-1%

 

 

 

 

 

49,0 Hz

-2%

 

 

 

 

 

 

 

 

 

 

 

48,5 Hz

-3%

 

 

 

 

 

48,0 Hz

-4%

 

 

 

 

 

Figure 8.

2.9Operation principle: Isochronous Speed Control Mode

In the isochronous speed control mode, the Micro Grid frequency reference is kept the same as the grid frequency with help of OPT-D7. This will keep power at zero regardless of grid frequency. While drive operates in drooping mode, the actual power is controlled by base current reference. This reference needs to be controller by power management system (PMS) that will handle power sharing between different machines on the grid.

2

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

Classified as Public

 

arfiff03 Grid Converter

VACON® · 21

 

 

2.10Voltage compensation

Grid Converter system will have voltage losses. Depending on the system, the losses may be more than 50 Vac when operating close to Grid Converter nominal currents with low power factor between points U3 and U5. This voltage loss needs to be compensated so that the grid voltage stays at nominal. This also sets requirements for the needed DC link voltage.

50 Hz

 

Q2

 

~

 

SG

Filter

U2

UDC

 

 

 

 

U1

 

=

 

 

 

 

 

Figure 9.

D7

 

T1

 

60 Hz

 

 

MCB Control

 

 

=

U3

U4

U5

 

 

 

 

Filter

Q1

S1

~

 

 

 

 

T2

 

 

 

U4 = Transf. GC Side

 

 

 

U5 = Transf. Grid Side

 

Voltage compensation

<![if ! IE]>

<![endif]>Utility Grid

The normal operation voltage range in a land-based grid is usually between 80% and 115% of the grid nominal voltage.

The voltage losses compensation is handled separately for Active power (kW) and Reactive power (kVar), the latter being more significant. The Active power voltage losses are compensated with Inductor Losses parameter (P2.2.6.6) and Reactive power voltage losses are compensated with Inductor Size parameter (P2.2.6.5).

Uncompensated system may result in unnecessary reactive power circulation in a grid between the different power sources and wrong grid voltage.

OPT-D7 can be used to compensate the voltage losses (closed loop voltage compensation) but it is recommended to do an open loop voltage compensation tuning in case of OPT-D7 failure. When the OPT-D7 measurements exceed the set limit values, the voltage compensation falls back to open loop control.

Inductor Size and Losses affect

Grid Nom. Voltage: 400 Vac, Reactive Current: 30%, Active Current 50%, Inductor Size: 15%, Inductor Losses: 15%, Voltage Correction: 0 Vac.

Reactive Increase:

400

Vac×30%×15%=18 Vac

Active Increase:

400

VacIncrease: or Losses: 15% 400 Vac×50%×15%×15%=4.5 Vac

Total increase:

18 Vac+4.5 Vac =22.5 Vac

See also document: Voltage Compensation Vxxx.pdf.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

2

Classified as Public

 

22 · VACON®

arfiff03 Grid Converter

 

 

2.11OPT-D7

OPTD7 is an AC sinusoidal voltage measurement board. Using this board, the drive measures the line voltage, the frequency and the voltage angle information.

The drive can compare this information with its output voltage angle when it runs. This feature can be used to make synchronisations to a grid that is measured. For example, for line synchronisation purposes you can use APFIFF44 LineSynch II Application. That will work as a smooth starter.

In Grid Converter application this can be used:

-To synchronise to existing external grid while the drive is running to enable bumpless transfer from a generator operation to a shore powered operation in a ship.

-To control the grid voltage (Voltage losses compensation).

-To enable a zero power connection to an existing grid.

-To help in the commissioning of drive active power and reactive power voltage losses compensation when the actual grid voltage is visible in NCDrive.

The OPT-D7 board is delivered with the transformer which is suitable for a voltage range up to 690 Vac. The transformer cannot be used with a pulse width modulated (PWM) voltage input.

It is possible to use a customised transformer when the input voltage to be measured is not within the OPT-D7 transformer voltage range. The transformation ratio parameter can be adjusted according to the transformer primary to secondary ratio. See details in the OPT-D7 user manual.

Synchronisation to the grid can be made without the OPT-D7 when the drive operates in the AFE or the Micro Grid mode. This requires that the output terminals of the drive are connected to the existing grid when the drive is in the STOP state. When a start command has been given in AFE or Micro Grid mode, the drive will make standard AFE synchronisation. Depending on the operation mode, the drive will start to keep constant DC voltage (AFE) or start to share power based on grid frequency (Micro Grid). Using OPT-D7 for synchronisation will make the start of the drive smoother.

If the drive does not detect an existing line voltage or frequency in Micro Grid mode, the output voltage is raised defined time (VoltageRiseTime). In the Island mode, the detection of the grid is not made and the voltage is raised from zero in the set time (VoltageRiseTime).

NOTE: The OPT-D7 board (in slot C) is mandatory for the Grid Converter unit.

2

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

Classified as Public

 

arfiff03 Grid Converter

VACON® · 23

 

 

2.12Master Follower

2.12.1General

In master follower modes master is sending control word and DC Voltage reference to follower drives. Follower drives send a status word to master including some command see details from monitoring values description.

Start command is synchronized

Master sends run request to followers when all drives indicates that MCB is closed.

o Status is monitored even if follower do not have own MCB or status from the MCB. If any of the drive goes state where MCB is needed to open all drives will open the MCB. Control signals to follower drives

oDC voltage reference, can be selected in follower drive if used master or own reference.

2.12.2Grid Converter Standard master follower

In standard master follower mode modulation is not synchronized in any way through system bus communication. This mode can be used when all the units can work independently but e.g. start and DC-Link voltage reference is only wanted to give master drive and only four units are needed for parallel operation.

3-LCL-filters are needed to use Up to 4 parallel units.

2.12.3Grid Converter DriveSynch

In DriveSynch master follower modulation is synchronized between the drives, basically all follower will do exactly what master will do.

3-pole LC-filters or standard sine-filters can be used instead of LCL-filters when common point is connected to transformer.

Up to 4 parallel units.

2.12.4Grid Converter D2-Synch

In D2-Synch each unit operate independently only modulation switching is synchronised to eliminate rotating currents.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

2

Classified as Public

 

24 · VACON®

 

 

 

 

arfiff03 Grid Converter

 

 

 

 

 

 

 

 

 

Applicable if MV

 

 

 

400-690 / MV

 

 

 

 

 

OPT-D7

Transformer

<![if ! IE]>

<![endif]>for <1m length cable-11V Limit performance EMC better

MCB

 

 

 

 

 

See note 1.

Control

 

 

 

 

 

 

 

MCB

 

 

 

 

 

 

Feedback

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<![if ! IE]>

<![endif]>Optional

<![if ! IE]>

<![endif]>Optional

OPT-A1

N

<![if ! IE]>

<![endif]>Optional

OPT-A2

 

OPT-D7

X

OPT-D2

P

OPT-??

 

 

Master

Optical

Fibre

See note 2.

OPT-A1

N

OPT-A1

N

OPT-A2

OPT-A2

OPT-D7

X

 

X

OPT-D2

P

OPT-D2

P

OPT-??

OPT-??

 

Follower

 

Follower

 

Backup Master

 

 

 

 

 

DC-Link Fuses

 

 

 

According to

 

 

 

Discrimination Study

 

One option is to have many

 

 

 

parallel fuses (not drawn

 

 

 

here). Each fuse protects

 

 

 

one battery string and

 

 

 

cable.

 

 

Optional

Drive

Supply

Cable

L

R

See note 4.

See note 3.

NOTE:

1.Breaker to be equipped with optional precharging of Sine-Filter capacitors

(Can be parallel smaller breaker with resistors for example). Precharge will precharge DC-link capacitors as well.

2.High Frequency (HF) capacitors to be installed to limit Common Mode Voltage (CMV) for the batteries.

3.Breaker to be equipped with precharging of DC-Link capacitors

(Can be parallel smaller breaker with resistors for example) 4. Verify that the battery side fuse selection is according to discrimination.

2

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

Classified as Public

 

arfiff03 Grid Converter

VACON® · 25

 

 

3. Control I/O

3.1Slot A and Slot B terminals

Table 1. Minimum recommended I/O configuration.

OPT-A1

 

 

Terminal

 

 

 

Signal

 

Description

1

 

 

+10Vref

Reference voltage output

 

Voltage for potentiometer, etc.

2

 

 

AI1+

Analogue input 1.

 

Input range selected by jumpers.

 

 

 

 

 

 

Range 0-10V, Ri = 200

 

Default range: Voltage 0 – 10 V

 

 

 

 

 

 

Range 0-20 mA Ri = 250

 

 

 

3

 

 

AI1-

I/O Ground

 

Ground for reference and controls

4

 

 

AI2+

Analogue input 2.

 

Input range selected by jumpers.

5

 

 

AI2-

Range 0-10V, Ri = 200

 

Default range: Current 0 – 20 mA

 

 

 

 

 

 

Range 0-20 mA Ri = 250

 

 

 

6

 

 

+24V

Control voltage output

 

Voltage for switches, etc. max 0.1 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

GND

I/O ground

 

Ground for reference and controls

8

 

 

DIN1

Programmable G2.2.1

 

 

 

9

 

 

DIN2

Programmable G2.2.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

DIN3

Programmable G2.2.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

 

 

CMA

Common for DIN 1– DIN 3

 

Connect to GND or +24V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

+24V

Control voltage output

 

Voltage for switches (see #6)

13

 

 

GND

I/O ground

 

Ground for reference and controls

14

 

 

DIN4

MCB Feedback

 

0 = MCB open

 

 

 

 

 

 

Programmable G2.2.1

 

1 = MCB closed

15

 

 

DIN5

Quick Stop

 

0 = Quick Stop Active

 

 

 

 

 

 

Programmable G2.2.1

 

1 = No Quick Stop

16

 

 

DIN6

Programmable G2.2.1

 

 

 

17

 

 

CMB

Common for DIN4– DIN6

 

Connect to GND or +24V

18

 

 

AO1+

Analogue output 1

 

Programmable

19

 

 

AO1-

 

 

 

 

 

 

Range 0– 20 mA/RL, max. 500

20

 

 

DO1

Digital output

 

Programmable P2.3.1.1

 

 

 

 

 

 

READY

 

Open collector, I 50mA, U 48 VDC

 

OPT-A2

 

 

 

 

 

 

 

 

 

21

 

 

RO1

 

 

 

 

Relay output 1

 

 

Switching capacity

 

 

 

 

 

 

 

 

 

 

 

 

22

 

 

RO1

 

 

 

 

Programmable P2.3.1.2

 

 

24 VDC / 8 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

23

 

 

RO1

 

 

 

 

 

 

 

250 VAC / 8A

 

 

 

 

 

 

 

 

 

 

 

 

 

125 VDC / 0.4 A

 

 

24

 

 

RO2

 

 

 

 

Relay output 2

 

 

This RO is not programmable.

 

 

 

 

 

 

 

 

 

 

 

 

25

 

 

RO2

 

 

 

 

MCB control

 

 

Fixed for MCB Control (Close)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

26

 

 

RO2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.2Terminal To Function (TTF)

The programming principle of the input and output signals in the Grid Converter Application is different compared to the conventional method used in other VACON® NX applications.

In the conventional programming method, Function to Terminal Programming Method (FTT), you have a fixed input or output that you define a certain function for. The applications mentioned above, however, use the Terminal to Function Programming method (TTF) in which the programming pro¬cess is carried out the other way round: Functions appear as parameters which the operator defines a certain input/output for.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

3

Classified as Public

 

26 · VACON®

arfiff03 Grid Converter

 

 

3.3Defining inputs and outputs

Connecting a certain input or output with a certain function (parameter) is done by giving the parameter an appropriate value. The value is formed of the Board slot on the VACON® NX control board (see VACON® NX User Manual) and the respective signal number, see below.

READY

I/Oterm

Function name AI Ref Faul/Warn

DigOUT:B.1

Slot

Terminal number

Terminal type

 

Example: You want to connect the digital output function Reference fault/warning (parameter 2.3.3.7) to the digital output DO1 on the basic board NXOPTA1 (see VACON® NX User Manual).

First find the parameter 2.3.3.7 on the keypad. Press the Menu button right once to enter the edit mode. On the value line, you will see the terminal type on the left (DigIN, DigOUT, An.IN, An.OUT) and on the right, the present input/output the function is connected to (B.3, A.2 etc.), or if not connected, a value (0.#).

When the value is blinking, hold down the Browser button up or down to find the desired board slot and signal number. The program will scroll the board slots starting from 0 and proceeding from A to E and the I/O selection from 1 to 10.

Once you have set the desired value, press the Enter button once to confirm the change.

READY

READY

READY

I/Oterm

I/Oterm

I/Oterm

AI Ref Faul/Warn

AI Ref Faul/Warn

AI Ref Faul/Warn

enter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DigOUT:0.0

DigOUT:0.0

 

 

DigOUT:B.1

 

 

 

 

 

 

3

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

Classified as Public

 

Danfoss VACON NXP GRID CONVERTER Application guide

arfiff03 Grid Converter

VACON® · 27

 

 

3.4Defining a terminal in NCDrive

If you use the VACON® NCDrive Programming Tool for parametrizing you will have to establish the connec¬tion between the function and input/output in the same way as with the control panel. Just pick the address code from the drop-down menu in the Value column (see the Figure below).

Figure 3 1. Screenshot of NCDrive programming tool; Entering the address code

 

 

 

Be ABSOLUTELY sure not to connect two functions to one and

 

 

 

same output in order to avoid function overruns and to ensure

 

 

 

flawless operation.

WARNING

 

Note: The inputs, unlike the outputs, cannot be changed in RUN state.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

3

Classified as Public

 

28 · VACON®

arfiff03 Grid Converter

 

 

4. Monitoring signals

The menu M1 (Monitoring) has all the monitoring values. Values are only for monitoring and cannot be altered on the control panel.

4.1Monitoring value tables

4.1.1Monitoring values 1

 

Code

 

Parameter

 

Unit

 

 

Form.

 

ID

 

 

Description

 

V1.1.1

 

DC-Link Voltage

 

V

#

 

1108

 

 

Measured DC Link voltage in volts,

 

 

 

 

 

 

filtered.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Used DC voltage reference by the

 

 

 

 

 

 

 

 

 

 

 

 

 

regenerative unit in % of Nominal DC

 

V1.1.2

 

DC Voltage Ref.

%

 

#,##

 

1200

 

 

voltage.

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal DC voltage = 1.35 * supply

 

 

 

 

 

 

 

 

 

 

 

 

 

voltage

 

V1.1.3

 

DC Voltage Act.

%

 

#,##

 

7

 

 

Same scaling as DC Voltage Ref.

 

V1.1.4

 

Total Current

 

A

 

Varies

1104

 

 

Filtered current

 

V1.1.5

 

Active Current

%

 

#,#

 

1125

 

 

> 0 power from AC side to DC side

 

 

 

 

 

 

< 0 power from DC side to AC side

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V1.1.6

 

Reactive Current

%

 

#,#

 

1157

 

 

 

 

V1.1.7

 

Power kW

 

kW

 

Varies

1508

 

 

> 0 power from AC side to DC side

 

 

 

 

 

 

< 0 power from DC side to AC side

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V1.1.8

 

Power %

%

 

#,#

 

5

 

 

> 0 power from AC side to DC side

 

 

 

 

 

 

< 0 power from DC side to AC side

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V1.1.9

 

Status Word

 

 

 

#

 

43

 

 

 

 

V1.1.10

 

Supply Frequency

 

Hz

#,##

 

1

 

 

Drive output frequency

 

V1.1.11

 

Supply Voltage

 

V

#,#

 

1107

 

 

Drive output voltage

 

V1.1.12

 

Line Frequency D7

 

Hz

#,##

 

1654

 

 

Measured line frequency

 

V1.1.13

 

Line Voltage D7

 

V

#

 

1650

 

 

Measured line voltage

 

V1.1.14

 

AC Voltage Reference

 

V

#

 

1556

 

 

Used AC Voltage Reference

 

V1.1.15

 

DC Ref Max Lim

%

 

#,##

 

1606

 

 

Internal limit for DC Voltage Ref.

4

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

Classified as Public

 

arfiff03 Grid Converter

VACON® · 29

 

 

4.1.2Monitoring values 2

 

Code

 

Parameter

 

Unit

 

Form.

 

ID

 

 

Description

 

V1.2.1

 

DC Voltage

 

V

#

 

44

 

 

Measured DC Link voltage in

 

 

 

 

 

 

volts, unfiltered.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0 = AFE

 

V1.2.2

 

Operation Mode

 

 

 

#

 

1615

 

 

1 = Island

 

 

 

 

 

 

 

 

 

 

 

 

2 = Micro Grid

 

 

 

 

 

 

 

 

 

 

 

 

Used current reference is

 

V1.2.3

 

Used Current Ref

%

 

#,#

 

1704

 

 

negated to parameter value.

 

 

 

 

 

 

Made to compare values in

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NCDrive easier to Active current

 

V1.2.4

 

D7 Synch. Error

 

 

 

#

 

1659

 

 

Synchronisation error to external

 

 

 

 

 

 

 

 

grid

 

 

 

 

 

 

 

 

 

 

 

 

 

V1.2.5

 

Cos Phi Actual

 

 

 

#,###

 

1706

 

 

 

 

V1.2.6

 

Unit Temperature

 

°C

#

 

1109

 

 

 

 

V1.2.7

 

Freq. Reference

 

Hz

#,#

 

1752

 

 

Used line frequency reference

 

V1.2.8

 

Current

 

A

Varies

1113

 

 

Unfiltered current

 

V1.2.9

 

Operation Hours

 

h

#,##

 

1856

 

 

 

 

V1.2.10

 

Reactive Current

%

 

#,#

 

1389

 

 

 

 

 

Reference

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V1.2.11

 

Grid State

 

 

 

#

 

1882

 

 

 

 

V1.2.12

 

Mindex

%

 

#,#

 

1858

 

 

Modulation Index

 

V1.2.13

 

Phase U Current

 

A

Varies

39

 

 

rms, 1 second linear filtering

 

V1.2.14

 

Phase V Current

 

A

Varies

40

 

 

rms, 1 second linear filtering

 

V1.2.15

 

Phase W Current

 

A

Varies

41

 

 

rms, 1 second linear filtering

 

V1.2.16

 

DC-Link Current

 

A

Varies

72

 

 

 

 

V1.2.17

 

DC-Link ActCurr

%

 

#,#

 

1158

 

 

 

 

V1.2.18

 

Crest Factor

 

 

 

#,###

 

1101

 

 

 

4.1.3Fieldbus monitoring values

Code

Parameter

Unit

Form.

ID

Description

V1.3.1

FB Control Word

 

#

1160

Control word from fieldbus

V1.3.2

FB Status Word

 

#

68

Status word to fieldbus

V1.3.3

Fault Word 1

 

#

1172

 

V1.3.4

Fault Word 2

 

#

1173

 

V1.3.5

Warning Word 1

 

#

1174

 

V1.3.6

FB Micro Grid CW1

 

#

1700

Control for Micro Grid operations

V1.3.7

FB Micro Grid SW1

 

#

1701

Status of Micro Grid operations

V1.3.8

Last Active Warning

 

#

74

 

V1.3.9

Last Active Fault

 

#

37

 

V1.3.10

MC Status

 

#

64

 

V1.3.11

FB Analogue Out

 

#,##

48

 

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

4

Classified as Public

 

30 · VACON®

arfiff03 Grid Converter

 

 

4.1.4I/O monitoring values

Code

Parameter

Unit

Form.

ID

Description

V1.4.1

DIN1, DIN2, DIN3

 

#

15

 

V1.4.2

DIN4, DIN5, DIN6

 

#

16

 

V1.4.3

DIN Status 1

 

#

56

 

V1.4.4

DIN Status 2

 

#

57

 

V1.4.5

Analogue Input 1

%

#,##

13

 

V1.4.6

Analogue Input 2

%

#,##

14

 

V1.4.7

Analogue input 3

%

#,##

27

AI3, unfiltered.

V1.4.8

Analogue input 4

%

#,##

28

AI4, unfiltered.

V1.4.9

Analogue Out 1

%

#,##

26

 

V1.4.10

Analogue Out 2

%

#,##

50

AO2

V1.4.11

Analogue Out 3

%

#,##

51

AO3

V1.4.12

PT100 Temp. 1

°C

#,#

50

 

V1.4.13

PT100 Temp. 2

°C

#,#

51

 

V1.4.14

PT100 Temp. 3

°C

#,#

52

 

V1.4.15

PT100 Temp. 4

°C

#,#

69

 

V1.4.16

PT100 Temp. 5

°C

#,#

70

 

V1.4.17

PT100 Temp. 6

°C

#,#

71

 

4.1.5Master/Follower

 

 

Code

 

Parameter

 

 

Unit

Form.

ID

 

Description

 

 

 

V1.5.1

 

SB SystemStatus

 

 

 

 

#

 

1819

 

 

 

 

 

V1.5.2

 

Master CW

 

 

 

 

#

 

93

 

 

 

 

 

 

Code

 

Parameter

 

 

Unit

 

 

ID

 

Description

 

 

 

V1.5.3.1

 

Current D1

 

 

A

Varies

1820

 

 

 

 

 

V1.5.3.2

 

Current D2

 

 

A

Varies

1821

 

 

 

 

 

V1.5.3.3

 

Current D3

 

 

A

Varies

1822

 

 

 

 

 

V1.5.3.4

 

Current D4

 

 

A

Varies

1823

 

 

 

 

 

Code

 

Parameter

 

 

Unit

 

 

ID

 

Description

 

 

 

V1.5.4.1

 

Status Word D1

 

 

 

 

#

 

1828

 

 

 

 

 

V1.5.4.2

 

Status Word D2

 

 

 

 

#

 

1829

 

 

 

 

 

V1.5.4.3

 

Status Word D3

 

 

 

 

#

 

1830

 

 

 

 

 

V1.5.4.4

 

Status Word D4

 

 

 

 

#

 

1831

 

 

 

4.1.6

 

Licence key activation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Code

 

Parameter

 

 

Unit

 

Form.

 

ID

 

 

Description

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Give this number to the

 

 

 

V1.6.1

 

Serial Number Key

 

 

 

 

#

 

1997

 

 

technical support of the

 

 

 

 

 

 

 

 

 

 

 

manufacturer in case of licence

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

key problems.

 

 

 

V1.6.2

 

Licence Status

 

 

 

 

#

 

1996

 

 

 

 

4.1.7

 

Line Monitoring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Code

 

Parameter

 

 

Unit

 

Form.

 

ID

 

 

Description

 

 

 

V1.7.1

 

Line Voltage D7

 

 

Hz

#,##

 

1654

 

 

Measured line voltage

 

 

 

V1.7.2

 

Line Frequency D7

 

 

V

#

 

1650

 

 

Measured line frequency

 

 

 

V1.7.3

 

Line Voltage THD

 

%

 

#,##

 

1670

 

 

Line voltage total harmonic

 

 

 

 

 

 

 

 

 

distortio

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V1.7.4

 

Line Voltage HF RMS

 

 

V

#,#

 

1671

 

 

RMS of high frequency

 

 

 

 

 

 

 

 

 

components

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

Classified as Public

 

Loading...
+ 155 hidden pages