Danfoss vacon nx apfiff08 power generation with general grid codes Application guide

vacon
®
nx
ac drives
arfiff08 power generation
with general grid codes
arfiff08 power generation VACON® 3
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
VACON® POWER GENERATION APPLICATION MANUAL
INDEX
Document code: DPD02125
Software code: ARFIFF08V040
Date: 26.8.2019
1. Introduction ..................................................................................................................8
1.1 Grid Code Support Information .................................................................................................. 8
1.2 Compatibility issues in parameters between versions ............................................................. 8
2. General .........................................................................................................................9
2.1 Basic features .............................................................................................................................. 9
2.2 Stand Alone .................................................................................................................................. 9
2.3 Multimaster (2 8 x inverter size)........................................................................................... 10
2.4 How to use.................................................................................................................................. 11
2.4.1
Keypad push buttons ........................................................................................................ 11
2.4.2
Inverter status indications ................................................................................................ 12
2.4.3
Control place indications .................................................................................................. 13
2.4.4
Status LEDs (green green red) ................................................................................... 13
2.4.5
Text lines............................................................................................................................ 14
3. Application .................................................................................................................. 15
3.1 Quick Application Commissioning Guide ................................................................................. 15
3.1.1
Commissioning Steps ....................................................................................................... 15
3.1.2
Multimaster PLC out of commission ............................................................................... 17
4. Monitoring signals ...................................................................................................... 18
4.1 Basic monitor values ................................................................................................................. 18
4.1.1
Monitoring values 1 ........................................................................................................... 18
4.1.2
Monitoring values 2 ........................................................................................................... 19
4.1.3
Fieldbus monitoring values .............................................................................................. 19
4.1.4
I/O monitoring values........................................................................................................ 19
4.1.5
MPPT .................................................................................................................................. 20
4.1.6
License key activation ....................................................................................................... 20
4.1.7
Grid code ............................................................................................................................ 20
4.1.8
PID Controller ................................................................................................................... 20
4.2 Monitor Values descriptions ..................................................................................................... 21
4.2.1
Monitoring values 1 ........................................................................................................... 21
4.2.2
Monitoring values 2 ........................................................................................................... 23
4.2.3
Fieldbus monitoring values .............................................................................................. 27
4.2.4
I/O monitoring values........................................................................................................ 29
4.2.5
MPPT .................................................................................................................................. 30
4.2.6
License key activation ....................................................................................................... 31
4.2.7
Gird code ............................................................................................................................ 31
4.2.8
PID Controller ................................................................................................................... 32
5. Parameters ................................................................ ................................................. 33
5.1 P2.1 Basic parameters .............................................................................................................. 33
5.1.1
DC Level Setup .................................................................................................................. 34
5.2 Reference Handling ................................................................................................................... 34
4 • VACON® arfiff08 power generation
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
5.2.1
DC Reference .................................................................................................................... 34
5.2.2
Power/frequency reference ............................................................................................. 35
5.2.2.1 PID Power Controller ............................................................................................... 35
5.2.3
AC Voltage reference ........................................................................................................ 35
5.3 IO Signals ................................................................................................................................... 36
5.3.1
Digital Inputs ..................................................................................................................... 36
5.3.1.1 Configuration............................................................................................................. 37
5.3.1.2 Analog Inputs ............................................................................................................ 37
5.3.1.3 Power Limitation ....................................................................................................... 37
5.3.1.4 Analog Input as Digital Input #1 & #2 ..................................................................... 38
5.3.1.5 DC Ground Measurement......................................................................................... 38
5.3.1.6 Customizable Analog Input ...................................................................................... 38
5.3.2
Digital Outputs ................................................................................................................... 39
5.3.2.1 Configuration............................................................................................................. 40
5.3.3
Analog Outputs .................................................................................................................. 41
5.4 Limit Settings ............................................................................................................................. 42
5.4.1
Current Limit ..................................................................................................................... 42
5.4.2
Generator Power Limit ..................................................................................................... 42
5.5 Inverter Control ......................................................................................................................... 43
5.5.1
Standby Control ................................................................................................................. 43
5.5.2
MPP Tracker ...................................................................................................................... 43
5.5.3
Bypass Control .................................................................................................................. 46
5.5.4
Multimaster Follower Control .......................................................................................... 46
5.5.5
Power Adjust ..................................................................................................................... 46
5.6 Drive Control .............................................................................................................................. 46
5.6.1
Control ............................................................................................................................... 46
5.7 Protections ................................................................................................................................. 47
5.7.1
General .............................................................................................................................. 47
5.7.2
DC Earth Fault ................................................................................................................... 47
5.7.3
AC Earth Fault ................................................................................................................... 47
5.7.4
Main Contactor .................................................................................................................. 48
5.7.5
Fieldbus ............................................................................................................................. 48
5.7.6
System bus ........................................................................................................................ 49
5.7.7
Auto reset .......................................................................................................................... 49
5.7.8
Analog Inputs ..................................................................................................................... 50
5.7.9
AC Voltage Protections ..................................................................................................... 50
5.7.10
AC Frequency Protections ............................................................................................ 50
5.8 Fieldbus ...................................................................................................................................... 51
5.9 System Tests .............................................................................................................................. 52
5.9.1
Power Simulation .............................................................................................................. 52
5.9.2
System bus ........................................................................................................................ 52
5.9.3
Simulated Grid................................................................................................................... 52
5.10 Counters ..................................................................................................................................... 53
5.11 Admin Parameters .................................................................................................................... 54
5.11.1
Ext Fan Control ............................................................................................................. 54
5.11.2
Datalogger ..................................................................................................................... 54
5.11.2.1 Trigger ....................................................................................................................... 54
5.11.2.2 Settings ..................................................................................................................... 55
5.12 Grid Codes .................................................................................................................................. 56
5.12.1
FRT ................................................................................................................................. 56
5.12.2
Reconnection ................................................................................................................. 56
5.12.3
Line Voltage ................................................................................................................... 57
5.12.4
Line Frequency .............................................................................................................. 57
arfiff08 power generation VACON® 5
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
5.12.5
Voltage Time Trip .......................................................................................................... 58
5.12.6
Line OK Limits ............................................................................................................... 58
5.12.7
Reactive Injection .......................................................................................................... 59
5.12.7.1 Linear UV ................................................................................................................... 59
5.12.7.2 Linear OV ................................................................................................................... 59
5.12.7.3 Power Lock UV .......................................................................................................... 59
5.12.7.4 Power Lock OV .......................................................................................................... 59
5.12.7.5 Q(U) Power ................................................................................................................ 60
5.12.8
Power Limit ................................................................................................................... 60
5.12.8.1 High Frequency ......................................................................................................... 60
5.12.8.2 High Voltage .............................................................................................................. 60
5.12.8.3 Low Frequency Power .............................................................................................. 60
5.12.8.4 Cos Phii Control ........................................................................................................ 61
5.12.8.5 External Input ........................................................................................................... 61
5.12.8.6 Options ...................................................................................................................... 61
5.13 Control........................................................................................................................................ 62
5.14 System menu ............................................................................................................................. 62
5.15 Expander boards (Control keypad: Menu M7) ......................................................................... 62
6. Parameters and descriptions ...................................................................................... 63
6.1 Basic Parameters ...................................................................................................................... 63
6.1.1
Transformer Parameters ................................................................................................. 64
6.1.2
Configuration Parameters ................................................................................................ 65
6.1.3
DC Level Setup .................................................................................................................. 66
6.2 Reference Handling ................................................................................................................... 67
6.2.1
DC Reference .................................................................................................................... 67
6.2.2
Power/ Frequency reference ........................................................................................... 68
6.2.2.1 PID Power Controller ............................................................................................... 69
6.2.3
AC Voltage reference ........................................................................................................ 70
6.3 IO signals.................................................................................................................................... 71
6.3.1
Digital inputs ..................................................................................................................... 71
6.3.1.1 Configuration............................................................................................................. 73
6.3.2
Analog inputs ..................................................................................................................... 74
6.3.2.1 Power limitation ........................................................................................................ 74
6.3.2.2 Analog Input as Digital Input #1 & #2 ..................................................................... 75
6.3.2.3 DC ground measurement ......................................................................................... 76
6.3.2.4 Custom analog input................................................................................................. 77
6.3.3
Digital outputs ................................................................................................................... 78
6.3.3.1 Configuration............................................................................................................. 79
6.3.4
Analog outputs .................................................................................................................. 80
6.4 Limit settings ............................................................................................................................. 81
6.4.1
Current limit ...................................................................................................................... 81
6.4.2
Generator power limit ....................................................................................................... 81
6.5 Inverter Control ......................................................................................................................... 82
6.5.1
Standby settings ................................................................................................................ 82
6.5.2
MPP tracker....................................................................................................................... 83
6.5.3
Bypass control ................................................................................................................... 85
6.5.4
Multimaster follower control ........................................................................................... 85
6.5.5
Power adjust ...................................................................................................................... 85
6.6 Drive Control .............................................................................................................................. 86
6.6.1
Control ............................................................................................................................... 88
6.7 Protections ................................................................................................................................. 89
6.7.1
General .............................................................................................................................. 89
6 • VACON® arfiff08 power generation
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
6.7.2
DC Earth fault .................................................................................................................... 90
6.7.3
AC Earth Fault ................................................................................................................... 90
6.7.4
Main Contactor .................................................................................................................. 90
6.7.5
Control Panel..................................................................................................................... 91
6.7.6
Systembus ......................................................................................................................... 91
6.7.7
Auto reset .......................................................................................................................... 92
6.7.8
Analog Inputs ..................................................................................................................... 93
6.7.9
AC Voltage Protection ....................................................................................................... 93
6.7.10
AC Frequency Protection .............................................................................................. 93
6.8 Fieldbus ...................................................................................................................................... 94
6.9 System Tests .............................................................................................................................. 95
6.9.1
Power Simulation .............................................................................................................. 95
6.9.2
Systembus test .................................................................................................................. 96
6.9.3
Simulated grid ................................................................................................................... 97
6.10 Counters ..................................................................................................................................... 98
6.11 Admin parameters .................................................................................................................... 99
6.11.1
External fan control ...................................................................................................... 99
6.11.2
Datalogger ................................................................................................................... 100
6.11.2.1 Datalogger trigger .................................................................................................. 100
6.11.2.2 Datalogger settings ................................................................................................ 101
6.12 Grid Code parameters ............................................................................................................. 102
6.12.1
FRT ............................................................................................................................... 103
6.12.2
Reconnection ............................................................................................................... 104
6.12.3
Line Voltage ................................................................................................................. 105
6.12.4
Line Frequency ............................................................................................................ 107
6.12.5
Voltage Time Trip ........................................................................................................ 109
6.12.6
Line OK Limits ............................................................................................................. 110
6.12.7
Reactive Injection ........................................................................................................ 111
6.12.7.1 Linear reference under voltage ............................................................................. 112
6.12.7.2 Linear reference over voltage ............................................................................... 113
6.12.7.3 Power Lock In and Out Reference under voltage. ................................................ 114
6.12.7.4 Power Lock In and Out Reference over voltage. .................................................. 115
6.12.7.5 Q(U) Power .............................................................................................................. 116
6.12.8
Power Limit ................................................................................................................. 117
6.12.8.1 High Frequency Power Limit ................................................................................. 117
6.12.8.2 High Voltage Power Limit ...................................................................................... 119
6.12.8.3 Low Freq Power ...................................................................................................... 120
6.12.9
Cos Phii Control .......................................................................................................... 121
6.12.9.1 Lock in and out control .......................................................................................... 121
6.12.9.2 Cos Phii Active Current Control ............................................................................. 122
6.12.10
External Input .............................................................................................................. 123
6.12.11
Grid Code Options ....................................................................................................... 124
7. Control...................................................................................................................... 125
8. Fieldbus interface ..................................................................................................... 126
8.1 Control Word ............................................................................................................................ 127
8.2 Status Words............................................................................................................................ 128
8.3 Warning Status words ............................................................................................................. 129
8.4 Monitoring values for Fieldbus use ........................................................................................ 131
9. Problem solving ........................................................................................................ 132
10. Application Fault Codes ............................................................................................. 133
arfiff08 power generation VACON® 7
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
11. State Machine: .......................................................................................................... 137
11.1 General state machine: ........................................................................................................... 137
11.1.1
Start Criterions: .......................................................................................................... 138
11.1.2
Activation command: .................................................................................................. 139
11.2 General Substate Machine ...................................................................................................... 140
11.2.1
Field OK ....................................................................................................................... 140
11.3 MPPT State: ............................................................................................................................. 141
12. IO-Connections ......................................................................................................... 142
12.1 Appendix ................................................................................................................................... 143
8 • VACON® arfiff08 power generation
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
1. INTRODUCTION
In this application is kept backwards compatibility with ARFIFF07. The power generation application is used to generate power to grid using the maximum power point tracker (MPPT) or manual DC reference.
1.1 Grid Code Support Information
In this application is used general grid codes.
1.2 Compatibility issues in parameters between versions
NOTE! This application is not kept backwards compatible. See release notes and this chapter before updating the application.
Update Note 1: When you update the application do not use NCDrive parameter download function. Instead upload parameters from the unit and compare them to the old parameter file. The application is constantly developed, and it includes changing parameter default values. If parameters are directly downloaded to drive, improved default values will be lost.
arfiff08 power generation VACON® 9
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
2. GENERAL
The power generation application is an answer to growing renewable energy market. The inverters need only DC voltage and the grid to start producing energy.
Picture 1. Basic solar system.
2.1 Basic features
The power generation application works with Multi master and Stand-alone configurations. It can be used with thin film and polycrystal Solar panels. Multi master configured system is controlled by external Touch panel.
Additional functions:
Grid Code functionality.
Possibility to send Power Limit also from Fieldbus
Multi-Master functionality with daily master change.
Maximum Power Point Tracking
Possibility to set any parameter value through Fieldbus interface.
2.2 Stand Alone
There is only one inverter unit which is producing energy to the grid. This system is working alone and there is no need to use any external control systems or backup systems.
10 • VACON® arfiff08 power generation
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
2.3 Multimaster ( 8 x inverter size)
The multi master functionality is used in bigger systems. There are two to eight inverter units which are producing energy to the grid. This system has always the touch panel, which controls the system. Inverters are equally loaded, because each time system is started, MPPT master is changed, which will extend the lifetime of the inverters.
In the multi master system there is one inverter which is controlling other inverters behavior and that inverter is called master inverter. Master inverter collects information of the DC bus and makes decisions regarding what DC reference is used.
Other inverters are slave inverters and they follow DC reference coming from the master inverter. Each of the inverters is responsible of its own behavior on the Grid side, i.e. complying with Grid Code Standard.
Each unit is sending status information to operator panel and they can be read in touch panel.
Picture 2. Multi master system master change function.
arfiff08 power generation VACON® • 11
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
2.4 How to use
2.4.1
Keypad push buttons
1
1
2
3
4
5
6
7
8
Picture 3. Keypad push buttons
1 = Start button.
Pressing this button unit goes to ready state in multi master system or if stand­alone configuration is used it goes to ready state and if there is enough DC voltage, it will try to run.
Pressing start button for 5 seconds when the Control Source is set to Panel forces
the drive to start regardless of DC level.
2 = Stop button.
Pressing this button stops the unit
3 = Enter button serves for:
1) confirmation of selections
4 = Select button is used to switch between two latest displays. May be useful when you
want to see how the changed new value influences some other value. 5 = Reset button is used to reset active faults. 6 = Browser button up and down
Browse the main menu and the pages of different submenus.
Edit values. 7 = Menu button left
Move backward in menu.
Move cursor left (in parameter menu).
Exit edit mode. 8 = Menu button right
Move forward in menu.
Move cursor right (in parameter menu).
Enter edit mode.
12 • VACON® arfiff08 power generation
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
2.4.2
Inverter status indications
Picture 4.Keypad Indicators
The inverter status indications tell the user what the status of the Inverter and the Inverter is and whether the Inverter control software has detected irregularities in Inverter functions.
RUN = Inverter is running;
= Indicates the direction of current flow.
STOP = Start c control panel.
READY = Lights when AC and DC Voltage is on. In case of a trip or stop button is pushed,
the symbol will not light up.
ALARM = Indicates that the Inverter is running outside a certain limit and a warning is
given.
FAULT = Indicates that unsafe operating conditions were encountered due to which the
Inverter was stopped.
arfiff08 power generation VACON® • 13
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
2.4.3
Control place indications
The symbols I/O term, Keypad and Bus/Comm (see Figure 7-1) indicate the choice of control place made in the Keypad control menu (M3).
= I/O terminals are the selected control place; i.e. START/STOP commands or
reference values etc. are given through the I/O terminals.
= Control keypad is the selected control place; i.e. the Inverter can be started or
stopped, or its reference values etc. altered from the keypad.
= The inverter is controlled through a fieldbus.
= Run enable not active
= Unit is ready to start in the morning.
2.4.4
Status LEDs (green green red)
The status LEDs light up in connection with the READY, RUN and FAULT Inverter status indicators.
(Ready) = Steady ON (no other LEDs): Start command has been given, all start criterions
have been fulfilled except that the drive has not detected high enough voltage to start up.
Blinking at 2 Hz: All external start criterions have been fulfilled but no start
command has been given.
(Run) = Steady ON: The Inverter is running.
Blinking: Stop command has been given and the inverter is ramping power
down.
(Fault) = Blinks when unsafe operating conditions were encountered due to which the
Inverter was stopped (Fault Trip). Simultaneously, the Inverter status indicator FAULT blinks on the display and the fault description can be seen on the panel.
14 • VACON® arfiff08 power generation
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
2.4.5
Text lines
menu structure as well as with information related to the operation of the Inverter.
Location indication; displays the symbol and number of menu, parameter etc.
Description line; Displays the description of menu, value or fault.
Value line; Displays the numerical and textual values of references,
parameters etc. and the number of submenus available in each menu.
arfiff08 power generation VACON® • 15
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
3. APPLICATION
3.1 Quick Application Commissioning Guide
The Power generation application has been design for easy and fast commissioning. The user only needs to set the Basic parameters and check if the there are any I/O parameters to be changed.
The Basic parameters are meant to be set in numerical order. Then the option board parameters are set correctly automatically and system is ready faster.
3.1.1
Commissioning Steps
Table 1. Application Commissioning Steps
Step #
Step
Description
1
If you are updating the application to newer version, write down the following counter values before updating: V1.1.10 Total Energy kWh V1.1.13 RunTime Total V1.1.16 Grid Connections V1.1.17 IntFanRunHours V1.1.18 ExtFanRunHours
These values need to be written down so that the counters can be reset to correct values after application update.
2
After application update, write the corresponding counter values to these parameters: P2.10.2 TotalEnergyPreset P2.10.3 GridConnPreset P2.10.4 TotalRunTimPrese P2.10.5 IntFanRuntPresVa P2.10.6 ExtFanRuntPresVa
Change parameter P2.10.1
This will set the counters to the values before application update.
3
Define right grid settings P2.1.1 Grid Nom Voltage
P2.1.2 Grid Nom Freq P2.1.6 Transf inv. side P2.1.7 Transf grid side
When grid settings are right drive voltage is calculated correct.
4
Set parameters P2.1.7 and P2.1.8 in numerical order.
By setting the parameters in numerical order the necessary option board parameters are set also automatically to their correct/default values.
This speeds up the process especially in Multimaster system commissioning.
5
If commissioning is done before large scale power production is possible, set P2.1.9.1 DC Start Level parameter to a level where the inverter will surely start when the sun is up.
Otherwise no need to change anything else in Basic Parameters
This parameter indicates the minimum DC voltage needed for the drive to try start up. If this is larger than the current DC level when the drive is stopped (as it is during morning or evening commissioning) the drive will not start.
6
Set the I/O parameters in G2.3 as required.
Some fault or warning may have been triggered due to wiring in customized cabinet solutions.
7
Reset any possible faults.
Reset the possible wiring related faults / warnings.
8
Set P2.9. any one unit
This will start a SystemBus test procedure that will blink the Ready, Run and Fault LEDs in all of the drives in order, starting from the inverter where the parameter was set.
If the LEDs do not blink in all of the units, check the optical cables, jumper settings in
16 • VACON® arfiff08 power generation
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
OPT-D2 option boards and Basic parameters in all of the drives.
9
Set P2.9.1.1 Simulation Mode to
and press start
in the Beijer panel
This activates the simulation mode where drives use simulated DC voltage (P2.5.1.6) and simulates power production which the Beijer touch panel can see.
This test ensures that the system works as a whole and the communication between the inverters and Beijer touch panel is working (in multimaster system) alright without actually having DC or real output power.
You may need to lower the limit for starting up the next follower in the Beijer parameters to enable follower start ups.
10
When every drive in the system has ran, press stop in the Beijer panel and set P2.9
This disables the simulation mode and enables the drive to run normally.
11
Give Start command. If drive has not started but Ready LED is lit
and power production should be possible, press Start button for 5 seconds.
If the DC is above the P2.1.9.1 DC Start Level the drive will start. Pressing the Start button for 5 seconds forces the drive to start regardless of DC level.
12
Make sure parameter P2.1.9.6 DC Start Level Max is set to appropriate value compared to the specified open circuit voltage of the panel field.
NOTE: during hot summer days, the actual open circuit voltage can go as low as 90% of the specified OC voltage, set the parameter accordingly!
P2.1.9.6 DC Start Level Max is the absolute maximum value that the addition of offset after natural stops will not exceed. This is to ensure that the start level never rises so high that the drive will never start up.
13
In Multimaster system when power production is ~75 % from system maximum, use P2.2.2 DC Calibration to tweak the output power of all of the drives to match each other.
This is done to ensure that the small DC voltage measurement errors between the drives are not causing adverse effects on the power production and the produced power values are close to the same in the Multimaster panel.
arfiff08 power generation VACON® • 17
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
3.1.2
Multimaster PLC out of commission
If it happens that the multimaster control PLC is out of order, the drives are able to work using master-follower operation mode where all of the drives are always working at the same time:
Step #
Step
Description
1
Set parameter P2.1.8 SB
This setting indicates for the unit #1 that it needs to send the start command to the other drives via SystemBus
2
Set P3.1 Control Source in the master to Panel
This way the user can use the Panel to give the Start command to the master unit and the drive no longer listens to commands from Fieldbus
3
Set P3.1 Control Source in all of the other drives to SystemBus
This way the follower drives listen for the Start command from SystemBus
4
Reset possible faults and give Start command to the master unit.
If drives have not started but Ready LED is lit in the Master unit and large scale power production is possible, press Start button for 5 seconds.
The drives start up and start producing power.
18 • VACON® arfiff08 power generation
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
4. MONITORING SIGNALS
The monitoring values are the actual values of parameters and signals as well as statuses and measurements. On the next pages you will find the lists of monitoring values within the respective monitor values groups. The monitor values descriptions are given on pages 16 to 25.
Column explanations: Code = Location indication on the keypad; Shows the operator the present parameter number
Values = Name of monitor value Unit = Unit of monitor value; Given if available ID = ID number of the parameter
All monitoring value is possible to monitoring from fieldbus by ID number
4.1 Basic monitor values
4.1.1
Monitoring values 1
Table 2. Monitoring values 1
Code
Values
Unit
ID
Description
V1.1.1
DC-Link Voltage
V
1108
Measured DC Link voltage in volts, filtered.
V1.1.2
DC Voltage Ref.
%
1200
Used DC voltage reference by the regenerative unit in % of Nominal DC voltage. Nominal DC voltage = 1.35 * supply voltage
V1.1.3
Output Current
A
1834
Output current of the inverter coming out of the cabinet.
V1.1.4
Reactive Current
%
1157
V1.1.5
Power kW
kW
1707
terminals.
V1.1.6
Supply Frequency
Hz
1123
Drive output frequency
V1.1.7
Supply Voltage
V
1107
Drive output voltage
V1.1.8
Grid Frequency
Hz
1835
Measured line frequency
V1.1.9
Grid Voltage
V
1709
Measured line voltage
V1.1.10
Total Energy kWh
kWh
1837
Total energy produced.
V1.1.11
Energy Today kWh
kWh
1708
Energy produced today.
V.1.1.12
Energy Yesterday
kWh
1733
Energy produced yesterday.
V1.1.13
Run Time Total
h
1836
Total time the inverter has been running.
V1.1.14
RunTime Today
h
1731
The time the inverter has been running today.
V.1.1.15
RunTimeYesterday
h
1732
The time the inverter was running yesterday.
V1.1.16
Grid Connections
1706
Total number of times the inverter has closed the main contactor and connected to the grid.
V1.1.17
Int Fan Run Hours
h
1511
Total time internal fan has been running
V1.1.18
Ext Fan Run Hours
h
1512
Total time external fan has been running
V1.1.19
StandbyRemaining
s
1201
Remaining time in standby mode, if standby mode is activated.
arfiff08 power generation VACON® • 19
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
4.1.2
Monitoring values 2
Table 3. Monitoring values 2
Code
Values
Unit
ID
Description
V1.2.1
Cos Phii Actual
1717 V1.2.2
Unit Temperature
°C
1109
V1.2.3
Reactive Current
Reference
%
1389
V1.2.4
Active Current
%
1125
V1.2.5
InverterStatus 1
1819
Diagnostic statusword 1
V1.2.6
InverterStatus 2
1820
Diagnostic statusword 2
V1.2.7
InverterStatus 3
1821
Diagnostic statusword 3
V1.2.8
InverterStatus 4
1822
Diagnostic statusword 4
V1.2.9
EEPROMSaveStatus
1106
Status of the nonvolatile memory (EEPROM) storing activated by the application 0 = IDLE 1 = ACTIVE 2 = RESOURCE ERROR 3 = WRITE ERROR 4 = NOT FOUND 5 = NOT SUPPORTED (e.g. NXP2)
V1.2.10
Status Word
43
V1.2.11
Used DC start level
V
1965
Monitoring Value for the currently used DC Start Level value.
V1.2.12
Mindex
%
1874
Modulation Index
V1.2.13
Calibrated DC Voltage
V
1839
4.1.3
Fieldbus monitoring values
Table 4. Fieldbus
Code
Values
Unit
ID
Description
V1.3.1
FB Control Word
1478
Control word from fieldbus
V1.3.2
FB Status Word
1479
Status word to fieldbus
V1.3.3
FB GenPowerLim
1481
Power limit sent by the fieldbus
V1.3.4
FB Q/PF Ref
Q: % PF: -
1480
Reactive Current or Power Factor reference sent by the fieldbus
V1.3.5
Day from PLC
1719
Day index sent from the PLC
4.1.4
I/O monitoring values
Table 5. I/O Monitor
Code
Values
Unit
ID
Description
V1.4.1
DIN1, DIN2, DIN3
15
V1.4.2
DIN4, DIN5, DIN6
16
V1.4.3
DIN Status 1
56
V1.4.4
DIN Status 2
57
V1.4.5
Analogue Input 1
%
13
V1.4.6
Analogue Input 2
%
14
V1.4.7
Custom AnOut 1
%
1240
20 • VACON® arfiff08 power generation
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
4.1.5
MPPT
Table 6. MPPT
Code
Values
Unit
ID
Description
V1.5.1
MPPT Reference
1816
The DC reference from the MPP tracker. Shows without ramping if ramping is used.
V1.5.2
Actual Step Size
1815
This value shows the actual momentary step size of the MPP tracker.
V1.5.3
Actual Step Ratio
1825
This value shows the actual step ratio. Power change divided by actual step size. The value is used for evaluating the size of the next step.
V1.5.4
Actual Step State
1817
State of the MPP tracker. For debugging purpose only.
V1.5.5
Power Window On
0
Power window status.
V1.5.6
Optimal DC Point
1724
Estimated optimal DC Point is the DC Reference point which giving the best simulated power.
4.1.6
License key activation
Table 7. License key activation
Code
Values
Unit
ID
Description
V1.6.1
Serial Number Key
1997
Give this number to the technical support of the manufacturer in case of licence key problems.
4.1.7
Grid code
Code
Parameter
Unit
Form.
ID
Description
V1.7.1
Line State
# 2202
V1.7.2
Line Voltage GC
%
#,##
1912
Line Voltage used by Grid Code
V1.7.3
Line Frequency GC
%
#,##
1913
Line Frequency used by Grid Code
V1.7.4
Line Voltage L1-L2
%
#,##
2203 V1.7.5
Line Voltage L2-L3
%
#,##
2204 V1.7.6
Line Voltage L3-L1
%
#,##
2205 V1.7.7
Trip State
2206
4.1.8
PID Controller
Code
Parameter
Unit
Form.
ID
Description
V1.8.1
PID Reference
#,#
20 V1.8.2
PID Actual Value
#,#
21 V1.8.3
PID Output
#,##
23
arfiff08 power generation VACON® • 21
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
4.2 Monitor Values descriptions
4.2.1
Monitoring values 1
V1.1 DC -link Voltage V ID 1108
Filtered DC Link voltage in Volts.
V1.2 DC Voltage Reference % ID 1200
Used DC voltage reference. 100 % = 1,35 x Nominal AC Voltage.
V1.3 Output Current A ID 1834
Output current of the inverter coming out of the cabinet.
V1.4 Reactive Current % ID 1157
The reactive current of the regenerative drive in % of System Rated Current.
V1.5 Output Power kW ID 1707
V1.6 Supply Frequency Hz ID 1123
The drive output frequency.
V1.7 Supply Voltage V ID 1107
The drive output voltage.
V1.8 Grid Frequency Hz ID 1835
Grid frequency in ##.## Hz. The sign indicates the phase order. Can be monitored only when UNIT is in RUN state.
V1.9 Grid Voltage V ID 1709
AC Voltage measured on the grid side of the main contactor by an external measurement circuit.
V1.10 Total Energy kWh kWh ID 1837
Total produced energy to the grid
V1.11 Energy Today kWh kWh ID 1708
Amount of energy produced today.
22 • VACON® arfiff08 power generation
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
V1.12 Energy Yesterday kWh ID 1733
Amount of energy produced yesterday.
V1.13 Run Time Total h ID 1836
Total time the inverter has been running.
V1.14 Run Time Today h ID 1731
The time the inverter has been running today.
V1.15 Run Time Yesterday h ID 1732
The time the inverter was running yesterday.
V1.16 Grid Connections ID 1706
Total number of times the inverter has closed the main contactor and connected to the grid.
V1.17 Int Fan Run Hours h ID 1511
Total time internal fan has been running
V1.18 Ext Fan Run Hours h ID 1512
Total time external fan has been running
V1.19 Standby Remaining s ID 1201
Remaining time in standby mode, if standby mode is activated.
arfiff08 power generation VACON® • 23
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
4.2.2
Monitoring values 2
V1.2.1 CosPhiiActual ID 1717
The calculated Cos Phi.
V1.2.2 Unit Temperature °C ID 1109
The heatsink temperature of the drive.
V1.2.3 Reactive Current Reference % ID1389
The final reactive current reference.
V1.2.4 Active Current % ID 1125
The active current in % of System Rated Current. A negative value means that the current is flowing to AC side from DC side.
24 • VACON® arfiff08 power generation
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
V1.2.5 Inverter statusword 1 ID 1819
Diagnostic statusword 1.
Bit
Name
Value = 0
Value = 1
Description
0
Main Switch Open Fault
No Fault
Fault
See Fault list 64
1
Main Switch Open Warning
No Alarm
Alarm
See Fault list 64
2
AC Voltage Max Fault
No Fault
Fault
See Fault list 72
3
AC Voltage Min Fault
No Fault
Fault
See Fault list 73
4
AC Freg Max Fault
No Fault
Fault
See Fault list 74
5
AC Freg Min Fault
No Fault
Fault
See Fault list 75
6
DC Ground Warning
No Alarm
Alarm
See Fault list 76
7
DC Ground Fault
No Fault
Fault
See Fault list 77
8
Surge Alarm
No Alarm
Alarm
See Fault list 83
9
FB Heardbeat timeout
No Fault
Fault
See Fault list 85
10
Input Switch Alarm
No Alarm
Alarm
See Fault list 86
11
Emergency Switch
No Fault
Fault
See Fault list 87
12
UnBalance
No Alarm
Alarm
See Fault list 18
13
Thermistor Fault
No Fault
Fault
See Fault list 29
14
Safe Disable
No Fault
Fault
See Fault list 30
15
Reserved
No Fault
Fault
V1.2.6 Inverter statusword 2 ID 1820
Diagnostic statusword 2.
Bit
Name
Value = 0
Value = 1
Description
0
Overvoltage
No Fault
Fault
See Fault list 2
1
Earth Fault
No Fault
Fault
See Fault list 3
2
Inverter Fault
No Fault
Fault
See Fault list 4
3
Charge Switch Fault
No Fault
Fault
See Fault list 5
4
Saturation
No Fault
Fault
See Fault list 7
5
Unknown Fault
No Fault
Fault
See Fault list 8
6
Undervoltage
No Fault
Fault
See Fault list 9
7
Input Phase Fault
No Fault
Fault
See Fault list 10
8
Input Phase Warning
No Alarm
Alarm
See Fault list 10
9
Supply Phase Loss
No Fault
Fault
See Fault list 11
10
Supply Phase Warning
No Alarm
Alarm
See Fault list 11
11
Over Temperature
No Fault
Fault
See Fault list 14
12
Over Temperature Warning
No Alarm
Alarm
See Fault list 14
13
Undertemp
No Fault
Fault
See Fault list 13
14
Temperature Power limit warning
No Alarm
Alarm
See Fault list 97
15
OverCurrent
No Fault
Fault
See Fault list 1
arfiff08 power generation VACON® • 25
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
V1.2.7 Inverter statusword 3 ID 1821
Diagnostic statusword 3.
V1.2.8 Inverter statusword 4 ID 1822
Diagnostic statusword 4.
Bit
Name
Value = 0
Value = 1
Description
0
Processor Watchdog
No Fault
Fault
See Fault list 25
1
Reserved
2 IGBT HW Temp
No Fault
Fault
See Fault list 31
3
Cooling Fan
No Fault
Fault
See Fault list 32
4
Application Fault
No Fault
Fault
See Fault list 35
5
Control Unit Fault
No Fault
Fault
See Fault list 36
6
Device Changed
No Fault
Fault
See Fault list 37
7
Device Added
No Fault
Fault
See Fault list 38
8
Device Moved
No Fault
Fault
See Fault list 39
9
Device Unknown
No Fault
Fault
See Fault list 40
10
Device Changed
No Fault
Fault
See Fault list 44
11
Device Added
No Fault
Fault
See Fault list 45
12
EEprom Checksum fault
No Fault
Fault
See Fault list 22
13
Counter Fault
No Fault
Fault
See Fault list 24
14
Reserved
No Fault
Fault 15
Reserved
No Fault
Fault
Bit
Name
Value = 0
Value = 1
Description
0
IGBT Temperature
No Fault
Fault
See Fault list 41
1
EEPROM Fault
No Fault
Fault
See Fault list 48
2
Zero Divice Fault
No Fault
Fault
See Fault list 49
3
External Fault Active
No Fault
Fault
See Fault list 51
4
External Warning Active
No Alarm
Alarm
See Fault list 51
5
Reserved
6 Fieldbus Communication
No Fault
Fault
See Fault list 53
7
Slot Communication
No Fault
Fault
See Fault list 54
8
System bus Master Heartbeat Trip active
No Fault
Fault
See Fault list 59
9
System bus Communication Fault Trip Active
No Fault
Fault
See Fault list 55
10
LCL OverTemp Fault Active
No Fault
Fault
See Fault list 70
11
LCL OverTemp Warning Active
No Alarm
Alarm
See Fault list 70
12
User Temp Alarm
No Alarm
Alarm
Fault code 99
13
Analog Signal Too Low Fault active
No Fault
Fault
Fault code 50
14
Analog Signal Too Low Warning active
No Alarm
Alarm
Fault code 50
15
Reserved
26 • VACON® arfiff08 power generation
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
V1.2.9 EEPROM Saving Status ID 1106
Status of the nonvolatile memory (EEPROM) storing activated by the application 0 = IDLE 1 = ACTIVE 2 = RESOURCE ERROR 3 = WRITE ERROR 4 = NOT FOUND 5 = NOT SUPPORTED (e.g. NXP2)
V1.2.10 Status Word ID 43
Application Status Word combines different drive statuses to one data word.
Application Status Word ID43
FALSE
TRUE
b0
b1
Not in Ready state
Ready
b2
Not Running
Running
b3
No Fault
Fault
b4
b5
b6
Run Disabled
Run Enable
b7
No Warning
Warning
b8 Charging Switch closed (internal)
b9 MCB Control (DO Final)
b10 MCB Feedback
b11 DO Charging Active
b12
No Run Request
Run Request
b13
b14 PV Field OK
b15
V2.1.2.11 Used DC start level ID 1965
Monitoring Value for the currently used DC Start Level value.
V2.1.2.12 Mindex ID 1874
This value can be used to recognize low Dc-Link voltage when operating in island mode. If the value is above 90%, the drive is in limits to make correct voltage to the AC side.
V2.1.2.13 Calibrated DC Voltage ID 1839
Calibrated DC Voltage is used in the parallel drives
arfiff08 power generation VACON® • 27
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
4.2.3
Fieldbus monitoring values
V1.3.1 FB Control Word ID 1478
Control Word received from the Fieldbus Master.
FB Control Word
Signal
Comment
b0
Start
0 = Stop Command 1 = Start Command
b1
b2
Reset
0>1 Reset fault.
b3
b4
b5
b6
b7
b8
Master
Master command
b9
b10
b11
b12
b13
ReactCurrOr
CosPhiiRefSel
0 = Reactive Current Control 1 = CosPhii Control
b14
FB Force start
0 = Normal Start 1 = Force Start regardless of DC voltage level
b15
28 • VACON® arfiff08 power generation
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
V1.3.2 FB Status Word ID 1479
Status Word sent to the upper system/PLC via Fieldbus.
FB Status Word
Signal
Comment
b0
StartCriterions
FullFilled
Not only if Inverter control is ready, but if all b1
Inverter Activated
When active, the inverter can be in either in Standby or Inverter Running mode.
b2
b3
Fault
b4
Warning
b5
Inverter Activated Standby
b6
b7
Main contactor close
command
b8
Master
Master command
b9
Pulse 1s
Heartbeat bit. The inverter toggles this bit on and off. 1s on, 1s off.
b10
ChargeSwState
0 = Open 1 = Closed
b11
b12
b13
b14
b15
V1.3.3 FB GenPowerLim ID 1481
Power limit sent by the fieldbus.
V1.3.4 FB Q/PF Ref ID 1480
Reactive Current or Power Factor Reference received from Fieldbus. Control Word states which reverence is used.
V1.3.5 Day From PLC ID 1719
Day index sent from the PLC.
arfiff08 power generation VACON® • 29
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
4.2.4
I/O monitoring values
V1.4.1 DIN1, DIN2, DIN3 ID 15 V1.4.2 DIN4, DIN5, DIN6 ID 16
DIN1/DIN2/DIN3 status
DIN4/DIN5/DIN6 status
b0
DIN3
DIN6
b1
DIN2
DIN5
b2
DIN1
DIN4
V1.4.3 DIN Status 1 ID 56 V1.4.4 DIN Status 2 ID 57
DIN StatusWord 1
DIN StatusWord 2
b0
DIN: A.1
DIN: C.5
b1
DIN: A.2
DIN: C.6
b2
DIN: A.3
DIN: D.1
b3
DIN: A.4
DIN: D.2
b4
DIN: A.5
DIN: D.3
b5
DIN: A.6
DIN: D.4
b6
DIN: B.1
DIN: D.5
b7
DIN: B.2
DIN: D.6
b8
DIN: B.3
DIN: E.1
b9
DIN: B.4
DIN: E.2
b10
DIN: B.5
DIN: E.3
b11
DIN: B.6
DIN: E.4
b12
DIN: C.1
DIN: E.5
b13
DIN: C.2
DIN: E.6
b14
DIN: C.3
b15
DIN: C.4
V1.4.5 Analogue Input 1 % ID 13 V1.4.6 Analogue Input 2 % ID 14
V1.4.7 Custom AnOut 1 % ID 1240
Customized analogue output
30 • VACON® arfiff08 power generation
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
4.2.5
MPPT
V1.5.1 MPP Reference ID 1816
The DC reference of the MPP tracker.
V1.5.2 Actual Step Size ID 1815
This value shows the actual momentary step size of the MPP tracker.
V1.5.3 Actual Step Ratio ID 1825
This value shows the actual step ratio. Power change divided by actual step size. The value is used for evaluating the size of the next step.
V1.5.4 MPPT State ID 1817
State of the MPP tracker. For debugging purposes only.
P1.5.5 Power Window On
When the MPP tracker takes a step in any direction, the power change has to be bigger than the Power Window for making a decision if the Power has increased or decreased. Otherwise it will take another step in the same direction until the limit is exceeded.
V1.5.6 Simulated Optimal DC point ID 1724
Estimated optimal DC Point is the DC Reference point which giving the best simulated power.
Picture xx. Optimal DC point.
Loading...
+ 114 hidden pages