8 Monitoring data ..................................... 46
10
19
Software ID: smf089xx
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Page 2
11
1
11
GeneralGeneral
General
GeneralGeneral
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose II application is an extender
version of the normal Multipurpose application.
It has parameters for torque control and,
furthermore, for Fieldbus communication.
Following fieldbuses are supported: Interbus,
Modbus, Profibus, LonWorks, CAN-bus
(SDS, DeviceNet).
2 Control I/O2 Control I/O
2 Control I/O
2 Control I/O2 Control I/O
VV
aconacon
V
acon
VV
aconacon
Frequency reference, analogue and digital
outputs have extra alternatives in their control
parameters. Source of free analogue input can
now be selected from the I/O Expander. These
inputs have also parameters for signal area
etc. programming.
Reference
potentiometer
READY
RUN
220
VAC
FAULT
TerminalSignalDescription
1+10V
2Uin+Analogue input,Frequency reference
3GNDI/O groundGround for reference and controls
4Iin+Analogue input,Default setting: not used
-current (programmable)range 0—20 mA
5I
in
6+24VControl voltage outputVoltage for switches, etc. max. 0.1 A
7GNDI/O groundGround for reference and controls
8DIA1 Start forwardContact closed = start forward
9DIA2Start reverseContact closed = start reverse
10DIA3Fault resetContact open = no action
11CMACommon for DIA1—DIA3 Connect to GND or + 24V
12+24VControl voltage outputVoltage for switches, (same as #6)
13GNDI/O groundGround for reference and controls
14DIB4Jogging speed selectContact open = no action
15DIB5External faultContact open = no fault
16DIB6Accel./deceler. time select Contact open = par. 1.3, 1.4 in use
17CMBCommon for DIB4—DIB6 Connect to GND or + 24V
18I
application)
1 = Basic Application
2 = Standard Application
3 = Local/Remote Control
Application
4 = Multi-step Speed Application
5 = PI-control Application
6 = Multi-purpose Control
Application
7 = Pump and Fan Control
Application
0 = Loading ready / Select loading
1 = Load default setting
2 = Read up parameters to user's
set
3 = Load down user's set
parameters
4 = Read parameters up to the
panel (possible only with graphical
panel)
5 = Load down parameters from
panel (possible only with graphical
panel)
0 = English
0.3Language selection0-210
1 = Germany
2 = Finnish
Table 4-1 Parameter group 0.
0.10.1
0.1
0.10.1
Application selectionApplication selection
Application selection
Application selectionApplication selection
With this parameter the active application can be selected. If the device has been
ordered from the factory equipped with Multipurpose II application this has been loaded
to the unit as application 0. The application has also been set active at the factory.
However, check that the value of the parameter 0.1 is zero when you want to use
Multipurpose II.
If the application should be loaded to the device later it has to be set active always after
loading by setting the value of parameter 0.1 to zero.
0.20.2
0.2
0.20.2
Parameter loadingParameter loading
Parameter loading
Parameter loadingParameter loading
See User's Manual chapter 11.
0.30.3
0.3
0.30.3
LanguageLanguage
Language
LanguageLanguage
With this parameter, the language of the graphical panel can be selected.
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
VV
aconacon
V
acon Page 5
VV
aconacon
55
Basic Parameters, Group 1Basic Parameters, Group 1
5
Basic Parameters, Group 1
55
Basic Parameters, Group 1Basic Parameters, Group 1
5.15.1
Parameter tableParameter table
5.1
Parameter table
5.15.1
Parameter tableParameter table
Multi-purpose Control Application IIMulti-purpose Control Application II
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Page 6
5.2 Description of Group 1 parameters 5.2 Description of Group 1 parameters
5.2 Description of Group 1 parameters
5.2 Description of Group 1 parameters 5.2 Description of Group 1 parameters
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
VV
aconacon
V
acon
VV
aconacon
1. 1, 1. 21. 1, 1. 2
1. 1, 1. 2
1. 1, 1. 21. 1, 1. 2
1. 3, 1. 41. 3, 1. 4
1. 3, 1. 4
1. 3, 1. 41. 3, 1. 4
1. 51. 5
1. 5
1. 51. 5
Minimum / maximum frequencyMinimum / maximum frequency
Minimum / maximum frequency
Minimum / maximum frequencyMinimum / maximum frequency
Defines frequency limits of the frequency converter.
The default maximum value for parameters 1
..
. 1 and 1
..
120 Hz when the device is stopped (RUN indicator not lit) parameters 1
..
. 2 is 120 Hz. By setting 1
..
..
. 1 and 1
..
. .
. 2 =
. .
..
. 2
..
are changed to 500 Hz. At the same time the panel reference resolution is changed
from 0.01 Hz to 0.1 Hz.
Changing the max. value from 500 Hz to 120 Hz is done by setting the parameter
..
1
. 2 = 119 Hz when the device is stopped.
..
Acceleration time 1, deceleration time 1:Acceleration time 1, deceleration time 1:
Acceleration time 1, deceleration time 1:
Acceleration time 1, deceleration time 1:Acceleration time 1, deceleration time 1:
These limits correspond to the time required for the output frequency to
accelerate from the set minimum frequency (par. 1
frequency (par. 1
Reference selectionReference selection
Reference selection
Reference selectionReference selection
00
0Analogue voltage reference from terminals 2—3, e.g. a potentiometer
00
11
1Analogue current reference trom terminals 4—5, e.g. a transducer.
11
22
2Reference is formed by adding the values of the analogue inputs
22
33
3Reference is formed by subtracting the voltage input (U
33
. .
. 2).
. .
..
. 1) to the set maximum
..
) value
in
from the current input (Iin) value.
44
4Reference is formed by subtracting the current input (Iin ) value from the
44
voltage input (Uin) value.
55
5Reference is the formed by multiplying the values of the analogue inputs
55
66
6Joystick control from the voltage input (Uin).
66
Signal range
0—10 V0 V5 V+10 V
CustomPar. 2.7 x 10 V
-10 V—+ 10 V-10 V0 V+10 V
WW
arning!arning!
W
arning!Use only -10V—+10 V signal range. If a custom or 0—10 V signal
WW
arning!arning!
Max reverse
speed
Direction change
In the middle of
custom range
Max forward
speed
Par. 2.8 x 10 V
range is used, the drive starts to run at the max. reverse speed if the
!
77
7Joystick control from the current input (I
77
Signal rangeMax reverseDirection changeMax forward
WW
arning!arning!
W
arning!Use only 4—20 mA signal range. If custom or 0—20 mA signal range
WW
arning!arning!
reference signal is lost.
).
in
speedspeed
0—20 mA0 mA10 mA20 mA
CustomPar. 2
4—20 mA4 mA12 mA20 mA
..
. 13 x 20 mA In the middle ofPar. 2
..
custom range
..
. 14 x 20 mA
..
is used, the drive runs at max. reverse speed if the control signal is lost.
!
Set the reference fault (par. 7
is used, then the drive will stop to the reference fault if the reference
. .
. 2) active when the 4—20 mA range
. .
signal is lost.
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
VV
aconacon
V
acon Page 7
VV
aconacon
Note!Note!
Note! When joystick control is used, the direction control is generated from joystick
Note!Note!
Multi-purpose Control Application IIMulti-purpose Control Application II
reference signal. See figure 5.4-1.
Analogue input scaling, parameters 2
..
. 16—2
..
. .
. 19 are not used when joystick
. .
control is used.
Fout
Fmax
(par 1.2)
Fmin.
-10V
If minimum frequency (par 1
hysteresis is ± 2% at reversing point.there is no hysteresis at reversing point.
(par 1.1)
Fmin.
(par 1.1)
hystereesi +/-2% (+/-0,2 V)
Fmax
(par 1.2)
..
. 1) >0,If minimum frequency (par 1
..
Uin
+10V
-10V
Fmax
(par 1.2)
Fout
Fmax
(par 1.2)
+10V
..
. 1) = 0,
..
Uin
Uin
Fig. 5-1 Joystick control Uin signal -10 V—+10 V.
88
8Reference value is changed with digital input signals DIB5 and DIB6.
88
- switch in DIB5 closed = frequency reference increases
- switch in DIB6 closed = frequency reference decreases
Speed of reference change can be set with the parameter 2
99
9Same as setting 8 but the reference value is set to the minimum frequency
99
(par. 1
1010
10Same as setting 8 but the reference is stored to the memory over mains break.
1010
When the value of the parameter 1
parameters 2
11
11
1
1The minor of signals Uin and Iin is the frequency reference
11
11
1212
12The greater of signals Uin and Iin is the frequency reference
1212
1313
13Panel reference r1 is the frequency reference
1313
1414
14Maximum reference selection (recommended only at torque control)
1414
1515
15Uin/Iin digital selection (see par. 2.3)
1515
..
. 1) each time the frequency converter is stopped.
..
..
. 5 is set to 8, 9 or 10, the values of the
..
..
. 4 and 2
..
. .
. 5 are automatically set to 11.
. .
..
. 20.
..
1. 61. 6
1. 6
1. 61. 6
Jogging speed referenceJogging speed reference
Jogging speed reference
Jogging speed referenceJogging speed reference
Parameter value defines the jogging speed selected with the digital input
1. 71. 7
1. 7
1. 71. 7
Current limitCurrent limit
Current limit
Current limitCurrent limit
This parameter determines the maximum motor current from the freqeuency
converter. To avoid motor overload, set this parameter according to the rated current
of the motor.
1. 81. 8
1. 8
1. 81. 8
U/f ratio selectionU/f ratio selection
U/f ratio selection
U/f ratio selectionU/f ratio selection
Linear:The voltage of the motor changes linearly with the frequency in the
00
0constant flux area from 0 Hz to the field weakening point (par. 6
00
where the nominal voltage is also supplied to the motor. See figure
5-2. Linear U/f ratio should be used in constant torque applications.
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
..
. 3)
..
Page 8
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
This default setting should be used if there is no special needThis default setting should be used if there is no special need
This default setting should be used if there is no special need
This default setting should be used if there is no special needThis default setting should be used if there is no special need
for another setting.for another setting.
for another setting.
for another setting.for another setting.
VV
aconacon
V
acon
VV
aconacon
Squared:The voltage of the motor changes following a squared curve form
11
1with the frequency in the area from 0 Hz to the field weakening
11
point (par. 6
..
. 3) where the nominal voltage is also supplied to
..
the motor. See figure 5-2.
The motor runs undermagnetised below the field weakening point
and produces less torque and electromechanical noise. Squared
U/f ratio can be used in applications where torque demand of
the load is proportional to the square of the speed, e.g. in centrifugal
fans and pumps.
U[V]
Un
(Par 6. 4)
Default: Nominal
voltage of the motor
Linear
Field weakening
point
Squared
Default: Nominal
frequency of the
motor
(Par. 6. 3)
f[Hz]
UD012K07
Figure 5-2 Linear and squared U/f curves.
Programm. The U/f curve can be programmed with three different points.
U/f curveThe parameters for programming are explained in chapter 5.2.
22
2Programmable U/f curve can be used if the other settings do not
22
satisfy the needs of the application. See figure 5-3.
U[V]
Un
Par 6. 4
Par. 6. 6
(Def. 10%)
Par. 6. 7
(Def. 1.3%)
Default: Nominal
voltage of the motor
Par. 6. 5
(Def. 5 Hz)
Field weakening
point
Default: Nominal
frequency of the
motor
Par. 6. 3
f[Hz]
UD012K08
Figure 5-3 Programmable U/f curve.
1.9 U/f optimisation1.9 U/f optimisation
1.9 U/f optimisation
1.9 U/f optimisation1.9 U/f optimisation
AutomaticThe voltage to the motor changes automatically which makes the
torquemotor produce sufficient torque to start and run at low frequencies. The
boostvoltage increase depends on the motor type and power.
Automatic torque boost can be used in applications where starting
torque due to starting friction is high, e.g. in conveyors.
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
VV
aconacon
V
acon Page 9
VV
aconacon
Multi-purpose Control Application IIMulti-purpose Control Application II
NOTE!In high torque - low speed applications - it is likely the motor will
overheat.
!
If the motor has to run a prolonged time under these
conditions,
special attention must be paid to cooling the motor. Use external
cooling for the motor if the temperature tends to rise too high.
1. 101. 10
1. 10
1. 101. 10
1. 11. 1
1. 1
1. 11. 1
1. 121. 12
1. 12
1. 121. 12
1. 131. 13
1. 13
1. 131. 13
1. 141. 14
1. 14
1. 141. 14
1. 151. 15
1. 15
1. 151. 15
Nominal voltage of the motorNominal voltage of the motor
Nominal voltage of the motor
Nominal voltage of the motorNominal voltage of the motor
Find this value Unon the rating plate of the motor.
This parameter sets the voltage at the field weakening point, parameter 6
100% x U
11
1
11
Nominal frequency of the motorNominal frequency of the motor
Nominal frequency of the motor
Nominal frequency of the motorNominal frequency of the motor
Find this value fn on the rating plate of the motor.
This parameter sets the field weakening point, parameter 6. 3, to the same value.
Nominal speed of the motorNominal speed of the motor
Nominal speed of the motor
Nominal speed of the motorNominal speed of the motor
Find this value nn on the rating plate of the motor.
Nominal current of the motorNominal current of the motor
Nominal current of the motor
Nominal current of the motorNominal current of the motor
Find this value In on the rating plate of the motor.
Supply voltageSupply voltage
Supply voltage
Supply voltageSupply voltage
Set parameter value according to the nominal voltage of the supply.
Values are predefined for CX/CXL2, CX/CXL/CXS4, CX/CXL/CXS5 and CX6
ranges, see table 5-1.
Parameter concealParameter conceal
Parameter conceal
Parameter concealParameter conceal
Defines which parameter groups are available for editing:
0 = all parameter groups are visible
1 = only group 1 is visible
nmotor
.
. .
. 4, to
. .
1. 161. 16
1. 16
1. 161. 16
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Parameter value lockParameter value lock
Parameter value lock
Parameter value lockParameter value lock
Defines access to the changes of the parameter values:
0 = parameter value changes enabled
1 = parameter value changes disabled
Service:+358-40-8371 150E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Page 10
66
Special Parameters, Groups 2—10Special Parameters, Groups 2—10
6
Special Parameters, Groups 2—10
66
Special Parameters, Groups 2—10Special Parameters, Groups 2—10
6.16.1
Parameter tablesParameter tables
6.1
Parameter tables
6.16.1
Parameter tablesParameter tables
Group 2, Input signal parametersGroup 2, Input signal parameters
Group 2, Input signal parameters
Group 2, Input signal parametersGroup 2, Input signal parameters
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
= Parameter value can be changed only when the frequency converter is stopped.
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
1 = Voltage input
2 = Current input
3 = AIN1 I/O-expand
4 = AIN2 I/O-expand
5 = FB signal
VV
aconacon
V
acon
VV
aconacon
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
VV
aconacon
V
acon Page 13
VV
aconacon
Group 3, Output and supervision parametersGroup 3, Output and supervision parameters
Group 3, Output and supervision parameters
Group 3, Output and supervision parametersGroup 3, Output and supervision parameters
CodeParameterRangeStepDefaultC
Multi-purpose Control Application IIMulti-purpose Control Application II
DescriptionPage
u
s
t
o
m
Analogue output func-
3.1
tion
0—1411
0 = Not used
1 = O/P frequency
2 = Motor speed
3 = O/P current
4 = Motor torque
5 = Motor power
6 = Motor voltage
7 = DC-link volt.
8 = Input signal U
9 = Input signal I
10 = Refer. freq.
Scale 100%
(0—f
(0—max. speed
(0—2.0 x I
(0—2 x T
(0—2 x P
(0—100% x U
(0—1000 V)
in
in
max
)
)
nCX
)
nCX
)
nCX
nM
11 = Refer. torque
nMOT
nMOT
)
)
)
Analogue output filter
3.2
time
Analogue output inver-
3.3
sion
Analogue output mini-
3.4
mum
12 = Motor±torque
13 = Motor±power
14 = O/P freq.
(-2--+2xT
(-2--+2xT
(f
min—fmax
0.01—10 s0.011.0026
0—110
0—110
0 = Not inverted
1 = Inverted
0 = 0 mA
1 = 4 mA
3.5Analogue output scale10—1000%1%100%26
0 = Not used
1 = Ready
2 = Run
3 = Fault
4 = Fault inverted
5 = Vacon overheat warning
6 = External fault or warning
7 = Reference fault or warning
8 = Warning
9 = Reversed
10 = Jogging speed selected
3.6Digital output function0—2211
STOP
STOP
STOPSTO P
11 = At speed
12 = Motor regulator activated
13 = Output frequency limit superv. 1
14 = Output frequency limit superv. 2
15 = Torque limit supervision
16 = Reference limit supervision
17 = External brake control
18 = Control from I/O terminals
19 = Frequency converter temperature
limit supervision
20 = Unrequested rotation direction
21 = External brake control inverted
22 = Termistor fault or warning
3.7Relay output 1 function0—2212As parameter 3.6
STOP
STOP
STOPSTO P
3.8Relay output 2 function0—2213As parameter 3.6
STOP
STOP
STOPSTO P
3.9
3.10
3.11
3.12
Output frequency limit 1
supervision function
Output frequency limit 1
supervision value
Output frequency limit 2
supervision function
Output frequency limit 2
supervision value
0—210
0—f
max
(par. 1.2)0.1 Hz0 Hz27
0—210
0—f
max
(par. 1.2)
0.1 Hz0 Hz27
0 = No
1 = Low limit
2 = High limit
0 = No
1 = Low limit
2 = High limit
)
26
26
26
27
27
27
27
27
STOP
STOP
Note!Note!
Note!
Note!Note!
STOPSTOP
= Parameter value can be changed only when the frequency converter is stopped. (Continues)
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
DIA2: closed contact = start reverse,
See figure 6-1.
Output
FWD
frequency
REV
DIA1
DIA2
Figure 6-1 Start forward/Start reverse.
Stop function
(par 4. 7)
= coasting
123
UD009K09
t
1The first selected direction has the highest priority
2When DIA1 contact opens, the direction of rotation starts to change
3If Start forward (DIA1) and Start reverse (DIA2) signals are active
simultaneously, the Start forward signal (DIA1) has priority.
With these parameters, Uin can be set for any input signal span within 0—10 V.
Minimum setting: Set the Uin signal to its minimum level, select parameter 2
press the Enter button
Maximum setting: Set the Uin signal to its maximun level, select parameter 2
press the Enter button
Note!Note!
Note!These parameters can only be set with this procedure (not with the Browser
Note!Note!
buttons)
2. 92. 9
2. 9
2. 92. 9
UU
signal inversionsignal inversion
U
signal inversion
UU
signal inversionsignal inversion
inin
in
inin
Parameter 2. 9 = 0, no inversion
of analogue U
signal.
in
%
Unfiltered signal
100%
Parameter 2. 9 = 1, inversion
2. 102. 10
2. 10
2. 102. 10
of analogue U
signal filter timesignal filter time
UU
signal filter time
U
signal filter timesignal filter time
UU
inin
in
inin
signal.
in
63%
Filtered signal
Filters out disturbances from the
incoming analogue U
Long filtering time makes regulation response slower.
signal.
in
Par. 2. 10
t [s]
UD009K37
See figure 6-6.
Figure 6-6 U
signal filtering.
in
..
. 4,
..
..
. 5,
..
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
VV
aconacon
V
acon Page 25
VV
aconacon
2. 12. 1
2. 1
2. 12. 1
11
1
11
Analogue inputAnalogue input
Analogue input
Analogue inputAnalogue input
Multi-purpose Control Application IIMulti-purpose Control Application II
With these parameters, the
scaling of the input current
signal (Iin) range can be set
between 0—20 mA.
Minimum setting:
Set the Iin signal to its minimum
level, select parameter 2
..
. 12,
..
press the Enter button.
Maximum setting:
Set the Iin signal to its maximun
level, select parameter 2
..
. 13,
..
press the Enter button.
Note!Note!
Note! These parameters can only
Note!Note!
be set by this procedure (not with
the browser buttons)
%
Unfiltered signal
100%
Filtered signal
63%
Par. 2. 15
Figure 6-7 Analogue input Iin filter time
t [s]
UD012K40
2. 142. 14
2. 14
2. 142. 14
2. 152. 15
2. 15
2. 152. 15
2. 162. 16
2. 16
2. 162. 16
2. 172. 17
2. 17
2. 172. 17
2. 182. 18
2. 18
2. 182. 18
2. 192. 19
2. 19
2. 192. 19
Analogue input IAnalogue input I
Analogue input I
Analogue input IAnalogue input I
Parameter 2. 14 = 0, no inversion of I
Parameter 2. 14 = 1, inversion of I
Analogue input IAnalogue input I
Analogue input I
Analogue input IAnalogue input I
Filters out disturbances from the incoming analog I
inversion inversion
inversion
inversion inversion
inin
in
inin
filter time filter time
filter time
filter time filter time
inin
in
inin
input.
in
input
in
in
Long filtering time makes regulation response slower.
See figure 6-7.
UU
signal minimum scalingsignal minimum scaling
U
signal minimum scaling
UU
signal minimum scalingsignal minimum scaling
in in
in
in in
Sets the minimum scaling point for U
UU
signal maximum scalingsignal maximum scaling
U
signal maximum scaling
UU
signal maximum scalingsignal maximum scaling
in in
in
in in
Sets the maximum scaling point for U
I I
signal minimum scalingsignal minimum scaling
I
signal minimum scaling
I I
signal minimum scalingsignal minimum scaling
in in
in
in in
Sets the minimum scaling point for I
I I
signal maximum scalingsignal maximum scaling
I
signal maximum scaling
I I
signal maximum scalingsignal maximum scaling
in in
in
in in
Sets the maximum scaling point for I
signal. See figure 6-8.
in
signal. See figure 6-8.
in
signal. See figure 6-8.
in
signal. See figure 6-8.
in
signal.
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
Page 26
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
VV
aconacon
V
acon
VV
aconacon
2. 202. 20
2. 20
2. 202. 20
2. 212. 21
2. 21
2. 212. 21
functionfunction
function
functionfunction
100
0
0
0
4
Scaled
input signal [%]
Par. 2. 19 = 30%
Par. 2. 20 = 80%
Analogue
1008030
input [%]
10.0 V
8.03.0
20.0 mA
16.06.0
16.88.820.0 mA
(15.3 mA)
-30
100
76.5
17.7
(3.5 mA)
Scaled
input signal [%]
Par. 2. 19 = -30%
Par. 2. 20 = 140%
0
0
0
4
100140
10.0 V
20.0 mA
20.0 mA
Analogue
input [%]
UD012K34
Figure 6-8 Examples of the scaling of Uin and Iin inputs .
Free analogue input signalFree analogue input signal
Free analogue input signal
Free analogue input signalFree analogue input signal
Selection of input signal of free analogue input (an input not used for reference
signal):
0 = Not in use
1 = Voltage signal U
2 = Current signal I
in
in
3 = Voltage signal Ain1 from terminals 202-203 of I/O Expander
4 = Analogue signal Ain2 from terminal 204-205 of I/O Expander
- current signal Vacon CX 100 Opt
- voltage signal Vacon CX 102 Opt
5 = Fieldbus signal
- the signal comes through the fieldbus and depends on the option
board used
100%
Par. 1. 7
Torque limit
Free analogue input signalFree analogue input signal
Free analogue input signal
Free analogue input signalFree analogue input signal
This parameter sets the function
of the free analogue input:
00
0 = Function is not used
00
11
1 = Reducing motor current limit
11
(par. 1
..
. 7)
..
This signal will adjust the
10 V
20 mA
20 mA
Custom
Analogue
input
UD012K61
maximum motor current
between 0 and parameter
max. limit set with parameter
0 V
0 mA
4 mA
Custom
Signal range
1.7. See figure 6-9.
Figure 6-9 Reducing of max. motor current.
DC-braking
100%
Par. 4. 8
current
2 2
2 = Reducing DC brake current.
2 2
The DC braking current can
be reduced with the free
analogue input signal,
between 0.15xI
nCX
and
current set with parameter
..
4
. 8.
..
0,15 x I
See figure 6-10.
Figure 6-10 Reducing DC brake current.
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
nFU
0
Signal range
Free analogue
input
UD012K58
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
VV
aconacon
V
acon Page 27
VV
aconacon
33
3Reducing acceleration and
33
deceleration times.
The acceleration and
deceleration times can be
Multi-purpose Control Application IIMulti-purpose Control Application II
Factor R
10
reduced with the free analog
input signal, according to the
following formula:
Reduced time =set acc./eceler.
..
..
..
time (par. 1
divided by the factor R from
figure 6-11.
. 3, 1
..
. 4; 4
..
Figure 6-11 Reducing acceleration
and deceleration times.
44
4Reducing torque supervision
44
. 3, 4
..
..
. 4)
..
2
1
Signal range
limit.
The set torque supervision
100%
Par. 3. 14
Torque limit
limit can be reduced with the
free analogue input signal
between 0 and set
supervision limit (par. 3
..
. 14),
..
see figure 6-12.
Free analogue
input
UD012K59
2. 222. 22
2. 22
2. 222. 22
2.232.23
2.23
2.232.23
2.242.24
2.24
2.242.24
2.252.25
2.25
2.252.25
2.262.26
2.26
2.262.26
Figure 6-12 Reducing torque
supervision limit.
Free analogue
input
UD012K60
Motor potentiometer ramp timeMotor potentiometer ramp time
Motor potentiometer ramp time
Motor potentiometer ramp timeMotor potentiometer ramp time
0
Signal range
Defines how fast the electronic motor potentiometer value changes.
Ain1 signal inversion (I/O-Expander)Ain1 signal inversion (I/O-Expander)
Ain1 signal inversion (I/O-Expander)
Ain1 signal inversion (I/O-Expander)Ain1 signal inversion (I/O-Expander)
Parameter 2.23 = 0, no inversion
Ain1 signal filter timeAin1 signal filter time
Ain1 signal filter time
Ain1 signal filter timeAin1 signal filter time
Filters out disturbances from the incoming analogue Ain1 signal. Long filtering
time makes regulation response slower.
Ain2 input (I/O-Expander) signal rangeAin2 input (I/O-Expander) signal range
Ain2 input (I/O-Expander) signal range
Ain2 input (I/O-Expander) signal rangeAin2 input (I/O-Expander) signal range
0 = 0—20 mA
1 = 4—20 mA
2 = 0—10 V (must be used with 102 OPT)
Ain2 signal inversion (I/O-Expander)Ain2 signal inversion (I/O-Expander)
Ain2 signal inversion (I/O-Expander)
Ain2 signal inversion (I/O-Expander)Ain2 signal inversion (I/O-Expander)
Parameter 2.26 = 0, no inversion
2.272.27
2.27
2.272.27
Ain2 signal filter time (I/O-Expander)Ain2 signal filter time (I/O-Expander)
Ain2 signal filter time (I/O-Expander)
Ain2 signal filter time (I/O-Expander)Ain2 signal filter time (I/O-Expander)
Filters out disturbances from the incoming analogue Ain2 signal. Long filtering
time makes regulation response slower.
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
Page 28
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
VV
aconacon
V
acon
VV
aconacon
2.282.28
2.28
2.282.28
Range: 0 - 5
Step: 1
Default: 0
Description:
0 = Not Used
1 = Voltage Input
2 = Current Input
3 = AIN1 I/O-expand
4 = AIN2 I/O-expand
5 = FB signal
2.292.29
2.29
2.292.29
Range: 0.0% - 200.0%
Step: 0.1%
Default: 0.0%
2.302.30
2.30
2.302.30
Range: 0.0% - 100.0%
Step: 0.1%
Default: 0.0%
Adjust InputAdjust Input
Adjust Input
Adjust InputAdjust Input
Adjust PrecentageAdjust Precentage
Adjust Precentage
Adjust PrecentageAdjust Precentage
Adjust OffsetAdjust Offset
Adjust Offset
Adjust OffsetAdjust Offset
f / Hz
(0%)
Parameter 2.30
OFFSET
0%
Frequency
reference
(Par. 1.5)
Parameter 2.29
Figure 6-13. parameter 2.29 and 2.30 settings.
50%
OO
100%
O
100%200%
(25%)
(50%)
Adjust
%
Percentage
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
VV
aconacon
V
acon Page 29
VV
aconacon
Multi-purpose Control Application IIMulti-purpose Control Application II
3. 13. 1
3. 1
3. 13. 1
3. 23. 2
3. 2
3. 23. 2
3.33.3
3.3
3.33.3
Analogue output functionAnalogue output function
Analogue output function
Analogue output functionAnalogue output function
See table on page 12.
Analogue output filter timeAnalogue output filter time
Analogue output filter time
Analogue output filter timeAnalogue output filter time
Filters the analogue output signal.
See figure 6-13.
Figure 6-13 Analogue output
filtering.
Analogue output invertAnalogue output invert
Analogue output invert
Analogue output invertAnalogue output invert
Inverts analogue output
max. output
value
min. output signal = maximum set
value
signal = minimum set
signal:
%
100%
63%
Analogue
output
current
20 mA
12 mA
10 mA
Unfiltered signal
Par. 3. 2
Filtered signal
t [s]
UD009K16
Param. 3. 5
= 50%
3. 43. 4
3. 4
3. 43. 4
3. 53. 5
3. 5
3. 53. 5
Figure 6-14 Analogue output invert.
Analogue output minimumAnalogue output minimum
Analogue output minimum
Analogue output minimumAnalogue output minimum
Defines the signal minimum to
be either 0 mA or 4 mA (living
zero). See figure 6-15.
Analogue output scaleAnalogue output scale
Analogue output scale
Analogue output scaleAnalogue output scale
Scaling factor for analogue output.
See figure 6-15.
SignalMax. value of the signal
Output fre-Max. frequency (p. 1. 2)
quency
Motor speed Max. speed (n
Output2 x I
current
Motor torque 2 x T
Motor power2 x P
Motor voltage 100% x U
DC-link volt.1000 V
nCX
nCX
nCX
nmotor
Uin signalMax Uin
Iin signalMax Iin
nxfmax/fn
)
4 mA
0 mA
Analogue
output
current
20 mA
12 mA
10 mA
Param. 3. 5
= 100%
Param. 3. 5
= 200%
0
0.5
Param. 3. 5
= 200%
Selected (para. 3. 1)
signal max. value
1.0
Param. 3. 5
= 100%
Param. 3. 5
= 50%
UD012K17
Par. 3. 4 = 1
4 mA
Figure 6-15 Analogue output
scale.
Par. 3. 4 = 0
0 mA
0
0.5
Max. value of signal
selected by param. 3. 1
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
1.0
UD012K18
Page 30
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
VV
aconacon
V
acon
VV
aconacon
3. 63. 6
3. 6
3. 63. 6
3. 73. 7
3. 7
3. 73. 7
3. 83. 8
3. 8
3. 83. 8
Digital output functionDigital output function
Digital output function
Digital output functionDigital output function
Relay output 1 functionRelay output 1 function
Relay output 1 function
Relay output 1 functionRelay output 1 function
Relay output 2 functionRelay output 2 function
Relay output 2 function
Relay output 2 functionRelay output 2 function
Setting valueSignal content
0 = Not usedOut of operation
Digital output DO1 sinks the current and programmable
relay (RO1, RO2) is activated when:
1 = ReadyThe frequency converter is ready to operate
2 = RunThe frequency converter operates (motor is running)
3 = FaultA fault trip has occurred
4 = Fault invertedA fault trip has not occurred
5 = Vacon overheat warningThe heat-sink temperature exceeds +70°C
..
. 12)
..
..
. 14)
..
..
. 16)
..
..
. 20)
..
..
. 2
..
..
. 1
..
6 = External fault or warningFault or warning depending on parameter 7
7 = Reference fault or warningFault or warning depending on parameter 7
- if analogue reference is 4—20 mA and signal is <4mA
8 = WarningAlways if a warning exists
9 = ReversedThe reverse command has been selected
10= Jogging speedJogging speed has been selected with digital input
11= At speedThe output frequency has reached the set reference
12= Motor regulator activatedOvervoltage or overcurrent regulator was activated
13= Output frequency supervision 1The output frequency goes outside of the set supervision
..
. 18)
..
..
. 9 and 3
..
..
. 11 and 3
..
..
. 13 and 3
..
..
. 15 and 3
..
Low limit/ High limit (par. 3
14= Output frequency supervision 2The output frequency goes outside of the set supervision
Low limit/ High limit (par. 3
15= Torque limit supervisionThe motor torque goes outside of the set supervision
Low limit/ High limit (par. 3
16= Reference limit supervisionReference goes outside of the set supervision
Low limit/ High limit (par. 3
17= External brake controlExternal brake ON/OFF control with programmable de-
lay (par 3
18= Control from I/O terminalsExternal control mode selected with progr. push-button
#2
19= Frequency converterTemperature on frequency converter goes outside the
temperature limit supervisionset supervision limits (par. 3
..
. 17 and 3
..
..
. 10)
..
..
. 19 and 3
..
3. 93. 9
3. 9
3. 93. 9
3. 13. 1
3. 1
3. 13. 1
3. 103. 10
3. 10
3. 103. 10
3. 123. 12
3. 12
3. 123. 12
20= Unrequested rotation directionRotation direction of the motor shaft is different from the
requested one
21 = External brake control invertedExternal brake ON/OFF control (par. 3.17 and 3.18),
output active when brake control is OFF
22 = Termistor fault or warningThe termistor input of option board indicates
overtemperature. Fault or warning depending on
parameter 7.19
Table 6-2 Output signals via DO1 and output relays RO1 and RO2.
Output frequency limit 1, supervision functionOutput frequency limit 1, supervision function
Output frequency limit 1, supervision function
Output frequency limit 1, supervision functionOutput frequency limit 1, supervision function
11
1
11
Output frequency limit 2, supervision functionOutput frequency limit 2, supervision function
Output frequency limit 2, supervision function
Output frequency limit 2, supervision functionOutput frequency limit 2, supervision function
0 = No supervision
1 = Low limit supervision
2 = High limit supervision
If the output frequency goes under/over the set limit (3
..
. 10, 3
..
..
. 12) this function
..
generates a warning message via the digital output DO1 and via a relay output RO1
..
or RO2 depending on the settings of the parameters 3
Output frequency limit 1, supervision valueOutput frequency limit 1, supervision value
Output frequency limit 1, supervision value
Output frequency limit 1, supervision valueOutput frequency limit 1, supervision value
Output frequency limit 2, supervision valueOutput frequency limit 2, supervision value
Output frequency limit 2, supervision value
Output frequency limit 2, supervision valueOutput frequency limit 2, supervision value
The frequency value to be supervised by the parameter 3
. 6—3
..
..
. 9 (3
..
..
. 8.
..
..
. 11).
..
See figure 6-16.
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
VV
aconacon
V
acon Page 31
VV
aconacon
Multi-purpose Control Application IIMulti-purpose Control Application II
0 = No supervision
1 = Low limit supervision
2 = High limit supervision
f[Hz]
Par. 3.9 = 2
If the calculated torque value goes
under/over the set limit (3
..
. 14) this
..
Par 3. 10
function generates a warning
message via the digital output
DO1, via a relay output RO1 or
RO2 depending on the settings of
..
the parameters 3
Figure 6-16 Output frequency
supervision.
TT
orque limit , supervision valueorque limit , supervision value
T
orque limit , supervision value
TT
orque limit , supervision valueorque limit , supervision value
. 6—3
..
..
. 8.
..
Example:
21 RO1
22 RO1
23 RO1
21 RO1
22 RO1
23 RO1
The calculated torque value to be supervised by the parameter 3
Reference limit , supervision functionReference limit , supervision function
Reference limit , supervision function
Reference limit , supervision functionReference limit , supervision function
..
. 13.
..
UD009K19
21 RO1
22 RO1
23 RO1
t
0 = No supervision
1 = Low limit supervision
2 = High limit supervision
If the reference value goes under/over the set limit (3
..
. 16) this function generates a
..
warning message via the digital output DO1 or via a relay output RO1 or
RO2 depending on the settings of the parameters 3
..
. 6—3
..
..
. 8. The supervised
..
reference is the currently active reference. It can be source A or B reference depending
on DIB6 input or the panel reference if panel is the active control source.
3. 163. 16
3. 16
3. 163. 16
3. 173. 17
3. 17
3. 173. 17
3. 183. 18
3. 18
3. 183. 18
3. 193. 19
3. 19
3. 193. 19
3. 203. 20
3. 20
3. 203. 20
Reference limit , supervision valueReference limit , supervision value
Reference limit , supervision value
Reference limit , supervision valueReference limit , supervision value
The frequency value to be supervised by the parameter 3
With these parameters the timing of external brake can be linked to the Start and
Stop control signals, see Figure 6-18.
The brake control signal can be programmed via the digital output DO1 or via one
..
of relay outputs RO1 and RO2, see parameters 3
Frequency converter temperature limit supervision functionFrequency converter temperature limit supervision function
Frequency converter temperature limit supervision function
Frequency converter temperature limit supervision functionFrequency converter temperature limit supervision function
. 6—3
..
..
. 8.
..
0 = No supervision
1 = Low limit supervision
2 = High limit supervision
If the temperature of the frequency converter goes under/over the set limit (3
..
. 20)
..
this function generates a warning message via the digital output DO1 or via the relay
..
outputs RO1 or RO2 depending on the settings of the parameters 3
Frequency converter temperature limit valueFrequency converter temperature limit value
Frequency converter temperature limit value
Frequency converter temperature limit valueFrequency converter temperature limit value
The temperature value to be supervised by the parameter 3
..
. 19.
..
. 6—3
..
..
. 8.
..
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
The start and end of the acceleration and deceleration ramps can be smoothed with
these parameters. Setting value 0 gives linear ramp shape which causes acceleration
and deceleration to act immediately to the changes in the reference signal with the
time constant set by the parameter 1
Setting value 0.1—10 seconds for
. .
4
. 1 (4
. .
. .
. 2) causes linear
. .
..
. 3 and 1
..
[Hz]
..
. 4
..
. .
(4
. 3 and 4
. .
. .
. 4).
. .
acceleration/deceleration to adopt
an S-shape. Parameter 1
4
(4
. .
. 3 and 4
. .
. .
. 4) determines the
. .
..
. 3 and 1
..
time constant of acceleration/
..
.
..
1. 3, 1. 4
(4. 3, 4. 4)
deceleration in the middle of the
curve. See figure 6-20.
Figure 6-20 S-shaped acceleration/
deceleration.
4. 1 (4. 2)
4. 1 (4. 2)
[t]
UD009K20
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
VV
aconacon
V
acon Page 35
VV
aconacon
Multi-purpose Control Application IIMulti-purpose Control Application II
4. 34. 3
4. 3
4. 34. 3
4. 44. 4
4. 4
4. 44. 4
4. 54. 5
4. 5
4. 54. 5
4. 64. 6
4. 6
4. 64. 6
Acceleration time 2Acceleration time 2
Acceleration time 2
Acceleration time 2Acceleration time 2
Deceleration time 2Deceleration time 2
Deceleration time 2
Deceleration time 2Deceleration time 2
These values correspond to the time required for the output frequency to accelerate
from the set minimum frequency (par. 1
(par. 1
. .
. 2). These times give the possibility to set two different acceleration/
. .
. .
. 1) to the set maximum frequency
. .
deceleration time sets for one application. The active set can be selected with the
programmable signal DIA3 of this application, see parameter 2
..
. 2.
..
Acceleration/deceleration times can be reduced with an external free analogue input
signal, see parameters 2
Brake chopperBrake chopper
Brake chopper
Brake chopperBrake chopper
..
. 18 and 2
..
..
. 19.
..
0 = No brake chopper
1 = Brake chopper and brake resistor installed
2 = External brake chopper
When the frequency converter is decelerating the motor, the inertia of the motor and
the load are fed into the external brake resistor. This enables the frequency converter
to decelerate the load with the torque equal to that of acceleration, if the brake resistor
is selected correctly. See separate Brake resistor installation manual.
Start functionStart function
Start function
Start functionStart function
Ramp:
00
0The frequency converter starts from 0 Hz and accelerates to the set referen-
00
ce frequency within the set acceleration time. (Load inertia or starting friction
may cause prolonged acceleration times).
Flying start:
11
1The frequency converter is able to start into running motor by applying a small
11
torque to motor and searching for frequency corresponding to the speed the
motor is running at. Searching starts from the maximum frequency towards
the actual frequency until the correct value is detected. Thereafter the output
frequency will be accelerated/decelerated to the set reference value according
to the set acceleration/deceleration parameters.
Use this mode if the motor is coasting when the start command is given.
With the flying start it is possible to ride through short mains voltage
interruptions.
4. 74. 7
4. 7
4. 74. 7
Stop functionStop function
Stop function
Stop functionStop function
Coasting:
00
0The motor coasts to a halt without any control from the frequency converter,
00
after the Stop command.
Ramp:
11
1After the Stop command, the speed of the motor is decelerated according to
11
the set deceleration parameters.
If the regenerated energy is high it may be necessary to use an external
braking resistor for faster deceleration.
4. 84. 8
4. 8
4. 84. 8
DC braking currentDC braking current
DC braking current
DC braking currentDC braking current
Defines the current injected into the motor during the DC braking.
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
Page 36
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
VV
aconacon
V
acon
VV
aconacon
4. 94. 9
4. 9
4. 94. 9
DC braking time at stopDC braking time at stop
DC braking time at stop
DC braking time at stopDC braking time at stop
Defines if braking is ON or OFF and the braking time of the DC-brake when the motor
is stopping. The function of the DC-brake depends on the stop function, parameter
. .
4
. 7. See figure 6-21.
. .
00
0DC-brake is not used
00
>0>0
>0DC-brake is in use and its function depends on the Stop function,
>0>0
(param. 4
..
. 7), and the time depends on the value of parameter 4
..
..
. 9:
..
Stop-function = 0 (coasting):
After the stop command, the motor coast to a stop without any control from
the frequency converter.
With DC-injection, the motor can be electrically stopped in the shortest possible
time, without using an optional external braking resistor.
The braking time is scaled according to the frequency when the DCbraking starts. If the frequency is
>nominal frequency of the motor (par. 1.11),
setting value of parameter 4.9 determines the braking time. When the frequency
is <10% of the nominal, the braking time is 10% of the set value of parameter
4.9.
f
out
f
n
Output frequency
Motor speed
f
out
f
n
Output frequency
Motor speed
DC-braking ON
t = 0.1 x par. 4. 9
t
UD009K21
RUN
STOP
DC-braking ON
t = 1 x par. 4. 9
t
0,1x f
n
RUN
STOP
Figure 6-21 DC-braking time when stop = coasting.
Stop-function = 1 (ramp):
After the Stop command, the speed of the motor is reduced according to
the set deceleration parameters, as fast as possible, to a speed defined with
the parameter 4
The braking time is defined
with parameter 4
..
. 10, where the DC-braking starts.
..
f
out
..
. 9.
..
Motor speed
Output frequency
If high inertia exists, it is
recommended to use an
external braking resistor for
faster deceleration. See
figure 6-22.
Param. 4. 10
DC-braking
Figure 6-22 DC-braking
time when stop function =
ramp.
RUN
STOP
t = param. 4. 9
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
t
UD009K23
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
VV
aconacon
V
acon Page 37
VV
aconacon
Multi-purpose Control Application IIMulti-purpose Control Application II
4. 104. 10
4. 10
4. 104. 10
Execute frequency of DC-brake during ramp StopExecute frequency of DC-brake during ramp Stop
Execute frequency of DC-brake during ramp Stop
Execute frequency of DC-brake during ramp StopExecute frequency of DC-brake during ramp Stop
See figure 6-22.
4. 14. 1
4. 1
4. 14. 1
11
1
11
DC-brake time at startDC-brake time at start
DC-brake time at start
DC-brake time at startDC-brake time at start
>0>0
>0DC-brake is actived when
>0>0
4. 12 - 4. 184. 12 - 4. 18
4. 12 - 4. 18
4. 12 - 4. 184. 12 - 4. 18
00
0DC-brake is not used
00
the start command is given
and this parameter defines
the time before the brake is
released. After the brake is
released, the output
frequency increases
according to the set start
function parameter 4
Parameter value defines the Multi-Step speeds selected with the digital inputs.
Prohibit frequency areaProhibit frequency area
Prohibit frequency area
Prohibit frequency areaProhibit frequency area
Low limit/High limitLow limit/High limit
Low limit/High limit
Low limit/High limitLow limit/High limit
f
out
[Hz]
In some systems it may be
necessary to avoid certain
frequencies because of
mechanical resonance problems.
With these parameters it is
possible to set limits for three "skip
frequency" regions.
Figure 6-24 Example of prohibit
frequency area setting.
Motor control modeMotor control mode
Motor control mode
Motor control modeMotor control mode
0 = Frequency control: The I/O terminal and panel references are frequency references and
the frequency converter controls the output frequency (output frequency resolution = 0.01 Hz)
1 = Speed control: The I/O terminal and panel references are speed references and the
frequency converter controls the motor speed (regulation accuracity ± 0,5%).
2 = Torque control: The I/O terminal and panel references are torque references and the frequency
converter controls the motor torque (regulation accuracity ± 3 % ; proper tuning required: motor
nameplate values, U/f -setting).
5. 1 5. 2
5. 3 5. 4
5. 5 5. 6
frequency
reference
[Hz]
UD009K33
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
Page 38
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
VV
aconacon
V
acon
VV
aconacon
6. 2 6. 2
6. 2
6. 2 6. 2
6. 36. 3
6. 3
6. 36. 3
6. 46. 4
6. 4
6. 46. 4
6. 56. 5
6. 5
6. 56. 5
Switching frequencySwitching frequency
Switching frequency
Switching frequencySwitching frequency
Motor noise can be minimized using a high switching frequency. Increasing the
switching frequency reduces the capacity of the frequency converter unit.
Before changing the frequency from the factory default 10 kHz (3.6 kHz from 30 kW
upwards), check the allowed capacity from the curve in the figure 5.2-3 of chapter
5.2 of the User's Manual.
Field weakening pointField weakening point
Field weakening point
Field weakening pointField weakening point
VV
oltage at the field weakening pointoltage at the field weakening point
V
oltage at the field weakening point
VV
oltage at the field weakening pointoltage at the field weakening point
The field weakening point is the output frequency at which the output voltage reaches
the set maximum value (par. 6
..
. 4). Above that frequency the output voltage remains
..
at the set maximum value.
Below that frequency the output voltage depends on the setting of the U/f curve
..
..
..
parameters 1
. 8, 1
..
. 9, 6
..
When the parameters 1
..
. 5, 6
. 6 and 6
..
..
..
. 10 and 1
..
the motor, are set, also parameters 6
..
. 7. See figure 6-25.
..
..
. 11, nominal voltage and nominal frequency of
..
..
. 3 and 6
..
..
. 4 are set automatically to the
..
corresponding values. If different values for the field weakening point and
the maximum output voltage are required, change these parameters
the parameters 1
U/f curve, middle point frequencyU/f curve, middle point frequency
U/f curve, middle point frequency
U/f curve, middle point frequencyU/f curve, middle point frequency
..
. 10 and 1
..
..
. 11.
..
If the programmable U/f curve has been selected with the parameter 1
after setting
..
. 8 this
..
parameter defines the middle point frequency of the curve. See figure 6-25.
6. 66. 6
6. 6
6. 66. 6
6. 76. 7
6. 7
6. 76. 7
U/f curve, middle point voltageU/f curve, middle point voltage
U/f curve, middle point voltage
U/f curve, middle point voltageU/f curve, middle point voltage
If the programmable U/f curve has been selected with the parameter 1
parameter defines the middle point voltage of the curve. See figure 6-25.
Output voltage at zero frequencyOutput voltage at zero frequency
Output voltage at zero frequency
Output voltage at zero frequencyOutput voltage at zero frequency
If the programmable U/f curve has been selected with the parameter 1
parameter defines the zero frequency voltage of the curve. See figure 6-25.
U[V]
Un
Par 6. 4
Par. 6. 6
(Def. 10%)
Par. 6. 7
(Def. 1.3%)
Default: Nominal
voltage of the motor
Par. 6. 5
(Def. 5 Hz)
Field weakening
point
Default: Nominal
frequency of the
motor
Par. 6. 3
f[Hz]
UD012K08
..
. 8 this
..
..
. 8 this
..
Figure 6-25 Programmable U/f curve.
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
VV
aconacon
V
acon Page 39
VV
aconacon
Multi-purpose Control Application IIMulti-purpose Control Application II
These parameters allow the over/undervoltage controllers to be switched out of
operation. This may be useful, for example, if the mains supply voltage varies more
than -15%—+10% and the application will not tolerate this over-/undervoltage, the
regulator controls the output frequency according to the supply fluctuations.
Over/undervoltage trips may occur when controllers are switched out of operation.
Response to the reference faultResponse to the reference fault
Response to the reference fault
Response to the reference faultResponse to the reference fault
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to parameter 4.7
3 = Fault, stop mode after fault always by coasting
A warning or a fault action and message is generated if 4—20 mA reference signal
is used and the signal falls below 4 mA. The information can also be programmed
via digital output DO1 and via relay outputs RO1 and RO2.
Response to external faultResponse to external fault
Response to external fault
Response to external faultResponse to external fault
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to parameter 4.7
3 = Fault, stop mode after fault always by coasting
A warning or a fault action and message is generated from the external fault signal
in the digital input DIA3. The information can also be programmed into digital output
DO1 and into relay outputs RO1 and RO2.
Phase supervision of the motorPhase supervision of the motor
Phase supervision of the motor
Phase supervision of the motorPhase supervision of the motor
0 = No action
1 = Warning
2 = Fault
Phase supervision of the motor ensures that the motor phases have approximately
equal current.
Earth fault protectionEarth fault protection
Earth fault protection
Earth fault protectionEarth fault protection
0 = No action
1 = Warning
2 = Fault
Earth fault protection ensures that the sum of the motor phase currents is zero.
The overcurrent protection is always working and protects the frequency converter
from earth faults with high currents.
Parameters 7. 5—7. 9 Motor thermal protectionParameters 7. 5—7. 9 Motor thermal protection
Parameters 7. 5—7. 9 Motor thermal protection
Parameters 7. 5—7. 9 Motor thermal protectionParameters 7. 5—7. 9 Motor thermal protection
GeneralGeneral
General
GeneralGeneral
Motor thermal protection is to protect the motor from overheating. Vacon CX/CXL/CXS drive is
capable of supplying higher than nominal current to the motor. If the load requires this high current
there is a risk that motor will be thermally overloaded. This is true especially at low frequencies.
At low frequencies the cooling effect of the motor is reduced as well as is the capacity of the
motor. If the motor is equipped with an external fan the load reduction on low speeds is small.
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
Page 40
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
VV
aconacon
V
acon
VV
aconacon
Motor thermal protection is based on a calculated
model and it uses the output current of the drive to
determine the load on the motor. When the power
of the drive is turned on, the calculated model uses
the heatsink temperature to determine the initial
thermal stage for the motor. The calculated model
assumes that the ambient temperature of the motor
is 40°C.
Motor thermal protection can be adjusted by setting
the parameters. The thermal current IT specifies
the load current above which the motor is overloaded.
This current limit is a function of the output
frequency. The curve for IT is set with parameters
..
..
7
. 6, 7
. 7 and 7
..
..
parameters have their default values taken from the
motor name plate data.
CAUTION!
!
7. 57. 5
7. 5
7. 57. 5
..
. 9, refer to the figure 6-26. The
..
The calculated model does not protect the motor if the airflow to the
motor is reduced by blocked air intake grill.
Motor thermal protectionMotor thermal protection
Motor thermal protection
Motor thermal protectionMotor thermal protection
Operation:
0 = Not in use
1 = Warning
2 = Trip function
Tripping and warning will display the same message code. If tripping is selected the
drive will stop and activate the fault stage.
Deactivating the protection, setting parameter to 0, will reset the thermal stage of
the motor to 0%.
7. 67. 6
7. 6
7. 67. 6
Motor thermal protection, break point currentMotor thermal protection, break point current
Motor thermal protection, break point current
Motor thermal protection, break point currentMotor thermal protection, break point current
The current can be set between 50.0—150.0% x I
This parameter sets the value for thermal current at frequencies above the
break point on the thermal current curve. Refer to the figure 6-26.
The value is set in percentage which refers to the name plate data of the
motor, parameter 1
..
. 13, nominal current of the motor, not the drive's nominal output
..
current.
The motor's nominal current is the current which the motor can withstand in direct
on-line use without being overheated.
If parameter 1
..
. 13 is adjusted, this parameter is automatically restored to the default
..
value.
Setting this parameter (or parameter 1
current of the drive. Parameter 1
of the drive.
With the output current at IT the thermal stage will
reach the nominal value (100%). The thermal stage
changes by the square of the current. With output
current at 75% from IT the thermal stage will reach
56% value and with output current at 120% from I
the thermal stage would reach 144% value. The
function will trip the device (refer par. 7
thermal stage will reach a value of 105%. The speed
of change in thermal stage is determined with the
time constant parameter 7
the longer it takes to reach the final temperature.
The thermal stage of the motor can be monitored
through the display. Refer to the table for monitoring
items. (User's Manual, table 7.3-1).
.
nMotor
..
. 13) does not affect the maximum output
..
..
. 7 alone determines the maximum output current
..
..
. 8. The bigger the motor
..
..
. 5) if the
..
T
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
VV
aconacon
V
acon Page 41
VV
aconacon
Multi-purpose Control Application IIMulti-purpose Control Application II
Figure 6-26 Motor thermal current
IT curve.
Current
limit
par. 1. 7
I
7. 77. 7
7. 7
7. 77. 7
Par. 7. 6
Par. 7. 7
I
T
f
Overload area
UMCH7_91
Motor thermal protection, zero frequency currentMotor thermal protection, zero frequency current
Motor thermal protection, zero frequency current
Motor thermal protection, zero frequency currentMotor thermal protection, zero frequency current
The current can be set between 10.0—150.0% x I
nMotor
Par. 7. 9
. This parameter sets the
value for thermal current at zero frequency. Refer to figure 6-26.
The default value is set assuming that there is no external fan cooling the motor. If
an external fan is used this parameter can be set to 90% (or even higher).
The value is set as a percentage of the
motor name plate data, parameter 1
motor's nominal current, not the drive's
nominal output current. Motor's nominal
current is the current which the motor can
stand in direct on-line use without being
overheated.
..
. 13,
..
If you change the parameter 1
parameter is automatically restored to the
default value.
Setting this parameter (or parameter 1
does not affect to the maximum output current
of the drive. Parameter 1
the maximum output current of the drive.
..
. 7 alone determines
..
..
. 13 this
..
..
. 13)
..
7. 87. 8
7. 8
7. 87. 8
Motor thermal protection, time constantMotor thermal protection, time constant
Motor thermal protection, time constant
Motor thermal protection, time constantMotor thermal protection, time constant
This time can be set between 0.5—300 minutes.
This is the thermal time constant of the motor.The bigger the motor the bigger
the time constant. The time constant is the time within which the calculated thermal
stage has reached 63% of its final value.
The motor thermal time is specific for the
motor design and it varies between different
motor manufacturers.
The default value for the time constant is
calculated basing on the motor name plate
data given with parameters 1
either of these parameters is set, this
parameter is set to default value.
If the motor's t6 -time is known (given by the
motor manufacturer) the time constant
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
..
. 12 and 1
..
..
. 13. If
..
parameter could be set basing on t6 -time.
As a rule of thumb, the motor thermal time
constant in minutes equals to 2xt6 (t6 in
seconds is the time a motor can safely
operate at six times the rated current). If the
drive is in stop stage the time constant is
internally increased to three times the set
parameter value. The cooling in the stop stage
is based on convection and the time constant
is increased.
Page 42
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
VV
aconacon
V
acon
VV
aconacon
7. 97. 9
7. 9
7. 97. 9
Motor thermal protection, breakpoint frequencyMotor thermal protection, breakpoint frequency
Motor thermal protection, breakpoint frequency
Motor thermal protection, breakpoint frequencyMotor thermal protection, breakpoint frequency
The frequency can be set between 10—500 Hz.
This is the breakpoint of thermal current curve. With frequencies above this point
the thermal capacity of the motor is assumed to be constant. Refer to the figure
6-26.
The default value is based on the motor's name plate data, parameter 1
..
. 11. It is 35
..
Hz for a 50 Hz motor and 42 Hz for a 60 Hz motor. More generally it is 70% of the
frequency at field weakening point (parameter 6
11 or 6
..
. 3 will restore this parameter to its default value.
Motor stall protection protects the motor from short time overload situations like a stalled shaft.
The reaction time of stall protection can be set shorter than with motor thermal protection. The
stall state is defined with two parameters, 7.11. Stall Current and 7.13. Stall Frequency. If the
current is higher than the set limit and output frequency is lower than the set limit, the stall state
is true. There is actually no real indication of the shaft rotation. Stall protection is a type of
overcurrent protection.
7. 107. 10
7. 10
7. 107. 10
Stall protectionStall protection
Stall protection
Stall protectionStall protection
Operation:
0 = Not in use
1 = Warning
2 = Trip function
Tripping and warning will display the same message code. If tripping is set on, the
drive will stop and activate the fault stage.
Setting the parameter to 0 will deactivate the protection and will reset the stall time
counter to zero.
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
VV
aconacon
V
acon Page 43
VV
aconacon
7. 17. 1
7. 1
7. 17. 1
11
1
11
Stall current limitStall current limit
Stall current limit
Stall current limitStall current limit
Multi-purpose Control Application IIMulti-purpose Control Application II
I
The current can be set to 0.0—
200% x I
nMotor
.
In a stall stage the current has to
be above this limit. Refer to figure
6-28. The value is set as a
percentage of the motor's name
plate data, parameter 1
. .
. 13,
. .
Stall area
motor's nominal current. If
parameter 1
..
.13 is adjusted, this
..
Par. 7. 11
parameter is automatically
restored to the default value.
Figure 6-28 Setting the stall
characteristics.
Par. 7. 13
f
UMCH7_11
7. 127. 12
7. 12
7. 127. 12
7. 137. 13
7. 13
7. 137. 13
Stall timeStall time
Stall time
Stall timeStall time
The time can be set between 2.0—120 s.
This is the maximum allowed time for a stall stage. There is an internal up/down
counter to count the stall time. Refer to figure 6-29.
If the stall time counter value goes above this limit the protection will cause a trip
(refer to parameter 7
Maximum stall frequencyMaximum stall frequency
Maximum stall frequency
Maximum stall frequencyMaximum stall frequency
The frequency can be set between
1—f
max
(par. 1
..
. 2).
..
..
. 10).
..
Par. 7. 12
Stall time counter
Trip area
Trip/warning
par. 7. 10
In a stall state, the output
frequency has to be smaller than
this limit. Refer to figure 6-28.
The purpose of motor underload protection is to ensure that there is load on the motor when the
drive is running. If the motor loses its load there might be a problem in the process, e.g. a broken
belt or dry pump.
Motor underload protection can be adjusted by
setting the underload curve with parameters
. .
7
. 15 and 7
. .
curve set between zero frequency and the field
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
..
. 16. The underload curve is a squared
..
Service:+358-40-8371 150E-mail: vacon@vacon.com
weakening point. The protection is not active below
5Hz (the underload counter value is stopped). Refer
to figure 6-30.
Page 44
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
VV
aconacon
V
acon
VV
aconacon
The torque values for setting the underload curve
are set in percentage which refer to the nominal
torque of the motor. The motor's name plate data,
parameter 1. 13, the motor's nominal current and
7. 147. 14
7. 14
7. 147. 14
Underload protectionUnderload protection
Underload protection
Underload protectionUnderload protection
Operation:
0 = Not in use
1 = Warning
2 = Fault
Tripping and warning will display the same message code. If tripping is set active
the drive will stop and activate the fault stage.
Deactivating the protection by setting the parameter to 0 will reset the underload time
counter to zero.
7. 157. 15
7. 15
7. 157. 15
Underload protection, field weakening area loadUnderload protection, field weakening area load
Underload protection, field weakening area load
Underload protection, field weakening area loadUnderload protection, field weakening area load
The torque limit can be set between 20.0—150 % x T
This parameter gives the value for
the minimum torque allowed when
the output frequency is above the
field weakening point.
Refer to figure 4.5-22.
If parameter 1
..
. 13 is adjusted, this
..
parameter is automatically
restored to the default value.
the drive's nominal current ICT are used to find the
scaling ratio for the internal torque value. If other
than nominal motor is used with the drive, the
accuracy of the torque calculation decreases.
.
nMotor
Torque
Par. 7. 15
7. 167. 16
7. 16
7. 167. 16
7. 177. 17
7. 17
7. 177. 17
Figure 6-30 Setting of minimum
load.
Underload protection, zeroUnderload protection, zero
Underload protection, zero
Underload protection, zeroUnderload protection, zero
frequency loadfrequency load
frequency load
frequency loadfrequency load
The torque limit can be set
between 10.0—150 % x T
nMotor
.
Par. 7. 16
5 Hz
Underload area
Fieldweakening
point par. 6. 3
f
UMCH7_15
This parameter gives value for the minimum torque allowed with zero frequency.
Refer to figure 6-30. If parameter 1
..
. 13 is adjusted this parameter is automatically
..
restored to the default value.
Underload timeUnderload time
Underload time
Underload timeUnderload time
This time can be set between 2.0—600.0 s.
This is the maximum allowed time for an underload state. There is an internal up/
down counter to accumulate the underload time. Refer to figure 6-31.
If the underload counter value goes above this limit the protection will cause a trip
(refer to the parameter 7
. .
. 14). If the drive is stopped the underload counter
. .
is reset to zero.
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
VV
aconacon
V
acon Page 45
VV
aconacon
Figure 6-31 Counting the under-
load time.
Multi-purpose Control Application IIMulti-purpose Control Application II
Underload time counter
Trip area
Par. 7. 17
Underl.
No underl.
Trip/warning
par. 7. 14
UMCH7_17
Time
7. 187. 18
7. 18
7. 187. 18
.
7. 197. 19
7. 19
7. 197. 19
7. 207. 20
7. 20
7. 207. 20
Phase supervision of the supply voltagePhase supervision of the supply voltage
Phase supervision of the supply voltage
Phase supervision of the supply voltagePhase supervision of the supply voltage
0 = No action
1 = Warning
2 = Fault
By setting the parameter value to zero, the phase supervision of the supply voltage
will not cause tripping
Thermistor input of IO-ExpanderThermistor input of IO-Expander
Thermistor input of IO-Expander
Thermistor input of IO-ExpanderThermistor input of IO-Expander
0 = No action
1 = Warning
2 = Fault
The thermistor connected to the thermistor input of the I/O-expander board supervises
the temperature of the motor. With parameter 7.19 the response of the frequency
converter can be programmed when the thermistor indicates overtemperature.
Response to the fieldbus faultResponse to the fieldbus fault
Response to the fieldbus fault
Response to the fieldbus faultResponse to the fieldbus fault
0 = No response
1 = Warning message
2 = Fault message, stop mode after fault according to parameter 4.7
A warning or a fault action and message is generated from the fieldbus card if the
error occurs of the bus system physical layer.
8. 18. 1
8. 1
8. 18. 1
8. 28. 2
8. 2
8. 28. 2
Automatic restart: number of triesAutomatic restart: number of tries
Automatic restart: number of tries
Automatic restart: number of triesAutomatic restart: number of tries
Automatic restart: trial timeAutomatic restart: trial time
Automatic restart: trial time
Automatic restart: trial timeAutomatic restart: trial time
The Automatic restart function restarts the frequency converter after the faults selected
..
with parameters 8
parameter 8
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
. .
. 3.
. .
Service:+358-40-8371 150E-mail: vacon@vacon.com
..
. 4—8
. 8. The Start function for Automatic restart is selected with
..
..
Page 46
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
Number of faults
during t = t
4
3
trial
t
trial
t
trial
VV
aconacon
V
acon
VV
aconacon
8. 38. 3
8. 3
8. 38. 3
2
1
Three faults
RUN
STOP
Figure 6-32 Automatic restart
Parameter 8
..
. 1 determines how many automatic restarts can be made during the
..
trial time set by the parameter 8
..
. 2.
..
Par. 8. 2 = 3
t
trial
Four faults
= par. 8. 1
t
UD009K25
The time counting starts from the first autorestart. If the number of restarts does not
exceed the value of the parameter 8
..
. 1 during the trial time, the counting is cleared
..
after the time is elapsed and next fault starts the counting again.
Automatic restart, start functionAutomatic restart, start function
Automatic restart, start function
Automatic restart, start functionAutomatic restart, start function
The parameter defines the start mode:
0 = Start with ramp
1 = Flying start, see parameter 4
..
. 6.
..
8. 48. 4
8. 4
8. 48. 4
8. 58. 5
8. 5
8. 58. 5
8. 68. 6
8. 6
8. 68. 6
8. 78. 7
8. 7
8. 78. 7
8. 88. 8
8. 8
8. 88. 8
Automatic restart after undervoltage tripAutomatic restart after undervoltage trip
Automatic restart after undervoltage trip
Automatic restart after undervoltage tripAutomatic restart after undervoltage trip
0 = No automatic restart after undervoltage fault trip
1 = Automatic restart after undervoltage fault condition returns to normal
condition (DC-link voltage returns to the normal level)
Automatic restart after overvoltage tripAutomatic restart after overvoltage trip
Automatic restart after overvoltage trip
Automatic restart after overvoltage tripAutomatic restart after overvoltage trip
0 = No automatic restart after overvoltage fault trip
1 = Automatic restart after overvoltage fault condition returns to the normal
condition (DC-link voltage returns to the normal level)
Automatic restart after overcurrent tripAutomatic restart after overcurrent trip
Automatic restart after overcurrent trip
Automatic restart after overcurrent tripAutomatic restart after overcurrent trip
0 = No automatic restart after overcurrent fault trip
1 = Automatic restart after overcurrent faults
Automatic restart after reference fault tripAutomatic restart after reference fault trip
Automatic restart after reference fault trip
Automatic restart after reference fault tripAutomatic restart after reference fault trip
0 = No automatic restart after reference fault trip
1 = Automatic restart after analog current reference signal (4—20 mA)
returns to the normal level (>4 mA)
Automatic restart after over-/undertemperature fault tripAutomatic restart after over-/undertemperature fault trip
Automatic restart after over-/undertemperature fault trip
Automatic restart after over-/undertemperature fault tripAutomatic restart after over-/undertemperature fault trip
0 = No automatic restart after temperature fault trip
1 = Automatic restart after heatsink temperature has returned to its normal
level between -10°C—+75°C.
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
VV
aconacon
V
acon Page 47
VV
aconacon
TT
orque controlorque control
T
orque control
TT
orque controlorque control
Multi-purpose Control Application IIMulti-purpose Control Application II
Torque control can be activated either by setting parameter 6.1 to torque control or with
digital input DIA3 (parameter 2.2=10). Torque reference source is selected with parameter
9.1 and reference scaling with parameters 9.2 and 9.3.
orque reference scaling gainorque reference scaling gain
T
orque reference scaling gain
TT
orque reference scaling gainorque reference scaling gain
The additional scaling function can be used for scaling the torque reference. The
torque reference is always fed to the torque controller even if it is not activated.
T
= gain × T
ref. out
TC time constantTC time constant
TC time constant
TC time constantTC time constant
ref. in
+ bias
Defines the time constant for the torque controller. A short time constant means
fast response.
TC min. control limitTC min. control limit
TC min. control limit
TC min. control limitTC min. control limit
Defines frequency limit below which the frequency converter operates normally
in frequency control mode.
The internal torque calculation is inaccurate at low speeds (< nominal slip of the
motor). It is recommended to operate in frequency control operation mode at low
speeds.
The reference value in frequency controlled operation mode is selected with parameter 1. 5.
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Page 48
Fieldbus controlFieldbus control
Fieldbus control
Fieldbus controlFieldbus control
Fieldbus control can be activated with parameter 10.1. Then the frequency or speed reference comes from the fieldbus as well as the Start/Stop and Reverse control.
First two parameters in group 10 concern all fieldbuses. Parameters 10.3 - 10.6 are only for
Modbus, parameters 10.7 - 10.13 only for Profibus and 10.14 only for LonWorks.
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
VV
aconacon
V
acon
VV
aconacon
10. 110. 1
10. 1
10. 110. 1
10.210.2
10.2
10.210.2
Parameters 10.3 - 10.6 only for Modbus protocolParameters 10.3 - 10.6 only for Modbus protocol
Parameters 10.3 - 10.6 only for Modbus protocol
Parameters 10.3 - 10.6 only for Modbus protocolParameters 10.3 - 10.6 only for Modbus protocol
10.310.3
10.3
10.310.3
10.410.4
10.4
10.410.4
Fieldbus controlFieldbus control
Fieldbus control
Fieldbus controlFieldbus control
Defines the active control source:
0:0:
0: control via I/O terminals
0:0:
1:1:
1: control via Fielbus board
1:1:
DIC1 functionDIC1 function
DIC1 function
DIC1 functionDIC1 function
0:0:
0: Fieldbus control, contact open = Active control source are I/O terminals
0:0:
contact closed = Active control source is the Fieldbus
1:1:
1: External Fault, closing contact = Fault is shown and motor is stopped
1:1:
Slave addressSlave address
Slave address
Slave addressSlave address
Defines slave device address. Maximum value for this parameter is 247
and minimum is 1.
Baud RateBaud Rate
Baud Rate
Baud RateBaud Rate
1:1:
1: 300 baud
1:1:
2:2:
2: 600 baud
2:2:
3:3:
3: 1200 baud
3:3:
4:4:
4: 2400 baud
4:4:
5:5:
5: 4800 baud
5:5:
6:6:
6: 9600 baud
6:6:
7:7:
7: 19200 baud
7:7:
board
when the input is active
10.510.5
10.5
10.510.5
10.610.6
10.6
10.610.6
Parameters 10.7 to 10.13 only for Profibus DP protocolParameters 10.7 to 10.13 only for Profibus DP protocol
Parameters 10.7 to 10.13 only for Profibus DP protocol
Parameters 10.7 to 10.13 only for Profibus DP protocolParameters 10.7 to 10.13 only for Profibus DP protocol
10.710.7
10.7
10.710.7
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Parity typeParity type
Parity type
Parity typeParity type
0:0:
0: None
0:0:
1:1:
1: Even
1:1:
2:2:
2: Odd
2:2:
Modbus time-outModbus time-out
Modbus time-out
Modbus time-outModbus time-out
The Modbus time-out determines how long the Fieldbus board waits for a
message from a master device and is specified in seconds.
Time can be set between 0 - 3600 s. Time 0 s = No time-out
Profibus slave addressProfibus slave address
Profibus slave address
Profibus slave addressProfibus slave address
Defines slave device address. Maximum value for this parameter is 126 and
minimum 2.
Service:+358-40-8371 150E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
VV
aconacon
V
acon Page 49
VV
aconacon
Multi-purpose Control Application IIMulti-purpose Control Application II
10.810.8
10.8
10.810.8
10.910.9
10.9
10.910.9
10.1010.10
10.10
10.1010.10
10.110.1
10.1
10.110.1
10.1210.12
10.12
10.1210.12
10.1310.13
10.13
10.1310.13
Profibus baud rateProfibus baud rate
Profibus baud rate
Profibus baud rateProfibus baud rate
1:1:
1:9.6kbaud
1:1:
2:2:
2:19.2kbaud
2:2:
3:3:
3:93.75kbaud
3:3:
4:4:
4:187.5kbaud
4:4:
5:5:
5:500kbaud
5:5:
6:6:
6:1.5Mbaud
6:6:
7:7:
7:3Mbaud
7:7:
8:8:
8:6Mbaud
8:8:
9:9:
9:12Mbaud
9:9:
10:10:
10:AUTO(Automatic baud rate select)
10:10:
Profibus PPO TProfibus PPO T
Profibus PPO T
Profibus PPO TProfibus PPO T
ypeype
ype
ypeype
Selection of profibus PPO type.
1:1:
1:PPO 1(Parameter data 8 bytes, Control data 4 bytes)
1:1:
2:2:
2:PPO 2(Parameter data 8 bytes, Control data 12 bytes)
2:2:
3:3:
3:PPO 3(Control data 4 bytes)
3:3:
4:4:
4:PPO 4(Control data 12 bytes)
4:4:
Profibus process Data 1Profibus process Data 1
Profibus process Data 1
Profibus process Data 1Profibus process Data 1
11
Profibus process Data 2Profibus process Data 2
1
Profibus process Data 2
11
Profibus process Data 2Profibus process Data 2
Profibus process Data 3Profibus process Data 3
Profibus process Data 3
Profibus process Data 3Profibus process Data 3
Profibus process Data 4Profibus process Data 4
Profibus process Data 4
Profibus process Data 4Profibus process Data 4
Selection of profibus process data source.
Value 1...22 Number of actual value (= V1...V22 in Monitoring Menu)
99Active fault code
Parameter 10.14 only for LonWorks protocolParameter 10.14 only for LonWorks protocol
Parameter 10.14 only for LonWorks protocol
Parameter 10.14 only for LonWorks protocolParameter 10.14 only for LonWorks protocol
10.1410.14
10.14
10.1410.14
LonWorks service buttonLonWorks service button
LonWorks service button
LonWorks service buttonLonWorks service button
Changing the value of this parameter from 0 to 1 or vice versa and pressing
the Enter button causes the unique LonWorks ID number to be sent to the
network.
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205
Service:+358-40-8371 150E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Page 50
77
FF
AULAUL
7
F
AUL
77
FF
AULAUL
T CODET CODE
T CODE
T CODET CODE
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
The Multipurpose Application II has an extra fault code:
Fault numberFaultPossible causeChecking
VV
aconacon
V
acon
VV
aconacon
27Fieldbus
8 MONIT8 MONIT
8 MONIT
8 MONIT8 MONIT
communication error
ORING DAORING DA
ORING DA
ORING DAORING DA
TT
T
TT
AA
A
AA
Fieldbus board has detected the reset or
error of the Bus system (physical layer)
Reset the fault and restart
again. If the fault comes
again:
- check the host system
- check the cables
The Multipurpose Application II has extra items for monitoring (V1 - V24). See table 8-1
DataDataUnitDescription
numbername
V1Output frequencyHzFrequency to the motor
V2Motor speedrpmCalculated motor speed
V3Motor currentAMeasured motor current
V4Motor torque%Calculated actual torque/nominal torque of the unit
V5Motor power%Calculated actual power/nominal power of the unit
V6Motor voltageVCalculated motor voltage
V7DC-link voltageVMeasured DC-link voltage
V8Temperature°CTemperature of the heat sink
V9Operating day counterDD.ddOperating days 1), not resettable
V10Operating hours,HH.hhOperating hours 2), can be reset with
"trip counter" programmable button #3
V11MW-hoursMWhTotal MW-hours, not resettable
V12MW-hours,MWhMW-hours, can be reset with programmable
"trip counter"button #4
V13Voltage/analogue inputVVoltage of the terminal Uin+ (term. #2)
V14Current/analogue inputmACurrent of terminals Iin+ and Iin- (term. #4, #5)
V15Digital input status, gr. A
V16Digital input status, gr. B
V17Digital and relay output
status
V18Control programVersion number of the control software
V19Unit nominal powerkWShows the power size of the unit
V20Motor temperature rise %100%= temperature of motor has risen to nominal
V21Reference frequencyHzFrequency reference
V22Torque reference%Torque reference when torque control in use
V23Digital inputs (opt. board)
V24Fieldbus status
Used with Profibus option board onlyUsed with Profibus option board only
Used with Profibus option board only
Used with Profibus option board onlyUsed with Profibus option board only
0 = Master-Slave communication not started
1 = Master-Slave communication is starting up
2 = Master-Slave communication started and OK.
..
.
..
1)
DD = full days, dd = decimal part of a day
2)
HH = full hours, hh = decimal part of an hour
Table 8-1 Monitoring items
V acon PlcPhone:+358-(0)201 2121Fax: +358-(0)201 212 205