Danfoss VACON CX, VACON CXL, VACON CXS Application guide

VACON CX /CXL/CXS
FREQUENCY CONVERTERS
Multi-purpose Control
Application II
USER'S MANUAL
Subject to changes without notice
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
aconacon
V
acon Page 1
aconacon
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purposeMulti-purpose
Multi-purpose
Multi-purposeMulti-purpose Control Application IIControl Application II
Control Application II
Control Application IIControl Application II
(par. 0.1 = 0)
CONTENTSCONTENTS
CONTENTS
CONTENTSCONTENTS
1 General ................................................... 2
2 Control I/O............................................... 2
3 Control signal logic ................................. 3
4 Parameter Group 0 ................................. 4
5 Parameters Group 1 ............................... 5
5.1 Parameter table ............................ 5
5.2 Description of Group1 par. ............ 6
6 Special parameters, Groups 2-11......... 10
6.1 Parameter tables .........................
6.2 Description of Group 2 par..........
7 Fault code ............................................. 46
8 Monitoring data ..................................... 46
10 19
Software ID: smf089xx
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Page 2
11
1
11
GeneralGeneral
General
GeneralGeneral
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose II application is an extender version of the normal Multipurpose application. It has parameters for torque control and, furthermore, for Fieldbus communication. Following fieldbuses are supported: Interbus, Modbus, Profibus, LonWorks, CAN-bus (SDS, DeviceNet).
2 Control I/O2 Control I/O
2 Control I/O
2 Control I/O2 Control I/O
aconacon
V
acon
aconacon
Frequency reference, analogue and digital outputs have extra alternatives in their control parameters. Source of free analogue input can now be selected from the I/O Expander. These inputs have also parameters for signal area etc. programming.
Reference potentiometer
READY
RUN
220 VAC
FAULT
Terminal Signal Description
1 +10V 2Uin+ Analogue input, Frequency reference
3 GND I/O ground Ground for reference and controls 4Iin+ Analogue input, Default setting: not used
- current (programmable) range 0—20 mA
5I
in
6 +24V Control voltage output Voltage for switches, etc. max. 0.1 A 7 GND I/O ground Ground for reference and controls 8 DIA1 Start forward Contact closed = start forward
9 DIA2 Start reverse Contact closed = start reverse
10 DIA3 Fault reset Contact open = no action
11 CMA Common for DIA1—DIA3 Connect to GND or + 24V 12 +24V Control voltage output Voltage for switches, (same as #6) 13 GND I/O ground Ground for reference and controls 14 DIB4 Jogging speed select Contact open = no action
15 DIB5 External fault Contact open = no fault
16 DIB6 Accel./deceler. time select Contact open = par. 1.3, 1.4 in use
17 CMB Common for DIB4—DIB6 Connect to GND or + 24V 18 I
out
19 I
out
20 DO1 Digital output Programmable (par. 3
21 RO1 Relay output 1 Programmable (par. 3 22 RO1 RUN 23 RO1 24 RO2 Relay output 2 Programmable (par. 3 25 RO2 FAULT 26 RO2
Reference output Voltage for a potentiometer, etc.
ref
voltage (programmable) range 0—10 V DC
(programmable)
(Programmable)
(programmable) Contact closed = fault reset
(programmable) Contact closed = jogging speed
(programmable) Contact closed = fault
(programmable) Contact closed = par. 4.3, 4.4 in use
+ Output frequency Programmable (par. 3
- Analogue output Range 0—20 mA/RL max. 500
READY Open collector, I
..
. 1)
..
..
. 6)
..
<50 mA, U<48 VDC
..
. 7)
..
..
. 8)
..
Figure 2-1 Default I/O configuration and connection example of the
Multi-purpose Control Application.
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
aconacon
V
acon Page 3
aconacon
3 Control signal logic3 Control signal logic
3 Control signal logic
3 Control signal logic3 Control signal logic
Multi-purpose Control Application IIMulti-purpose Control Application II
In figure 3-1 the logic of I/O-control signals and push button signals from the panel are presented.
PARAMETERS
1. 5 Reference selection
1. 6 Jogging speed ref.
Uin+
Joystick control
Iin±
Joystick control
Uin + I Uin - I I
in
Uin x I
DIB5
Up
DIB6
Down
Jogging speed selection
DIB4
(programmable)
DIA1
Start FWD
DIA2
Start REV.
DIA3
Fault reset (programmable)
DIB5
External fault (programmable)
DIB6
Accel./deceler. time select (programmable)
Motorised potentio­meter reference
Programm. Start/Stop and Reverse signal logic
- U
PROGRAMMABLE PUSH-BUTTON 2
Internal
P
Multi-step speeds (If any of DI_ inputs are pro­grammed
for this in in
in
in
function)
P
P
>1
control line
=
signal line
=
frequency reference
Internal Start/Stop
Internal reverse
Internal fault reset
UD012K05
Figure 3-1 Control signal logic of the Multipurpose II Application.
Switch positions correspond to factory settings.
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Page 4
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
aconacon
V
acon
aconacon
44
4
44
Number Parameter Range Step Default Customer Description
0.1
0.2 Parameter loading 0-5 1 0
Parameter group 0Parameter group 0
Parameter group 0
Parameter group 0Parameter group 0
Application
selection
0-7 1 0
0 = Multipurpose II (loaded special
application) 1 = Basic Application 2 = Standard Application 3 = Local/Remote Control Application
4 = Multi-step Speed Application 5 = PI-control Application 6 = Multi-purpose Control Application 7 = Pump and Fan Control Application
0 = Loading ready / Select loading 1 = Load default setting 2 = Read up parameters to user's set 3 = Load down user's set parameters
4 = Read parameters up to the panel (possible only with graphical panel) 5 = Load down parameters from panel (possible only with graphical panel)
0 = English
0.3 Language selection 0-2 1 0
1 = Germany 2 = Finnish
Table 4-1 Parameter group 0.
0.10.1
0.1
0.10.1
Application selectionApplication selection
Application selection
Application selectionApplication selection
With this parameter the active application can be selected. If the device has been ordered from the factory equipped with Multipurpose II application this has been loaded to the unit as application 0. The application has also been set active at the factory. However, check that the value of the parameter 0.1 is zero when you want to use Multipurpose II.
If the application should be loaded to the device later it has to be set active always after loading by setting the value of parameter 0.1 to zero.
0.20.2
0.2
0.20.2
Parameter loadingParameter loading
Parameter loading
Parameter loadingParameter loading
See User's Manual chapter 11.
0.30.3
0.3
0.30.3
LanguageLanguage
Language
LanguageLanguage
With this parameter, the language of the graphical panel can be selected.
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
aconacon
V
acon Page 5
aconacon
55
Basic Parameters, Group 1Basic Parameters, Group 1
5
Basic Parameters, Group 1
55
Basic Parameters, Group 1Basic Parameters, Group 1
5.15.1
Parameter tableParameter table
5.1
Parameter table
5.15.1
Parameter tableParameter table
Multi-purpose Control Application IIMulti-purpose Control Application II
Code Parameter Range Step Default Custom Description Page
1.1 Minimum frequency 0120/500 Hz 1 Hz 0 Hz 6
1.2 Maximum frequency 0120/500 Hz 1 Hz 50 Hz *) 6
1.3 Acceleration time 1 0.13000 s 0.1 s 3 s Time from f
1.4 Deceleration time 1 0.13000 s 0.1 s 3 s Time from f
1.5 Reference selection 015 1 0 0 = U 1 = I
STOP
STOP
STOPSTOP
in
2 = Uin + I 6 = U
(1.1) to f
min
(1.2) to f
max
in
in
joystick control
in
(1.2) 6
max
(1.1) 6
min
3 = Uin – I 4 = Iin – U 5 = Uin * I
in
in
in
7 = Iin joystick control 8 = Signal from internal motor pot. 9 = Signal from internal motor pot.
6
reset if Vacon unit is stopped
10 = Signal from internal motor
pot. (stored in menory over
mains break 11= Min (Uin, Iin) 12 = Max (Uin, Iin) 13 = Panel reference r1 14 = Max reference 15 = Uin/Iin selection
Jogging speed
1.6 reference
1.7 Current limit 0.12.5 x I
f
– f
min
max
(1.1) (1.2)
0.1 Hz 5 Hz 7
nCX
0.1 A 1.5 x I
cCX
Output current limit [A] of the unit 7 0 = Linear
1.8 U/f ratio selection 0—210
STOP
STOP
STOPSTOP
1 = Squared
7
2 = Programmable U/f ratio
1.9 U/f optimisation 0—110
STOP
230 V
1.10
Nominal voltage of the motor
STOP
STOP
STOPSTOP
180690 1 V
400 V 500 V 690 V
Nominal frequency of
1.11
1.12
the motor
Nominal speed of the motor
STOP
STOP
STOPSTOP
30500 Hz 1 Hz 50 Hz fn on the rating plate of the motor
30020000 rpm 1 rpm 1440 rpm
STOP
STOP
STOPSTOP
0 = None 1 = Automatic torque boost Vacon range CX/CXL2 Vacon range CX/CXL/CXS4 Vacon range CX/CXL/CXS5 Vacon range CX6
n
on the rating plate of the motor
n
8
9
9
9
1.13
Nominal current of the motor
STOP
STOP
STOPSTOP
2.5 x I
nCX
0.1 A I
nCX
180250 230 V Vacon range CX/CXL2
1.14 Supply voltage
STOP
STOP
STOPSTOP
380440 400 V Vacon range CX/CXL/CXS4 380500 500 V Vacon range CX/CXL/CXS5 525690 690 V Vacon range CX6
1.15 Parameter conceal 0—110
1.16 Parameter value lock 0—110
Table 5-1. Group 1 basic parameters
..
*) If 1
. 2 >motor synchr. speed, check suitability for motor and drive system.
..
STOP
STOP
Note!Note!
Note!
Note!Note!
STOPSTOP
= Parameter value can be changed only when the frequency converter is stopped. (Continues)
In on the rating plate of the motor 9
0 = All parameter groups visible 1 = Only group 1 visible
0 = Parameter changes enabled 1 = parameter changes disabled
9
9
9
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Page 6
5.2 Description of Group 1 parameters 5.2 Description of Group 1 parameters
5.2 Description of Group 1 parameters
5.2 Description of Group 1 parameters 5.2 Description of Group 1 parameters
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
aconacon
V
acon
aconacon
1. 1, 1. 21. 1, 1. 2
1. 1, 1. 2
1. 1, 1. 21. 1, 1. 2
1. 3, 1. 41. 3, 1. 4
1. 3, 1. 4
1. 3, 1. 41. 3, 1. 4
1. 51. 5
1. 5
1. 51. 5
Minimum / maximum frequencyMinimum / maximum frequency
Minimum / maximum frequency
Minimum / maximum frequencyMinimum / maximum frequency
Defines frequency limits of the frequency converter. The default maximum value for parameters 1
..
. 1 and 1
..
120 Hz when the device is stopped (RUN indicator not lit) parameters 1
..
. 2 is 120 Hz. By setting 1
..
..
. 1 and 1
..
. .
. 2 =
. .
..
. 2
..
are changed to 500 Hz. At the same time the panel reference resolution is changed from 0.01 Hz to 0.1 Hz. Changing the max. value from 500 Hz to 120 Hz is done by setting the parameter
..
1
. 2 = 119 Hz when the device is stopped.
..
Acceleration time 1, deceleration time 1:Acceleration time 1, deceleration time 1:
Acceleration time 1, deceleration time 1:
Acceleration time 1, deceleration time 1:Acceleration time 1, deceleration time 1:
These limits correspond to the time required for the output frequency to accelerate from the set minimum frequency (par. 1 frequency (par. 1
Reference selectionReference selection
Reference selection
Reference selectionReference selection 00
0 Analogue voltage reference from terminals 23, e.g. a potentiometer
00 11
1 Analogue current reference trom terminals 45, e.g. a transducer.
11 22
2 Reference is formed by adding the values of the analogue inputs
22 33
3 Reference is formed by subtracting the voltage input (U
33
. .
. 2).
. .
..
. 1) to the set maximum
..
) value
in
from the current input (Iin) value.
44
4 Reference is formed by subtracting the current input (Iin ) value from the
44
voltage input (Uin) value.
55
5 Reference is the formed by multiplying the values of the analogue inputs
55 66
6 Joystick control from the voltage input (Uin).
66
Signal range
010 V 0 V 5 V +10 V
Custom Par. 2.7 x 10 V
-10 V+ 10 V -10 V 0 V +10 V
WW
arning!arning!
W
arning! Use only -10V+10 V signal range. If a custom or 010 V signal
WW
arning!arning!
Max reverse
speed
Direction change
In the middle of
custom range
Max forward
speed
Par. 2.8 x 10 V
range is used, the drive starts to run at the max. reverse speed if the
!
77
7 Joystick control from the current input (I
77
Signal range Max reverse Direction change Max forward
WW
arning!arning!
W
arning! Use only 420 mA signal range. If custom or 020 mA signal range
WW
arning!arning!
reference signal is lost.
).
in
speed speed
020 mA 0 mA 10 mA 20 mA
Custom Par. 2
420 mA 4 mA 12 mA 20 mA
..
. 13 x 20 mA In the middle of Par. 2
..
custom range
..
. 14 x 20 mA
..
is used, the drive runs at max. reverse speed if the control signal is lost.
!
Set the reference fault (par. 7 is used, then the drive will stop to the reference fault if the reference
. .
. 2) active when the 420 mA range
. .
signal is lost.
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
aconacon
V
acon Page 7
aconacon
Note!Note!
Note! When joystick control is used, the direction control is generated from joystick
Note!Note!
Multi-purpose Control Application IIMulti-purpose Control Application II
reference signal. See figure 5.4-1. Analogue input scaling, parameters 2
..
. 162
..
. .
. 19 are not used when joystick
. .
control is used.
Fout
Fmax (par 1.2)
Fmin.
-10V
If minimum frequency (par 1 hysteresis is ± 2% at reversing point. there is no hysteresis at reversing point.
(par 1.1)
Fmin. (par 1.1)
hystereesi +/-2% (+/-0,2 V)
Fmax (par 1.2)
..
. 1) >0, If minimum frequency (par 1
..
Uin
+10V
-10V
Fmax (par 1.2)
Fout
Fmax (par 1.2)
+10V
..
. 1) = 0,
..
Uin
Uin
Fig. 5-1 Joystick control Uin signal -10 V—+10 V.
88
8 Reference value is changed with digital input signals DIB5 and DIB6.
88
- switch in DIB5 closed = frequency reference increases
- switch in DIB6 closed = frequency reference decreases Speed of reference change can be set with the parameter 2
99
9 Same as setting 8 but the reference value is set to the minimum frequency
99
(par. 1
1010
10 Same as setting 8 but the reference is stored to the memory over mains break.
1010
When the value of the parameter 1 parameters 2
11
11
1
1 The minor of signals Uin and Iin is the frequency reference
11
11
1212
12 The greater of signals Uin and Iin is the frequency reference
1212 1313
13 Panel reference r1 is the frequency reference
1313 1414
14 Maximum reference selection (recommended only at torque control)
1414 1515
15 Uin/Iin digital selection (see par. 2.3)
1515
..
. 1) each time the frequency converter is stopped.
..
..
. 5 is set to 8, 9 or 10, the values of the
..
..
. 4 and 2
..
. .
. 5 are automatically set to 11.
. .
..
. 20.
..
1. 61. 6
1. 6
1. 61. 6
Jogging speed referenceJogging speed reference
Jogging speed reference
Jogging speed referenceJogging speed reference
Parameter value defines the jogging speed selected with the digital input
1. 71. 7
1. 7
1. 71. 7
Current limitCurrent limit
Current limit
Current limitCurrent limit
This parameter determines the maximum motor current from the freqeuency converter. To avoid motor overload, set this parameter according to the rated current of the motor.
1. 81. 8
1. 8
1. 81. 8
U/f ratio selectionU/f ratio selection
U/f ratio selection
U/f ratio selectionU/f ratio selection
Linear: The voltage of the motor changes linearly with the frequency in the
00
0 constant flux area from 0 Hz to the field weakening point (par. 6
00
where the nominal voltage is also supplied to the motor. See figure 5-2. Linear U/f ratio should be used in constant torque applications.
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
..
. 3)
..
Page 8
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
This default setting should be used if there is no special needThis default setting should be used if there is no special need
This default setting should be used if there is no special need
This default setting should be used if there is no special needThis default setting should be used if there is no special need
for another setting.for another setting.
for another setting.
for another setting.for another setting.
aconacon
V
acon
aconacon
Squared: The voltage of the motor changes following a squared curve form
11
1 with the frequency in the area from 0 Hz to the field weakening
11
point (par. 6
..
. 3) where the nominal voltage is also supplied to
..
the motor. See figure 5-2. The motor runs undermagnetised below the field weakening point and produces less torque and electromechanical noise. Squared U/f ratio can be used in applications where torque demand of the load is proportional to the square of the speed, e.g. in centrifugal fans and pumps.
U[V]
Un (Par 6. 4)
Default: Nominal voltage of the motor
Linear
Field weakening point
Squared
Default: Nominal frequency of the motor
(Par. 6. 3)
f[Hz]
UD012K07
Figure 5-2 Linear and squared U/f curves.
Programm. The U/f curve can be programmed with three different points. U/f curve The parameters for programming are explained in chapter 5.2.
22
2 Programmable U/f curve can be used if the other settings do not
22
satisfy the needs of the application. See figure 5-3.
U[V]
Un
Par 6. 4
Par. 6. 6 (Def. 10%)
Par. 6. 7 (Def. 1.3%)
Default: Nominal voltage of the motor
Par. 6. 5 (Def. 5 Hz)
Field weakening point
Default: Nominal frequency of the motor
Par. 6. 3
f[Hz]
UD012K08
Figure 5-3 Programmable U/f curve.
1.9 U/f optimisation1.9 U/f optimisation
1.9 U/f optimisation
1.9 U/f optimisation1.9 U/f optimisation
Automatic The voltage to the motor changes automatically which makes the torque motor produce sufficient torque to start and run at low frequencies. The boost voltage increase depends on the motor type and power.
Automatic torque boost can be used in applications where starting torque due to starting friction is high, e.g. in conveyors.
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
aconacon
V
acon Page 9
aconacon
Multi-purpose Control Application IIMulti-purpose Control Application II
NOTE! In high torque - low speed applications - it is likely the motor will
overheat.
!
If the motor has to run a prolonged time under these
conditions,
special attention must be paid to cooling the motor. Use external
cooling for the motor if the temperature tends to rise too high.
1. 101. 10
1. 10
1. 101. 10
1. 11. 1
1. 1
1. 11. 1
1. 121. 12
1. 12
1. 121. 12
1. 131. 13
1. 13
1. 131. 13
1. 141. 14
1. 14
1. 141. 14
1. 151. 15
1. 15
1. 151. 15
Nominal voltage of the motorNominal voltage of the motor
Nominal voltage of the motor
Nominal voltage of the motorNominal voltage of the motor
Find this value Un on the rating plate of the motor. This parameter sets the voltage at the field weakening point, parameter 6 100% x U
11
1
11
Nominal frequency of the motorNominal frequency of the motor
Nominal frequency of the motor
Nominal frequency of the motorNominal frequency of the motor
Find this value fn on the rating plate of the motor. This parameter sets the field weakening point, parameter 6. 3, to the same value.
Nominal speed of the motorNominal speed of the motor
Nominal speed of the motor
Nominal speed of the motorNominal speed of the motor
Find this value nn on the rating plate of the motor.
Nominal current of the motorNominal current of the motor
Nominal current of the motor
Nominal current of the motorNominal current of the motor
Find this value In on the rating plate of the motor.
Supply voltageSupply voltage
Supply voltage
Supply voltageSupply voltage
Set parameter value according to the nominal voltage of the supply. Values are predefined for CX/CXL2, CX/CXL/CXS4, CX/CXL/CXS5 and CX6 ranges, see table 5-1.
Parameter concealParameter conceal
Parameter conceal
Parameter concealParameter conceal
Defines which parameter groups are available for editing:
0 = all parameter groups are visible 1 = only group 1 is visible
nmotor
.
. .
. 4, to
. .
1. 161. 16
1. 16
1. 161. 16
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Parameter value lockParameter value lock
Parameter value lock
Parameter value lockParameter value lock
Defines access to the changes of the parameter values:
0 = parameter value changes enabled 1 = parameter value changes disabled
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Page 10
66
Special Parameters, Groups 2—10Special Parameters, Groups 2—10
6
Special Parameters, Groups 2—10
66
Special Parameters, Groups 2—10Special Parameters, Groups 2—10
6.16.1
Parameter tablesParameter tables
6.1
Parameter tables
6.16.1
Parameter tablesParameter tables
Group 2, Input signal parametersGroup 2, Input signal parameters
Group 2, Input signal parameters
Group 2, Input signal parametersGroup 2, Input signal parameters
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
aconacon
V
acon
aconacon
Code Parameter Range Step Default Description Page
DIA1 DIA2
2.1
Start/Stop logic selection
STOP
STOP
STOPSTOP
041 0
0 = Start forw. 1 = Start/Stop 2 = Start/Stop 3 = Start pulse 4 = Start/stop pulse
Start reverse Reverse Run enable Stop pulse
Run enable 0 = Not used 1 = External fault, closing contact 2 = External fault, opening contact 3 = Run enable
STOP
STOP
2.2
DIA3 function (terminal 10)
STOPSTOP
012 1 7
4 = Accel./decel. time selection 5 = Reverse 6 = Jogging speed 7 = Fault reset 8 = Accel./decel. operation prohibit 9 = DC-braking command 10 = Torque control 11 = Torque reference sign 12 = Run enable with coasting 0 = Not used 1 = External fault, closing contact 2 = External fault, opening contact 3 = Run enable
STOP
STOP
STOPSTOP
4 = Accel./decel. time selection 5 = Reverse 6 = Jogging speed
2.3
DIB4 function (terminal 14)
015 1 6
7 = Fault reset 8 = Accel./decel. operation prohibit 9 = DC-braking command 10 = Multi-step speed select 1 11 = Selection between I
and U
in
in
12 = Run enable with coasting 13 = Fieldbus control 14 = Par. 1.5 / U 15 = Par. 1.5 / I
in
in
0 = Not used 1 = External fault, closing contact 2 = External fault, opening contact 3 = Run enable 4 = Accel./decel. time selection 5 = Reverse 6 = Jogging speed 7 = Fault reset
2.4
DIB5 function (terminal 15)
STOP
STOP
STOPSTOP
013 1 1
8 = Accel./decel. operation prohibit 9 = DC-braking command 10 = Multi-step speed select 2 11 = Motorised pot. speed up 12 = Run enable with coasting 13 = Fieldbus control 0 = Not used 1 = External fault, closing contact 2 = External fault, opening contact 3 = Run enable 4 = Accel./decel. time selection 5 = Reverse 6 = Jogging speed 7 = Fault reset
2.5
DIB6 function (terminal 16)
STOP
STOP
STOPSTOP
013 1 4
8 = Accel./decel. operation prohibit 9 = DC-braking command 10 = Multi-step speed select 3 11 = Motorised pot. speed down 12 = Run enable with coasting 13 = Fieldbus control
19
20
22
22
22
STOP
STOP
Note!Note!
Note!
Note!Note!
STOPSTOP
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
= Parameter value can be changed only when the frequency converter is stopped.
Service: +358-40-8371 150 E-mail: vacon@vacon.com
(Continues)
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
aconacon
V
acon Page 11
aconacon
Multi-purpose Control Application IIMulti-purpose Control Application II
Code Parameter Range Step Default Custom Description Page
2. 6 U
signal range 0—2 1 0 0 = 010 V
in
1 = Custom setting range 2 = -10+10 V (can be used with
Joystick control only)
. .
2
. 7U
. . . .
2
. 8U
. . . .
2
. 9U
. .
custom setting min. 0—100% 0.01% 0.00% 22
in
custom setting max. 0—100% 0.01% 100.00% 22
in
signal inversion
in
0—1
1 0 0 = Not inverted 22
1 = Inverted
..
2
. 10 U
.. ..
2
. 11 I
..
signal filter time
in
signal range 0210 0 = 0—20 mA 23
in
0 —10s
0.01s 0.1s 0 = No filtering 22
1 = 420 mA 2 = Custom setting range
..
2
. 12 I
.. ..
2
. 13 I
.. ..
2
. 14 I
..
custom setting minim. 0—100% 0.01% 0.00% 23
in
custom setting maxim. 0—100% 0.01% 100.00% 23
in
signal inversion
in
0—1
1 0 0 = Not inverted 23
1 = Inverted
. .
2
. 15 I
. . ..
2
. 16 U
..
signal filter time
in
minimum scaling -320,00% 0% 0,01 0% = no minimum scaling 23
in
0 —10s
0.01s 0.1s 0 = No filtering 23
+320,00 %
..
2
. 17 U
..
maximum scaling -320,00% 100% 0,01 100% = no maximum scaling 23
in
+320,00 %
..
2
. 18 I
..
minimum scaling -320,00% 0% 0,01 0% = no minimum scaling 23
in
+320,00 %
..
2
. 19 I
..
maximum scaling -320,00% 100% 0,01 100% = no maximum scaling 23
in
+320,00 %
. .
2
. 20 Free analogue input, 05 1 0 0 = Not use 24
. .
signal selection 1 = U
(analogue voltage input)
in
2 = Iin (analogue current input) 3 = Ain1 (option board) 4 = Ain2 (option board) 5 = Fieldbus signal
..
2
. 21 Free analogue input, 04 1 0 0 = No function 24
..
function 1 = Reduces current limit
(par. 1
..
.7)
..
2 = Reduces DC-braking current 3 = Reduces acc. and decel. times 4 = Reduces torque supervis. limit
..
2
. 22 Motorised potentiometer 0.12000.0 0.1 10.0 25
..
ramp time Hz/s Hz/s Hz/s
. .
2
. 23 Option board Ain1 signal 01 1 0 0 = Not inverted 25
. .
inversion 1 = Inverted
..
2
. 24 Option board Ain1 signal 010s 0.01s 0.1s 0 = No filtering 25
..
filter time
..
2
. 25 Option board Ain2 signal 0210 0 = 020 mA 25
..
signal range 1 = 420 mA
2 = 010 V
..
2
. 26 Option board Ain2 signal 01 1 0 0 = Not inverted 25
..
inversion 1 = Inverted
. .
2
. 27 Option board Ain2 signal 0 10s 0.01s 0.1s 0 = No filtering 25
. .
filter time
STOP
STOP
Note! Note!
Note!
Note! Note!
STOPSTOP
= Parameter value can be changed only when the frequency converter is stopped. (Continues)
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Page 12
Code Parameter Range Step Default Custom Description Page
2.28 Adjust Input 0 - 5 1 0 0 = Not used
2.29 Adjust Percentage 0.0% - 200.0% 0.1% 0.0%
2.30 Adjust Offset 0.0% - 100.0% 0.1% 0.0%
STOP
STOP
Note!Note!
Note!
Note!Note!
STOPSTOP
= Parameter value can be changed only when the frequency converter is stopped.
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
1 = Voltage input 2 = Current input 3 = AIN1 I/O-expand 4 = AIN2 I/O-expand 5 = FB signal
aconacon
V
acon
aconacon
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
aconacon
V
acon Page 13
aconacon
Group 3, Output and supervision parametersGroup 3, Output and supervision parameters
Group 3, Output and supervision parameters
Group 3, Output and supervision parametersGroup 3, Output and supervision parameters
Code Parameter Range Step Default C
Multi-purpose Control Application IIMulti-purpose Control Application II
Description Page u s t o m
Analogue output func-
3.1 tion
014 1 1
0 = Not used 1 = O/P frequency 2 = Motor speed 3 = O/P current 4 = Motor torque 5 = Motor power 6 = Motor voltage 7 = DC-link volt. 8 = Input signal U 9 = Input signal I 10 = Refer. freq.
Scale 100% (0—f (0max. speed (02.0 x I (02 x T (02 x P (0100% x U (01000 V)
in
in
max
)
)
nCX
)
nCX
)
nCX
nM
11 = Refer. torque
nMOT nMOT
)
) )
Analogue output filter
3.2 time
Analogue output inver-
3.3 sion
Analogue output mini-
3.4 mum
12 = Motor±torque 13 = Motor±power 14 = O/P freq.
(-2--+2xT (-2--+2xT (f
min—fmax
0.0110 s 0.01 1.00 26
011 0
011 0
0 = Not inverted 1 = Inverted 0 = 0 mA 1 = 4 mA
3.5 Analogue output scale 10—1000% 1% 100% 26
0 = Not used 1 = Ready 2 = Run 3 = Fault 4 = Fault inverted 5 = Vacon overheat warning 6 = External fault or warning 7 = Reference fault or warning 8 = Warning 9 = Reversed 10 = Jogging speed selected
3.6 Digital output function 0—22 1 1
STOP
STOP
STOPSTO P
11 = At speed 12 = Motor regulator activated 13 = Output frequency limit superv. 1 14 = Output frequency limit superv. 2 15 = Torque limit supervision 16 = Reference limit supervision 17 = External brake control 18 = Control from I/O terminals 19 = Frequency converter temperature
limit supervision 20 = Unrequested rotation direction 21 = External brake control inverted 22 = Termistor fault or warning
3.7 Relay output 1 function 022 1 2 As parameter 3.6
STOP
STOP
STOPSTO P
3.8 Relay output 2 function 022 1 3 As parameter 3.6
STOP
STOP
STOPSTO P
3.9
3.10
3.11
3.12
Output frequency limit 1 supervision function
Output frequency limit 1 supervision value
Output frequency limit 2 supervision function
Output frequency limit 2 supervision value
021 0
0f
max
(par. 1.2) 0.1 Hz 0 Hz 27
021 0
0f
max
(par. 1.2)
0.1 Hz 0 Hz 27
0 = No 1 = Low limit 2 = High limit
0 = No 1 = Low limit 2 = High limit
)
26
26
26
27
27
27
27
27
STOP
STOP
Note!Note!
Note!
Note!Note!
STOPSTOP
= Parameter value can be changed only when the frequency converter is stopped. (Continues)
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Page 14
Code Parameter Range Step Default Custom Description Page
..
3
. 13 Torque limit 02 1 0 0 = No 28
..
supervision function 1 = Low limit
..
3
. 14 Torque limit 0200% 1% 100% 28
..
supervision value xT
..
3
. 15 Reference limit 02 1 0 0 = No 28
..
supervision function 1 = Low limit
..
3
. 16 Reference limit 0f
..
supervision value (par. 1
..
3
. 17 Extern. brake Off-delay 0100.0 s 0.1 s 0.5 s 28
.. ..
3
. 18 Extern. brake On-delay 0100.0 s 0.1 s 1.5 s 28
.. ..
3
. 19 Frequency converter 02 1 0 0 = No 28
..
temperature limit 1 = Low limit supervision function 2 = High limit
..
3
. 20 Frequency converter -10+75°C1°C +40°C28
..
temperature limit value
..
3
. 21 I/O-expander board (opt.) 014 1 3 See parameter 3
..
analogue output content
..
3
. 22 I/O-expander board (opt.) 0.0110 s 0.01 1.00 See parameter 3
..
analogue output filter time
..
3
. 23 I/O-expander board (opt.) 01 1 0 See parameter 3
..
analogue output inversion
..
3
. 24 I/O-expander board (opt.) 01 1 0 See parameter 3
..
analogue output minimum
..
3
. 25 I/O-expander board (opt.) 101000% 1 100% See parameter 3
..
analogue output scale
3. 26 Analog output offset -100 1 100% 29 (basic control board) 100,0%
3. 27 I/O-expander board (opt.) -100 1 100% 29 analogue output offset +100,0%
..
3
. 28 Digital output DO1 0320,00s 0,01 0,00 0,00 = delay not in use 29
..
on delay
..
3
. 29 Digital output DO1 0320,00s 0,01 0,00 0,00 = delay not in use 29
..
off delay
..
3
. 30 Relay output RO1 0320,00s 0,01 0,00 0,00 = delay not in use 29
..
on delay
..
3
. 31 Relay output RO1 0320,00s 0,01 0,00 0,00 = delay not in use 29
..
off delay
..
3
. 32 Relay output RO1 0320,00s 0,01 0,00 0,00 = delay not in use 29
..
on delay
3.33 Relay output RO2 0320,00s 0,01 0,00 0,00 = delay not in use 29 off delay
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
2 = High limit
nCX
2 = High limit
0.1 Hz 0 Hz 28
max
..
. 2)
..
..
. 1
..
..
. 2
..
..
. 3
..
..
. 4
..
..
. 5
..
aconacon
V
acon
aconacon
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
aconacon
V
acon Page 15
aconacon
Group 4, Drive control parametersGroup 4, Drive control parameters
Group 4, Drive control parameters
Group 4, Drive control parametersGroup 4, Drive control parameters
Multi-purpose Control Application IIMulti-purpose Control Application II
Code Parameter Range Step Default Custom Description Page
. .
4
. 1 Acc./Dec. ramp 1 shape 010 s 0.1 s 0 0 = Linear 30
. .
>0 = S-curve acc./dec. time
. .
4
. 2 Acc./Dec. ramp 2 shape 010 s 0.1 s 0 0 = Linear 30
. .
>0 = S-curve acc./dec. time
. .
4
. 3 Acceleration time 2 0.13000 s 0.1 s 10 s 31
. . . .
4
. 4 Deceleration time 2 0.13000 s 0.1 s 10 s 31
. . ..
4
. 5 Brake chopper 01 1 0 0 = Brake chopper not in use 31
..
STOP
STOP
STOPSTOP
1 = Brake chopper in use 2 = External brake chopper
..
4
. 6 Start function 01 1 0 0 = Ramp 31
..
1 = Flying start
. .
4
. 7 Stop function 01 1 0 0 = Coasting 31
. .
1 = Ramp
. .
4
. 8 DC-braking current 0.151.5 0.1 A 0.5 x I
. .
x I
(A)
nCX
. .
4
. 9 DC-braking time at Stop 0250.0 s 0.1 s 0 s 0 = DC-brake is off at Stop 32
. . . .
4
. 10 Execute freq. of DC- 0.110 Hz 0.1 Hz 1.5 Hz 33
. .
nCX
brake during ramp Stop
. .
4
. 11 DC-brake time at Start 0.025.0 s 0.1 s 0 s 0 = DC-brake is off at Start 33
. . ..
4
. 12 Multi-step speed f
..
reference 1 (1
..
4
. 13 Multi-step speed f
..
reference 2 (1
..
4
. 14 Multi-step speed f
..
reference 3 (1
..
4
. 15 Multi-step speed f
..
reference 4 (1
..
4
. 16 Multi-step speed f
..
reference 5 (1
..
4
. 17 Multi-step speed f
..
reference 6 (1
..
4
. 18 Multi-step speed f
..
reference 7 (1
f
min
..
. 1) (1
..
f
min
..
. 1) (1
..
f
min
..
. 1) (1
..
f
min
..
. 1) (1
..
f
min
..
. 1) (1
..
f
min
..
. 1) (1
..
f
min
..
. 1) (1
..
0.1 Hz 10 Hz 33
max
..
. 2)
..
0.1 Hz 15 Hz 33
max
..
. 2)
..
0.1 Hz 20 Hz 33
max
..
. 2)
..
0.1 Hz 25 Hz 33
max
..
. 2)
..
0.1 Hz 30 Hz 33
max
..
. 2)
..
0.1 Hz 40 Hz 33
max
..
. 2)
..
0.1 Hz 50 Hz 33
max
..
. 2)
..
31
STOP
STOP
Note!Note!
Note! = Parameter value can be changed only when the frequency converter is stopped.
Note!Note!
STOPSTOP
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Page 16
Group 5, Prohibit frequency parameters Group 5, Prohibit frequency parameters
Group 5, Prohibit frequency parameters
Group 5, Prohibit frequency parameters Group 5, Prohibit frequency parameters
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
aconacon
V
acon
aconacon
Code Parameter Range Step Default Custom Description Page
. .
5
. 1 Prohibit frequency 0f
. .
range 1 low limit (1
..
5
. 2 Prohibit frequency 0f
..
range 1 high limit (1
. .
5
. 3 Prohibit frequency 0f
. .
range 2 low limit (1
..
5
. 4 Prohibit frequency 0f
..
range 2 high limit (1
. .
5
. 5 Prohibit frequency 0f
. .
range 3 low limit (1
..
5
. 6 Prohibit frequency 0f
..
range 3 high limit (1
Group 6, Motor control parameters Group 6, Motor control parameters
Group 6, Motor control parameters
Group 6, Motor control parameters Group 6, Motor control parameters
max
..
. 2)
..
max
..
. 2)
..
max
..
. 2)
..
max
..
. 2)
..
max
..
. 2)
..
max
..
. 2)
..
0.1 Hz 0 Hz 33
0.1 Hz 0 Hz 0 = Prohibit range 1 is off 33
0.1 Hz 0 Hz 33
0.1 Hz 0 Hz 0 = Prohibit range 2 is off 33
0.1 Hz 0 Hz 33
0.1 Hz 0 Hz 0 = Prohibit range 3 is off 33
Code Parameter Range Step Default Custom Description Page
. .
6
. 1 Motor control mode 02 1 0 0 = Frequency control 33
. .
STOP
STOP
STOPSTOP
. .
6
. 2 Switching frequency 116 kHz 0.1 kHz 10/3.6 kHz Dependant on kW 34
. . . .
6
. 3 Field weakening point 30500 Hz 1 Hz Param. 34
. .
..
6
. 4 Voltage at field 15 200% 1% 100% 34
..
weakening point x U
. .
6
. 5 U/F-curve mid 0500 Hz 0,1 Hz 0 Hz 34
. .
point frequency
. .
6
. 6 U/F-curve mid 0100% 0.01% 0 % 34
. .
point voltage x U
. .
6
. 7 Output voltage at 0100% 0.01% 0 % 34
. .
zero frequency x U
. .
6
. 8 Overvoltage controller 01 1 1 0 = Controller is not operating 35
. .
..
6
. 9 Undervoltage controller 01 1 1 0 = Controller is not operating 35
..
STOP
STOP
STOPSTOP
STOP
STOP
STOPSTOP
STOP
STOP
STOPSTOP
STOP
STOP
STOPSTOP
STOP
STOP
STOPSTOP
STOP
STOP
STOPSTOP
nmot
nmot
nmot
..
1
. 11
..
1 = Speed control (open loop) 2 = Torque control (open loop)
1 = Controller is operating
1 = Controller is operating
STOP
STOP
STOPSTOP
= Parameter value can be changed only when the frequency converter is stopped.
Note!Note!
Note!
Note!Note!
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
aconacon
V
acon Page 17
aconacon
Group 7, Protections Group 7, Protections
Group 7, Protections
Group 7, Protections Group 7, Protections
Code Parameter Range Step Default Custom Description Page
. .
7
. 1 Response to 03 1 0 0 = No action 35
. .
reference fault 1 = Warning
. .
7
. 2 Response to 03 1 2 0 = No action 35
. .
external fault 1 = Warning
. .
7
. 3 Phase supervision of 02 1 2 0 = No action 35
. .
the motor 1 = Warning
. .
7
. 4 Earth fault protection 02 1 2 0 = No action 35
. .
. .
7
. 5 Motor thermal protection 02 1 2 0 = No action 36
. .
..
Motor thermal
7
. 6
..
break point current x I
..
7
. 7
Motor thermal
..
zero frequency current x I
..
7
. 8
Motor thermal
..
time constant minutes min. to motor nominal current
..
7
. 9
Motor thermal
..
break point frequency
..
7
. 10 Stall protection 02 1 1 0 = No action 38
..
..
7
. 11 Stall current limit 10.0200% 1.0% 130.0% 39
..
..
7
. 12 Stall time 2.0120 s 1.0 s 15.0 s 39
.. ..
7
. 13 Maximum stall frequency 1f
.. ..
7
. 14 Underload protection 02 1 0 0 = No action 40
..
..
7
. 15 Underload prot., field 20.0150 % 1.0% 50.0% 40
..
weakening area load x T
..
7
. 16 Underload protection, 10.0150.0% 1.0% 10.0% 40
..
zero frequency load x T
..
7
. 17 Underload time 2.0600.0 s 1.0 s 20.0s 40
.. . .
7
. 18 Phase supervision of 02 1 2 0 = No action 41
. .
the supply voltage 1 = Warning
. .
7
. 19 Termistor input of 02 1 2 0 = No action 41
. .
I/O-Expander 1 = Warning
7.20 Response to fieldbus 0—2 1 0 0 = Not used 41 fault 1 = Warning
protection 50.0150 % 1.0 % 100.0% 36
protection 10.0150% 1.0 % 45.0% 37
protection 0.5300.0 0,5 Default value is set according 37
protection 10500 Hz 1 Hz 35 Hz 38
Multi-purpose Control Application IIMulti-purpose Control Application II
2 = Fault, stop according to par 4.7 3 = Fault, stop always by coasting
2 = Fault, stop according to par 4.7 3 = Fault, stop always by coasting
2 = Fault
1 = Warning 2 = Fault
1 = Warning 2 = Fault
nMOTOR
nMOTOR
1 = Warning 2 = Fault
x I
nMOTOR
max
nMOTOR
nMOTOR
1 Hz 25 Hz 39
1 = Warning 2 = Fault
2 = Fault
2 = Fault
2 = Fault
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Page 18
Group 8, Autorestart parametersGroup 8, Autorestart parameters
Group 8, Autorestart parameters
Group 8, Autorestart parametersGroup 8, Autorestart parameters
Code Parameter Range Step Default Custom Description Page
..
8
. 1 Automatic restart: 010 1 0 0 = not in use 41
..
number of tries
. .
8
. 2 Automatic restart: 16000 s 1 s 30 s 41
. .
trial time
..
8
. 3 Automatic restart: 01 1 0 0 = Ramp 42
..
start function 1 = Flying start
..
8
. 4 Automatic restart of 01 1 0 0 = No 42
..
undervoltage 1 = Yes
..
8
. 5 Automatic restart of 01 1 0 0 = No 42
..
overvoltage 1 = Yes
..
8
. 6 Automatic restart of 01 1 0 0 = No 42
..
overcurrent 1 = Yes
. .
8
. 7 Automatic restart of 01 1 0 0 = No 42
. .
reference fault 1 = Yes
..
8
. 8 Automatic restart after 01 1 0 0 = No 42
..
over/undertemperature 1 = Yes fault
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
2 = Fault
aconacon
V
acon
aconacon
Group 9, TGroup 9, T
Group 9, T
Group 9, TGroup 9, T
Code Parameter Range Step Default Custom Description Page
Torque reference
9.1 selection
Torque reference
9.2 scaling bias
Torque reference
9.3 scaling gain
9.4 TC time constant 11000 ms 1 ms 15 ms 43 TC minimum control
9.5 limit
orque Controlorque Control
orque Control
orque Controlorque Control
100%--
320%--
010.00 Hz
0610
+100%
+320%
1 0 0 = Not in use 43
1 100 100 = No scaling 43
0.01
3.00 Hz 43
Hz
0 = None 1 = U
in
2 = I
in
3 = Panel Trq reference r2 4 = Ain1 (option board) 5 = Ain2 (option board) 6 = Fieldbus control
43
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
aconacon
V
acon Page 19
aconacon
Group 10, Fieldbus parametersGroup 10, Fieldbus parameters
Group 10, Fieldbus parameters
Group 10, Fieldbus parametersGroup 10, Fieldbus parameters
Code Parameter Range Step Default Custom Description Page
..
10
. 1 Fieldbus control select 01 1 0 0 = Control via I/O terminals 44
..
. .
10
. 2 DIC1 function 01 0 1 0 = Fieldbus control 44
. .
(term. 301, fieldbus board) 1 = External fault
..
10
. 3 MODBUS Slave address 1247 1 1 44
.. ..
10
. 4 Baud rate 17 1 6 1 = 300 baud 44
..
..
10
. 5 MB Parity type 02 1 0 0 = None 44
..
..
10
. 6 Modbus time-out 03600 s 1 s 0 s 0 = No time-out 44
..
10.7 Profibus slave address 2—126 1 126 44
10.8 Profibus baud rate 110 1 10 1 = 9.6 kbaud 45
10.9 Profibus PPO Type 14 1 1 1 = PPO 1 45
10.10 Profibus Process Data 1 0—99 1 1 45
10.11. Profibus Process Data 2 0—99 1 2 45
10.12 Profibus Process Data 3 0—99 1 3 45
10.13 Profibus Process Data 4 0—99 1 99 45
10.14 LonWorks Service Button 0110 45
Multi-purpose Control Application IIMulti-purpose Control Application II
1 = Control via Fieldbus board
2 = 600 baud 3 = 1200 baud 4 = 2400 baud 5 = 4800 baud 6 = 9600 baud 7 = 19200 baud
1 = Even 2 = Odd
2 = 19.2 kbaud 3 = 93.75 kbaud 4 = 187.5 kbaud 5 = 500 kbaud 6 = 1.5 Mbaud 7 = 3 Mbaud 8 = 6 Mbaud 9 = 12 Mbaud 10 = AUTO
2 = PPO 2 3 = PPO 3 4 = PPO 4
Table 6-1. Special parameters, Groups 2-10
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Page 20
6.2 Description of Groups 210 parameters6.2 Description of Groups 210 parameters
6.2 Description of Groups 210 parameters
6.2 Description of Groups 210 parameters6.2 Description of Groups 210 parameters
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
aconacon
V
acon
aconacon
2. 12. 1
2. 1
2. 12. 1
Start/Stop logic selectionStart/Stop logic selection
Start/Stop logic selection
Start/Stop logic selectionStart/Stop logic selection 0:0:
0: DIA1: closed contact = start forward
0:0:
DIA2: closed contact = start reverse, See figure 6-1.
Output
FWD
frequency
REV
DIA1
DIA2
Figure 6-1 Start forward/Start reverse.
Stop function (par 4. 7) = coasting
1 2 3
UD009K09
t
1 The first selected direction has the highest priority 2 When DIA1 contact opens, the direction of rotation starts to change 3 If Start forward (DIA1) and Start reverse (DIA2) signals are active
simultaneously, the Start forward signal (DIA1) has priority.
1:1:
1: DIA1: closed contact = start open contact = stop
1:1:
DIA2: closed contact = reverse open contact = forward See figure 6-2.
Output
FWD
frequency
REV
DIA1
DIA2
Figure 6-2 Start, Stop,reverse.
Stop function (par 4. 7 = coasting
t
UD012K10
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
aconacon
V
acon Page 21
aconacon
2:2:
2: DIA1: closed contact = start open contact = stop
2:2:
Multi-purpose Control Application IIMulti-purpose Control Application II
DIA2: closed contact = start enabled open contact = start disabled
3:3:
3: 3-wire connection (pulse control):
3:3:
DIA1: closed contact = start pulse DIA2: closed contact = stop pulse (DIA3 can be programmed for reverse command) See figure 6-3
Output
FWD
REV
DIA1 Start
DIA2 Stop
frequency
min 50 ms
Stop function (par 4. 7) = coasting
If Start and Stop pulses are simultaneous the Stop pulse overrides the Start pulse
t
UD009K11
Figure 6.3 Start pulse / Stop pulse
4:4:
4: DIA1: closed contact = start/stop pulse
4:4:
DIA2: closed contact = start enabled
Output
FWD
frequency
REV
DIA1 Start
DIA2 Stop
Run Enable
Figure 6-4. Start / Stop pulse, Run enable.
min. 50 ms
t
UD009K12
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Page 22
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
aconacon
V
acon
aconacon
2.22.2
2.2
2.22.2
DIA3 functionDIA3 function
DIA3 function
DIA3 functionDIA3 function 1:1:
1: External fault, closing contact =
1:1:
Fault is shown and motor is stopped when the input is active.
2:2:
2: External fault, opening contact =
2:2:
Fault is shown and motor is stopped when the input is not active.
3:3:
3: Run enable
3:3:
contact open = Motor start disabled contact closed = Motor start enabled
4:4:
4: Acc./Dec contact open = Acceleration/deceleration time 1 selected
4:4:
time select. contact closed = Acceleration/deceleration time 2 selected
5:5:
5: Reverse
5:5:
contact open = Forward Can be used for reversing if contact closed = Reverse parameter 2.1 has value 3
6:6:
6: Jogg. speed
6:6:
contact closed = Jogging speed selected for freq. reference
7:7:
7: Fault reset
7:7:
contact closed = Resets all faults
8:8:
8: Acc./Dec. operation prohibited
8:8:
contact closed = Stops acceleration or deceleration until the contact is opened
9:9:
9: DC-braking command contact closed =
9:9:
In Stop mode, the DC-braking operates until the contact is opened, see figure 6.5. DC-brake current is set with parameter 4.8.
10:10:
10: Torque control
10:10:
contact closed = Forces the motor control mode to torque control, refer to par. 6.1
11
1:1:
1
1:
Torque reference sign
11
1:1:
This selection changes the sign of the torque reference
12: 12:
12: Run enable with coasting
12: 12:
contact open = Run and start disabled (stop always with coasting)
contact closed = Motor run enabled
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
aconacon
V
acon Page 23
aconacon
Multi-purpose Control Application IIMulti-purpose Control Application II
Output frequency
Param. 4. 10
DIA3
RUN STOP
a) DIA3 as DC-brake command input and stop-mode = Ramp
t
UD012K32
t
DIA3
RUN STOP
b) DIA3 as DC-brake command input and stop-mode = Coasting
UD012K32
Figure 6-5 DIA3 as DC-brake command input: a) Stop-mode = Ramp,
b) Stop-mode = Coasting.
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Page 24
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
aconacon
V
acon
aconacon
2. 32. 3
2. 3
2. 32. 3
2. 42. 4
2. 4
2. 42. 4
2. 52. 5
2. 5
2. 52. 5
DIB4 functionDIB4 function
DIB4 function
DIB4 functionDIB4 function
Selections are the same as in 2
10:10:
10: Multi-Step contact closed = Selection 1 active
10:10:
. .
. 2 except :
. .
speed select 1
11
1:1:
1
1: Uin/Iin digital selection for frequency reference
11
1:1:
13:13:
13: Fieldbus control: Selection between I/O and fieldbus control
13:13: 14:14:
14: Parameter 1.5 / Uin
14:14: 15:15:
15: Parameter 1.5 / Iin
15:15:
DIB5 functionDIB5 function
DIB5 function
DIB5 functionDIB5 function
Selections are the same as in 2
10:10:
10: Multi-Step contact closed = Selection 2 active
10:10:
..
. 2 except :
..
speed select 2
11
1:1:
1
1: Motor pot. contact closed = Reference decreases until the contact is
11
1:1:
UP opened
13:13:
13: Fieldbus control: Selection between I/O and fieldbus control
13:13:
DIB6 functionDIB6 function
DIB6 function
DIB6 functionDIB6 function
Selections are the same as in 2
10:10:
10: Multi-Step contact closed = Selection 3 active
10:10:
..
. 2 except :
..
speed select 3
11
1:1:
1
1: Motor pot. contact closed = Reference decreases until the contact is
11
1:1:
DOWN opened
13:13:
13: Fieldbus control: Selection between I/O and fieldbus control
13:13: Note! Note!
Note! (
Note! Note!
ParPar
. 2.3, 2.4, 2.5. 2.3, 2.4, 2.5
Par
. 2.3, 2.4, 2.5): In the fieldbus control par. 10.1 = 1 and 10.2 = 0.
ParPar
. 2.3, 2.4, 2.5. 2.3, 2.4, 2.5
2. 62. 6
2. 6
2. 62. 6
UU
signal rangesignal range
U
signal range
UU
signal rangesignal range
inin
in
inin
0 = Signal range 0+10 V 1 = Custom setting range from custom minimum (par. 2 maximum (par. 2
..
. 5)
..
..
. 4) to custom
..
2 = Signal range -10+10 V , can be used only with Joystick control
2. 72. 7
2. 7
2. 72. 7
2. 82. 8
2. 8
2. 82. 8
UU
custom setting minimum/maximum custom setting minimum/maximum
U
custom setting minimum/maximum
UU
custom setting minimum/maximum custom setting minimum/maximum
inin
in
inin
With these parameters, Uin can be set for any input signal span within 010 V. Minimum setting: Set the Uin signal to its minimum level, select parameter 2
press the Enter button
Maximum setting: Set the Uin signal to its maximun level, select parameter 2
press the Enter button
Note!Note!
Note! These parameters can only be set with this procedure (not with the Browser
Note!Note!
buttons)
2. 92. 9
2. 9
2. 92. 9
UU
signal inversionsignal inversion
U
signal inversion
UU
signal inversionsignal inversion
inin
in
inin
Parameter 2. 9 = 0, no inversion of analogue U
signal.
in
%
Unfiltered signal
100%
Parameter 2. 9 = 1, inversion
2. 102. 10
2. 10
2. 102. 10
of analogue U
signal filter timesignal filter time
UU
signal filter time
U
signal filter timesignal filter time
UU
inin
in
inin
signal.
in
63%
Filtered signal
Filters out disturbances from the incoming analogue U Long filtering time makes regula­tion response slower.
signal.
in
Par. 2. 10
t [s]
UD009K37
See figure 6-6.
Figure 6-6 U
signal filtering.
in
..
. 4,
..
..
. 5,
..
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
aconacon
V
acon Page 25
aconacon
2. 12. 1
2. 1
2. 12. 1
11
1
11
Analogue inputAnalogue input
Analogue input
Analogue inputAnalogue input
Multi-purpose Control Application IIMulti-purpose Control Application II
II
signal range signal range
I
signal range
II
signal range signal range
inin
in
inin
0 = 020 mA 1 = 420 mA 2 = Custom signal span
2. 122. 12
2. 12
2. 122. 12
2. 132. 13
2. 13
2. 132. 13
Analogue inputAnalogue input
Analogue input
Analogue inputAnalogue input setting minimum/maximumsetting minimum/maximum
setting minimum/maximum
setting minimum/maximumsetting minimum/maximum
II
custom custom
I
custom
II
custom custom
inin
in
inin
With these parameters, the scaling of the input current signal (Iin) range can be set between 020 mA.
Minimum setting: Set the Iin signal to its minimum level, select parameter 2
..
. 12,
..
press the Enter button.
Maximum setting: Set the Iin signal to its maximun level, select parameter 2
..
. 13,
..
press the Enter button.
Note!Note!
Note! These parameters can only
Note!Note!
be set by this procedure (not with the browser buttons)
%
Unfiltered signal
100%
Filtered signal
63%
Par. 2. 15
Figure 6-7 Analogue input Iin filter time
t [s]
UD012K40
2. 142. 14
2. 14
2. 142. 14
2. 152. 15
2. 15
2. 152. 15
2. 162. 16
2. 16
2. 162. 16
2. 172. 17
2. 17
2. 172. 17
2. 182. 18
2. 18
2. 182. 18
2. 192. 19
2. 19
2. 192. 19
Analogue input IAnalogue input I
Analogue input I
Analogue input IAnalogue input I
Parameter 2. 14 = 0, no inversion of I Parameter 2. 14 = 1, inversion of I
Analogue input IAnalogue input I
Analogue input I
Analogue input IAnalogue input I
Filters out disturbances from the incoming analog I
inversion inversion
inversion
inversion inversion
inin
in
inin
filter time filter time
filter time
filter time filter time
inin
in
inin
input.
in
input
in
in
Long filtering time makes regulation response slower. See figure 6-7.
UU
signal minimum scalingsignal minimum scaling
U
signal minimum scaling
UU
signal minimum scalingsignal minimum scaling
in in
in
in in
Sets the minimum scaling point for U
UU
signal maximum scalingsignal maximum scaling
U
signal maximum scaling
UU
signal maximum scalingsignal maximum scaling
in in
in
in in
Sets the maximum scaling point for U
I I
signal minimum scalingsignal minimum scaling
I
signal minimum scaling
I I
signal minimum scalingsignal minimum scaling
in in
in
in in
Sets the minimum scaling point for I
I I
signal maximum scalingsignal maximum scaling
I
signal maximum scaling
I I
signal maximum scalingsignal maximum scaling
in in
in
in in
Sets the maximum scaling point for I
signal. See figure 6-8.
in
signal. See figure 6-8.
in
signal. See figure 6-8.
in
signal. See figure 6-8.
in
signal.
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Page 26
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
aconacon
V
acon
aconacon
2. 202. 20
2. 20
2. 202. 20
2. 212. 21
2. 21
2. 212. 21 functionfunction
function
functionfunction
100
0
0
0 4
Scaled input signal [%]
Par. 2. 19 = 30% Par. 2. 20 = 80%
Analogue
1008030
input [%]
10.0 V
8.03.0
20.0 mA
16.06.0
16.88.8 20.0 mA
(15.3 mA)
-30
100
76.5
17.7
(3.5 mA)
Scaled input signal [%]
Par. 2. 19 = -30% Par. 2. 20 = 140%
0
0 0 4
100 140
10.0 V
20.0 mA
20.0 mA
Analogue input [%]
UD012K34
Figure 6-8 Examples of the scaling of Uin and Iin inputs .
Free analogue input signalFree analogue input signal
Free analogue input signal
Free analogue input signalFree analogue input signal
Selection of input signal of free analogue input (an input not used for reference signal):
0 = Not in use 1 = Voltage signal U 2 = Current signal I
in
in
3 = Voltage signal Ain1 from terminals 202-203 of I/O Expander 4 = Analogue signal Ain2 from terminal 204-205 of I/O Expander
- current signal Vacon CX 100 Opt
- voltage signal Vacon CX 102 Opt
5 = Fieldbus signal
- the signal comes through the fieldbus and depends on the option board used
100% Par. 1. 7
Torque limit
Free analogue input signalFree analogue input signal
Free analogue input signal
Free analogue input signalFree analogue input signal
This parameter sets the function of the free analogue input:
00
0 = Function is not used
00 11
1 = Reducing motor current limit
11
(par. 1
..
. 7)
..
This signal will adjust the
10 V 20 mA 20 mA Custom
Analogue input
UD012K61
maximum motor current between 0 and parameter max. limit set with parameter
0 V 0 mA 4 mA Custom
Signal range
1.7. See figure 6-9.
Figure 6-9 Reducing of max. motor current.
DC-braking
100% Par. 4. 8
current
2 2
2 = Reducing DC brake current.
2 2
The DC braking current can be reduced with the free analogue input signal, between 0.15xI
nCX
and
current set with parameter
..
4
. 8.
..
0,15 x I
See figure 6-10.
Figure 6-10 Reducing DC brake current.
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
nFU
0
Signal range
Free analogue input
UD012K58
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
aconacon
V
acon Page 27
aconacon
33
3 Reducing acceleration and
33
deceleration times. The acceleration and deceleration times can be
Multi-purpose Control Application IIMulti-purpose Control Application II
Factor R
10
reduced with the free analog input signal, according to the following formula:
Reduced time =set acc./eceler.
..
..
..
time (par. 1 divided by the factor R from
figure 6-11.
. 3, 1
..
. 4; 4
..
Figure 6-11 Reducing acceleration
and deceleration times.
44
4 Reducing torque supervision
44
. 3, 4
..
..
. 4)
..
2
1
Signal range
limit.
The set torque supervision
100% Par. 3. 14
Torque limit
limit can be reduced with the free analogue input signal between 0 and set supervision limit (par. 3
..
. 14),
..
see figure 6-12.
Free analogue input
UD012K59
2. 222. 22
2. 22
2. 222. 22
2.232.23
2.23
2.232.23
2.242.24
2.24
2.242.24
2.252.25
2.25
2.252.25
2.262.26
2.26
2.262.26
Figure 6-12 Reducing torque
supervision limit.
Free analogue input
UD012K60
Motor potentiometer ramp timeMotor potentiometer ramp time
Motor potentiometer ramp time
Motor potentiometer ramp timeMotor potentiometer ramp time
0
Signal range
Defines how fast the electronic motor potentiometer value changes.
Ain1 signal inversion (I/O-Expander)Ain1 signal inversion (I/O-Expander)
Ain1 signal inversion (I/O-Expander)
Ain1 signal inversion (I/O-Expander)Ain1 signal inversion (I/O-Expander)
Parameter 2.23 = 0, no inversion
Ain1 signal filter timeAin1 signal filter time
Ain1 signal filter time
Ain1 signal filter timeAin1 signal filter time
Filters out disturbances from the incoming analogue Ain1 signal. Long filtering time makes regulation response slower.
Ain2 input (I/O-Expander) signal rangeAin2 input (I/O-Expander) signal range
Ain2 input (I/O-Expander) signal range
Ain2 input (I/O-Expander) signal rangeAin2 input (I/O-Expander) signal range
0 = 020 mA 1 = 420 mA 2 = 010 V (must be used with 102 OPT)
Ain2 signal inversion (I/O-Expander)Ain2 signal inversion (I/O-Expander)
Ain2 signal inversion (I/O-Expander)
Ain2 signal inversion (I/O-Expander)Ain2 signal inversion (I/O-Expander)
Parameter 2.26 = 0, no inversion
2.272.27
2.27
2.272.27
Ain2 signal filter time (I/O-Expander)Ain2 signal filter time (I/O-Expander)
Ain2 signal filter time (I/O-Expander)
Ain2 signal filter time (I/O-Expander)Ain2 signal filter time (I/O-Expander)
Filters out disturbances from the incoming analogue Ain2 signal. Long filtering time makes regulation response slower.
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Page 28
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
aconacon
V
acon
aconacon
2.282.28
2.28
2.282.28
Range: 0 - 5 Step: 1 Default: 0 Description: 0 = Not Used 1 = Voltage Input 2 = Current Input 3 = AIN1 I/O-expand 4 = AIN2 I/O-expand 5 = FB signal
2.292.29
2.29
2.292.29
Range: 0.0% - 200.0% Step: 0.1% Default: 0.0%
2.302.30
2.30
2.302.30
Range: 0.0% - 100.0% Step: 0.1% Default: 0.0%
Adjust InputAdjust Input
Adjust Input
Adjust InputAdjust Input
Adjust PrecentageAdjust Precentage
Adjust Precentage
Adjust PrecentageAdjust Precentage
Adjust OffsetAdjust Offset
Adjust Offset
Adjust OffsetAdjust Offset
f / Hz
(0%)
Parameter 2.30
OFFSET
0%
Frequency reference (Par. 1.5)
Parameter 2.29
Figure 6-13. parameter 2.29 and 2.30 settings.
50%
OO
100%
O
100% 200%
(25%)
(50%)
Adjust
%
Percentage
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
aconacon
V
acon Page 29
aconacon
Multi-purpose Control Application IIMulti-purpose Control Application II
3. 13. 1
3. 1
3. 13. 1
3. 23. 2
3. 2
3. 23. 2
3.33.3
3.3
3.33.3
Analogue output functionAnalogue output function
Analogue output function
Analogue output functionAnalogue output function
See table on page 12.
Analogue output filter timeAnalogue output filter time
Analogue output filter time
Analogue output filter timeAnalogue output filter time
Filters the analogue output signal. See figure 6-13.
Figure 6-13 Analogue output
filtering.
Analogue output invertAnalogue output invert
Analogue output invert
Analogue output invertAnalogue output invert
Inverts analogue output
max. output value min. output signal = maximum set value
signal = minimum set
signal:
%
100%
63%
Analogue output current
20 mA
12 mA
10 mA
Unfiltered signal
Par. 3. 2
Filtered signal
t [s]
UD009K16
Param. 3. 5 = 50%
3. 43. 4
3. 4
3. 43. 4
3. 53. 5
3. 5
3. 53. 5
Figure 6-14 Analogue output invert.
Analogue output minimumAnalogue output minimum
Analogue output minimum
Analogue output minimumAnalogue output minimum
Defines the signal minimum to be either 0 mA or 4 mA (living zero). See figure 6-15.
Analogue output scaleAnalogue output scale
Analogue output scale
Analogue output scaleAnalogue output scale
Scaling factor for analogue output. See figure 6-15.
Signal Max. value of the signal Output fre- Max. frequency (p. 1. 2)
quency Motor speed Max. speed (n Output 2 x I current Motor torque 2 x T Motor power 2 x P Motor voltage 100% x U DC-link volt. 1000 V
nCX
nCX nCX
nmotor
Uin signal Max Uin Iin signal Max Iin
nxfmax/fn
)
4 mA
0 mA
Analogue output current
20 mA
12 mA 10 mA
Param. 3. 5 = 100%
Param. 3. 5 = 200%
0
0.5
Param. 3. 5 = 200%
Selected (para. 3. 1) signal max. value
1.0
Param. 3. 5 = 100%
Param. 3. 5 = 50%
UD012K17
Par. 3. 4 = 1
4 mA
Figure 6-15 Analogue output
scale.
Par. 3. 4 = 0
0 mA
0
0.5
Max. value of signal selected by param. 3. 1
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
1.0
UD012K18
Page 30
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
aconacon
V
acon
aconacon
3. 63. 6
3. 6
3. 63. 6
3. 73. 7
3. 7
3. 73. 7
3. 83. 8
3. 8
3. 83. 8
Digital output functionDigital output function
Digital output function
Digital output functionDigital output function Relay output 1 functionRelay output 1 function
Relay output 1 function
Relay output 1 functionRelay output 1 function Relay output 2 functionRelay output 2 function
Relay output 2 function
Relay output 2 functionRelay output 2 function
Setting value Signal content
0 = Not used Out of operation
Digital output DO1 sinks the current and programmable
relay (RO1, RO2) is activated when: 1 = Ready The frequency converter is ready to operate 2 = Run The frequency converter operates (motor is running) 3 = Fault A fault trip has occurred 4 = Fault inverted A fault trip has not occurred 5 = Vacon overheat warning The heat-sink temperature exceeds +70°C
..
. 12)
..
..
. 14)
..
..
. 16)
..
..
. 20)
..
..
. 2
.. ..
. 1
..
6 = External fault or warning Fault or warning depending on parameter 7 7 = Reference fault or warning Fault or warning depending on parameter 7
- if analogue reference is 420 mA and signal is <4mA 8 = Warning Always if a warning exists 9 = Reversed The reverse command has been selected 10= Jogging speed Jogging speed has been selected with digital input 11= At speed The output frequency has reached the set reference 12= Motor regulator activated Overvoltage or overcurrent regulator was activated 13= Output frequency supervision 1 The output frequency goes outside of the set supervision
..
. 18)
..
..
. 9 and 3
..
..
. 11 and 3
..
..
. 13 and 3
..
..
. 15 and 3
..
Low limit/ High limit (par. 3
14= Output frequency supervision 2 The output frequency goes outside of the set supervision
Low limit/ High limit (par. 3
15= Torque limit supervision The motor torque goes outside of the set supervision
Low limit/ High limit (par. 3
16= Reference limit supervision Reference goes outside of the set supervision
Low limit/ High limit (par. 3
17= External brake control External brake ON/OFF control with programmable de-
lay (par 3
18= Control from I/O terminals External control mode selected with progr. push-button
#2
19= Frequency converter Temperature on frequency converter goes outside the
temperature limit supervision set supervision limits (par. 3
..
. 17 and 3
..
..
. 10)
..
..
. 19 and 3
..
3. 93. 9
3. 9
3. 93. 9
3. 13. 1
3. 1
3. 13. 1
3. 103. 10
3. 10
3. 103. 10
3. 123. 12
3. 12
3. 123. 12
20= Unrequested rotation direction Rotation direction of the motor shaft is different from the
requested one
21 = External brake control inverted External brake ON/OFF control (par. 3.17 and 3.18),
output active when brake control is OFF
22 = Termistor fault or warning The termistor input of option board indicates
overtemperature. Fault or warning depending on parameter 7.19
Table 6-2 Output signals via DO1 and output relays RO1 and RO2.
Output frequency limit 1, supervision functionOutput frequency limit 1, supervision function
Output frequency limit 1, supervision function
Output frequency limit 1, supervision functionOutput frequency limit 1, supervision function
11
1
11
Output frequency limit 2, supervision functionOutput frequency limit 2, supervision function
Output frequency limit 2, supervision function
Output frequency limit 2, supervision functionOutput frequency limit 2, supervision function
0 = No supervision 1 = Low limit supervision 2 = High limit supervision If the output frequency goes under/over the set limit (3
..
. 10, 3
..
..
. 12) this function
..
generates a warning message via the digital output DO1 and via a relay output RO1
..
or RO2 depending on the settings of the parameters 3
Output frequency limit 1, supervision valueOutput frequency limit 1, supervision value
Output frequency limit 1, supervision value
Output frequency limit 1, supervision valueOutput frequency limit 1, supervision value Output frequency limit 2, supervision valueOutput frequency limit 2, supervision value
Output frequency limit 2, supervision value
Output frequency limit 2, supervision valueOutput frequency limit 2, supervision value
The frequency value to be supervised by the parameter 3
. 63
..
..
. 9 (3
..
..
. 8.
..
..
. 11).
..
See figure 6-16.
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
aconacon
V
acon Page 31
aconacon
Multi-purpose Control Application IIMulti-purpose Control Application II
3. 133. 13
3. 13
3. 133. 13
3. 143. 14
3. 14
3. 143. 14
3. 153. 15
3. 15
3. 153. 15
TT
orque limit , supervisionorque limit , supervision
T
orque limit , supervision
TT
orque limit , supervisionorque limit , supervision
functionfunction
function
functionfunction
0 = No supervision 1 = Low limit supervision 2 = High limit supervision
f[Hz]
Par. 3.9 = 2
If the calculated torque value goes under/over the set limit (3
..
. 14) this
..
Par 3. 10
function generates a warning message via the digital output DO1, via a relay output RO1 or RO2 depending on the settings of
..
the parameters 3
Figure 6-16 Output frequency
supervision.
TT
orque limit , supervision valueorque limit , supervision value
T
orque limit , supervision value
TT
orque limit , supervision valueorque limit , supervision value
. 63
..
..
. 8.
..
Example:
21 RO1 22 RO1 23 RO1
21 RO1 22 RO1 23 RO1
The calculated torque value to be supervised by the parameter 3
Reference limit , supervision functionReference limit , supervision function
Reference limit , supervision function
Reference limit , supervision functionReference limit , supervision function
..
. 13.
..
UD009K19
21 RO1 22 RO1 23 RO1
t
0 = No supervision 1 = Low limit supervision 2 = High limit supervision If the reference value goes under/over the set limit (3
..
. 16) this function generates a
..
warning message via the digital output DO1 or via a relay output RO1 or RO2 depending on the settings of the parameters 3
..
. 63
..
..
. 8. The supervised
..
reference is the currently active reference. It can be source A or B reference depending on DIB6 input or the panel reference if panel is the active control source.
3. 163. 16
3. 16
3. 163. 16
3. 173. 17
3. 17
3. 173. 17
3. 183. 18
3. 18
3. 183. 18
3. 193. 19
3. 19
3. 193. 19
3. 203. 20
3. 20
3. 203. 20
Reference limit , supervision valueReference limit , supervision value
Reference limit , supervision value
Reference limit , supervision valueReference limit , supervision value
The frequency value to be supervised by the parameter 3
External brake-off delayExternal brake-off delay
External brake-off delay
External brake-off delayExternal brake-off delay External brake-on delayExternal brake-on delay
External brake-on delay
External brake-on delayExternal brake-on delay
..
. 15.
..
With these parameters the timing of external brake can be linked to the Start and Stop control signals, see Figure 6-18. The brake control signal can be programmed via the digital output DO1 or via one
..
of relay outputs RO1 and RO2, see parameters 3
Frequency converter temperature limit supervision functionFrequency converter temperature limit supervision function
Frequency converter temperature limit supervision function
Frequency converter temperature limit supervision functionFrequency converter temperature limit supervision function
. 63
..
..
. 8.
..
0 = No supervision 1 = Low limit supervision 2 = High limit supervision If the temperature of the frequency converter goes under/over the set limit (3
..
. 20)
..
this function generates a warning message via the digital output DO1 or via the relay
..
outputs RO1 or RO2 depending on the settings of the parameters 3
Frequency converter temperature limit valueFrequency converter temperature limit value
Frequency converter temperature limit value
Frequency converter temperature limit valueFrequency converter temperature limit value
The temperature value to be supervised by the parameter 3
..
. 19.
..
. 63
..
..
. 8.
..
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Page 32
3.21 I/O-expander board (opt.) analogue output content3.21 I/O-expander board (opt.) analogue output content
3.21 I/O-expander board (opt.) analogue output content
3.21 I/O-expander board (opt.) analogue output content3.21 I/O-expander board (opt.) analogue output content
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
0 = Not used Scale 100% 1 = O/P frequency (0—f
max
) 2 = Motor speed (0max. speed) 3 = O/P current (02.0 x I 4 = Motor torque (02 x T 5 = Motor power (02 x P
nCX
nCX
nCX
)
)
) 6 = Motor voltage (0100% x UnM) 7 = DC-link volt. (01000 V) 8 = Input signal U 9 = Input signal I
in
in
10 = Refer. freq. 11 = Refer. torque 12 = Motor±torque (-2—+2xT 13 = Motor±power (-2—+2xT 14 = O/P freq. (f
3.22 I/O-expander board (opt.) analogue output filter time3.22 I/O-expander board (opt.) analogue output filter time
3.22 I/O-expander board (opt.) analogue output filter time
3.22 I/O-expander board (opt.) analogue output filter time3.22 I/O-expander board (opt.) analogue output filter time
min—fmax
nMOT
nMOT
)
) )
Range is 0.01 - 10 s Step: 0.01 Default: 1.00
aconacon
V
acon
aconacon
3.23 I/O-expander board (opt.) analogue output inversion3.23 I/O-expander board (opt.) analogue output inversion
3.23 I/O-expander board (opt.) analogue output inversion
3.23 I/O-expander board (opt.) analogue output inversion3.23 I/O-expander board (opt.) analogue output inversion
0 = No inverted 1 = Inverted Default: 0 = no inverted
3.24 I/O-expander board (opt.) analogue output minimum3.24 I/O-expander board (opt.) analogue output minimum
3.24 I/O-expander board (opt.) analogue output minimum
3.24 I/O-expander board (opt.) analogue output minimum3.24 I/O-expander board (opt.) analogue output minimum
0 = 0 mA 1 = 4 mA Default: 0 = 0 mA
3.25 I/O-expander board (opt.) analogue output scale3.25 I/O-expander board (opt.) analogue output scale
3.25 I/O-expander board (opt.) analogue output scale
3.25 I/O-expander board (opt.) analogue output scale3.25 I/O-expander board (opt.) analogue output scale
Range is 10% - 1000% Step: 1% Default: 100%
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
aconacon
V
acon Page 33
aconacon
Multi-purpose Control Application IIMulti-purpose Control Application II
3.263.26
3.26
3.263.26
3.273.27
3.27
3.273.27
Analogue output offsetAnalogue output offset
Analogue output offset
Analogue output offsetAnalogue output offset I/O-Expander analogue output offsetI/O-Expander analogue output offset
I/O-Expander analogue output offset
I/O-Expander analogue output offsetI/O-Expander analogue output offset
With these parameters the offsets of the basic control board and I/O-Expander analogue outputs can be set. See figure 6-17.
Analogue output current
20 mA
Param. 3. 26 = 25% (+5 mA)
0 mA
0
0.5
Param. 3. 5 = 100%
1.0
Param. 3. 26 = -30%(-6mA)
Maximum value of selected signal
ao-offse.fh3
Figure 6-17. Analogue output offset
3.283.28
3.28
3.283.28
3.293.29
3.29
3.293.29
3.303.30
3.30
3.303.30
3.313.31
3.31
3.313.31
3.323.32
3.32
3.323.32
3.333.33
3.33
3.333.33
Digital output DO1 on-delayDigital output DO1 on-delay
Digital output DO1 on-delay
Digital output DO1 on-delayDigital output DO1 on-delay Digital output DO1 off-delayDigital output DO1 off-delay
Digital output DO1 off-delay
Digital output DO1 off-delayDigital output DO1 off-delay Relay output RO1 on-delayRelay output RO1 on-delay
Relay output RO1 on-delay
Relay output RO1 on-delayRelay output RO1 on-delay Relay output RO1 off-delayRelay output RO1 off-delay
Relay output RO1 off-delay
Relay output RO1 off-delayRelay output RO1 off-delay Relay output RO2 on-delayRelay output RO2 on-delay
Relay output RO2 on-delay
Relay output RO2 on-delayRelay output RO2 on-delay Relay output RO2 off-delayRelay output RO2 off-delay
Relay output RO2 off-delay
Relay output RO2 off-delayRelay output RO2 off-delay
With these parameters it is possible to set on- and off-delays to digital and relay outputs. See figure 6-18.
Signal programmed to digital or relay output
DO, RO1 or RO2 output
ON-delay OFF-delay
ud182k_2
Figure 6-18. Digital and relay outputs. On- and off-delays
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Page 34
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
a)
t
= Par. 3. 17 tON = Par. 3. 18
OFF
External BRAKE: OFF ON
DIA1: RUN FWD STOP
DIA2: RUN REV STOP
b)
t
= Par. 3. 17 tON = Par. 3. 18
OFF
External BRAKE: OFF ON
DIA1: START PULSE
DIA2: STOP PULSE
Digital or relay output
UD012K45
Digital or relay output
aconacon
V
acon
aconacon
t
t
4. 14. 1
4. 1
4. 14. 1
4. 24. 2
4. 2
4. 24. 2
Figure 6-19 External brake control: a) Start/Stop logic selection par. 2. 1 = 0, 1 or 2
b)Start/Stop logic selection par. 2. 1 = 3.
Acc/Dec ramp 1 shapeAcc/Dec ramp 1 shape
Acc/Dec ramp 1 shape
Acc/Dec ramp 1 shapeAcc/Dec ramp 1 shape Acc/Dec ramp 2 shapeAcc/Dec ramp 2 shape
Acc/Dec ramp 2 shape
Acc/Dec ramp 2 shapeAcc/Dec ramp 2 shape
The start and end of the acceleration and deceleration ramps can be smoothed with these parameters. Setting value 0 gives linear ramp shape which causes acceleration and deceleration to act immediately to the changes in the reference signal with the time constant set by the parameter 1
Setting value 0.110 seconds for
. .
4
. 1 (4
. .
. .
. 2) causes linear
. .
..
. 3 and 1
..
[Hz]
..
. 4
..
. .
(4
. 3 and 4
. .
. .
. 4).
. .
acceleration/deceleration to adopt an S-shape. Parameter 1 4
(4
. .
. 3 and 4
. .
. .
. 4) determines the
. .
..
. 3 and 1
..
time constant of acceleration/
..
.
..
1. 3, 1. 4 (4. 3, 4. 4)
deceleration in the middle of the curve. See figure 6-20.
Figure 6-20 S-shaped acceleration/
deceleration.
4. 1 (4. 2)
4. 1 (4. 2)
[t]
UD009K20
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
aconacon
V
acon Page 35
aconacon
Multi-purpose Control Application IIMulti-purpose Control Application II
4. 34. 3
4. 3
4. 34. 3
4. 44. 4
4. 4
4. 44. 4
4. 54. 5
4. 5
4. 54. 5
4. 64. 6
4. 6
4. 64. 6
Acceleration time 2Acceleration time 2
Acceleration time 2
Acceleration time 2Acceleration time 2 Deceleration time 2Deceleration time 2
Deceleration time 2
Deceleration time 2Deceleration time 2
These values correspond to the time required for the output frequency to accelerate from the set minimum frequency (par. 1 (par. 1
. .
. 2). These times give the possibility to set two different acceleration/
. .
. .
. 1) to the set maximum frequency
. .
deceleration time sets for one application. The active set can be selected with the programmable signal DIA3 of this application, see parameter 2
..
. 2.
..
Acceleration/deceleration times can be reduced with an external free analogue input signal, see parameters 2
Brake chopperBrake chopper
Brake chopper
Brake chopperBrake chopper
..
. 18 and 2
..
..
. 19.
..
0 = No brake chopper 1 = Brake chopper and brake resistor installed 2 = External brake chopper When the frequency converter is decelerating the motor, the inertia of the motor and the load are fed into the external brake resistor. This enables the frequency converter to decelerate the load with the torque equal to that of acceleration, if the brake resistor is selected correctly. See separate Brake resistor installation manual.
Start functionStart function
Start function
Start functionStart function
Ramp:
00
0 The frequency converter starts from 0 Hz and accelerates to the set referen-
00
ce frequency within the set acceleration time. (Load inertia or starting friction may cause prolonged acceleration times).
Flying start:
11
1 The frequency converter is able to start into running motor by applying a small
11
torque to motor and searching for frequency corresponding to the speed the motor is running at. Searching starts from the maximum frequency towards the actual frequency until the correct value is detected. Thereafter the output frequency will be accelerated/decelerated to the set reference value according to the set acceleration/deceleration parameters. Use this mode if the motor is coasting when the start command is given. With the flying start it is possible to ride through short mains voltage interruptions.
4. 74. 7
4. 7
4. 74. 7
Stop functionStop function
Stop function
Stop functionStop function
Coasting:
00
0 The motor coasts to a halt without any control from the frequency converter,
00
after the Stop command.
Ramp:
11
1 After the Stop command, the speed of the motor is decelerated according to
11
the set deceleration parameters. If the regenerated energy is high it may be necessary to use an external braking resistor for faster deceleration.
4. 84. 8
4. 8
4. 84. 8
DC braking currentDC braking current
DC braking current
DC braking currentDC braking current
Defines the current injected into the motor during the DC braking.
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Page 36
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
aconacon
V
acon
aconacon
4. 94. 9
4. 9
4. 94. 9
DC braking time at stopDC braking time at stop
DC braking time at stop
DC braking time at stopDC braking time at stop
Defines if braking is ON or OFF and the braking time of the DC-brake when the motor is stopping. The function of the DC-brake depends on the stop function, parameter
. .
4
. 7. See figure 6-21.
. .
00
0 DC-brake is not used
00 >0>0
>0 DC-brake is in use and its function depends on the Stop function,
>0>0
(param. 4
..
. 7), and the time depends on the value of parameter 4
..
..
. 9:
..
Stop-function = 0 (coasting): After the stop command, the motor coast to a stop without any control from the frequency converter. With DC-injection, the motor can be electrically stopped in the shortest possible time, without using an optional external braking resistor. The braking time is scaled according to the frequency when the DC­braking starts. If the frequency is
>nominal frequency of the motor (par. 1.11), setting value of parameter 4.9 determines the braking time. When the frequency is <10% of the nominal, the braking time is 10% of the set value of parameter
4.9.
f
out
f
n
Output frequency Motor speed
f
out
f
n
Output frequency Motor speed
DC-braking ON
t = 0.1 x par. 4. 9
t
UD009K21
RUN STOP
DC-braking ON
t = 1 x par. 4. 9
t
0,1x f
n
RUN STOP
Figure 6-21 DC-braking time when stop = coasting.
Stop-function = 1 (ramp):
After the Stop command, the speed of the motor is reduced according to the set deceleration parameters, as fast as possible, to a speed defined with the parameter 4
The braking time is defined
with parameter 4
..
. 10, where the DC-braking starts.
..
f
out
..
. 9.
..
Motor speed Output frequency
If high inertia exists, it is recommended to use an external braking resistor for faster deceleration. See figure 6-22.
Param. 4. 10
DC-braking
Figure 6-22 DC-braking time when stop function = ramp.
RUN STOP
t = param. 4. 9
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
t
UD009K23
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
aconacon
V
acon Page 37
aconacon
Multi-purpose Control Application IIMulti-purpose Control Application II
4. 104. 10
4. 10
4. 104. 10
Execute frequency of DC-brake during ramp StopExecute frequency of DC-brake during ramp Stop
Execute frequency of DC-brake during ramp Stop
Execute frequency of DC-brake during ramp StopExecute frequency of DC-brake during ramp Stop
See figure 6-22.
4. 14. 1
4. 1
4. 14. 1
11
1
11
DC-brake time at startDC-brake time at start
DC-brake time at start
DC-brake time at startDC-brake time at start
>0>0
>0 DC-brake is actived when
>0>0
4. 12 - 4. 184. 12 - 4. 18
4. 12 - 4. 18
4. 12 - 4. 184. 12 - 4. 18
00
0 DC-brake is not used
00
the start command is given and this parameter defines the time before the brake is released. After the brake is released, the output frequency increases according to the set start function parameter 4
..
. 6 and
..
acceleration parameters (1 3, 4
..
. 1 or 4
..
..
. 2, 4
..
..
. 3), see
..
figure 6-23.
Figure 6-23 DC-braking at start
Multi-Step speed references 1-7Multi-Step speed references 1-7
Multi-Step speed references 1-7
Multi-Step speed references 1-7Multi-Step speed references 1-7
Output frequency
..
.
..
Par 4. 11
RUN STOP
t
UD009K22
5. 15. 1
5. 1
5. 15. 1
5. 25. 2
5. 2
5. 25. 2
5. 35. 3
5. 3
5. 35. 3
5. 45. 4
5. 4
5. 45. 4
5. 55. 5
5. 5
5. 55. 5
5. 65. 6
5. 6
5. 65. 6
6. 16. 1
6. 1
6. 16. 1
Parameter value defines the Multi-Step speeds selected with the digital inputs.
Prohibit frequency areaProhibit frequency area
Prohibit frequency area
Prohibit frequency areaProhibit frequency area Low limit/High limitLow limit/High limit
Low limit/High limit
Low limit/High limitLow limit/High limit
f
out
[Hz]
In some systems it may be necessary to avoid certain frequencies because of mechanical resonance problems. With these parameters it is possible to set limits for three "skip frequency" regions.
Figure 6-24 Example of prohibit
frequency area setting.
Motor control modeMotor control mode
Motor control mode
Motor control modeMotor control mode
0 = Frequency control: The I/O terminal and panel references are frequency references and the frequency converter controls the output frequency (output frequency resolution = 0.01 Hz) 1 = Speed control: The I/O terminal and panel references are speed references and the frequency converter controls the motor speed (regulation accuracity ± 0,5%). 2 = Torque control: The I/O terminal and panel references are torque references and the frequency converter controls the motor torque (regulation accuracity ± 3 % ; proper tuning required: motor nameplate values, U/f -setting).
5. 1 5. 2
5. 3 5. 4
5. 5 5. 6
frequency reference
[Hz]
UD009K33
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Page 38
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
aconacon
V
acon
aconacon
6. 2 6. 2
6. 2
6. 2 6. 2
6. 36. 3
6. 3
6. 36. 3
6. 46. 4
6. 4
6. 46. 4
6. 56. 5
6. 5
6. 56. 5
Switching frequencySwitching frequency
Switching frequency
Switching frequencySwitching frequency
Motor noise can be minimized using a high switching frequency. Increasing the switching frequency reduces the capacity of the frequency converter unit. Before changing the frequency from the factory default 10 kHz (3.6 kHz from 30 kW upwards), check the allowed capacity from the curve in the figure 5.2-3 of chapter
5.2 of the User's Manual.
Field weakening pointField weakening point
Field weakening point
Field weakening pointField weakening point VV
oltage at the field weakening pointoltage at the field weakening point
V
oltage at the field weakening point
oltage at the field weakening pointoltage at the field weakening point
The field weakening point is the output frequency at which the output voltage reaches the set maximum value (par. 6
..
. 4). Above that frequency the output voltage remains
..
at the set maximum value. Below that frequency the output voltage depends on the setting of the U/f curve
..
..
..
parameters 1
. 8, 1
..
. 9, 6
..
When the parameters 1
..
. 5, 6
. 6 and 6
..
..
..
. 10 and 1
..
the motor, are set, also parameters 6
..
. 7. See figure 6-25.
..
..
. 11, nominal voltage and nominal frequency of
..
..
. 3 and 6
..
..
. 4 are set automatically to the
..
corresponding values. If different values for the field weakening point and the maximum output voltage are required, change these parameters the parameters 1
U/f curve, middle point frequencyU/f curve, middle point frequency
U/f curve, middle point frequency
U/f curve, middle point frequencyU/f curve, middle point frequency
..
. 10 and 1
..
..
. 11.
..
If the programmable U/f curve has been selected with the parameter 1
after setting
..
. 8 this
..
parameter defines the middle point frequency of the curve. See figure 6-25.
6. 66. 6
6. 6
6. 66. 6
6. 76. 7
6. 7
6. 76. 7
U/f curve, middle point voltageU/f curve, middle point voltage
U/f curve, middle point voltage
U/f curve, middle point voltageU/f curve, middle point voltage
If the programmable U/f curve has been selected with the parameter 1 parameter defines the middle point voltage of the curve. See figure 6-25.
Output voltage at zero frequencyOutput voltage at zero frequency
Output voltage at zero frequency
Output voltage at zero frequencyOutput voltage at zero frequency
If the programmable U/f curve has been selected with the parameter 1 parameter defines the zero frequency voltage of the curve. See figure 6-25.
U[V]
Un
Par 6. 4
Par. 6. 6 (Def. 10%)
Par. 6. 7 (Def. 1.3%)
Default: Nominal voltage of the motor
Par. 6. 5 (Def. 5 Hz)
Field weakening point
Default: Nominal frequency of the motor
Par. 6. 3
f[Hz]
UD012K08
..
. 8 this
..
..
. 8 this
..
Figure 6-25 Programmable U/f curve.
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
aconacon
V
acon Page 39
aconacon
Multi-purpose Control Application IIMulti-purpose Control Application II
6. 86. 8
6. 8
6. 86. 8
6. 96. 9
6. 9
6. 96. 9
7. 17. 1
7. 1
7. 17. 1
7. 27. 2
7. 2
7. 27. 2
7. 37. 3
7. 3
7. 37. 3
7. 47. 4
7. 4
7. 47. 4
Overvoltage controllerOvervoltage controller
Overvoltage controller
Overvoltage controllerOvervoltage controller Undervoltage controllerUndervoltage controller
Undervoltage controller
Undervoltage controllerUndervoltage controller
These parameters allow the over/undervoltage controllers to be switched out of operation. This may be useful, for example, if the mains supply voltage varies more than -15%+10% and the application will not tolerate this over-/undervoltage, the regulator controls the output frequency according to the supply fluctuations. Over/undervoltage trips may occur when controllers are switched out of operation.
Response to the reference faultResponse to the reference fault
Response to the reference fault
Response to the reference faultResponse to the reference fault
0 = No response 1 = Warning 2 = Fault, stop mode after fault according to parameter 4.7 3 = Fault, stop mode after fault always by coasting A warning or a fault action and message is generated if 420 mA reference signal is used and the signal falls below 4 mA. The information can also be programmed via digital output DO1 and via relay outputs RO1 and RO2.
Response to external faultResponse to external fault
Response to external fault
Response to external faultResponse to external fault
0 = No response 1 = Warning 2 = Fault, stop mode after fault according to parameter 4.7 3 = Fault, stop mode after fault always by coasting A warning or a fault action and message is generated from the external fault signal in the digital input DIA3. The information can also be programmed into digital output DO1 and into relay outputs RO1 and RO2.
Phase supervision of the motorPhase supervision of the motor
Phase supervision of the motor
Phase supervision of the motorPhase supervision of the motor
0 = No action 1 = Warning 2 = Fault Phase supervision of the motor ensures that the motor phases have approximately equal current.
Earth fault protectionEarth fault protection
Earth fault protection
Earth fault protectionEarth fault protection
0 = No action 1 = Warning 2 = Fault Earth fault protection ensures that the sum of the motor phase currents is zero. The overcurrent protection is always working and protects the frequency converter from earth faults with high currents.
Parameters 7. 57. 9 Motor thermal protectionParameters 7. 57. 9 Motor thermal protection
Parameters 7. 57. 9 Motor thermal protection
Parameters 7. 57. 9 Motor thermal protectionParameters 7. 57. 9 Motor thermal protection
GeneralGeneral
General
GeneralGeneral
Motor thermal protection is to protect the motor from overheating. Vacon CX/CXL/CXS drive is capable of supplying higher than nominal current to the motor. If the load requires this high current there is a risk that motor will be thermally overloaded. This is true especially at low frequencies.
At low frequencies the cooling effect of the motor is reduced as well as is the capacity of the motor. If the motor is equipped with an external fan the load reduction on low speeds is small.
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Page 40
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
aconacon
V
acon
aconacon
Motor thermal protection is based on a calculated model and it uses the output current of the drive to determine the load on the motor. When the power of the drive is turned on, the calculated model uses the heatsink temperature to determine the initial thermal stage for the motor. The calculated model assumes that the ambient temperature of the motor is 40°C.
Motor thermal protection can be adjusted by setting the parameters. The thermal current IT specifies the load current above which the motor is overloaded. This current limit is a function of the output frequency. The curve for IT is set with parameters
..
..
7
. 6, 7
. 7 and 7
..
..
parameters have their default values taken from the motor name plate data.
CAUTION!
!
7. 57. 5
7. 5
7. 57. 5
..
. 9, refer to the figure 6-26. The
..
The calculated model does not protect the motor if the airflow to the
motor is reduced by blocked air intake grill.
Motor thermal protectionMotor thermal protection
Motor thermal protection
Motor thermal protectionMotor thermal protection
Operation:
0 = Not in use 1 = Warning 2 = Trip function
Tripping and warning will display the same message code. If tripping is selected the drive will stop and activate the fault stage. Deactivating the protection, setting parameter to 0, will reset the thermal stage of the motor to 0%.
7. 67. 6
7. 6
7. 67. 6
Motor thermal protection, break point currentMotor thermal protection, break point current
Motor thermal protection, break point current
Motor thermal protection, break point currentMotor thermal protection, break point current
The current can be set between 50.0150.0% x I This parameter sets the value for thermal current at frequencies above the break point on the thermal current curve. Refer to the figure 6-26. The value is set in percentage which refers to the name plate data of the motor, parameter 1
..
. 13, nominal current of the motor, not the drive's nominal output
..
current. The motor's nominal current is the current which the motor can withstand in direct on-line use without being overheated. If parameter 1
..
. 13 is adjusted, this parameter is automatically restored to the default
..
value. Setting this parameter (or parameter 1 current of the drive. Parameter 1 of the drive.
With the output current at IT the thermal stage will reach the nominal value (100%). The thermal stage changes by the square of the current. With output current at 75% from IT the thermal stage will reach 56% value and with output current at 120% from I the thermal stage would reach 144% value. The function will trip the device (refer par. 7 thermal stage will reach a value of 105%. The speed of change in thermal stage is determined with the time constant parameter 7 the longer it takes to reach the final temperature.
The thermal stage of the motor can be monitored through the display. Refer to the table for monitoring items. (User's Manual, table 7.3-1).
.
nMotor
..
. 13) does not affect the maximum output
..
..
. 7 alone determines the maximum output current
..
..
. 8. The bigger the motor
..
..
. 5) if the
..
T
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
aconacon
V
acon Page 41
aconacon
Multi-purpose Control Application IIMulti-purpose Control Application II
Figure 6-26 Motor thermal current IT curve.
Current limit par. 1. 7
I
7. 77. 7
7. 7
7. 77. 7
Par. 7. 6
Par. 7. 7
I
T
f
Overload area
UMCH7_91
Motor thermal protection, zero frequency currentMotor thermal protection, zero frequency current
Motor thermal protection, zero frequency current
Motor thermal protection, zero frequency currentMotor thermal protection, zero frequency current
The current can be set between 10.0150.0% x I
nMotor
Par. 7. 9
. This parameter sets the
value for thermal current at zero frequency. Refer to figure 6-26.
The default value is set assuming that there is no external fan cooling the motor. If an external fan is used this parameter can be set to 90% (or even higher).
The value is set as a percentage of the motor name plate data, parameter 1 motor's nominal current, not the drive's nominal output current. Motor's nominal current is the current which the motor can stand in direct on-line use without being overheated.
..
. 13,
..
If you change the parameter 1 parameter is automatically restored to the default value.
Setting this parameter (or parameter 1 does not affect to the maximum output current
of the drive. Parameter 1 the maximum output current of the drive.
..
. 7 alone determines
..
..
. 13 this
..
..
. 13)
..
7. 87. 8
7. 8
7. 87. 8
Motor thermal protection, time constantMotor thermal protection, time constant
Motor thermal protection, time constant
Motor thermal protection, time constantMotor thermal protection, time constant
This time can be set between 0.5300 minutes. This is the thermal time constant of the motor.The bigger the motor the bigger the time constant. The time constant is the time within which the calculated thermal stage has reached 63% of its final value.
The motor thermal time is specific for the motor design and it varies between different motor manufacturers.
The default value for the time constant is calculated basing on the motor name plate data given with parameters 1 either of these parameters is set, this parameter is set to default value.
If the motor's t6 -time is known (given by the motor manufacturer) the time constant
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
..
. 12 and 1
..
..
. 13. If
..
parameter could be set basing on t6 -time. As a rule of thumb, the motor thermal time constant in minutes equals to 2xt6 (t6 in seconds is the time a motor can safely operate at six times the rated current). If the drive is in stop stage the time constant is internally increased to three times the set parameter value. The cooling in the stop stage is based on convection and the time constant is increased.
Page 42
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
aconacon
V
acon
aconacon
7. 97. 9
7. 9
7. 97. 9
Motor thermal protection, breakpoint frequencyMotor thermal protection, breakpoint frequency
Motor thermal protection, breakpoint frequency
Motor thermal protection, breakpoint frequencyMotor thermal protection, breakpoint frequency
The frequency can be set between 10500 Hz. This is the breakpoint of thermal current curve. With frequencies above this point the thermal capacity of the motor is assumed to be constant. Refer to the figure 6-26. The default value is based on the motor's name plate data, parameter 1
..
. 11. It is 35
..
Hz for a 50 Hz motor and 42 Hz for a 60 Hz motor. More generally it is 70% of the frequency at field weakening point (parameter 6 11 or 6
..
. 3 will restore this parameter to its default value.
..
Motor temperature
..
. 3). Changing either parameter 1
..
Trip area
105%
Motor current
I/I
T
Time constant T
Motor temperature
*)
adjusted with parameter 7. 8
*)
Θ = (I/IT)2 x (1-e
Changed with motor size and
Trip/warning par. 7. 5
-t/T
)
Time
UMCH7_92
..
.
..
Figure 6-27 Calculating motor temperature.
Parameters 7. 10 7. 13, Stall protectionParameters 7. 10 7. 13, Stall protection
Parameters 7. 10 7. 13, Stall protection
Parameters 7. 10 7. 13, Stall protectionParameters 7. 10 7. 13, Stall protection GeneralGeneral
General
GeneralGeneral
Motor stall protection protects the motor from short time overload situations like a stalled shaft. The reaction time of stall protection can be set shorter than with motor thermal protection. The stall state is defined with two parameters, 7.11. Stall Current and 7.13. Stall Frequency. If the current is higher than the set limit and output frequency is lower than the set limit, the stall state is true. There is actually no real indication of the shaft rotation. Stall protection is a type of overcurrent protection.
7. 107. 10
7. 10
7. 107. 10
Stall protectionStall protection
Stall protection
Stall protectionStall protection
Operation:
0 = Not in use 1 = Warning
2 = Trip function Tripping and warning will display the same message code. If tripping is set on, the drive will stop and activate the fault stage. Setting the parameter to 0 will deactivate the protection and will reset the stall time counter to zero.
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
aconacon
V
acon Page 43
aconacon
7. 17. 1
7. 1
7. 17. 1
11
1
11
Stall current limitStall current limit
Stall current limit
Stall current limitStall current limit
Multi-purpose Control Application IIMulti-purpose Control Application II
I
The current can be set to 0.0 200% x I
nMotor
. In a stall stage the current has to be above this limit. Refer to figure 6-28. The value is set as a percentage of the motor's name plate data, parameter 1
. .
. 13,
. .
Stall area
motor's nominal current. If parameter 1
..
.13 is adjusted, this
..
Par. 7. 11
parameter is automatically restored to the default value.
Figure 6-28 Setting the stall
characteristics.
Par. 7. 13
f
UMCH7_11
7. 127. 12
7. 12
7. 127. 12
7. 137. 13
7. 13
7. 137. 13
Stall timeStall time
Stall time
Stall timeStall time
The time can be set between 2.0120 s. This is the maximum allowed time for a stall stage. There is an internal up/down counter to count the stall time. Refer to figure 6-29. If the stall time counter value goes above this limit the protection will cause a trip (refer to parameter 7
Maximum stall frequencyMaximum stall frequency
Maximum stall frequency
Maximum stall frequencyMaximum stall frequency
The frequency can be set between 1f
max
(par. 1
..
. 2).
..
..
. 10).
..
Par. 7. 12
Stall time counter
Trip area
Trip/warning par. 7. 10
In a stall state, the output frequency has to be smaller than this limit. Refer to figure 6-28.
UMCH7_12
Figure 6-29 Counting the stall time.
Time
Stall No stall
Parameters 7. 14 7. 17, Underload protectionParameters 7. 14 7. 17, Underload protection
Parameters 7. 14 7. 17, Underload protection
Parameters 7. 14 7. 17, Underload protectionParameters 7. 14 7. 17, Underload protection GeneralGeneral
General
GeneralGeneral
The purpose of motor underload protection is to ensure that there is load on the motor when the drive is running. If the motor loses its load there might be a problem in the process, e.g. a broken belt or dry pump.
Motor underload protection can be adjusted by setting the underload curve with parameters
. .
7
. 15 and 7
. .
curve set between zero frequency and the field
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
..
. 16. The underload curve is a squared
..
Service: +358-40-8371 150 E-mail: vacon@vacon.com
weakening point. The protection is not active below 5Hz (the underload counter value is stopped). Refer to figure 6-30.
Page 44
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
aconacon
V
acon
aconacon
The torque values for setting the underload curve are set in percentage which refer to the nominal torque of the motor. The motor's name plate data, parameter 1. 13, the motor's nominal current and
7. 147. 14
7. 14
7. 147. 14
Underload protectionUnderload protection
Underload protection
Underload protectionUnderload protection
Operation:
0 = Not in use 1 = Warning
2 = Fault Tripping and warning will display the same message code. If tripping is set active the drive will stop and activate the fault stage. Deactivating the protection by setting the parameter to 0 will reset the underload time counter to zero.
7. 157. 15
7. 15
7. 157. 15
Underload protection, field weakening area loadUnderload protection, field weakening area load
Underload protection, field weakening area load
Underload protection, field weakening area loadUnderload protection, field weakening area load
The torque limit can be set between 20.0150 % x T
This parameter gives the value for the minimum torque allowed when the output frequency is above the field weakening point. Refer to figure 4.5-22. If parameter 1
..
. 13 is adjusted, this
..
parameter is automatically restored to the default value.
the drive's nominal current ICT are used to find the scaling ratio for the internal torque value. If other than nominal motor is used with the drive, the accuracy of the torque calculation decreases.
.
nMotor
Torque
Par. 7. 15
7. 167. 16
7. 16
7. 167. 16
7. 177. 17
7. 17
7. 177. 17
Figure 6-30 Setting of minimum load.
Underload protection, zeroUnderload protection, zero
Underload protection, zero
Underload protection, zeroUnderload protection, zero frequency loadfrequency load
frequency load
frequency loadfrequency load
The torque limit can be set between 10.0150 % x T
nMotor
.
Par. 7. 16
5 Hz
Underload area
Fieldweakening point par. 6. 3
f
UMCH7_15
This parameter gives value for the minimum torque allowed with zero frequency. Refer to figure 6-30. If parameter 1
..
. 13 is adjusted this parameter is automatically
..
restored to the default value.
Underload timeUnderload time
Underload time
Underload timeUnderload time
This time can be set between 2.0600.0 s. This is the maximum allowed time for an underload state. There is an internal up/ down counter to accumulate the underload time. Refer to figure 6-31. If the underload counter value goes above this limit the protection will cause a trip (refer to the parameter 7
. .
. 14). If the drive is stopped the underload counter
. .
is reset to zero.
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
aconacon
V
acon Page 45
aconacon
Figure 6-31 Counting the under-
load time.
Multi-purpose Control Application IIMulti-purpose Control Application II
Underload time counter
Trip area
Par. 7. 17
Underl. No underl.
Trip/warning par. 7. 14
UMCH7_17
Time
7. 187. 18
7. 18
7. 187. 18
.
7. 197. 19
7. 19
7. 197. 19
7. 207. 20
7. 20
7. 207. 20
Phase supervision of the supply voltagePhase supervision of the supply voltage
Phase supervision of the supply voltage
Phase supervision of the supply voltagePhase supervision of the supply voltage
0 = No action
1 = Warning
2 = Fault
By setting the parameter value to zero, the phase supervision of the supply voltage
will not cause tripping
Thermistor input of IO-ExpanderThermistor input of IO-Expander
Thermistor input of IO-Expander
Thermistor input of IO-ExpanderThermistor input of IO-Expander
0 = No action
1 = Warning
2 = Fault
The thermistor connected to the thermistor input of the I/O-expander board supervises
the temperature of the motor. With parameter 7.19 the response of the frequency
converter can be programmed when the thermistor indicates overtemperature.
Response to the fieldbus faultResponse to the fieldbus fault
Response to the fieldbus fault
Response to the fieldbus faultResponse to the fieldbus fault
0 = No response
1 = Warning message
2 = Fault message, stop mode after fault according to parameter 4.7
A warning or a fault action and message is generated from the fieldbus card if the
error occurs of the bus system physical layer.
8. 18. 1
8. 1
8. 18. 1
8. 28. 2
8. 2
8. 28. 2
Automatic restart: number of triesAutomatic restart: number of tries
Automatic restart: number of tries
Automatic restart: number of triesAutomatic restart: number of tries
Automatic restart: trial timeAutomatic restart: trial time
Automatic restart: trial time
Automatic restart: trial timeAutomatic restart: trial time
The Automatic restart function restarts the frequency converter after the faults selected
..
with parameters 8
parameter 8
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
. .
. 3.
. .
Service: +358-40-8371 150 E-mail: vacon@vacon.com
..
. 48
. 8. The Start function for Automatic restart is selected with
..
..
Page 46
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
Number of faults
during t = t 4 3
trial
t
trial
t
trial
aconacon
V
acon
aconacon
8. 38. 3
8. 3
8. 38. 3
2 1
Three faults
RUN STOP
Figure 6-32 Automatic restart
Parameter 8
..
. 1 determines how many automatic restarts can be made during the
..
trial time set by the parameter 8
..
. 2.
..
Par. 8. 2 = 3 t
trial
Four faults
= par. 8. 1
t
UD009K25
The time counting starts from the first autorestart. If the number of restarts does not exceed the value of the parameter 8
..
. 1 during the trial time, the counting is cleared
..
after the time is elapsed and next fault starts the counting again.
Automatic restart, start functionAutomatic restart, start function
Automatic restart, start function
Automatic restart, start functionAutomatic restart, start function
The parameter defines the start mode:
0 = Start with ramp 1 = Flying start, see parameter 4
..
. 6.
..
8. 48. 4
8. 4
8. 48. 4
8. 58. 5
8. 5
8. 58. 5
8. 68. 6
8. 6
8. 68. 6
8. 78. 7
8. 7
8. 78. 7
8. 88. 8
8. 8
8. 88. 8
Automatic restart after undervoltage tripAutomatic restart after undervoltage trip
Automatic restart after undervoltage trip
Automatic restart after undervoltage tripAutomatic restart after undervoltage trip
0 = No automatic restart after undervoltage fault trip 1 = Automatic restart after undervoltage fault condition returns to normal
condition (DC-link voltage returns to the normal level)
Automatic restart after overvoltage tripAutomatic restart after overvoltage trip
Automatic restart after overvoltage trip
Automatic restart after overvoltage tripAutomatic restart after overvoltage trip
0 = No automatic restart after overvoltage fault trip 1 = Automatic restart after overvoltage fault condition returns to the normal
condition (DC-link voltage returns to the normal level)
Automatic restart after overcurrent tripAutomatic restart after overcurrent trip
Automatic restart after overcurrent trip
Automatic restart after overcurrent tripAutomatic restart after overcurrent trip
0 = No automatic restart after overcurrent fault trip 1 = Automatic restart after overcurrent faults
Automatic restart after reference fault tripAutomatic restart after reference fault trip
Automatic restart after reference fault trip
Automatic restart after reference fault tripAutomatic restart after reference fault trip
0 = No automatic restart after reference fault trip 1 = Automatic restart after analog current reference signal (420 mA)
returns to the normal level (>4 mA)
Automatic restart after over-/undertemperature fault tripAutomatic restart after over-/undertemperature fault trip
Automatic restart after over-/undertemperature fault trip
Automatic restart after over-/undertemperature fault tripAutomatic restart after over-/undertemperature fault trip
0 = No automatic restart after temperature fault trip 1 = Automatic restart after heatsink temperature has returned to its normal
level between -10°C—+75°C.
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
aconacon
V
acon Page 47
aconacon
TT
orque controlorque control
T
orque control
TT
orque controlorque control
Multi-purpose Control Application IIMulti-purpose Control Application II
Torque control can be activated either by setting parameter 6.1 to torque control or with digital input DIA3 (parameter 2.2=10). Torque reference source is selected with parameter
9.1 and reference scaling with parameters 9.2 and 9.3.
9.19.1
9.1
9.19.1
9.29.2
9.2
9.29.2
9.39.3
9.3
9.39.3
9.49.4
9.4
9.49.4
9.59.5
9.5
9.59.5
TT
orque reference selectionorque reference selection
T
orque reference selection
TT
orque reference selectionorque reference selection
Defines the source for torque reference value: 0 = None 1 = U
in
2 = I
in
3 = Panel torque reference r2 4 = Ain1 (option board) 5 = Ain2 (option board) 6 = Fieldbus control
TT
orque reference scaling biasorque reference scaling bias
T
orque reference scaling bias
TT
orque reference scaling biasorque reference scaling bias
TT
orque reference scaling gainorque reference scaling gain
T
orque reference scaling gain
TT
orque reference scaling gainorque reference scaling gain
The additional scaling function can be used for scaling the torque reference. The torque reference is always fed to the torque controller even if it is not activated. T
= gain × T
ref. out
TC time constantTC time constant
TC time constant
TC time constantTC time constant
ref. in
+ bias
Defines the time constant for the torque controller. A short time constant means fast response.
TC min. control limitTC min. control limit
TC min. control limit
TC min. control limitTC min. control limit
Defines frequency limit below which the frequency converter operates normally in frequency control mode.
The internal torque calculation is inaccurate at low speeds (< nominal slip of the motor). It is recommended to operate in frequency control operation mode at low speeds. The reference value in frequency controlled operation mode is selected with para­meter 1. 5.
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Page 48
Fieldbus controlFieldbus control
Fieldbus control
Fieldbus controlFieldbus control
Fieldbus control can be activated with parameter 10.1. Then the frequency or speed refer­ence comes from the fieldbus as well as the Start/Stop and Reverse control.
First two parameters in group 10 concern all fieldbuses. Parameters 10.3 - 10.6 are only for Modbus, parameters 10.7 - 10.13 only for Profibus and 10.14 only for LonWorks.
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
aconacon
V
acon
aconacon
10. 110. 1
10. 1
10. 110. 1
10.210.2
10.2
10.210.2
Parameters 10.3 - 10.6 only for Modbus protocolParameters 10.3 - 10.6 only for Modbus protocol
Parameters 10.3 - 10.6 only for Modbus protocol
Parameters 10.3 - 10.6 only for Modbus protocolParameters 10.3 - 10.6 only for Modbus protocol
10.310.3
10.3
10.310.3
10.410.4
10.4
10.410.4
Fieldbus controlFieldbus control
Fieldbus control
Fieldbus controlFieldbus control
Defines the active control source:
0:0:
0: control via I/O terminals
0:0: 1:1:
1: control via Fielbus board
1:1:
DIC1 functionDIC1 function
DIC1 function
DIC1 functionDIC1 function
0:0:
0: Fieldbus control, contact open = Active control source are I/O terminals
0:0:
contact closed = Active control source is the Fieldbus
1:1:
1: External Fault, closing contact = Fault is shown and motor is stopped
1:1:
Slave addressSlave address
Slave address
Slave addressSlave address
Defines slave device address. Maximum value for this parameter is 247 and minimum is 1.
Baud RateBaud Rate
Baud Rate
Baud RateBaud Rate
1:1:
1: 300 baud
1:1: 2:2:
2: 600 baud
2:2: 3:3:
3: 1200 baud
3:3: 4:4:
4: 2400 baud
4:4: 5:5:
5: 4800 baud
5:5: 6:6:
6: 9600 baud
6:6: 7:7:
7: 19200 baud
7:7:
board
when the input is active
10.510.5
10.5
10.510.5
10.610.6
10.6
10.610.6
Parameters 10.7 to 10.13 only for Profibus DP protocolParameters 10.7 to 10.13 only for Profibus DP protocol
Parameters 10.7 to 10.13 only for Profibus DP protocol
Parameters 10.7 to 10.13 only for Profibus DP protocolParameters 10.7 to 10.13 only for Profibus DP protocol
10.710.7
10.7
10.710.7
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Parity typeParity type
Parity type
Parity typeParity type
0:0:
0: None
0:0: 1:1:
1: Even
1:1: 2:2:
2: Odd
2:2:
Modbus time-outModbus time-out
Modbus time-out
Modbus time-outModbus time-out
The Modbus time-out determines how long the Fieldbus board waits for a message from a master device and is specified in seconds. Time can be set between 0 - 3600 s. Time 0 s = No time-out
Profibus slave addressProfibus slave address
Profibus slave address
Profibus slave addressProfibus slave address
Defines slave device address. Maximum value for this parameter is 126 and minimum 2.
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
aconacon
V
acon Page 49
aconacon
Multi-purpose Control Application IIMulti-purpose Control Application II
10.810.8
10.8
10.810.8
10.910.9
10.9
10.910.9
10.1010.10
10.10
10.1010.10
10.110.1
10.1
10.110.1
10.1210.12
10.12
10.1210.12
10.1310.13
10.13
10.1310.13
Profibus baud rateProfibus baud rate
Profibus baud rate
Profibus baud rateProfibus baud rate
1:1:
1: 9.6 kbaud
1:1: 2:2:
2: 19.2 kbaud
2:2: 3:3:
3: 93.75 kbaud
3:3: 4:4:
4: 187.5 kbaud
4:4: 5:5:
5: 500 kbaud
5:5: 6:6:
6: 1.5 Mbaud
6:6: 7:7:
7: 3 Mbaud
7:7: 8:8:
8: 6 Mbaud
8:8: 9:9:
9: 12 Mbaud
9:9: 10:10:
10: AUTO (Automatic baud rate select)
10:10:
Profibus PPO TProfibus PPO T
Profibus PPO T
Profibus PPO TProfibus PPO T
ypeype
ype
ypeype
Selection of profibus PPO type.
1:1:
1: PPO 1 (Parameter data 8 bytes, Control data 4 bytes)
1:1: 2:2:
2: PPO 2 (Parameter data 8 bytes, Control data 12 bytes)
2:2: 3:3:
3: PPO 3 (Control data 4 bytes)
3:3: 4:4:
4: PPO 4 (Control data 12 bytes)
4:4:
Profibus process Data 1Profibus process Data 1
Profibus process Data 1
Profibus process Data 1Profibus process Data 1
11
Profibus process Data 2Profibus process Data 2
1
Profibus process Data 2
11
Profibus process Data 2Profibus process Data 2 Profibus process Data 3Profibus process Data 3
Profibus process Data 3
Profibus process Data 3Profibus process Data 3 Profibus process Data 4Profibus process Data 4
Profibus process Data 4
Profibus process Data 4Profibus process Data 4
Selection of profibus process data source.
Value 1...22 Number of actual value (= V1...V22 in Monitoring Menu)
99 Active fault code
Parameter 10.14 only for LonWorks protocolParameter 10.14 only for LonWorks protocol
Parameter 10.14 only for LonWorks protocol
Parameter 10.14 only for LonWorks protocolParameter 10.14 only for LonWorks protocol
10.1410.14
10.14
10.1410.14
LonWorks service buttonLonWorks service button
LonWorks service button
LonWorks service buttonLonWorks service button
Changing the value of this parameter from 0 to 1 or vice versa and pressing the Enter button causes the unique LonWorks ID number to be sent to the network.
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Multi-purpose Control Application IIMulti-purpose Control Application II
Page 50
77
FF
AULAUL
7
F
AUL
77
FF
AULAUL
T CODET CODE
T CODE
T CODET CODE
Multi-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
The Multipurpose Application II has an extra fault code:
Fault number Fault Possible cause Checking
aconacon
V
acon
aconacon
27 Fieldbus
8 MONIT8 MONIT
8 MONIT
8 MONIT8 MONIT
communication error
ORING DAORING DA
ORING DA
ORING DAORING DA
TT
T
TT
AA
A
AA
Fieldbus board has detected the reset or error of the Bus system (physical layer)
Reset the fault and restart again. If the fault comes again:
- check the host system
- check the cables
The Multipurpose Application II has extra items for monitoring (V1 - V24). See table 8-1
Data Data Unit Description number name
V1 Output frequency Hz Frequency to the motor V2 Motor speed rpm Calculated motor speed V3 Motor current A Measured motor current V4 Motor torque % Calculated actual torque/nominal torque of the unit V5 Motor power % Calculated actual power/nominal power of the unit V6 Motor voltage V Calculated motor voltage V7 DC-link voltage V Measured DC-link voltage V8 Temperature °C Temperature of the heat sink V9 Operating day counter DD.dd Operating days 1), not resettable
V10 Operating hours, HH.hh Operating hours 2), can be reset with
"trip counter" programmable button #3
V11 MW-hours MWh Total MW-hours, not resettable
V12 MW-hours, MWh MW-hours, can be reset with programmable
"trip counter" button #4 V13 Voltage/analogue input V Voltage of the terminal Uin+ (term. #2) V14 Current/analogue input mA Current of terminals Iin+ and Iin- (term. #4, #5) V15 Digital input status, gr. A V16 Digital input status, gr. B V17 Digital and relay output
status V18 Control program Version number of the control software
V19 Unit nominal power kW Shows the power size of the unit V20 Motor temperature rise % 100%= temperature of motor has risen to nominal V21 Reference frequency Hz Frequency reference V22 Torque reference % Torque reference when torque control in use V23 Digital inputs (opt. board) V24 Fieldbus status
Used with Profibus option board onlyUsed with Profibus option board only
Used with Profibus option board only
Used with Profibus option board onlyUsed with Profibus option board only
0 = Master-Slave communication not started 1 = Master-Slave communication is starting up 2 = Master-Slave communication started and OK.
..
.
..
1)
DD = full days, dd = decimal part of a day
2)
HH = full hours, hh = decimal part of an hour
Table 8-1 Monitoring items
V acon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
E-mail: vacon@vacon.com
Ud00182d
09.10.2000
Author: Jaana Kukkonen
phone: +358-(
212 331
email: jaana.kukkonen@vacon.com fax: +358-(0)201-212 205
0)201-
Vacon Plc
P.O.Box 25
Runsorintie 7
65381 VAASA
FINLAND
Tel: +358-(0)201-2121
Fax: +358-(0)201-212 205
Service: +358-40-8371 150
Loading...