Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
vacon • 2Safety
9000.emf
13006.emf
9001.emf
9000.emf
9000.emf
9000.emf
9000.emf
9000.emf
9000.emf
1.SAFETY
This manual contains clearly marked cautions and warnings that are intended for your personal
safety and to avoid any unintentional damage to the product or connected appliances.
Please read the information included in cautions and warnings carefully.
The cautions and warnings are marked as follows:
Table 1. Warning signs
= DANGER! Dangerous voltage
= WARNING or CAUTION
= Caution! Hot surface
1.1Danger
The components of the power unit are live when the drive is connected to mains
potential. Coming into contact with this voltage is extremely dangerous and may
cause death or severe injury.
The motor terminals U, V, W and the brake resistor terminals are live when the
AC drive is connected to mains, even if the motor is not running.
After disconnecting the AC drive from the mains, wait until the indicators on the
keypad go out (if no keypad is attached, see the indicators on the cover). Wait 5
more minutes before doing any work on the connections of the drive. Do not open
the cover before this time has expired. After expiration of this time, use a measuring equipment to absolutely ensure that no
absence of voltage before starting any electrical work!
The control I/O-terminals are isolated from the mains potential. However, the
relay outputs and other I/O-terminals may have a dangerous control voltage
present even when the AC drive is disconnected from mains.
voltage is present.
Always ensure
Before connecting the AC drive to mains make sure that the front and cable covers of the drive are closed.
During a ramp stop (see the Application Manual), the motor is still generating
voltage to the drive. Therefore, do not touch the components of the AC drive
before the motor has completely stopped. Wait until the indicators on the keypad
go out (if no keypad is attached, see the indicators on the cover). Wait additional 5
minutes before starting any work on the drive.
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
1
Safetyvacon • 3
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
1.2Warnings
The AC drive is meant for fixed installations only.
Do not perform any measurements when the AC drive is connected to the mains.
The earth leakage current of the AC drives exceeds 3.5mA AC. According to stan-
dard EN61800-5-1, a reinforced protective ground connection must be ensured.
See Chapter 1.3.
If the AC drive is used as a part of a machine, the machine manufacturer is responsible for providing the machine with a supply disconnecting device (EN
60204-1).
Only spare parts delivered by VACON
®
can be used.
At power-up, power break or fault reset the motor will start immediately if the
start signal is active, unless the pulse control for
Start/Stop logic has been selected
Furthermore, the I/O functionalities (including start inputs) may change if parameters, applications or software are changed. Disconnect, therefore, the motor if
an unexpected start can cause danger.
The motor starts automatically after automatic fault reset if the auto restart
function is activated. See the Application Manual for more detailed information.
Prior to measurements on the motor or the motor cable, disconnect the motor
cable from the AC drive.
Do not touch the components on the circuit boards. Static voltage discharge may
damage the components.
Check that the EMC level of the AC drive corresponds to the requirements of your
supply network.
Wear protective gloves when you do mounting, cabling or maintenance operations. There can be sharp edges in the AC drive that can cause cuts.
.
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
1
vacon • 4Safety
13006.emf 13006.emf
1.3Earthing and earth fault protection
CAUTION!
The AC drive must always be earthed with an earthing conductor connected to the earthing terminal
marked with .
The earth leakage current of the drive exceeds 3.5mA AC. According to EN61800-5-1, one or more
of the following conditions for the associated protective circuit must be satisfied:
a)The protective conductor must have a cross-sectional area of at least 10 mm2 Cu or 16
mm2 Al, through its total run.
b)Where the protective conductor has a cross-sectional area of less than 10 mm2 Cu or 16
mm2 Al, a second protective conductor of at least the same cross-sectional area must be
provided up to a point where the protective conductor has a cross-sectional area not less
than 10 mm2 Cu or 16 mm2 Al.
c)Automatic disconnection of the supply in case of loss of continuity of the protective conduc-
tor.
The cross-sectional area of every protective earthing conductor which does not form part of the
supply cable or cable enclosure must, in any case, be not less than:
-2.5mm
-4mm
2
if mechanical protection is provided or
2
if mechanical protection is not provided.
The earth fault protection inside the AC drive protects only the drive itself against earth faults in the
motor or the motor cable. It is not intended for personal safety.
Due to the high capacitive currents present in the AC drive, fault current protective switches may
not function properly.
Do not perform any voltage withstand tests on any part of the AC drive. There is
a certain procedure according to which the tests must be performed. Ignoring
this procedure may result in damaged product.
NOTE! You can download the English and French product manuals with applicable safety,
warning and caution information from
REMARQUE Vous pouvez télécharger les versions anglaise et française des manuels produit
contenant l’ensemble des informations de sécurité, avertissements et mises en garde
applicables sur le site http://drives.danfoss.com/knowledge-center/technical-documentation/
.
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
1
BACnet - general infovacon • 5
BACnet IP - Ethernet
Ethernet to
MS/TP
Router
Switch
BACnet IP
BACnet MS/TP
7061.emf
2.BACNET - GENERALINFO
BACnet stands for ‘Building Automation and Control Networks’. It is the common name for the
communication standard ISO 16484-5 which defines the methods and the protocol for cooperating
building automation devices to communicate. Devices can be designed to operate using BACnet
communication protocol as well as utilising BACnet protocol to communicate between systems.
BACnet is an internationally accepted protocol for building automation (e.g. lightning control, air
conditioning and heating automation) and control over a communications network.
BACnet provides a method by which computer-based control equipment, from different
manufacturers can work together, or 'interoperate'. For this to be achieved, components must be
able to exchange and understand BACnet data messages.
®
Your VACON
100 family AC drive is equipped with BACnet support as standard.
Figure 1. Principal example diagram of BACnet
®
If you need to contact VACON
problem together with the Drive Info File taken with VACON
download the Service Information file with the VACON
service in problems related to BACnet, send a description of the
®
®
Live to your local support. You can
Live tool. In BACnet/IP networks, also send
a log file captured with the Wireshark tool that contains the error situation.
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
2
vacon • 6BACnet technical data
3.BACNETTECHNICALDATA
3.1BACnet MS/TP protocol
Table 2.
InterfaceRS-485
Data transfer methodRS-485 MS/TP, half-duplex
Transfer cable
Connections and
communications
Connector
Electrical isolationFunctional
BACnet MS/TP
Baud rate
3.2BACnet IP protocol
Interface100BaseTX, IEEE 802.3 compatible
Data transfer methodEthernet half/full -duplex
Data transfer speed10/100 MBit/s, autosensing
Connections and
communications
ProtocolBACnet over UDP/IP
ConnectorShielded RJ45 connector.
Cable typeCAT5e STP
STP (Shielded Twisted Pair), type
Belden 9841 or similar
2.5 mm
As described in ANSI/ASHRAE Standards 135-2010 Ver.1 Rev.12
9600, 19200, 38400 and 76800
baud(supports autobaud detection)
Table 3.
2
BACnet IP
IP address modeSelectable: Static or DHCP
As described in ANSI/ASHRAE Standards 135-2010 Ver.1 Rev.12
3.3ACD (Address Conflict Detection)
The VACON® 100 family AC drives implement the ACD algorithm (IETF RFC 5227).
The ACD algorithm tries to actively detect if the IP address configured to this device is been used by
another device in the same network. To accomplish this, ACD sends four ARP request packets when
the device's Ethernet interface goes up or when its IP address changes. ACD prevents the use of the
Ethernet interface until the ARP probing finishes. This delays the startup of fieldbus protocols about
one second. During the delay or after it, the ACD passively checks incoming ARP messages for use
of the device's IP address.
If another device with the same IP address is detected, the ACD will try to defend its IP address with
a single ARP message. If the other device with the same IP address also supports ACD, it should
stop using the address. If not, the ACD will close the Ethernet connection and indicate the situation
with an Alarm. This is done according the "DefendWithPolicyB". Acknowledging of the Alarm is not
possible if the problem is active. ACD opens Ethernet connection if the other device with the same
IP address disappears from the network. Alarm can be acknowledged after this. Other policies are
not supported. If the fieldbus protocol has been active, a fieldbus fault may be activated (depends
on the fieldbus and drive application configuration).
3
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Programmingvacon • 7
4.PROGRAMMING
You will find basic information on how to use the control keypad in the Application Manual of your
VACON
Below you will find some examples of navigation paths to the fieldbus parameters.
®
100 family AC drive.
Table 4.
1. First ensure that the right fieldbus protocol is selected.
Activating BACnet MSTP (P5.8.1.1)
Main Menu > I/O and Hardware > RS-485 > Common settings > Protocol > BACnet MSTP <
Activating BACnet IP (P5.9.3.1.4)
Main Menu > I/O and Hardware > Ethernet > Bacnet IP > Protocol in
use > Yes <
2. Select
3. Activate Remote control.
4. Select controlling fieldbus
5. Set up Protocol Parameters.
‘Fieldbus control’ as the Remote Control Place.
Control Place (P3.2.1)
Main Menu > Parameters > Start/Stop Setup > Rem Control Place >
FieldbusCTRL <
Local/Remote (P3.2.2)
Main Menu > Parameters > Start/Stop Setup > Local/Remote >
Remote <
Controlling Fieldbus (P5.13.1)
Main Menu > I/O and Hardware > Fieldbus General > Controlling
Fieldbus > Automatic/BACnet IP/RS-485 <
BACnet MS/TP parameters see Chapter 4.1
BACnet IP parameters see Chapter 4.2
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
4
vacon • 8Programming
4.1BACnet MS/TP parameters and monitoring values
Table 5. Parameters related with BACnet used through MS/TP
CodeParameterMinMaxDefaultIDDescription
Communication speed
1 = 9600
P5.8.3.1.1Baud rate96007680096002392
P5.8.3.1.2MAC Address112712331BACnet device MAC address
P5.8.3.1.3Instance number04194304automatic2332
P5.8.3.1.4MaxMaster11271272561
P5.8.3.1.5
P5.8.3.1.6MaxAPDUcycle06553502554
Communication
time-out
065535102333
2 = 19200
3 = 38400
4 = 76800
5 = Autobaud
Device Object's instance number.
0 = Automatically
generated from the last 22 bit from
Ethernet MAC address.
Max Master parameter of device object.
This can be used to reduce poll for
master cycles.
Defines the number of seconds after
which a communication timeout is indicated after a communication break.
Value 0 disables this feature.
Defines the number of seconds after
which the next application level message is shown after a communication
break. Value 0 disables this feature.
Table 6. Monitoring values
CodeParameterMinMaxIDDescription
V5.8.3.2.1 Fieldbus protocol status INITIALIZING INACTIVE2393See Table 11
V5.8.3.2.2Communication status0.099.9992394
V5.8.3.2.3Actual instance041943042395
See fault codes
V5.8.3.2.4Last fault
V5.8.3.2.5UartDBG0.0.0
V5.8.3.2.6ActiveCOVcount0202558Number of active COV subscriptions
V5.8.3.2.7Control Word0FFFFFFFF2397Control word monitor value
V5.8.3.2.8Status Word0FFFFFFFF2398Status word monitor value
(table Table 10)2396Information about the latest fault detected.
32767.
32767.
32767
2559
Counter for failed and good messages
failed msg's <-> good msg's
Actual instance in use. If the instance
parameter is 0, the generated instance
number shows here.
Uart error counters in the following order:
framing errors.
overrun errors.
parity errors.
4
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
P5.9.1.5Default gateway--02485Default gateway in use
P5.9.1.6MAC address---2486MAC address
Duplicate IP Detec-
tion
0112569
0 = Fixed IP
1 = DHCP with AutoIP
This is setting for enabling ACD
(See Chapter 3.3). When disabled
drive does not check for or react to
address conflict situation.
0 = Disabled
1 = Enabled
The parameter is in use if P5.9.1.1
= 0/Fixed IP
The parameter is in use if P5.9.1.1
= 0/Fixed IP
The parameter is in use if P5.9.1.1
= 0/Fixed IP
4.2.2BACnet IP settings
Table 8. Parameters related with BACnet used through Ethernet
CodeParameterMinMaxDefaultIDDescription
Device Object’s instance
P5.9.3.1.1Instance number04194304automatic2406
P5.9.3.1.2BACnet Port Number4780847823478082538
P5.9.3.1.2Communication time-out065535102407
P5.9.3.1.3Protocol in use0102408Activates BACnet IP protocol
P5.9.3.1.4ForeignDeviceSub menu for Foreign Device setting
P5.9.3.1.5.1ForeignDeviceNoYesNo2555
P5.9.3.1.5.2BBMD IP192.168.0.12409
P5.9.3.1.5.3BBMD Port4780847823478082410BBMD port number
P5.9.3.1.5.4RegistrationInterval165535102411
0 = Automatically generated from
the last 22 bit from the Ethernet
MAC address.
UDP port for BACnet IP communication.
Defines the number of seconds
after which a communication
timeout is indicated after a communication break. Value 0 disables this feature.
Activates foreign device registration
IP address of BBMD device to
send registration
Registration interval to keep a
live connection to BBMD.
NOTE! Registration message
TTL is twice as long as this time.
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
4
vacon • 10Programming
Table 9. Monitoring values
CodeParameterMinMaxIDDescription
V5.9.3.2.1
V5.9.3.2.2
V5.9.3.2.3Actual instance041943042414
V5.9.3.2.4Last fault
V5.9.3.2.5ActiveCOVcount0202557Number of active COV subscriptions
V5.9.3.2.6Control Word0FFFFFFFF2397Control word monitor value
V5.9.3.2.7Status Word0FFFFFFFF2398Status word monitor value
Fieldbus protocol
status
Communication
status
INITIALIZING INACTIVE2412See Table 11
0.099.9992413
See fault codes
(Table 10)
2556The fault code of the latest fault detected.
Counter for failed and good messages
failed msg's <-> good msg's
Actual instance is use. In case instance parameter is zero you can see here generated
instance number
Table 10. Fault Code values
Fault
Number
0No faultNo fault detected since the last power-up.
1Connection timeout Timeout occurred in communication.
2MAC addressDuplicate MAC address detected.
3Autobaud ErrorError during baudrate detection.
4Ethernet link lostEthernet cable disconnected during communication.
Fault TextDescription
Table 11. Fieldbus Protocol Status
ValueTex tDescription
1INITIALIZINGProtocol is starting
2STOPPEDProtocol is stopped
3OPERATIONALCommunicating
4FAULTEDTimeout/APDU time expired
5INACTIVENo communication
4
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Programmingvacon • 11
4.3BACnet MS/TP parameter descriptions
4.3.1BACnet MS/TP Parameters
P5.8.3.1.1BAUDRATE
Select the communication speed for the network. The default value is 9600 baud. If Autobauding is
selected, the node will detect the baudrate. There must be at least one device in the bus to select
the baud rate and to start token transmitting. When the baudrate is detected, it is saved into this
parameter.
NOTE! Autobauding is disabled after baudrate is detected.
P5.8.3.1.2MAC ADDRESS
The parameters of every device must be set before connecting to the bus. Especially the
parameters
The first parameter, BACnet MAC (Medium Access Control) address, must be unique on the
network to which it is connected. The same MAC address may be used on a device on another
network within the internetwork.
Addresses 128-254 are reserved for slaves. Addresses 1-127 are valid for both masters and slaves.
The portion of the address space that is actually used for masters in a particular installation is
determined by the value of the Max_Master property of the Device object.
MAC address and Baud rate must be the same as in the master’s configuration.
It is recommended that MAC address 0 be reserved for use by the MS/TP router. 255 is reserved for
broadcasts.
P5.8.3.1.3INSTANCENUMBER
The Device Object's Instance number must be unique across the entire BACnet internetwork
because it is used to uniquely identify the BACnet devices. It may be used to conveniently identify
the BACnet device from other devices during installation.
If 0 (default) is selected, the Device Instance number is generated from the last 22 bit of the
Ethernet MAC address. This unique number is then shown in the Monitor menu (actual instance).
P5.8.3.1.4MAXMASTER
This parameter defines the last possible master on the network segment. Each master node is
responsible for searching new devices from network using the ‘poll for master’ messages. The
nodes are searched up to MAC address defined by MaxMaster parameter.
This parameter affects the cycle time of the token. We recommend to use the highest MAC address
value in the network for this parameter.
P5.8.3.1.5COMMUNICATION TIMEOUT
The BACnet MS/TP indicates timeout error if the node is not receiving a token within time defined
by this parameter. It can be used to detect communication loss to other nodes. Time unit is
seconds.
NOTE! Application parameter P3.9.1.6 (ID 733) can be use to define action for communication
timeout.
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
4
vacon • 12Programming
P5.8.3.1.6MAXAPDUCYCLE
This parameter defines the maximum time in seconds between APDU messages addressed to this
node. The APDU messages are Application layer messages, for example, 'ReadParameter' and
'Write Parameter' messages. This can be used to detect communication loss to the controlling
node.
NOTE! The application parameter P3.9.1.6 (ID 733) can be used to define the action for
communication timeout.
4.3.2BACnet MS/TP monitoring values
V5.8.3.2.1FIELDBUSPROTOCOLSTATUS
Fieldbus Protocol Status tells the status of the protocol.
V5.8.3.2.2COMMUNICATIONSTATUS
The Communication status shows how many error and how many good messages the AC drive has
received. The Communication status includes a common error counter that counts CRC and parity
errors and a counter for good messages.
Only messages to the current slave in use are counted in the good messages, not MS/TP token
packages.
Table 12 .
Good messages
0…999
Number of messages received without errors
Bad Frames
0…99
V5.8.3.2.3ACTUALINSTANCENUMBER
Number of messages received with
errors
Shows the actual instance number.
V5.8.3.2.4LASTFAULT
This monitor value consist of text string that gives extra information about the fault condition. Can
be used to track the reason for communication timeout. See Table 10.
V5.8.3.2.5UARTDBG
This is advanced debug information from RS-485 uart module. It shows parity, framing and overrun
errors occurred while receiving the MSTP messages.
4
V5.8.3.2.6ACTIVECOVCOUNT
This shows the number of active COV subscriptions on the device.
V5.8.3.2.7 CONTROL WORD
Shows control word that is written by BACnet MS/TP into drive application. This is shown in panel
as hexadecimal format.
V5.8.3.2.8 STATUS WORD
Shows control word that is written by BACnet MS/TP into drive application. This is shown in panel
as hexadecimal format.
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.