Danfoss VACON 1000 Operating guide

Operating Guide
VACON® 1000
drives.danfoss.com
VACON® 1000
Operating Guide

Contents

1
1.1
Purpose of this Operating Guide 8
Additional Resources 8
1.2
Manual Version 8
1.3
1.4
Disposal 8
2
Safety 9
2.1
Safety Symbols 9
2.2
Qualified Personnel 9
2.3
Danger and Warnings 9
2.4
Cautions and Notices 10
Product Overview 13
3
Product Characteristics 13
3.1
Contents
3.2
Applications 13
3.3
System Hardware 14
3.3.1
Control Cabinet 15
3.3.1.1
3.3.2
Power Cell Cabinet 18
3.3.3
Transformer Cabinet 20
3.3.4
Junction Cabinet 21
3.3.5
Start-up Cabinet 21
3.3.6
Output Filter Cabinet 23
3.3.7
Bypass Cabinet 24
3.3.7.1
3.3.7.2
3.3.7.3
3.4
System Operation 29
3.4.1
Main Circuit 29
3.4.2
Power Cells 30
Controls and Indicators 17
Manual Bypass Cabinet 24
Automatic Bypass Cabinet 25
Synchronous Transfer Cabinet 28
3.4.3
Control System 31
3.5
Type Code Description 33
3.6
Available Options 34
3.6.1
Cabinet Bypass 36
3.6.2
Input Devices 36
3.6.3
Output Devices 37
3.6.4
Mechanical Options 37
AQ363633621020en-000201/172F3117 | 3Danfoss A/S © 2021.06
VACON® 1000
Operating Guide
3.7
VACON® 1000 PC Tool 37
4
Receiving the Delivery 38
4.1
Checking the Delivery 38
4.2
Storage 38
4.3
Lifting and Moving the Drive 38
4.3.1
Lifting the Standalone Cabinets 38
4.3.2
Lifting the Line-up Cabinets 40
4.3.3
Using a Forklift 40
5
Mechanical Installation 42
5.1
Operating Environment 42
5.2
Cabinet Installation 42
5.2.1
Attaching the Cabinets 42
5.2.2
Mounting the Cabinets 44
Contents
5.3
Installing the Power Cells 44
5.4
Dimensions of the Enclosed Drive 45
5.5
Cooling and Free Space Around the Enclosed Drive 45
5.5.1
Air Ducting Guidelines 46
6
Electrical Installation 47
6.1
The Main Circuit 47
6.2
Main Circuit Breaker and Fuses 47
6.3
Galvanic Isolation Between the MV and LV Sections 47
6.4
Terminals 47
6.4.1
Terminal Locations in the Standalone Cabinet 47
6.4.2
Terminal Locations in the Line-up Cabinet 48
6.5
Cable Entry and Termination 49
6.5.1
Power Cable Entry of Standalone Cabinet 49
6.5.2
Power Cable Entry of Line-up Cabinet 50
6.5.3
Power Cable Termination 51
6.5.4
Control Cable Entry 51
6.6
Grounding 53
6.7
Power Cable Selection 53
6.8
Additional Instructions for Cable Installation 54
6.9
Control Wiring 54
6.9.1
Control Cable Selection 54
6.9.2
Control Power Wiring 54
6.9.3
Control Circuit Wiring 55
AQ363633621020en-000201/172F31174 | Danfoss A/S © 2021.06
VACON® 1000
Operating Guide
6.9.4
Application Wiring Example 59
6.9.5
PLC Configuration 60
6.9.5.1
6.9.5.2
7
Human-Machine Interface 63
7.1
The VACON® 1000 HMI 63
7.2
HMI Homepage 63
7.2.1
System Status 63
7.2.2
Dashboard 64
7.2.3
Single-line Diagram 64
7.3
Control Panel 64
7.4
Status 65
7.4.1
Power Cell 65
7.4.2
Cooling Fan 65
PLC Basic Configuration 60
Options and Customized Designs 61
Contents
7.5
Graphs & Reports 65
7.6
Setup & Service 66
7.6.1
Operation Mode 67
7.6.2
Motor Parameter 67
7.6.3
Functions 68
7.6.4
Protections 68
7.6.5
PID Setup 68
7.6.6
System Configuration 69
7.7
Events 69
7.7.1
Warning & Fault 69
7.7.2
Event Log 70
7.8
Administration 71
7.9
Tool Settings 72
7.9.1
Language 72
7.9.2
Software Version 72
7.9.3
HMI Set 72
8
Commissioning 74
8.1
Safety Checks before Starting the Commissioning 74
8.2
Personnel Requirements 74
8.3
Commissioning Checks 74
8.4
Commissioning Report 76
8.5
Operating the Drive 76
8.5.1
Powering the Drive 76
AQ363633621020en-000201/172F3117 | 5Danfoss A/S © 2021.06
VACON® 1000
Operating Guide
8.5.2
Starting the Drive 76
8.5.3
Stopping the Drive 77
8.5.4
Powering Off the Drive 77
8.6
Interlocking System 78
8.6.1
Electromagnetic Interlocking System 78
8.6.2
Mechanical Interlocking System 78
9
Maintenance 79
9.1
Safety 79
9.2
Standard Maintenance Process 80
9.3
Maintenance Schedule 80
9.3.1
Daily Maintenance 80
9.3.2
Yearly Maintenance 81
9.4
Replacing the Air Filters 82
9.4.1
Air Filters of Standalone Cabinets 82
Contents
9.4.2
Air Filters of Transformer and Power Cell Cabinets 83
9.4.3
Air Filters of Control Cabinet 84
9.5
Replacing the HMI Battery 84
9.6
Replacing the Cooling Fans 85
9.6.1
Diagram of the Cooling Fan Replacement 86
9.7
UPS Battery 86
9.7.1
Replacing the UPS Battery 86
9.7.2
UPS Battery Maintenance 86
9.8
Power Cells 87
9.8.1
Power Cell Maintenance 87
9.8.2
Replacing the Power Cells 88
9.8.2.1
9.8.3
Reforming the Power Cell Capacitors 90
9.8.3.1
9.8.3.2
9.9
Dielectric Withstand Test 91
Diagram of the Power Cell Replacement 89
Reforming with an AC Supply 90
Reforming with a DC Supply 91
9.9.1
Testing Input and Output Together 92
9.9.2
Testing Input and Output Separately 92
10
Fault Tracing 94
10.1
Fault Types 94
10.2
Fault Response Configuration 94
10.3
Faults and Alarms 94
AQ363633621020en-000201/172F31176 | Danfoss A/S © 2021.06
VACON® 1000
Operating Guide
11
Specifications 108
Technical Data 108
11.1
11.2
Power Ratings and Dimensions 111
IEC Ratings 111
11.2.1
11.2.2
UL Ratings 119
11.3
Internal Cables and Terminals 133
11.4
Replacement Fuses 135
11.5
Standards 136
11.6
Abbreviations 140
Contents
AQ363633621020en-000201/172F3117 | 7Danfoss A/S © 2021.06
Version
Release date
Remarks
B
29.06.2021
Updates to dimensions and weights
VACON® 1000
Operating Guide
Introduction

1 Introduction

1.1 Purpose of this Operating Guide

This Operating Guide provides information for safe installation and commissioning of the AC drive. It is intended for use by qualified personnel.
Read and follow the instructions to use the drive safely and professionally. Pay particular attention to the safety instructions and general warnings. Always keep this Operating Guide with the drive. VLT® is a registered trademark for Danfoss A/S.

1.2 Additional Resources

Other resources are available to understand advanced AC drive functions, programming, and options.
The VACON® 1000 Application Guide provides greater detail on how to work with the application and how to set the parame­ters of the AC drive.
User guides for product options.
Supplementary publications and manuals are available from Danfoss. See

1.3 Manual Version

This manual is regularly reviewed and updated. All suggestions for improvement are welcome. The original language of this manual is English.
www.danfoss.com for listings.
Table 1: VACON® 1000 Operating Guide Version

1.4 Disposal

Do not dispose of equipment containing electrical components together with domestic waste. Collect it separately in accordance with local and currently valid legislation.
AQ363633621020en-000201 / 172F31178 | Danfoss A/S © 2021.06
VACON® 1000
Operating Guide

2 Safety

2.1 Safety Symbols

The following symbols are used in this manual:
D A N G E R
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
W A R N I N G
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
C A U T I O N
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
N O T I C E
Indicates information considered important, but not hazard-related (for example, messages relating to property damage).
Safety

2.2 Qualified Personnel

To allow trouble-free and safe operation of the unit, only qualified personnel with proven skills are allowed to transport, store, as­semble, install, program, commission, maintain, and decommission this equipment.
Persons with proven skills:
Are qualified electrical engineers, or persons who have received training from qualified electrical engineers and are suitably experienced to operate devices, systems, plant, and machinery in accordance with pertinent laws and regulations.
Are familiar with the basic regulations concerning health and safety/accident prevention.
Have read and understood the safety guidelines given in all manuals, especially the instructions given in the operating guide of the unit.
Have good knowledge of the generic and specialist standards applicable to the specific application.
Are familiar with the structure and operation of medium-voltage drives and the related risks. Special training for medium-volt­age installations may be necessary.

2.3 Danger and Warnings

D A N G E R
SHOCK HAZARD FROM POWER UNIT COMPONENTS
The power unit components are live when the drive is connected to mains. Contact with this voltage can result in death or seri-
ous injury.
Do not touch the components of the power unit when the drive is connected to mains.
-
Do not do any work on live equipment. Before doing any work on internal drive components, follow proper lock out and tag out procedure. Before connecting the drive to mains, make sure that all covers are installed on the drive and the enclosure doors are closed.
D A N G E R
SHOCK HAZARD FROM TERMINALS
The motor terminals U, V, W, and the DC-link terminals must be treated as live when the drive is connected to mains. Contact with
this voltage can lead to death or serious injury.
Do not touch the motor terminals U, V, W, or the DC terminals when the drive is connected to mains.
-
Do not do any work on live equipment. Before doing any work on the drive, follow proper lock out and tag out procedure. Before connecting the drive to mains, make sure that all covers are installed on the drive and the enclosure doors are closed.
AQ363633621020en-000201 / 172F3117 | 9Danfoss A/S © 2021.06
VACON® 1000
Operating Guide
D A N G E R
SHOCK HAZARD FROM DC LINK OR EXTERNAL SOURCE
The terminal connections and the components of the drive can be live several minutes after the drive is disconnected from the
mains and the motor has stopped. The load side of the drive can also generate voltage. A contact with this voltage can lead to
death or serious injury.
Do not do touch the main circuit of the drive or the motor before the system is powered off and grounded.
-
Disconnect the drive from the mains and make sure that the motor has stopped. Disconnect the motor. Lock out and tag out the power source to the drive. Make sure that no external source generates unintended voltage during work. Ground the drive for work. Wait at least 15 minutes for the DC-link capacitors to discharge fully before opening the cabinet door or the cover of the AC drive. Use a measuring device to make sure that there is no voltage.
W A R N I N G
SHOCK HAZARD FROM CONTROL TERMINALS
The control terminals can have a dangerous voltage also when the drive is disconnected from mains. A contact with this voltage
can lead to injury.
Make sure that there is no voltage in the control terminals before touching the control terminals.
-
Safety
W A R N I N G
ACCIDENTAL MOTOR START
When there is a power-up, a power break, or a fault reset, the motor starts immediately if the start signal is active, unless the pulse
control for Start/Stop logic is selected. If the parameters, the applications or the software change, the I/O functions (including the
start inputs) can change. If you activate the auto reset function, the motor starts automatically after an automatic fault reset. See
the Application Guide. Failure to ensure that the motor, system, and any attached equipment are ready for start can result in
personal injury or equipment damage.
Disconnect the motor from the drive if an accidental start can be dangerous. Make sure that the equipment is safe to operate
-
under any condition.
W A R N I N G
ELECTRICAL SHOCK HAZARD - LEAKAGE CURRENT HAZARD >3.5 MA
Leakage currents exceed 3.5 mA. Failure to connect the drive properly to protective earth (PE) can result in death or serious in-
jury.
Ensure reinforced protective earthing conductor according to IEC 60364-5-54 cl. 543.7 or according to local safety regula-
-
tions for high touch current equipment. The reinforced protective earthing of the drive can be done with:
a PE conductor with a cross-section of at least 10 mm2 (8 AWG) Cu or 16 mm2 (6 AWG) Al.
-
an extra PE conductor of the same cross-sectional area as the original PE conductor as specified by IEC 60364-5-54 with a
-
minimum cross-sectional area of 2.5 mm2 (14 AWG) (mechanical protected) or 4 mm2 (12 AWG) (not mechanical protected).
a PE conductor completely enclosed with an enclosure or otherwise protected throughout its length against mechanical
-
damage.
a PE conductor part of a multi-conductor power cable with a minimum PE conductor cross-section of 2.5 mm2 (14 AWG)
-
(permanently connected or pluggable by an industrial connector. The multi-conductor power cable shall be installed with an appropriate strain relief).
NOTE: In IEC/EN 60364-5-54 cl. 543.7 and some application standards (for example IEC/EN 60204-1), the limit for requiring
-
reinforced protective earthing conductor is 10 mA leakage current.

2.4 Cautions and Notices

AQ363633621020en-000201 / 172F311710 | Danfoss A/S © 2021.06
VACON® 1000
Operating Guide
C A U T I O N
DAMAGE TO THE AC DRIVE FROM INCORRECT SPARE PARTS
Using spare parts that are not from the manufacturer can damage the drive.
Do not use spare parts that are not from the manufacturer.
-
C A U T I O N
DAMAGE TO THE AC DRIVE FROM CHANGES TO DRIVE COMPONENTS
Doing electrical or mechanical changes to the drive components can cause malfunctions and can damage the AC Drive.
Do not make electrical or mechanical changes to the drive components.
-
C A U T I O N
DAMAGE TO THE AC DRIVE FROM INSUFFICIENT GROUNDING
Not using a grounding conductor can damage the drive.
Always ground the AC drive with a grounding conductor that is connected to the grounding terminal that is identified with
-
the PE symbol.
Safety
C A U T I O N
DAMAGE TO THE AC DRIVE DUE TO DISCONNECTED CONTROL POWER
Disconnecting the control auxiliary power when the AC drive is connected to mains or when the power indicator is on can cause
abnormalities in the function of the power cells and damage the cells.
Do not disconnect the control auxiliary power supply when the AC drive is connected to mains or if the power indicator is
-
on.
C A U T I O N
CUT HAZARD FROM SHARP EDGES
There can be sharp edges in the AC drive that can cause cuts.
Wear protective gloves when mounting, cabling, or doing maintenance operations.
-
C A U T I O N
BURN HAZARD FROM HOT SURFACES
Touching surfaces, which are marked with the 'hot surface' sticker, can result in injury.
Do not touch surfaces which are marked with the 'hot surface' sticker.
-
N O T I C E
DAMAGE TO THE AC DRIVE FROM STATIC VOLTAGE
Some of the electronic components inside the AC drive are sensitive to ESD. Static voltage can damage the components.
Use ESD protection when working with electronic components of the AC drive. Do not touch the components on the circuit
-
boards without proper ESD protection.
N O T I C E
DAMAGE TO THE AC DRIVE FROM INCORRECT EMC LEVEL
The EMC level requirements for the AC drive depend on the installation environment. An incorrect EMC level can damage the
drive.
Before connecting the AC drive to the mains, make sure that the EMC level of the AC drive is correct for the mains.
-
AQ363633621020en-000201 / 172F3117 | 11Danfoss A/S © 2021.06
VACON® 1000
Operating Guide
N O T I C E
MAINS DISCONNECTION DEVICE
If the AC drive is used as a part of a machine, the machine manufacturer must supply a mains disconnection device (refer to EN
60204-1).
N O T I C E
MALFUNCTION OF FAULT CURRENT PROTECTIVE SWITCHES
Because there are high capacitive currents in the AC drive, it is possible that the fault current protective switches do not operate
correctly.
N O T I C E
VOLTAGE WITHSTAND TESTS
If done improperly, doing voltage withstand tests can damage the drive.
Megohmmeter testing is the only recommended test type for field installations.
-
Only a qualified field service engineer is allowed to perform this test. Refer to the proper high potential/megohmmeter testing instructions in the service guide.
Safety
N O T I C E
WARRANTY
If the power modules are opened, the warranty is not valid.
Do not open the power modules.
-
N O T I C E
PERSONAL PROTECTIVE EQUIPMENT AND APPROVED TOOLS
When doing electrical work on the AC drive, always use personal protective equipment (PPE) and tools which are approved for
work with medium-voltage devices.
AQ363633621020en-000201 / 172F311712 | Danfoss A/S © 2021.06
VACON® 1000
Operating Guide
Product Overview

3 Product Overview

3.1 Product Characteristics

The VACON® 1000 medium-voltage drive is an alternating current speed regulating device from Danfoss. The drive features include excellent performance, easy and convenient operation, and a wide range of applications using IGBT power devices and complete digital control.
High efficiency and low distortion
The used multi-pulse input rectification transformer technology efficiently lowers the content of the input side distortion cur­rent to less than 5%. It meets the IEEE 519-1992 standard and the strict requirements of electric grids for distortion, and enhan­ces the power factor to more than 0.96 lagging.
With the used cell-cascaded multilevel technology, there is normally no need for an output filter, and the output voltage wave­form is similar to a sine-wave.
System efficiency >98.5% (at rated frequency, excluding transformer).
Tolerant to power disturbances and wide applicable scope
When the input voltage is as low as 70%, the system can still continue derated operation.
With automatic output voltage adjusting function, when the input voltage fluctuates between 90–110%, the output voltage can still be kept steady. Thus, safe and steady operation of the motor is possible.
High reliability
SOA (Service-oriented architecture) design ensures that the system operates in a wide safe range:
-
Sufficient design margin makes sure that each device operates in the middle area of the safe operating area.
-
Optimized thermal design ensures temperature margin for the devices.
-
The DC-link capacitors are designed for long lifetime service.
Redundant auxiliary control power.
The system provides a self-diagnosis function to show the position and type of failure and warn the user about the fault occur­rence.
Automatic detection and warning function for cooling fan failure or excessive dust in the inlet air filter notifying the user to conduct maintenance.
Production quality management, control flow process, and perfect test equipment and methods ensure the effective imple­mentation of each test item for devices, components, and units during the manufacturing process at Danfoss.
Site flexibility
The compact structure and high power density of VACON® 1000 can reduce the space requirements on site.
The electric connections between the cabinets use highly reliable connectors which are easy to install and maintain.
Easy-to-operate human-machine interface.
Sufficient communication interfaces, which can be professionally configured in accordance with the application requirements.
All PCBs are coated to avoid problems with pollution and corrosive environments.

3.2 Applications

VACON® 1000 is used for the speed control of square torque loads such as fans, pumps, and compressors, as well as for mills, crush­ers, and conveyor belts that require constant torque operation over the entire speed range. Accurate speed and torque controls result in better energy saving, improved process quality, and prolonged equipment lifetime. Various industries that require reliable and stable operation can benefit from the high performance of VACON® 1000.
Power generation: Coal mills, blower fans, and water pumps.
Metallurgy: Conveyor belts, positive displacement pumps, fans, and water pumps.
Mining: Crushers, conveyor belts, PD pumps, fans, and water pumps.
Petrochemical: Compressors, PD pumps, centrifugal pumps, fans, and water pumps.
Cement and materials: Crushers, mixers, extruders, rotary kilns, drying furnaces, fans, and water pumps.
Sugar and ethanol: Mills, pumps, and fans.
Municipal works: Water supply pumps, sewage pumps, heat network pumps.
AQ363633621020en-000201 / 172F3117 | 13Danfoss A/S © 2021.06
C
D
e30bi640.10
A
B
A
Control cabinet
B
Power cell cabinet
C
Junction cabinet
D
Transformer cabinet
VACON® 1000
Operating Guide
Product Overview

3.3 System Hardware

The VACON® 1000 medium-voltage drive consists of a controller cabinet, power cell cabinet, transformer cabinet, and junction cabi­net. Other cabinets can be configured in accordance with customer requirements in the actual application.
There are two types of drive enclosure:
Standalone type with current ratings up to 215 A
Line-up type with current ratings 215–680 A (IEC ratings up to 11 kV, UL ratings up to 6.9 kV)
Illustration 1: Standalone System Structure
AQ363633621020en-000201 / 172F311714 | Danfoss A/S © 2021.06
A B C D
e30bi639.10
A
Control cabinet
B
Power cell cabinet
C
Transformer cabinet
D
Junction cabinet
VACON® 1000
Operating Guide
Product Overview
Illustration 2: Line-up System Structure
3.3.1 Control Cabinet
The control cabinet includes:
Main control system
PLC
HMI
Battery
Other accessories
AQ363633621020en-000201 / 172F3117 | 15Danfoss A/S © 2021.06
e30bi642.10
A
B
C
D
E
F
A
Control rack
B
Terminal block
C
UPSDAirflow pressure switch
E
PLCFIsolation transformer
e30bi641.10
A
B
C
D
E
F
G
VACON® 1000
Operating Guide
Product Overview
Illustration 3: Control Cabinet in VACON® 1000 Standalone Systems
Illustration 4: Control Cabinet in VACON® 1000 Line-up Systems
AQ363633621020en-000201 / 172F311716 | Danfoss A/S © 2021.06
A
Control rack
B
Terminal block
C
Battery
D
PLCEAirflow pressure switch
F
DC power supply
G
Isolation transformer
e30bi643.10
A
B
C
D
E
A
Power supply board
B
I/O board
C
A/D board
D
Main control board
E
Fiber optical boards
VACON® 1000
Operating Guide
The main control system is mounted in the control rack and consists of:
Main control board
I/O board
A/D board
Two fiber optical boards (extendable)
Power supply board
Bus motherboard, which connects the boards to each other.
Product Overview
Illustration 5: Main Control System
3.3.1.1 Controls and Indicators
The following are mounted on the control cabinet door:
High voltage power-on indicator: A green indicator, which indicates high voltage applied to the drive.
Operation indicator: A green indicator, which indicates that the drive is in operation.
Fault indicator: A red indicator, which indicates that the system is in “failure” state.
Emergency Stop button (E-stop): This button is used to break the high-voltage power of the drive when the system has an emergency (such as unexpected incidents threatening the safety of the personnel or equipment). The button has a self-locking function. Turn the button clockwise to reset and to turn power on again.
Human-machine interface: See 7 Human-Machine Interface.
Mechanical interlocking system: Standard in UL type drives and available as option +MMKI for IEC type drives. See 8.6.2 Mechan-
ical Interlocking System.
AQ363633621020en-000201 / 172F3117 | 17Danfoss A/S © 2021.06
e30bi644.10
A
B
D
C
C
D
A
Line-up cabinet
B
Standalone cabinet
C
HMIDMechanical interlocking system
e30bi646.10
A
B
C
A
Cooling fan
B
Output current Hall sensor
VACON® 1000
Operating Guide
Product Overview
Illustration 6: Controls and Indicators on the Door of the Control Cabinet
3.3.2 Power Cell Cabinet
The power cell cabinet contains the power cells and their accessories.
Illustration 7: Power Cell Cabinet in VACON® 1000 Standalone Systems
AQ363633621020en-000201 / 172F311718 | Danfoss A/S © 2021.06
C
Power cell
e30bi645.10
A
B
A
Cooling fan
B
Power cell
e30bi647.10
A
B
C
D
E
VACON® 1000
Operating Guide
Product Overview
Illustration 8: Power Cell Cabinet in VACON® 1000 Line-up Systems
The power cells in the cabinet have the same electrical and mechanical parameters and can be replaced by each other.
Illustration 9: Power Cell
AQ363633621020en-000201 / 172F3117 | 19Danfoss A/S © 2021.06
A
Output terminal
B
Heat sink
C
Handle
D
FuseEInput terminal
RS
Optical fiber (receive)
TS
Optical fiber (transmit)
COM
Communication fail indicator
DRV
Drive fault indicator
UV
Undervoltage indicator
TMP
Overtemperature indicator
PWR
Power indicator
OV
Overvoltage indicator
CDL
50 V DC-link voltage indicator
e30bi649.10
A
B
C
A
Cooling fan
B
Phase-shift transformer
C
Input current Hall sensor
VACON® 1000
Operating Guide
Product Overview
3.3.3 Transformer Cabinet
The transformer cabinet includes the phase-shift transformer and its accessories. The transformer is integrated with the cabinet base through screws for the convenience of transportation and installation. The sys-
tem default setting is that, when the transformer temperature exceeds 95°C, the system reports an excessive high temperature alarm but does not shut down. When the temperature exceeds 110°C, the system reports an extra-high temperature fault and shuts down.
In standalone systems, the same fan is used to cool the transformer and power cell cabinets.
Illustration 10: Transformer Cabinet in VACON® 1000 Standalone Systems
AQ363633621020en-000201 / 172F311720 | Danfoss A/S © 2021.06
e30bi648.10
A
B
C
D
A
Cooling fan
B
Phase-shift transformer
C
Input current Hall sensor
D
Output current Hall sensor
HV~
MCB
M
Junction
cabinet
Startup cabinet
Drive
KM51
Output filter
cabinet
e30bi650.10
VACON® 1000
Operating Guide
Product Overview
Illustration 11: Transformer Cabinet in VACON® 1000 Line-up Systems
3.3.4 Junction Cabinet
The junction cabinet is used for field cable connections. See 6.5 Cable Entry and Termination.
3.3.5 Start-up Cabinet
The start-up cabinet (+PSTC) is an option for the VACON® 1000 line-up systems. The main function of the start-up cabinet is to de­press inrush currents that can lead to a dip in the supply voltage:
A phase-shifting transformer with a large capacity can produce a magnetizing surge as high as 6–8 times the rated current of the transformer itself.
The power cells of the drive contain several capacitors, which require a large precharge current when high voltage is applied.
Illustration 12: Start-up Cabinet Primary Side Diagram
Install the start-up cabinet between the high-voltage power input and phase-shifting transformer. When the MCB of the drive is closed, the start-up cabinet limits the magnetizing surge and charge current of the capacitance quickly and efficiently. After the drive is powered up, the current-limiting resistance passes through the KM51 bypass, and the drive can function normally.
The main electrical components of the start-up cabinet are a high-voltage switch (vacuum contactor or vacuum breaker) and a cur­rent-limiting resistor.
AQ363633621020en-000201 / 172F3117 | 21Danfoss A/S © 2021.06
e30bi651.10
VACON® 1000
Operating Guide
Product Overview
Illustration 13: Start-up Cabinet
The function of current-limiting resistance is to limit the primary current when a high voltage is connected. Each resistor can bear a 30 kJ energy during the power-up. The capacity of the drive defines how much resistance is needed in the start-up cabinet: the larger the capacity, the more current-limiting resistors are needed.
The function of the high-voltage switch is to bypass the current-limiting resistor after the powering-up procedure, making the drive function under normal load. If the rated current is small, a vacuum contactor can be used. If the rated current is large, a vacuum breaker can be used.
Operation process
Power up the drive.
The control program confirms if the system is ready and if the cabinet switch is separated or not.
Power up the start-up cabinet and the control program counts the time it takes to complete the process. The process requires about 5 s.
The closing of the start-up cabinet switch bypasses the charged resistor and the drive has status 'running allowed'.
When to select the Start-up cabinet option?
The MCB protection at the installation site must not trip because of the inrush current when the drive is powered up or in normal overload conditions. The overcurrent protection of the MCB must be set in the grey area shown in Illustration 14.
If the MCB meets these requirements, the start-up cabinet is not required. It is important to verify this condition, especially in retrofit applications where a circuit breaker is already installed at the motor control center panel.
Even if it is not required, a start-up cabinet can still be installed to:
Reduce inrush current.
Reduce stresses in the electrical installation during the drive power-up operation.
AQ363633621020en-000201 / 172F311722 | Danfoss A/S © 2021.06
20T
O
t(I)
I/I
LN
0.2I
ratio
0.4I
ratio
0.6I
ratio
0.8I
ratio
I
ratio
15T
O
10T
O
5T
O
0
0
e30bj032.10
I
Inrush current
ILNRated input current of the drive
I
ratio
I/I
LN
t(I)
Time of the inrush current decay
TOThe basic period: 20 ms for 50 Hz or 16.7 ms for
60 Hz
L71-a
L71-b
L71-c
To
inverter
To
motor
R72A
R74A
R78A
R76A
R71A
R73A
R77A
R75A
R72B
R74B
R78B
R76B
R71B
R73B
R77B
R75B
R72C
R74C
R78C
R76C
R71C
R73C
R77C
R75C
e30bi652.10
VACON® 1000
Operating Guide
Illustration 14: Overcurrent Protection Setting Area
Product Overview
3.3.6 Output Filter Cabinet
The output filter cabinet is an optional cabinet which is connected at the output of the drive, between the inverter and motor. The filter is used to:
Reduce the dU/dt of the voltage waveform.
Prevent resonance/overvoltage caused by motor cables.
Reduce the charging current of the cable.
Illustration 15: Output Filter Cabinet Circuit Diagram
Install the output filter cabinet between the drive and motor. The filter consists of a reactor and paralleling damping resistors. The reactor decreases the rising edge of the PWM. The resistor damps the resonance caused by the reactor and stray inductance.
AQ363633621020en-000201 / 172F3117 | 23Danfoss A/S © 2021.06
e30bi653.10
HV~
MCB
M
Manual bypass cabinet
QS41
DN41
QS42
QS43
Drive
e30bi747.10
VACON® 1000
Operating Guide
Product Overview
Illustration 16: Output Filter Cabinet
When to select the Output Filter cabinet option?
The need for an output filter is application and case specific. Several things must be considered to find out if a dU/dt Filter is re­quired:
The type of the motor.
The type of the motor cable.
The length of the motor cable.
To evaluate if a dU/dt Filter is required, contact Danfoss.
3.3.7 Bypass Cabinet
Different bypass cabinets are available as options:
Manual bypass cabinet
Automatic bypass cabinet
Synchronous transfer cabinet
3.3.7.1 Manual Bypass Cabinet
Illustration 17 shows a typical bypass cabinet configuration, where:
QS41 is a single-pole isolation switch with a manual grounding knife gate.
QS42 and QS43 are double-pole double-throw manual knife gate isolation switches.
Illustration 17: Manual Bypass Cabinet Circuit Diagram
The bypass cabinet includes an isolation switch, which:
AQ363633621020en-000201 / 172F311724 | Danfoss A/S © 2021.06
A
B
e30bi750.10
A
Manual knife gate switch
B
Dual-isolation switch panel
HV~
MCB
M
Automatic bypass/Synchronous transfer cabinet
Manual bypass cabinet
QS41KM41 KM42
KM43
DN41
QS42
Drive
e30bi748.10
VACON® 1000
Operating Guide
Realizes the electrical isolation between the phase-shift transformer and the power distribution system.
Provides the power frequency and variable frequency switching function and related electrical protection measures.
Product Overview
Illustration 18: Manual Bypass Cabinet
3.3.7.2 Automatic Bypass Cabinet
Illustration 19 shows an automatic bypass cabinet configuration, where:
KM41–KM43, high-voltage vacuum contactors.
QS41–QS42, manual separation knife switches.
Illustration 19: Automatic Bypass Cabinet Circuit Diagram
When the drive is running:
QS41 and QS42 are closed.
KM41 and KM42 are closed.
KM43 is open.
When the drive is bypassed:
KM41 and KM42 are open.
KM43 is closed.
When maintenance is performed on the drive:
AQ363633621020en-000201 / 172F3117 | 25Danfoss A/S © 2021.06
VACON® 1000
Operating Guide
QS41 and QS42 are open.
KM41 and KM42 are open.
KM43 is closed.
The sequence in which the drive is switched from running to bypassed:
1. KM41 is opened.
2. KM42 is opened.
3. KM43 is closed.
Secondary Control Logic
The three switches KM41–KM43 use assistant contact interlock to ensure that the time course is followed.
KM41 does not open and KM42 does not act when the normally closed contactor of KM41 is connected into the opening circuit of KM42.
The normally closed contactor of KM42 is connected to the MCB-closed circuit of KM43.
The normally closed contactor of KM43 is connected to the MCB-closed circuit of KM42.
KM43 is not able to close the MCB when KM42 is not opening.
KM42 is not able to close MCB when KM43 is not opening.
The status of the five switches KM41–KM43 and QS41–QS42 is monitored through the PLC.
If any switch is not at the right working position, the system does not allow the MCB to close, and powering up high voltage to the system is forbidden.
If the drive goes into fault, the system breaks the switch automatically to cut off the HV input for safety, if KM41 is not able to open during the process of VF switching to working frequency automatically.
The two switches KM42 and KM43 control the function of reserving postponed action in the circuit, which can adjust the action interval of the switch during the process of VF switching to working frequency. It can be more convenient to calibrate the machine on site according to the status of the electric motor and load, to switch speed reasonably to avoid an overcurrent malfunction be­cause of the electric motor remanence.
Product Overview
AQ363633621020en-000201 / 172F311726 | Danfoss A/S © 2021.06
e30bi751.10
AC/DC 220 V
501
ZK1
FU21
504
415
415
415
415
415
415
415
415
415
415
415
417
1
2
1
2
5
6
7
8
3
4
542
543
548
527
530
537
538
539
533
544
415
540
541
524
536
535
534
546
413
532
528
KA12
SF2
SA3
SB2
SF1
SF2
SB1
SF1
KT2
KA1-I
KA1
KA1
KA1
K4
SB3
SA2
SA1
KA2
KT3
KT3
KT3
KT2
KT1
KT1
KM43
KM43
KM43
KM42
KM41
KA2
KA2
KA2
KA2
KA1
KA1-II
KA2-I
KA2-II
KT1
KM42
KM43
KM41
KM41
KM42
KM43 closing coil
KM41 opening
coil
KM42 opening coil
KM43 opening coil
KM42 open switch
KM43 opening switch
KM43 close switch
KM41 close switch
KM41 close switch
KM42 close switch
SF1
503
505
AC 220 V
Micro breaker
Fuse
PF auto transfer switch
VF to PF manual transfer switch SF2
PF to VF manual transfer switch SF2
KA2 self-lock circuit
Operation mode switch SF1
KM41 open push button SB1
KM43 open push button SB3
KM42 close push button SA2
KM41 close push button SA1
KM42 open command
KM43 open command
KM42 open push button SB2
KM43 close command
KM41 close command
KM42 close command
Time relay
Time relay circuit
KM43 close push button
KM42 close coil
KM41 close coil
e30bi752.10
VACON® 1000
Operating Guide
Product Overview
Illustration 20: Secondary Control Logic Diagram of VF Switching to PF
Operation Mode Switches
Switch SF1 is used to select the working mode to prevent incorrect operation.
Auto: Allows switching to PF bypass automatically when the drive is in a serious fault.
Manual: Allows manual switching to working-frequency bypass according to the real production requirements when the drive is normally running.
Forbidden: If the production conditions do not allow the switching to working-frequency bypass, this mode can be selected to prevent incorrect operation.
Illustration 21: Working Mode Selection Switch SF1
AQ363633621020en-000201 / 172F3117 | 27Danfoss A/S © 2021.06
e30bi753.10
HV~
MCB
M
Automatic bypass/Synchronous transfer cabinet
Manual bypass cabinet
QS41KM41 KM42
KM43
DN41
QS42
Drive
e30bi748.10
VACON® 1000
Operating Guide
Product Overview
Switch SF2 is used to select between variable-frequency (VF) and power-frequency (PF) switching.
When the automatic bypass cabinet is in manual operation mode, and switch SF2 is in PF position, the drive switches the system to PF bypass status automatically.
When switch SF2 is in VF position, the drive can switch from power-frequency bypass status to variable-frequency mode auto­matically (QS41 and QS42 must be closed). This function needs the coordination of engine racing starting-up. Therefore, engine racing must be enabled and must comply with all the related electric motor parameters.
VF logic sequence:
-
KM41 is closed.
-
If self-detection shows normal after 10 s, bypass switch KM43 is opened.
-
KM42 is closed.
-
Automatic engine racing of the drive starts up.
-
PF is switched to VF.
Illustration 22: Switching Mode Selection Switch SF2
3.3.7.3 Synchronous Transfer Cabinet
The synchronous transfer function can realize undisturbed transfer between the grid and the drive, and reduce the impact on the motor and grid. The primary circuit is shown in Illustration 23. The switching devices and cabinets are the same as in the automatic bypass cabinet. QS41 and QS42 are for drive maintenance use and are closed during operation.
Illustration 23: Synchronous Transfer Cabinet Circuit Diagram
Process sequence of load transfer from the drive to the grid
Initial state: KM41 and KM42 are closed, and KM43 is open.
Phase lock: The drive runs to grid frequency and starts to lock phase to grid voltage.
Synchronous transfer: After phase lock, KM43 is closed and the load transfer to grid is started.
Synchronous transfer finished: After the load transfer, KM42 and KM41 are opened.
Process sequence of load transfer from the grid to the drive
Initial state: KM41 and KM42 are open, and KM43 is closed.
Phase lock: KM41 is closed. The drive runs to grid frequency and starts to lock phase to grid voltage.
Synchronous transfer: After phase lock, KM42 is closed and the load transfer to the drive is started.
Synchronous transfer finished: After the load transfer, KM43 is opened.
AQ363633621020en-000201 / 172F311728 | Danfoss A/S © 2021.06
Motor
Phase-shift
Transformer
-12°
-24°
12°
24°
Power Cells
Source
e30bi654.10
Drive series
Number of power cells per phase
System cell number
Output phase voltage (V)
Output line voltage (V)
2.4 kV
391385
2400
3 kV39
1732
3000
3.3 kV
391905
3300
4.16 kV
4122400
4160
6 kV515
3464
6000
VACON® 1000
Operating Guide
Product Overview

3.4 System Operation

3.4.1 Main Circuit
The typical main circuit topological structure diagram of VACON® 1000 medium-voltage drive is shown in Illustration 24.
Illustration 24: Main Circuit Diagram of VACON® 1000
The phase-shift rectifier transformer is a 3-phase air-cooled dry-type transformer directly connected with the incoming high voltage. The secondary windings use an extended delta connection, which can lower the content of the input side current distortion. The phase-shift angle between the secondary windings can be calculated according to the following formula:
Phase − shiftangle =
The secondary windings of the transformer provide input power for each power cell respectively. The number of secondary wind­ings and the phase-shift angle between the windings are determined according to the voltage level and structure of the drive, as
Numberofpowercells
shown in Table 2.
Table 2: Power Cell Configuration for VACON® 1000
60°
AQ363633621020en-000201 / 172F3117 | 29Danfoss A/S © 2021.06
Drive series
Number of power cells per phase
System cell number
Output phase voltage (V)
Output line voltage (V)
6.6 kV
6183810
6600
6.9 kV
6183984
6900
10 kV
8245774
10000
11 kV
9276351
11000
PWM1
PWM2
PWM3
PWM4
PWM5
PWM6
Time (ms)
Output phase voltage
0 4 8 12 16
20
e30bi655.10
VACON® 1000
Operating Guide
Product Overview
3.4.2 Power Cells
The power cell is the basic module of the medium-voltage drive, which produces a variable voltage and frequency output. It is com­posed of fast acting fuses, a rectification bridge, DC-link capacitance, IGBT inverting bridge, and so on.
The input terminals of the power cells are connected with the 3-phase winding of the secondary side of the phase-shift transformer. The 3-phase diode provides full-wave rectification to charge the DC-link capacitance, and the voltage on the capacitance is provi­ded to the H-bridge 1-phase bridge inverter circuit formed by 4 IGBTs.
The power cell receives signals through optical fibers, and controls the closing and opening of the S1–S4 IGBTs by using PWM mod­ulation mode to output a 1-phase impulse modulated waveform. Each cell has only 3 possible output states:
When S1 and S4 are closed, the state of the output voltage VUV is VDC.
When S2 and S3 are closed, the output voltage VUV is -VDC.
When S1 and S3 or S2 and S4 are closed, the output voltage VUV is 0.
Illustration 25 shows the waveform diagram of the output voltage of each power cell and the superimposed output phase voltage
waveform when 6 cells are connected in series. As shown in the figure, 13 voltage levels are obtained through connecting the 6 power cells in series. The increasing number of the voltage levels reduces the distortion content of the output voltage and simulta­neously lowers the risk of damaging the motor insulation caused by dU/dt. Illustration 26 and Illustration 27 are the waveform dia­grams of the output voltage and current of the drive when loaded by a motor.
Illustration 25: Output and Phase-Voltage Diagrams
AQ363633621020en-000201 / 172F311730 | Danfoss A/S © 2021.06
Loading...
+ 114 hidden pages