Danfoss vacon 10 Operating guide

vacon®10
ac drives
complete user manual
Document: DPD00717F1
Version release date: Apr. 2014
1. Safety 1
1.1 Warnings 1
1.2 Safety instructions 3
1.3 Earthing and earth fault protection 3
2. Receipt of delivery 5
2.1 Type designation code 5
2.2 Storage 6
2.3 Maintenance 6
2.4 Warranty 6
2.5 Manufacturer’s declaration of conformity 7
3. Installation 9
3.1 Mechanical installation 9
3.1.1 Vacon 10 dimensions 10
3.1.2 Cooling 12
3.1.3 Power losses 13
3.1.4 EMC levels 18
3.1.5 Changing the EMC protection class from C2 to C4 19
3.2 Cabling and connections 20
3.2.1 Power cabling 20
3.2.2 Control cabling 21
3.2.3 Screw
3.2.4 Cable and fuse specifications 25
3.2.5 General cabling rules 28
3.2.6 Stripping lengths of motor and mains cables 29
3.2.7 Cable installation and the UL standards 29
3.2.8 Cable and motor insulation checks 29
4. Commissioning 31
4.1 Commissioning steps of Vacon 10 31
5. Fault tracing 33
6. Vacon 10 Application Interface 37
6.1 Introduction 37
6.2 Control I/O 39
7. Control panel 41
7.1 General 41
7.2 Display 41
7.3 Keypad 42
7.4 Navigation on the Vacon 10 control panel 44
7.4.1 Main menu 44
7.4.2 Refer
7.4.3 Monitoring menu 46
7.4.4 Parameter menu 48
7.4.5 System menu 50
of cables 23
ence menu 45
Software package: FW0135V010
INDEX
8. STANDARD application parameters 53
8.1 Quick setup parameters Virtual menu, shows when par. 17.2 = 1) 54
8.2 Motor settings (Control panel: Menu PAR -> P1) 56
8.3 Start / stop setup (Control panel: Menu PAR -> P2) 58
8.4 Frequency references (Control panel: Menu PAR -> P3) 58
8.5 Ramps and brakes setup (Control panel: Menu PAR -> P4) 59
8.6 Digital inputs (Control panel: Menu PAR -> P5) 60
8.7 Analogue inputs (Control panel: Menu PAR -> P6) 60
8.8 Digital outputs (Control panel: Menu PAR -> P8) 61
8.9 Analogue outputs (Control panel: Menu PAR -> P9) 61
8.10 Protections (Control panel: Menu PAR -> P13) 62
8.11 Fault autoreset parameters (Control panel: Menu PAR -> P14) 62
8.12 PI control parameters (Control panel: Menu PAR -> P15) 63
8.13 Application Setting (Control panel: Menu PAR -> P17) 63
8.14 System parameters 64
9. Parameter descriptions 67
9.1 Motor settings (Control panel: Menu PAR -> P1) 67
9.2 Start / stop setup (Control panel: Menu PAR -> P2) 72
9.3 Frequency references (Control panel: Menu PAR -> P3) 79
9.4 Ramps & brakes setup (Control panel: Menu PAR -> P4) 80
9.5 Digital inputs (Control panel: Menu PAR -> P5) 84
9.6 Analogue inputs (Control panel: Menu PAR -> P6) 85
9.7 Digital outputs (Control panel: Menu PAR -> P8) 86
9.8 Analogue outputs (Control panel: Menu PAR -> P9) 87
9.9 Protections (Control panel:Menu Par->P13) 88
9.10 Automatic reset (Control panel: Menu PAR -> P14) 92
9.11 PI control parameters (Control panel: Menu PAR -> P15) 93
9.12 Application setting (Control panel: Menu PAR->P17) 94
9.13 Modbus RTU 96
9.13.1 Termination resistor 96
9.13.2 Modbus address area 96
9.13.3 Modbus process data 97
10. Technical data 99
10.1 Vacon 10 technical data 99
10.2 Power ratings 101
10.2.1 Vacon 10 – Mains voltage 208-240 V 101
10.2.2 Vacon 10 – Mains voltage 115 V 102
10.2.3 Vacon 10 – Mains voltage 380-480 V 102
10.2.4 Vacon 10 – Mains voltage 600 V 103
10.3 Brake resistors 103
safety vacon 1

1. SAFETY

ONLY A COMPETENT ELECTRICIAN IS ALLOWED TO CARRY OUT THE ELECTRICAL INSTALLATION!
This manual contains clearly marked cautions and warnings which are intended for your personal safety and to avoid any unintentional damage to the product or con­nected appliances.
Please read the information included in cautions and warnings carefully:
=Dangerous voltage
Risk of death or severe injury
=General warning
Risk of damage to the product or connected appliances

1.1 Warnings

The components of the power unit of the frequency converter are live when Vacon 10 is connected to mains. Coming into contact with this voltage is extremely dangerous and may cause death or severe injury. The control unit is isolated from the mains potential.
The motor terminals U, V, W (T1, T2, T3) and the possible brake resistor terminals - / + are live when Vacon 10 is connected to mains, even if the motor is not running.
The control I / O-terminals are isolated from the mains poten­tial. However, the relay output terminals may have a danger­ous control voltage present even when Vacon 10 is disconnected from mains.
The earth leakage current of Vacon 10 frequency converters exceeds 3.5 mA AC. According to standard EN61800-5-1, a reinforced protective ground connection must be ensured.
If the frequency converter is used as a part of a ma chine, the machine manufacturer is responsible for providing the machine with a main switch (EN 60204-1).
If Vacon 10 is disconnected from mains while running the motor, it remains live if the motor is energized by the process. In this case the motor functions as a generator feeding energy to the frequency converter.
24-hour support (0)201 212 575 • Email: vacon@vacon.com
1
2 vacon safety
After disconnecting the frequency converter from the mains, wait until the fan stops and the indicators on the display go out. Wait 5 more minutes before doing any work on Vacon 10 connections.
The motor can start automatically after a fault situation, if the autoreset function has been activated.
1
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
safety vacon 3

1.2 Safety instructions

The Vacon 10 frequency converter has been designed for fixed installations only.
Do not perform any measurements when the frequency con­verter is connected to the mains.
Do not perform any voltage withstand tests on any part of Vacon 10. The product safety is fully tested at factory.
Prior to measurements on the motor or the motor cable, dis­connect the motor cable from the frequency converter.
Do not open the cover of Vacon 10. Static voltage discharge from your fingers may damage the components. Opening the cover may also damage the device. If the cover of Vacon 10 is opened, warranty becomes void.

1.3 Earthing and earth fault protection

The Vacon 10 frequency converter must always be earthed with an earthing conduc­tor connected to the earthing terminal. See figure below:
MI1 - MI3
The earth fault protection inside the frequency converter protects
only the converter itself against earth faults.
If fault current protective switches are used they must be tested
with the drive with earth fault currents that are possible to arise in fault situations.
24-hour support (0)201 212 575 • Email: vacon@vacon.com
1
4 vacon safety

1.4 Before running the motor

Checklist:
Before starting the motor, check that the motor is mounted properly and ensure that the machine connected to the motor allows the motor to be started.
Set the maximum motor speed (frequency) according to the motor and the machine connected to it.
Before reversing the motor shaft rotation direction make sure that this can be done safely.
Make sure that no power correction capacitors are connected to the motor cable.
NOTE! You can download the English and French product manuals with applica­ble safety, warning and caution information from www.vacon.com/downloads.
REMARQUE Vous pouvez télécharger les versions anglaise et française des ma­nuels produit contenant l’ensemble des informations de sécurité, avertisse­ments et mises en garde applicables sur le site www.vacon.com/downloads.
1
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
receipt of delivery vacon 5
VACON0010- 1L- 0001- 1 +OPTIONS
Vaco n1 0
1L = Single phase 3L = Threephases
1=115V 2=208-230V 4=380-480V 7 = 600V
Output Current
InputVoltage
+Options
EMC2 QPES
+DLNL = Dutch +DLNO = Norwegian +DLPT = Portuguese +DLRU = Russian +DLSE = Swedish +DLTR =Turkish +DLUS= US English empty = English
Language ofthe documentation
+DLCN = Chinese +DLCZ = Czech +DLDE =German +DLDK =Danish +DLES= Spanish +DLFI = Finnish +DLFR =French +DLIT = Italian
Input phase

2. RECEIPT OF DELIVERY

After unpacking the product, check that no signs of transport damages are to be found on the product and that the delivery is complete (compare the type designation of the product to the code below).
Should the drive have been damaged during the shipping, please contact primarily the cargo insurance company or the carrier.
If the delivery does not correspond to your order, contact the supplier immediately.

2.1 Type designation code

24-hour support (0)201 212 575 • Email: vacon@vacon.com
Figure 2.1: Vacon 10 type designation code
2
6 vacon receipt of delivery

2.2 Storage

If the frequency converter is to be kept in store before use make sure that the ambi­ent conditions are acceptable:
Storing temperature -40…+70°C
Relative humidity < 95%, no condensation

2.3 Maintenance

In normal operating conditions, Vacon 10 frequency converters are maintenance­free.

2.4 Warranty

Only manufacturing defects are covered by the warranty. The manufacturer as­sumes no responsibility for damages caused during or resulting from transport, re­ceipt of the delivery, installation, commissioning or use.
The manufacturer shall in no event and under no circumstances be held responsible for damages and failures resulting from misuse, wrong installation, unacceptable ambient temperature, dust, corrosive substances or operation outside the rated specifications. Neither can the manufacturer be held responsible for consequential damages.
The Manufacturer's time of warranty is 18 months from the delivery or 12 months from the commissioning whichever expires first (Vacon Warranty Terms).
The local distributor may grant a warranty time different from the above. This war­ranty time shall be specified in the distributor's sales and warranty terms. Vacon as­sumes no responsibility for any other warranties than that granted by Vacon itself.
In all matters concerning the warranty, please contact first your distributor.
2
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
receipt of delivery vacon 7
EC DECLARATION OF CONF ORMITY
We
Manufact urer's na me: Vaco n Oyj
Manufact urer's ad dress: P.O.Box 25
7eitnirosnuR
asaaV18356-NIF
dnalniF
hereby dec lare that the produc t
Product name: Vacon 10 Freq uency Converter
Model de signation : Vacon 10 1L 0001 2…to 00 09 2
21100ot…21000L301nocaV 42100ot…41000L301nocaV
has been designed a nd manufact ured in ac cordance with the fo llowing standards:
Safety:
EN 60204 -1:2009 (as re levant), EN 61800-5 -1:2007
EMC: EN 61800-3:2004 +A1:2012
and conforms to t he relevant safet y provisions of the Lo w Voltage Directive 2006/95/E C and EMC Directive 2004/108 /EC.
It is ensured through internal m easures and quality control t hat the product conforms at all times to the req uirements of the current D irective a nd the relevant st andards.
In Vaasa, 1 6th of Ap ril, 2014
isiaLaseV
tnediserP
The year t he CE m arking wa s affixed: 2011

2.5 Manufacturer’s declaration of conformity

24-hour support (0)201 212 575 • Email: vacon@vacon.com
2
8 vacon installation
=
M5
MI3
MI1
=M4
MI2
=M5
LOC REM
BACK RESET
OK
LOC REM
BACK
RESET
OK
LOC
REM
BACK
RESET
OK
12

3 INSTALLATION

3.1 Mechanical installation

There are two possible ways to mount Vacon 10 in the wall. For MI1-MI3, either screw or DIN-rail mounting. The mounting dimensions are given on the back of the drive and on the following page.
Figure 3.1: Screw mounting, MI1 - MI3
Figure 3.2: DIN-rail mounting, MI1 - MI3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
3
installation vacon 9

3.1.1 Vacon 10 dimensions

Figure 3.3: Vacon 10 dimensions, MI1 - MI3
Frame H1 H2 H3 W1 W2 W3 D1 D2
MI1 160.1 147 137.3 65.5 37.8 4.5 98.5 7 MI2 195 183 170 90 62.5 5.5 101.5 7 MI3 254.3 244 229.3 100 75 5.5 108.5 7
Table 3.1: Vacon 10 dimensions in millimetres
Frame Dimensions(mm) Weig ht*
W H D (kg.)
MI1 66 160 98 0.5 MI2 90 195 102 0.7 MI3 100 254.3 109 1
Table 3.2: Vacon 10 frame dimensions (mm) and weights (kg)
*without shipping package
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
10 vacon installation
Frame Dimensions(Inches) Weight *
W H D (Ibs.)
MI1 2.6 6.2 3.9 1.2 MI2 3.5 9.9 4 1.5 MI3 3.9 10.3 4.3 2.2
Table 3.3: Vacon 10 frame dimensions (Inch) and weights (Ibs)
Figure 3.4: Vacon10 dimensions, MI2 - 3 Display Location
*without shipping package
Dimensions(mm)
A 17 22.3 B 44 102
Table 3.4: Vacon 10 frame dimensions (mm)
3
Frame
MI2 MI3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installation vacon 11
B
C
B
A
D
A

3.1.2 Cooling

Enough free space shall be left above and below the frequency converter to ensure sufficient air circulation and cooling. You will find the required dimensions for free space in the table below.
If several units are mounted above each other the required free space equals C + D (see Installation space). Moreover, the outlet air used for cooling by the lower unit must be directed away from the air intake of the upper unit.
The amount of cooling air required is indicated below. Also make sure that the tem­perature of the cooling air does not exceed the maximum ambient temperature of the converter.
Min clearance (mm)
Frame A* B* C D
MI1 20 20 100 50 MI2 20 20 100 50 MI3 20 20 100 50
Table 3.5: Min. clearances ar ound AC drive
*. Min clearance A and B for drives for MI1 ~ MI3 can be 0 mm if the ambient temperature is below 40 degrees.
F ig ur e 3 .5 : I ns ta l la ti on sp ac e
A = clearance around the freq. converter (see also B) B = distance from one frequency converter to another or distance to cabinet wall C = free space above the frequency converter D = free space underneath the frequency converter
NOTE! See the mounting dimensions on the back of the drive. Leave free space for cooling above (100 mm), below (50 mm), and on the sides (20 mm) of Vacon 10! For MI1 - MI3, side-to-side installation allowed only if the am­bient temperature is below 40 °C.
Frame Cooling air required (m³/h)
MI1 10 MI2 10
Table 3.6: Required cooling air
MI3 30
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
12 vacon installation

3.1.3 Power losses

If the operator wants to raise the switching frequency of the drive for some reason (typically e.g. in order to reduce the motor noise), this inevitably affects the power losses and cooling requirements, for different motor shaft power, operator can se­lect the switching frequency according to the graphs below.
MI1 - MI3 3P 400 V POWER LOSS
3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installation vacon 13
MI1 - MI3 3P 230 V POWER LOSS
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
14 vacon installation
3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installation vacon 15
MI1 - MI3 1P 230 V POWER LOSS
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
16 vacon installation
3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installation vacon 17

3.1.4 EMC levels

EN61800-3 defines the division of frequency converters into four classes according to the level of electromagnetic disturbances emitted, the requirements of a power system network and the installation environment (see below). The EMC class of each product is defined in the type designation code.
Category C1: Frequency converters of this class comply with the requirements of category C1 of the product standard EN 61800-3 (2004). Category C1 ensures the best EMC characteristics and it includes converters the rated voltage of which is less than 1000 V and which are intended for use in the 1st environment. NOTE: The requirements of class C are fulfilled only as far as the conducted emis­sions are concerned.
Category C2: Frequency converters of this class comply with the requirements of category C2 of the product standard EN 61800-3 (2004). Category C2 includes con­verters in fixed installations and the rated voltage of which is less than 1000 V. The class C2 frequency converters can be used both in the 1st and the 2nd environment.
Category C4: The drives of this class do not provide EMC emission protection. These kinds of drives are mounted in enclosures.
Environments in product standard EN 61800-3 (2004)
First environment: Environment that includes domestic premises. It also includes establishments directly connected without intermediate transformers to a low-volt­age power supply network which supplies buildings used for domestic purposes.
NOTE: houses, apartments, commercial premises or offices in a residential building are examples of first environment locations.
Second environment: Environment that includes all establishments other than those directly connected to a low-voltage power supply network which supplies buildings used for domestic purposes. NOTE: industrial areas, technical areas of any building fed from a dedicated trans­former are examples of second environment locations.
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
18 vacon installation

3.1.5 Changing the EMC protection class from C2 to C4

The EMC protection class of MI1-3 frequency converters can be changed from class C2 to class C4 (except 115V and 600V drives) by removing the EMC-capacitor discon-
necting screw, see figure below.
Note! Do not attempt to change the EMC level back to class C2. Even if the procedure
above is reversed, the frequency converter will no longer fulfil the EMC require­ments of class C2!
Figure 3.6: EMC protection class, MI1 - MI3
3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installation vacon 19
1~ (230V)
3~ (230V, 400V)
Motor out
MAINS
MOTOR
Strip the plastic cable coating for 360° earthing
L1 L2/ N L 3 U/ T1 V/T2 W/ T3R+ R-
1~ (230V)
3~(230V, 400V,600V)
1~ (115V)
MAINS
MOTOR
BRAKE RESISTOR
Externalbrakeresistor
Motor out
Strip t he plastic cable coating for 360° earthing
3~(230V, 400V,600V)

3.2 Cabling and connections

3.2.1 Power cabling

Note! Tightening torque for power cables is 0.5 - 0.6 Nm
Figure 3.7:
24-hour support (0)201 212 575 • Email: vacon@vacon.com
Figure 3.8: Vacon 10 power connections, MI2 - MI3
3
20 vacon installation
Attach this plate BEFORE i nstallin g the p ow er ca bl es
Attach the support AFTER i nstalling the p ower c abl es

3.2.2 Control cabling

3
Figure 3.9: Mount the PE-plate and API cable support, MI1 - MI3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installation vacon 21
Strip the plastic cable coating for 360°earthing
Control cable tightening torque: 0.4 Nm
Figure 3.10: Open the lid, MI1 - MI3
Figure 3.11: Install the control cables. MI1 - MI3. See Chapter 6.2
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
22 vacon installation

3.2.3 Screw of cables

Figure 3.12: MI1 screws
3
Figure 3.13: MI2 screws
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installation vacon 23
Figure 3.14: MI3 screws
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
24 vacon installation

3.2.4 Cable and fuse specifications

Use cables with heat resistance of at least +70°C. The cables and the fuses must be dimensioned according to the tables below. Installation of cables according to UL regulations is presented in Chapter Cable installation and the UL standards.
The fuses function also as cable overload protection. These instructions apply only to cases with one motor and one cable connection from the frequency converter to the motor. In any other case, ask the factory for more in­formation.
EMC category cat. C2 cat. C4
Mains cable types 1 1 Motor cable types 3 1 Control cable types 4 4
Table 3.7: Cable types required to meet standards. EMC categories are described in Chapter EMC levels
Cable type Description
Power cable intended for fixed installation and the specific mains voltage.
1
Shielded cable not required. (NKCABLES / MCMK or similar recommended)
Power cable equipped with concentric protection wire and intended for
2
the specific mains voltage. (NKCABLES / MCMK or similar recommended).
Power cable equipped with compact low-impedance shield and intended for the specific mains voltage.
3
(NKCABLES / MCCMK, SAB / ÖZCUY-J or similar recommended).
*360º earthing of both motor and FC connection required to meet the standard
Screened cable equipped with compact low-impedance shield (NKCA-
4
Table 3.8: Cable type descriptions
BLES /Jamak, SAB / ÖZCuY-O or similar).
3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installation vacon 25
Terminal cable size (min/max)
Main
Earth
terminal
[mm
2
]
terminal
[mm
2
]
2
]
Control
terminal
[mm
2
]
terminal
Frame Ty pe
Fuse
[A]
Mains
cable
Cu [mm
2
]
Motor
cable
Cu [mm
MI2 0001-0004 20 2*2.5+2.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5 MI3 0005 32 2*6+6 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5
Table 3.9: Cable and fuse sizes for Vacon 10, 115 V, 1~
Terminal cable size (min/max)
Main
Earth
terminal
[mm
2
]
Control
terminal
[mm
2
]
terminal
[mm
2
]
terminal
Frame Ty pe
Fuse
[A]
Mains
cable
Cu [mm2]
Motor
cable
Cu [mm2]
MI1 0001-0003 10 2*1.5+1.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5 MI2 0004-0007 20 2*2.5+2.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5 MI3 0009 32 2*6+6 3*1.5+1.5 1.5-6 1.5-6 0.5-1.5 0.5-1.5
Table 3.10: Cable and fuse sizes for Vacon 10, 208 - 240 V, 1~
Terminal cable size (min/max)
Main
Earth
terminal
[mm
2
]
Control
terminal
[mm
2
]
terminal
[mm
2
]
terminal
Frame Ty pe
Fuse
[A]
Mains
cable
Cu [mm2]
Motor
cable
Cu [mm2]
MI1 0001-0003 6 3*1.5+1.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5 MI2 0004-0007 10 3*1.5+1.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5 MI3 0011 20 3*2.5+2.5 3*2.5+2.5 1.5-6 1.5-6 0.5-1.5 0.5-1.5
Table 3.11: Cable and fuse sizes for Vacon 10, 208 - 240 V, 3~
Relay
[mm
Relay
[mm
Relay
[mm
2
]
2
]
2
]
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
26 vacon installation
Terminal cable size (min/max)
Main
Earth
terminal
[mm
2
]
terminal
[mm
2
]
2
]
Control
terminal
[mm
2
]
terminal
Frame Ty pe
Fuse
[A]
Mains
cable
Cu
[mm2]
Motor
cable
Cu [mm
MI1 0001-0003 6 3*1.5+1.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5 MI2 0004-0006 10 3*1.5+1.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5 MI3 0008-0012 20 3*2.5+2.5 3*2.5+2.5 1.5-6 1.5-6 0.5-1.5 0.5-1.5
Table 3.12: Cable and fuse sizes for Vacon 10, 380 - 480 V, 3~
Terminal cable size (min/max)
Main
Earth
terminal
[mm
2
]
Control
terminal
[mm
2
]
terminal
[mm
2
]
terminal
Frame Typ e
Fuse
[A]
Mains
cable
Cu
[mm2]
Motor cable
Cu [mm2]
MI3 0002-0004 6 3*1.5+1.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5 MI3 0005-0006 10 3*1.5+1.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5 MI3 0009 20 3*2.5+2.5 3*2.5+2.5 1.5-6 1.5-6 0.5-1.5 0.5-1.5
Table 3.13: Cable and fuse sizes for Vacon 10, 600 V, 3~
Note! To fulfil standard EN61800-5-1, the protective conductor should be at least 10 mm2 Cu or 16 mm2 Al. Another possibility is to use an additional protective con-
ductor of at least the same size as the original one.
Relay
[mm
Relay
[mm
2
]
2
]
3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installation vacon 27

3.2.5 General cabling rules

Before starting the installation, check that none of the components of the fre-
1
quency converter is live.
Place the motor cables sufficiently far from other cables:
Avoid placing the motor cables in long parallel lines with other cables.
• If the motor cable runs in parallel with other cables, the minimum distance between the motor cable and other cables is 0.3 m.
• The given distance also applies between the motor cables and signal cables
2
3
4
of other systems.
• The maximum length of the motor cables for MI1-3 is 30 m. If use longer cable, current accuracy will be decreased.
• The motor cables should cross other cables at an angle of 90 degrees.
If cable insulation checks are needed, see Chapter Cable and motor insulation checks.
Connecting the cables:
• Strip the motor and mains cables as advised in Figure Stripping of cables.
• Connect the mains, motor and control cables into their respective termi­nals, see Figures Vacon 10 power connections, MI1 - Install the control cables.
• Note the tightening torques of chapter3.2.1 power cables and chapter 3.2.2 control cables given in Vacon 10 power connections, MI1 and Install the control cables. MI1 - MI3. See Chapter6.2.
• For information on cable installation according to UL regulations see Chap­ter Cable installation and the UL standards.
• Make sure that the control cable wires do not come in contact with th e elec­tronic components of the unit.
• If an external brake resistor (option) is used, connect its cable to the appro­priate terminal.
Check the connection of the earth cable to the motor and the frequency converter terminals marked with.
• Connect the separate shield of the motor cable to the earth plate of the frequency converter, motor and the supply centre.
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
28 vacon installation
20 mm
35 mm
8 mm
Earth conductor
8 mm

3.2.6 Stripping lengths of motor and mains cables

Figure 3.15: Stripping of cables
Note! Strip also the plastic cover of the cables for 360 degree earthing. See Figures Vacon 10 power connections, MI1, Vacon 10 power connections, MI2 - MI3 and Insta ll the control cables. MI1 - MI3. See Chapter 6.2.

3.2.7 Cable installation and th e UL standards

To meet the UL (Underwriters Laboratories) regulations, a UL-approved copper ca­ble with a minimum heat-resistance of +60 / 75°C must be used.
Use Class 1 wire only.
The units are suitable for use on a circuit capable of delivering not more than 50,000 rms symmetrical amperes, 600V maximum, when protected by T and J Class fuses.
Integral solid state short circuit protection does not provide branch circuit protec­tion. Branch circuit protection must be provided in accordance with the National Electric Code and any additional local codes. Branch circuit protection provided by fuses only.
Motor overload protection provided at 110% of full load current.

3.2.8 Cable and motor insulation checks

These checks can be performed as follows if motor or cable insulations are suspect­ed to be faulty.
1. Motor cable insulation checks
Disconnect the motor cable from terminals U / T1, V / T2 and W / T3 of the frequency converter and from the motor. Measure the insulation resistance of the motor cable between each phase conductor as well as between each phase conductor and the protective ground conductor.
The insulation resistance must be >1 MOhm.
3
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
installation vacon 29
2. Mains cable insulation checks
Disconnect the mains cable from terminals L1, L2 / N and L3 of the frequency con­verter and from the mains. Measure the insulation resistance of the mains cable be­tween each phase conductor as well as between each phase conductor and the protective ground conductor. The insulation resistance must be >1 MOhm.
3. Motor insulation checks
Disconnect the motor cable from the motor and open the bridging connections in the motor connection box. Measure the insulation resistance of each motor winding. The measurement voltage must equal at least the motor nominal voltage but not exceed 1000 V. The insulation resistance must be >1 MOhm.
24-hour support (0)201 212 575 • Email: vacon@vacon.com
3
30 vacon commissioning

4. COMMISSIONING

Before commissioning, read the warnings and instructions listed in Chapter 1!

4.1 Commissioning steps of Vacon 10

Read carefully the safety instructions in Chapter 1 and follow them.
1
After the installation, make sure that:
• both the frequency converter and the motor are grounded.
• the mains and motor cables comply with the requirements given in Chap­ter 3.2.4.
2
3 4 5
6
• the control cables are located as far as possible from the power. cables
(see Chapter 3.2.5, step 2) and the shields of the shielded cables are con­nected to protective earth.
Check the quality and quantity of cooling air (Chapter 3.1.2).
Check that all Start / Stop switches connected to the I / O terminals are in Stop- position.
Connect the frequency converter to mains.
Set the parameters of group 1 according to the requirements of your application. At least the following parameters should be set:
• motor nominal speed (par. 1.3)
• motor nominal current (par. 1.4)
• application type (par. 17.1)
You will find the values needed for the parameters on the motor rating plate.
4
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
commissioning vacon 31
Perform test run without motor. Perform either Test A or Test B:
A) Control from the I / O terminals:
• Turn the Start / Stop switch to ON position.
• Change the frequency reference.
• Check the Monitoring Menu and make sure that the value of Output fre­quency changes according to the change of frequency reference.
7
8
9
10
• Turn the Start / Stop switch to OFF position.
B) Control from the keypad:
• Select the keypad as the control place by pressing Loc / Rem button or select Local control with par 2.5.
• Push the Start button on the keypad.
• Check the Monitoring Menu and make sure that the value of Output fre­quency. changes according to the change of frequency reference.
• Push the Stop button on the keypad.
Run the no-load tests without the motor b eing connected to the process, if possi­ble. If this is impossible, secure the safety of each test prior to running it. Inform your co-workers of the tests.
• Switch off the supply voltage and wait up until the drive has stopped.
• Connect the motor cable to the motor and to the motor cable terminals of the frequency converter.
• See to that all Start / Stop switches are in Stop positions.
• Switch the mains ON.
• Repeat test 7A or 7B.
Perform an identification run (see par. 1.18), especially if the application requires a high startup torque or a high torque with low speed.
Connect the motor to the process (if the no-load test was running without the motor being connected).
• Before running the tests, make sure that this can be done safely.
• Inform your co-workers of the tests.
• Repeat test 7A or 7B.
24-hour support (0)201 212 575 • Email: vacon@vacon.com
4
32 vacon fault tracing
Fault code (2 = overvoltage)
FT 2

5. FAULT TRACING

When a fatal fault is detected by the frequency converter control electronics, the drive will stop and the symbol FT and the fault code blinked on the display are in the following format, e.g.:
The active fault can be reset by pressing BACK / RESET button when the API is in ac­tive fault menu level (FT XX), or pressing BACK / RESET button with long time (> 2 s) when the API is in active fault submenu level (F5.x ), or via the I / O terminal or field bus. Reset fault history (long push > 5 s), when the API is in fault history submenu level (F6.x). The faults with subcode and time labels are stored in the Fault history submenu which can be browsed. The different fault codes, their causes and correct­ing actions are presented in the table below.
5
Fault
Table 5.1: Fault codes
Fault name Possible cause Correcting actions
code
Overcurrent
1
Overvoltage
2
Earth fault
3
Frequency converter has detected too high a current
) in the motor cable:
(>4*I
N
• sudden heavy load increase
• short circuit in motor cables
• unsuitable motor
The DC-link voltage has exceeded the internal safety limit:
• deceleration time is too short
• high overvoltage spikes in mains
Current measurement has detected extra leakage current at start:
• insulation failure in cables or motor
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
Check loading. Check motor size. Check cables.
Increase the deceleration time (Par.4.3 or Par.4.6)
Check motor cables and motor
fault tracing vacon 33
Fault
Table 5.1: Fault codes
Fault name Possible cause Correcting actions
code
System fault
8
Undervoltage
9
Output phase fault
11
Frequency converter
13
undertemperature
Frequency converter
14
overtemperature
Motor stalled
15
Motor overtempera-
16
ture
Motor underload
17
• component failure
• faulty operation
The DC-link voltage has gone below the internal safety limit:
• most probable cause: supp ly voltage is too low
• frequency converter internal
fault
• Power outages
Current measurement has detected that there is no current in one motor phase.
Heat sink temperature is under
°C
-10
Heat sink is overheated.
Motor stall protection has tripped.
Motor overheating has been detected by frequency converter motor temperature model. Motor is overloaded.
Motor underload protection has tripped.
Reset the fault and restart . If the fault re-occurs, con­tact the distributor near to you. NOTE! If fault F8 occurs, find out the subcode of the fault from the Fault His­tory menu under Id xxx!
In case of temporary sup­ply voltage break reset the fault and restart the fre­quency converter. Check the supply voltage. If it is adequate, an internal fail­ure has occurred. Contact the distributor near to you.
Check motor cable and motor.
Check the ambient tem­perature.
Check that the cooling air flow is not blocked. Check the ambient tem­perature. Make sure that the switching frequency is not too high in relation to ambient temperature and motor load.
Check that the motor is able to rotate freely.
Decrease the motor load. If no motor overload exists, check the temper­ature model parameters.
Check motor and load, e.g. for broken belts or dry pumps.
24-hour support (0)201 212 575 • Email: vacon@vacon.com
5
34 vacon fault tracing
Fault
Table 5.1: Fault codes
Fault name Possible cause Correcting actions
code
EEPROM check sum
22
fault
Microcontroller
25
watchdog fault
Back EMF protection
27
Thermistor fault
29
Internal bus commu-
34
nication
Application fault
35
IGBT Overtemperature
41
Analog input select 20% - 100% (selected
50
signal range 4 to 20 mA or 2 to 10 V)
External fault
51
Fieldbus fault
53
Parameter save fault
• faulty operation
• component failure Note: Alarm 22 is issued for cali­bration data CRC check.
• faulty operation
• component failure
Drive has detected that the magnet­ized motor is runnin g in start situation.
• A rotating PM-motor
The thermistor input of option board has detected increase
Ambient interference or defective hard ware
Application is not working prop­erly.
Over temperature alarm is issued when the IGBT switch temperature exceeds 110 °C.
Current at the analogue input is < 4mA; Voltage at the analogue input is < 2 V.
• control cable is broken or loose.
• signal source has failed.
Digital input fault. Digital input has been programmed as external fault input and this input is active.
The data connection between the fieldbus Master and the fieldbus of the drive has broken.
Contact the distributor near to you.
Reset the fault and restart. If the fault re-occur, contact the distributor near to you.
Make sure that there is no rotating PM-motor when the start command is given.
Check motor cooling and loading. Check thermistor connection (If thermistor input of the option board is not in use it has to be shor t circuited).
If the fault re-occur, contact the distributor near to you.
Contact the distributor near to you.
Check loading. Check motor size. Make identification run.
Check the current loop circuitry.
Remove the external device fault.
Check installation. If installation is correct, contact the nearest Vacon distributor.
5
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
fault tracing vacon 35
Fault
111
Table 5.1: Fault codes
Fault name Possible cause Correcting actions
code
Wrong run fault (FWD/
55
REV conflict)
Identification fault Identification run has failed.
57
Tem per atur e fau lt
Run forward and backward at the same time.
Over low or over high tempera­ture
F08 SubCode Fault
82 MPI RX buffer overflow 84 MPI CRC 86 MPI2 CRC 87 MPI2 message buffer overflow 96 MPI queue full
97 MPI off line error 101 MODBUS out of buffer 115 Device Property data format tree too deep exceed 3
Table 5.2: Fault Subcode
F22 SubCode Fault
1 DA_CN, Power down data counter error 2 DA_PD, Power down data restore fail 3 DA_FH, Fault history data error 4 DA_PA, Restore parameter CRC error
Table 5.2: Fault Subcode
Check I/O control single 1 and I/O control single 2. Single 1 should be changed to signal 1, single 2 should be changed to signal 2.
Run command was removed before comple­tion of identification run. Motor is not connected to frequency converter. There is load on motor shaft.
Check temperature signal from OPTBH board
24-hour support (0)201 212 575 • Email: vacon@vacon.com
5
36 vacon vacon 10 api

6. VACON 10 APPLICATION INTERFACE

6.1 Introduction

There is only one version of Control Board available for the Vacon 10 drive:
Vers ion Composition
6 Digital inputs 2 Analogue inputs
Vacon 10
Table 6.1: Available Control Board
This section provides you with a description of the I / O-signals for Vacon 10 and in­structions for using the Vacon 10 general purpose application.
The frequency reference can be selected from Preset Speed 0-7, Keypad, Fieldbus, AI1, AI2, PI.
Basic properties:
• Digital inputs DI1…DI6 are freely programmable. The user can assign a single input to many functions.
• Digital-, relay- and analogue outputs are freely programmable.
• Analog output can be set as current output.
• Analog input 1 can be set as voltage input and Analog input 2 can be set as current input.
Special features:
• Programmable Start / Stop and Reverse signal logic
• Reference scaling
• DC-brake at start and stop
• Programmable U / f curve
• Adjustable switching frequency
• Auto reset function after fault
1 Analogue output 1 Digital output 2 Relay outputs
RS-485 Interface
6
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
vacon 10 api vacon 37
• Protections and supervisions (all fully programmable; off, alarm, fault):
• Analog input low fault
• Undervoltage fault
• Earth fault
• Output phase fault
• Motor thermal, stall and underload protection
• 8 preset speeds
• Analogue input range selection, signal scaling and filtering
• PI controller
24-hour support (0)201 212 575 • Email: vacon@vacon.com
6
38 vacon vacon 10 api
20


6.2 Control I/O

Terminal Signal Factory preset Description
1 +10Vref Ref. voltage out Maximum load 10 mA 2 AI1 Analog signal in 1
3 GND I/O signal ground 6 24Vout 24V output for DI's
7 GND I/O signal ground 8 DI1 Digital input 1 9 DI2 Digital input 2 10 DI3 Digital input 3
A A RS485 signal A FB Communication Negative B B RS485 signal B FB Communication Positive 4 AI2 Analog signal in 2
mA
5 GND I/O signal ground 13 GND I/O signal ground 14 DI4 Digital input 4 15 DI5 Digital input 5 16 DI6 Digital input 6
18 AO Analog Output 20 DO Digital signal out
22 RO1 NO Relay out 1 23 RO1 CM
24 RO2 NC Relay out 2 25 RO2 CM 26 RO2 NO
Table 6.2: Vacon 10 default I/O configuration and connections P) = Programmable function, see parameter lists and descriptions, chapters 8 and 9.
Freq. reference
Start forward P) Start reverse P) Fault reset P)
PI actual value P)
Preset speed B0 P) Preset speed B1 External fault
Output frequency P) Active = READY P)
Active = RUN P)
Active = FAULT
P)
0 - 10 V Ri = 300 k (min)
%, max. load 50 mA
positive: Logic1: 8…30V; Logic0: 0…1.5V,
Ri = 20 k
0(4) - 20 mA, Ri 200
Positive: Logic1: 8…30V;
P)
Logic0: 0…1.5V,
P)
Ri = 20 k 0(4) - 20 mA, RL 500
Open collector, max. load 35V/50mA Switching load: 250Vac/3A, 24V DC 3A
P)
Switching load: 250Vac/3A, 24V DC 3A
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
6
vacon 10 api vacon 39
ON
OFF
Figure 6.1: Vacon 10 I/O
24-hour support (0)201 212 575 • Email: vacon@vacon.com
6
40 vacon control panel

7. CONTROL PANEL

7.1 General

The panel is an irremovable part of the drive consisting of corresponding control board; The overlay with display status on the cover and the button are in clarifica­tions in the user language.
The User Panel consists o f an alphanumeric LCD display with back light and a keypad with the 9 push buttons (see Figure 7.1).

7.2 Display

The display includes 14-segment and 7-segment blocks, arrowheads and clear text unit symbols. The arrowheads, when visible, indicate some information about the drive, which is printed in clear text in user language on the overlay (numbers 1…14 in the figure below). The arrowheads are grouped in 3 groups with the following meanings and English overlay texts (see Figure 7.1):
Group 1 - 5; Drive status
1 = Drive is ready to start (READY) 2 = Drive is running (RUN) 3 = Drive has stopped (STOP) 4 = Alarm condition is active (ALARM) 5 = Drive has stopped due to a fault (FAULT)
Group 6 - 10; Control selections
6 = Motor is rotating forward (FWD) 7 = Motor is rotating reverse (REV) 8 = I/O terminal block is the selected control place (I / O) 9 = Keypad is the selected control place (KEYPAD) 10 = Fieldbus is the selected control place (BUS)
Group 11 - 14; Navigation main menu
11 = Reference main menu (REF) 12 = Monitoring main menu (MON) 13 = Parameter main menu (PAR) 14 = System main menu (SYS)
7
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
control panel vacon 41
1 2 3 4 5
6 7 8 9 10
11
13
14
12
READY RUN STOP ALARM FAULT
FWD REV I/O KEYPAD BUS
SYS
PAR
REF
MON
BACK
RESET
LOC
REM
OK

7.3 Keypad

The keypad section of the control panel consists of 9 buttons (see Figure 7.1). The buttons and their functions are described as Table 7.1.
The drive stops by pressing the keypad STOP button. The drive starts by pressing the keypad START button when the selected control
place is KEYPAD.
Figure 7.1: Vacon 10 Control panel
24-hour support (0)201 212 575 • Email: vacon@vacon.com
7
42 vacon control panel
OK
BACK
RESET
LOC REM
Symbol Button Name Function Description
Start Motor START from the panel
STOP Motor STOP from the panel
Used for confirmation. Enter edit mode for parameter
OK
Back / Reset
Up and Down
Left and Right
Alternate in display between the parameter value and parameter code. Reference frequency value adjusting no need to press OK-button to confir m
Cancels edited parameter Move backwards in menu levels Reset fault indication
Select root parameter number on root­parameter list, Up decrease / Down increase parameter number, Up increase / Down decrease parame­ter value change
Available in REF,PAR and SYS menu parameter digit setting when changing value MON,PAR and SYS can also u se left and right button to navigate the parameter group, like in MON menu use right but­ton from V1.x to V2.x to V3.x Can be used to change direction in REF menu in local mode:
- Right arrow would mean reverse (REV)
- Left arrow would mean forward (FWD)
7
Loc / Rem Change control place
Table 7.1: Keypad Function
NOTE! The status of all the 9 buttons are available for application program!
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
control panel vacon 43
FWD REV I/O K EYPAD BUS
REF
MON
PAR
SYS SYS
SYS SYS
SYS SYS
SYS SYS
FAU LTALARMSTOPREADY RU N
FWD REV I/O KEYPAD BU S
REF
PA R
FAULTALARMSTOPR EADY RUN
MON
FW D R EV I/O KEY PAD BUS
REF
PAR
FAULTALARMSTOPREADY RUN
MON
FWD REV I/O KEYPAD BUS
REF
PAR
FAULTALARMSTOPREADY RUN
MON
FWD REV I/O KEYPAD BUS
REF
PAR
FAULTALARMSTOPREADY RUN
MON
FWD REV I/O KEYPAD BUS
REF
PAR
FAULTALARMSTOPREADY RUN
MON
FWD REV I/O KEYPAD BUS
REF
PAR
FAU LTALARMST OPREADY RUN
MON
PRESS
PRESS
PRESS
PRESS
PRESS
FWD REV I/O KEYPAD B US
REF
MON
PAR
FAULTALARMSTOPRE ADY RUN
PRESS
PRESS
OK
OK
OK
OK
OK
In this men u you can browsethe monitoring values.
In this men u you can browseand editthe parameters.
Dispalys the keypad reference value regardlessof the sele cted contron place.
Here youwill be able tobrowse system parameter and fault submenu.
MONI TORING MENU
REFERENCE MENU
PARAMETER MENU
SYSTEM MENU
Hz
Hz

7.4 Navigation on the Vacon 10 control panel

This chapter provides you with information on na vigating the menus on Vacon 10 and editing the values of the parameters.

7.4.1 Main menu

The menu structure of Vacon 10 control software consists of a main menu and sev­eral submenus. Navigation in the main menu is shown below:
24-hour support (0)201 212 575 • Email: vacon@vacon.com
Figure 7.2: The main menu of Vacon 10
7
44 vacon control panel
Press to enter edit mode
Change value
OK
SYS
FWD REV I/O KEYPAD BUS
REF
MON
PA R
FAU LTALARMSTOPREADY R UN
Hz

7.4.2 Reference menu

Figure 7.3: Reference menu display
Move to the reference menu with the UP / DOWN button (see Figure 7.2). The reference value can be changed with UP / DOWN button as shown in Figure 7.3.
If the value has big change, first press Left and Right buttons to select the digit which has to be changed, then press Up button to increase and Down button to decreases the value in the selected digit. When the drive is in run mode, the reference value changed by Up/Down/Left/Right button will take effective no need to press OK button.
Note! LEFT and RIGHT buttons can be used to change the direction in
Ref menu in local control mode.
7
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
control panel vacon 45
OK
OK
OK
1
2
3
Press Lef t/Right to browse other Monitoring groups
Prsess Down to browse V4.5
5
Press OK V4.5 is display
4
Preess OK th e value is displayed
FAULTALARMSTOPREADY RUN
REF
MON
PAR
SYS
REF
MON
PAR
SYS
FAULTALARMSTOPREADY RUN
FWD R EV I/O KEYPAD BUS FWD R EV I/O KEYPAD BUS
Press OK to enter
Monitoring menu
REF
MON
PAR
SYS
FAULTALARMSTOPREADY RUN
FWD R EV I/O KEYPAD BUS
REF
MON
PAR
SYS
FAULTALARMSTOPREADY RUN
FWD REV I/O KEYPAD BUS
FAULTALARMSTOPREADY RUN
REF
MON
PAR
SYS
FWD R EV I/O KEYPAD BUS

7.4.3 Monitoring menu

Monitoring values are actual values of measured signals as well as status of some control settings. It is visible in Vacon 10 display, but it can not be edited. The moni­toring values are listed in Table 7.2.
Pressing Left/Right button to change the actual parameter to the first parameter of the next group, to browse monitor menu from V1.x to V2.1 to V4.1. After entering the desired group, the monitoring values can be browsed b y pressing UP /DOWN button, as shown in Figure 7.4.
In MON menu the selected signal and its value are alternateing in the display by pressing OK button.
24-hour support (0)201 212 575 • Email: vacon@vacon.com
Figure 7.4: Monitoring menu display
Note! Turn on drive power, arrowhead of main menu is at MON, V x. x
or monitor parameter value of Vx.x is displayed in Panel. Display Vx.x or monitor parameter value of Vx.x is determined
by the last show status before power shut down. E.g., it was V4.5, and it is also V4.5 when restart.
7
46 vacon control panel
Code Monitoring signal Unit ID Description
V1.1 Output frequency Hz 1 Output frequency to motor
V1.2 Frequency reference Hz 25
V1.3 Motor speed rpm 2 Calculated motor speed
V1.4 Motor current A 3 Measured motor current
V1.5 Motor torque % 4
V1.6 Motor Power % 5
V1.7 Motor voltage V 6 Motor voltage
V1.8 DC-link voltage V 7 Measured DC-link voltage
V1.9 Drive temperature °C 8 Heatsink temperature
V1.10 Motor temperature % 9 Calculated motor temperature
V2.1 Analog input 1 % 59
V2.2 Analog input 2 % 60
V2.3 Analog output % 81
Digital input status DI1,
V2.4
DI2, DI3
Digital input status DI4,
V2.5
DI5, DI6
V2.6 RO1, RO2, DO 17 Relay / digital output status
V4.1 PI setpoint % 20 Regulator setpoint
V4.2 PI feedback value % 21 Regulator actual value
V4.3 PI error % 22 Regulator error
V4.4 PI output % 23 Regulator output
Table 7.2: Vacon 10 monitoring signals
Frequency reference to motor con­trol
Calculated actual / nominal torque of the motor
Calculated actual / nominal power of the motor
AI1 signal range in percent of used range
AI2 signal range in percent of used range
AO signal range in percent of used range
15 Digital input status
16 Digital input status
7
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
control panel vacon 47
OK
OK
2
Press Right to browse otherPa r. group
4
Press OK button to ent er edit mode
3
Press down button to browse P3.4
5
Press Up / Down to change value
OK
6
Press OK to confirm
FAU LTALARMSTOPREADY RUN
REF
MON
PAR
SYS
REF
MON
PAR
SYS
REF
MON
PAR
SYS
FAU LTALARMSTOPREADY RUN
FAU LTALARMSTOPREADY RUN
FWD REV I/O KEYPAD BUS FWD R EV I/O KEYPAD BUS
FWD REV I/O KEYPAD BUS
1 Press OK to enter Pa r. menu
FAULTALARMSTOPREADY RU N
REF
MON
PAR
SYS
FWD REV I/O KEYPAD BUS
FAUL TALARMSTOPREADY RUN
REF
MON
PAR
SYS
FWD REV I/O KEYPAD BUS
Hz

7.4.4 Parameter menu

In Parameter menu only the Quick setup parameter list is shown as default. By giving the value 0 to the parameter 17.2, it is possible to open other advanced parameter
groups. The parameter lists and descriptions can be found in chapters 8 and 9. The following figure shows the parameter menu view:
The parameter can be changed as the Figure 7.5. Left / Right button is available inside Parameter menu. Pressing Left / Right button
to change the actual parameter to the first parameter of the next group (Example: any parameter of P1… is displayed -> RIGHT button -> P2.1 is displayed -> RIGHT but­ton -> P3.1 is displayed …). After entering the desired group, pressing UP / DOWN button to select root parameter number, and then press OK button to display the val­ue of the parameter and also enter edit mode.
24-hour support (0)201 212 575 • Email: vacon@vacon.com
Figure 7.5: Parameter menu
7
48 vacon control panel
In edit mode, Left and Right buttons are used to select the digit which has to be changed, and Up increases / Down decreases parameter value.
In edit mode, the value of Px.x is displayed blinkingly in the panel. After about 10 s, Px.x is displayed in the panel again if you don't press any button.
Note! In edit mode, if you edit the value and don't press OK button, the
value isn't changed successfully. In edit mode, if you don't edit the value, you can press Reset /
Back button to display Px.x again.
7
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
control panel vacon 49
OK
Press OK to enter V1.1
1
Press Left/Right button to browse othergroups
2
Press down to browse other active faults
3
REF
MON
PAR
SYS
FAULTALARMSTOP
FWD REV I/O K EYPAD BUS
READY RUN
OK
Press OK to select one fault to browse its time
4
REF
MON
PAR
SYS
FAULTALARMSTOPREADY RU N
FWD R EV I/O K EYPAD B US
Browse for faultcode(C xx), subcode(Id xx), days(d xx), hours(H xx), minutes(M xx)
5
REF
MON
PAR
SYS
FAULTALARMSTOPREADY RUN
FWD R EV I/O K EYPAD B US
REF
MON
PAR
SYS
FAULTALARMSTOPREADY RUN
FWD R EV I/O K EYPAD BU S
REF
MON
PAR
SYS
FAULTALARMSTOPREADY RUN
FWD R EV I/O K EYPAD B US

7.4.5 System menu

SYS menu including fault submenu and system parameter submenu, and the display and operation of the system parameter submenu is similar to PAR menu or MON menu.In system parameter submenu, there are some editable parameter (P) and some uneditable parameter (V).
The Fault submenu of SYS menu includes active fault submenu and fault history sub ­menu.
In active fault situation, FAULT arrow is blinking and the display is blinking active fault menu item with fault code. If there are several active faults, you can check it by entering the active fault submenu F5.x. F5.1 is always the latest active fault code. The active faults can be reset by pressing BACK / RESET button with long time (>2 s), when the API is in active fault submenu level (F5.x). If the fault cannot be reset, the blinking continues. It is possible to select other display menus durin g active fault, but in this case the display returns automatically to the fault menu if no button is pressed in 10 seconds. The fault code, subcode and the operating day, hour and minute val­ues at the fault instant are shown in the value menu (operating hours = displayed reading).
24-hour support (0)201 212 575 • Email: vacon@vacon.com
Figure 7.6: Fault menu
7
50 vacon control panel
Note! Fault History can be reset by long pressing the BACK / RESET
button for 5 second time,when the API is in fault history sub­menu level (F6.x), it will also clear all active faults.
See Chapter5 for fault descriptions
7
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameters vacon 51
i

8. STANDARD APPLICATION PARAMETERS

On the next pages you can find the lists of parameters within the respective param­eter groups. The parameter descriptions are given in Chapter 9 .
Explanations:
Code: Location indication on the keypad; Shows the operator the present
Parameter: Name of monitoring value or parameter Min: Minimum value of parameter Max: Maximum value of parameter Unit: Unit of parameter value; given if available Default: Factory preset value ID: ID number of the parameter (used with fieldbus control)
NOTE: This manual is for Vacon 10 standard application only. please downl oad the appropriate user manuals on http://www.vacon.com -> Support & Download if special application details needed.
Monitoring value number or Parameter number
More information on this parameter available in chapter 9: ‘Param­eter descriptions’ click on the parameter name.
Modifiable only in stop state
24-hour support (0)201 212 575 • Email: vacon@vacon.com
8
52 vacon parameters
P1.1
P1.2
P1.3
P1.4
P1.5
i
iii
i
i
i
i
i
i
P1.7
P1.15
P2.2
P2.3
P3.1
P3.2

8.1 Quick setup parameters (Virtual menu, shows when par. 17.2 = 1)

Code Parameter Min Max Unit Default ID Note
Motor nominal
voltage
Motor nominal
frequency
Motor nominal
speed
Motor nominal
current
Motor cos
(Power Factor)
Current limit
Torque boost 0 1 0 109
Remote control
P2.1
place selection
Start function
Stop function
Min frequency 0,00 P3.2 Hz 0,00 101 Minimum freq reference
Max frequency P3.1 320,00 Hz
Remote Control Place frequency
P3.3
refere nce selec-
tion
P3.4 Preset s peed 0 P3.1 P3.2 Hz 5,00 1 80 Activated by digital inputs P3.5 Preset speed 1 P3.1 P3.2 Hz 10,00 105 Activated by digital inputs
P3.6 Preset speed 2 P3.1 P3.2 Hz 15,00 106
P3.7 Preset speed 3 P3.1 P3.2 Hz 20,00 126
Table 8.1: Quick setup parameters
180 690 V Varies 110
30,00 320,00 Hz
30 20000 rpm
2,0 x
0,2 x
I
I
Nunit
Nunit
0,30 1,00 0,85 120
2,0 x
0,2 x
I
I
Nunit
Nunit
0 1 0 172
0
1 0 505
0
1 0 506
1 6 4 117
50,00 /
60,00
1440 /
1720
I
A
Nunit
1,5 x
A
I
Nunit
50,00 /
60,00
Check rating plate on the motor.
Check rating plate on the
111
motor.
Default a pplies for a 4-
112
pole motor.
Check rating plate on the
113
motor.
Check rating plate on the motor.
107 Maximum motor current
0 = Not used 1 = Used
0 = I / O terminal 1 = Fieldbus
0 = Ramp 1 = Flying start
0 = Coasting 1 = Ramp
Maximum freq refer-
102
ence
1 = Preset speed 0-7 2 = Keypad 3 = Fieldbus 4 = AI1 5 = AI2 6 = PI
Activated by digital inputs
Activated by digital inputs
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
8
parameters vacon 53
P4.2
P4.3
P14.1
Code Paramete r Min Max Unit Default ID Note
Acceleration time
Deceleration time
P6.1 AI1 Signal range 0 1 0 379
P6.5 AI2 Signal range 0 1 0 390
Automatic reset 0 1 0 731
Parameter
P17.2
Table 8.1: Quick setup parameters
conceal
0,1 3000,0 s 3,0 103
1
0,1 3000,0 s 3,0 104
1
01 1 115
Acceleration time from 0 Hz to maximum frequency.
Deceleration time from maximum frequency to 0 Hz.
0 = 0 - 100% 1 = 20% - 100%
20% is the same as 2 V minimum signal level.
0 = 0 - 100% 1 = 20% - 100%
20% is t he sa me as 4 mA minimum signal level.
0 = Disable 1 = Enable
0 = All parameters visi-
ble 1 = Only quick setup parameter group visible
24-hour support (0)201 212 575 • Email: vacon@vacon.com
8
54 vacon parameters
P1.1
P1.2
P1.3
i
iiiiiii
i
i
i
P1.4
P1.5P1.7
P1.8
P1.9
P1.10
P1.11
P1.12
P1.13
P1.14
P1.15
P1.16
P1.17

8.2 Motor settings (Control panel: Menu PAR -> P1)

Code Parameter Min Max Unit Default ID Note
Motor nominal
voltage
Motor nominal fre-
quency
Motor nominal
speed
Motor nominal
current
Motor cos
(Power Factor)
Current limit
Motor control
mode
U / f ratio 0 2 0 108
Field weakening
point
Field weakening
point voltage
U / f mid point
frequency
U / f mid point
voltage
Zero freq voltage 0,00 40,00 % 0,00 606
Tor que Boo st 0 1 0 10 9
Switching fre-
quency
Brake Chopper 0 2 0 504
Table 8.2: Motor settings
180 690 V Varies 110
30,00 320,00 Hz
30 20000 rpm
2,0 x
0,2 x
I
I
Nunit
Nunit
0,30 1,00 0,85 120
2,0 x
0,2 x
I
I
Nunit
Nunit
01 0600
8,00
320,00 Hz
10,00 200,00 % 100,00 603
0,00 P1.10 Hz
0,00 P1.11 % 100,00 605
1,5 16,0 kHz 4,0 / 2,0 601
50,00 /
60,00
1440 /
1720
I
A
Nunit
1,5 x
A
I
Nunit
50,00 /
60,00
50,00 /
60,00
Check rating plate on the motor
Check rating plate on the
111
motor
Default applie s for a 4-pole
112
motor.
Check rating plate on the
113
motor
Check rating plate on the motor
107 Maximum motor current
0 = Frequency control 1 = Open loop speed control
0 = Linear 1 = Square 2 = Programmable
Field weakening point fre-
602
quency Voltage at field weakening
point as % of U
Mid point frequency for
604
programmable U / f Mid point voltage for pro-
grammable U / f as % of U
nmot
Voltage at 0 Hz as % of U
nmot
0 = Disabled 1 = Enabled
PWM frequency. If values are higher than default, reduce the current capacity
0 = Disabled 1 = Enabled: Always 2 = Run state
nmot
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
8
parameters vacon 55
iii
P1.19
P1.20
P1.21
P1.22
P1.23
P1.24
Code Parameter Min Max Unit Default ID Note
Motor identifica-
tion
Rs voltage drop 0,00 100,00 % 0,00 662
Overvoltage con-
troller
Undervoltage
controller
Sine filter 0 1 0 522
0 65535 2 8928 6 48
Table 8.2: Motor settings
01 0631
02 1607
01 1608
0 = Not active 1 = Standstill identification
(need run command within 20 s to activate)
Voltage drop over motor windings as % of U
nominal current.
0 = Disabled 1 = Enabled, Standard
mode 2 = Enable d, Shock load mode
0 = Disable 1 = Enable
0 = not in use 1 = in use
Modulator configuration word: B1 = discontinuous modu­lation (DPWMMIN) B2 = Pulse dropping in overmodulation
B6 = under modulation B8 = instantaneous DC volt-
age compensation*
B11 = Low noise B12 = Dead time compen-
sation* B13 = Flux error compen­sation* *Enable by default
NOTE! These parameters are shown, when P17.2 = 0.
nmot
at
24-hour support (0)201 212 575 • Email: vacon@vacon.com
8
56 vacon parameters
iiiii
P2.2
P2.3
P2.9
P3.1
P3.2
iiiiiiiii

8.3 Start / stop setup (Control panel: Menu PAR -> P2)

Code Parameter Min Max Unit Default ID Note
Remote Control
P2.1
Place Selection
Start function
Stop function
I / O Start / Stop
P2.4
P2.5 Local / Remote 0 1 0 211
P2.6
Table 8.3: Start / stop setup
logic
Keypad control
direction
Keypad button
lock
0
1 0 172
0
1 0 505
0
1 0 506
0 3 2 300
0 1 0 123
0 1 0 15520

8.4 Frequency references (Control panel: Menu PAR -> P3)

Code Parameter Min Max Unit Default ID Note
Min frequency 0,00 P3.2 Hz 0,00 101
Max frequency P3.1 320,00 Hz
Remote Control
Place frequency
P3.3
referenc e
selection
P3.4 Preset speed 0 P3.1 P3.2 Hz 5,00 180 Activated by digital inputs P3.5 Preset speed 1 P3.1 P3.2 Hz 10,00 105 Activated by digital inputs P3.6 Preset speed 2 P3.1 P3.2 Hz 15,00 106 Activated by digital inputs P3.7 Preset speed 3 P3.1 P3.2 Hz 20,00 126 Activated by digital inputs P3.8 Preset speed 4 P3.1 P3.2 Hz 25,00 127 Activated by digital inputs
P3.9 Preset speed 5 P3.1 P3.2 Hz 30,00 128 Activated by digital inputs P3.10 Preset speed 6 P3.1 P3.2 Hz 40,00 129 Activated by digital inputs P3.11 Preset speed 7 P3.1 P3.2 Hz 50,00 130 Activated by digital inputs
Table 8.4: Frequency references
16 4117
NOTE! These parameters are shown, when P17.2 = 0.
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
8
0 = I / O terminals 1 = Fieldbus
0 = Ramp 1 = Flying start
0 = Coasting 1 = Ramp
I / O control I / O control signal 1 signal 2 0 Forward Reverse 1 Fw d( edg e) In ver te d St op 2 Fwd(edge) Rev(edge) 3 Start Reverse
0 = Remote control 1 = Local control
0 = Forward 1 = Reverse
0 = unlock all keypad button 1 = Lock/Rem button locked
50,00 /
102
60,00
Minimum allowed frequency reference
Maximum allowed frequency reference
1 = Preset speed 0-7 2 = Keypad 3 = Fieldbus 4 = AI1 5 = AI2 6 = PI
parameters vacon 57
i
i
iii
i
P4.1
P4.2
P4.3
P4.4
P4.5
P4.6
P4.7
P4.8
P4.9
P4.10
P4.11
P4.12

8.5 Ramps and brakes setup (Control panel: Menu PAR -> P4)

Code Parameter Min Max Unit Default ID Note
Ramp S-shape 0,0 10,0 s 0,0 500
Acceleration time 1 0,1 3000,0 s 3,0 103
Deceleration time 1 0,1 3000,0 s 3,0 104
Ramp S-shape 2 0,0 10,0 s 0,0 501 See t he parameter P4.1
Acceleration time 2 0,1 3000,0 s 10,0 502
Deceleration time 2 0,1 3000,0 s 10,0 503
Flux Braking 0 3 0 520
2,0 x
Flux Braking
Current
DC Braking Current
Stop DC current
time
Stop DC current
frequency
Start DC current
time
Table 8.5: Ramps and brakes setup
0,5 x
I
I
Nunit
Nunit
2,0 x
0,3 x
I
I
Nunit
Nunit
0,00 600,00 s 0,00 508
0,10 10,00 Hz 1,50 515
0,00 600,00 s 0,00 516 0,00 = Not active
I
A
Nunit
I
A
Nunit
0 = Linear >0 = S-curve ramp time
Defines the time required for the output frequency to increase from zero frequency to maximum frequency.
Defines the time required for the output frequency to decrease from maxi­mum frequency to zero frequency.
See the parameter P4.2
See the parameter P4.3
0 = Off 1 = Deceleration 2 = Chopper 3 = Full Mode
Defines the current level
519
for flux braking.
Defines the current
507
injected into the motor during DC brakeing.
Determines if braking is ON or OFF and the braking time of the DC-brake when the motor is stopping. 0,00 = Not active
The output frequency at which the DC-braking is applied.
24-hour support (0)201 212 575 • Email: vacon@vacon.com
8
58 vacon parameters
iii
i

8.6 Digital inputs (Control panel: Menu PAR -> P5)

Code Parameter Min Max Unit Default ID Note
0 = Not used 1 = DI1
I / O control signal 1 0 6 1 403
P5.1
P5.2 I / O control signal 2 0 6 2 404 As parameter 5.1 P5.3 Reverse 0 6 0 412 As parameter 5.1 P5.4 Ext. fault Close 0 6 6 405 As parameter 5.1 P5.5 Ext. fault Open 0 6 0 406 As parameter 5.1 P5.6 Fault reset 0 6 3 414 As parameter 5.1 P5.7 Run enable 0 6 0 407 As parameter 5.1 P5.8 Preset speed B0 0 6 4 419 As parameter 5.1
P5.9 Preset speed B1 0 6 5 420 As parameter 5.1 P5.10 Preset speed B2 0 6 0 421 As parameter 5.1 P5.11 Ramp time 2 selection 0 6 0 408 As parameter 5.1 P5.12 Disable PI 0 6 0 1020 As parameter 5.1 P5.13 Force to I/O 0 6 0 409 As parameter 5.1
Table 8.6: Digital inputs
2 = DI2 3 = DI3 4 = DI4 5 = DI5 6 = DI6

8.7 Analogue inputs (Control panel: Menu PAR -> P6)

Code Parame ter Min Max Unit Default ID Note
AI1 Signal range 0 1 0 379
P6.1
-100,00
P6.2 AI1 Custom min
P6.3 AI1 Custom max
P6.4 AI1 filter time 0,0 10,0 s 0,1 378 0 = no filtering
P6.5 AI2 signal range 0 1 0 390
P6.6 AI2 Custom min
P6.7 AI2 Custom max
P6.8 AI2 filter time 0,0 10,0 s 0,1 389 0 = no filtering
Table 8.7: Analogue inputs
100,00 % 0,00 380 0,00 = no min scaling
-100,00
300,00 % 100,00 381 100,00 = no max scaling
-100,00
100,00 % 0,00 391 0,00 = no min scaling
-100,00
300,00 % 100,00 392 100,00 = no max scaling
0 = 0 - 100% ( 0 - 10 V) 1 = 20% - 100% ( 2 - 10 V)
0 = 0 - 100% ( 0 - 20 mA) 1 = 20% - 100% (4 -20 mA)
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
8
parameters vacon 59
i
i
i

8.8 Digital outputs (Control panel: Menu PAR -> P8)

Code Parameter Min Max Unit Default ID Selections
0 = Not used 1 = Ready 2 = Run 3 = Fault
RO1 signal
P8.1
selection
RO2 signal
P8.2
selcetion
DO1 signal
P8.3
selcetion
P8.4 RO2 inversion 0 1 0 1588
Table 8.8: Digital outputs
0 11 2 313
0 11 3 314 As parameter 8.1
0 11 1 312 As parameter 8.1
4 = Fault Inverted 5 = Warning 6 = Reversed 7 = At Speed 8 = Motor regula tor active 9 = FB C ontrol Wo rd.B13 10 = FB C ontrol Wo rd.B14 11 = FB C ontrol Wo rd.B15
0 = No inversion 1 = Inverted

8.9 Analogue outputs (Control panel: Menu PAR -> P9)

Code Parameter Min Max Unit Default ID Selections
0 = Not used
Analog output
P9.1
signal selection
Analog output
P9.2
minimum
Table 8.9: Analogue output s
0 4 1 307
0 1 0 310
1 = Output freq. (0-f 2 = Output current (0-I 3 = Motor torque (0-T 4 = PI output (0 - 100%)
0 = 0 mA 1 = 4 mA
max
)
nMotor
nMotor
)
)
24-hour support (0)201 212 575 • Email: vacon@vacon.com
8
60 vacon parameters
P13.2
P13.3
P13.4
i
iiiii
P13.5
P13.6
P13.7
P13.8
P13.9
P13.10
P13.23
P14.1
P14.2
i
i
P14.3
P14.5

8.10 Protections (Control panel: Menu PAR -> P13)

Code Param eter Min Max Unit Default ID Note
Analog Input low
P13.1
Table 8.10: Protections
fault
Under voltage
fault
Earth fault
Output Phase Fault
Stall protection
Under load protection
Motor thermal
protection
Mtp:Ambient
temperature
Mtp:Zero speed
cooling
Mtp:Thermal time
constant
FWD/REV conflict
supervision
0 2 1 700
1 2 2 727
0
2 2 703 As parameter 13.1
0
2 2 702 As parameter 13.1
0
2 0 709 As parameter 13.1
0
2 0 713 As parameter 13.1
0
2 2 704 As parameter 13.1
-20
100
0,0
150,0 % 40,0 706 Cooling as % at 0 speed
1
200 min 45 707
0
2 1 1463 Same as P13.1
40 705
°C
NOTE! These parameters are shown, when P17.2 = 0.

8.11 Fault autoreset parameters (Control panel: Menu PAR -> P14)

Code Paramete r Min Max Unit Default ID Note
Automatic Reset 0 1 0 731
Wait time 0,10 10,00 s 0,50 717 Waiting time after fault
Trial time 0,00 60,00 s 30,00 718 Maximum time for trials
Restart Function 0 2 2 719
Table 8.11: Fault autoreset parameters
NOTE! These parameters are shown, when P17.2 = 0.
0 = No action 1 = Alarm 2 = Fault: Coast
1 = No response (no fault
generated but drive still stops modulation) 2 = Faul t:Coa st
Environment tempera­tion
Motor thermal time con­stant
0 = Disabled 1 = Enable
0 = Ramping 1 = Flying 2 = From Start Function
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
8
parameters vacon 61
i
i
i
i
P17.1

8.12 PI control parameters (Control panel: Menu PAR -> P15)

Code Parameter Min Max Unit Default ID Note
Setpoint source
P15.1
selection
P15.2 Fixed setpoint 0,0 100,0 % 50,0 167 Fixed setpoint
Feedb ack
P15.4
source selection
Feedback value
P15.5
minumum
Feedback value
P15.6
maximum P15.7 P gain 0,0 1000,0 % 100,0 118 Proportional gain P15.8 I time 0,00 320,00 s 10,00 119 Integrative time
P15.10 Error inversion 0 1 0 340
Table 8.12: PI control parameters
0 3 0 332
0 2 1 334
0,0 50,0 % 0,0 336 Value at minimum signal
10,0 300,0 % 100,0 337 Value at maximum signal
NOTE! These parameters are shown, when P17.2 = 0.

8.13 Application Setting (Control panel: Menu PAR -> P17)

0 = Fixed setpoint % 1 = AI1 2 = AI2 3 = Fiel-bus (ProcessDataIn1)
0 = AI1 1 = AI2 2 = Field-bus (Process-DataIn2)
0 = Direct (Feedback < Set-
point ->Increase PID out­put) 1 = Inverted (Feedback > Setpoint -> Decrease PID output)
Code Parameter Min Max Unit Default ID Note
0 = Basic 1 = Pump
Application Type 0 3 0 540
Parameter
P17.2
conceal
Table 8.13: Application Setting parameters
0 1 1 115
2 = Fan dr ive 3 = High Torque NOTE! Visible only when
Startup wizard is active.
0 = All parameters visible 1 = Only quick setup
parameter group visible
24-hour support (0)201 212 575 • Email: vacon@vacon.com
8
62 vacon parameters

8.14 System parameters

Code Parameter Min Max Default ID Note
V1.1 API SW ID 2314 V1.2 API SW version 835 V1.3 Power SW ID 2315 V1.4 Power SW version 834 V1.5 Application ID 837 V1.6 Application revision 838 V1.7 System load 839
V2.1 Communication status 808
P2.2 Fieldbus protocol 0 1 0 809
P2.3 Slave address 1 255 1 810
P2.4 Baud rate 0 5 5 811
P2.7 Communication time out 0 255 10 814
Reset communication
P2.8
Table 8.14: System parameters
Software information (MENU SYS -> V1)
Fieldbus parameter (MENU SYS ->V2)
status
0 1 0 815
Status of Modbus communication. Format: xx.yyy where xx = 0 - 64 (Number of error messages) yyy = 0 - 999 (Number of good messages)
0 = Not used 1 = Modbus used
Default setting: None parity, 1 stop bit
0 = 300 1 = 600 2 = 1200 3 = 2400 4 = 4800 5 = 9600
1 = 1 sec 2 = 2 secs, etc
8
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameters vacon 63
P4.2
Code Parameter Min Max Default ID Note
V3.1 MWh counter 827 Million Watt Hour V3.2 Power on days 828 V3.3 Power on hours 829 V3.4 Run counter: Days 840 V3.5 Run counter: Hours 841 V3.6 Fault counter 842
Restore factory defaults 0 1 0 831
F5.x Active Fault menu F6.x Fault History menu
Table 8.14: System parameters
Other information
1 = Restores factory
defaults for all param­eters
24-hour support (0)201 212 575 • Email: vacon@vacon.com
8
64 vacon parameter descriptions

9. PARAMETER DESCRIPTIONS

On the next pages you can find the descriptions of certain parameters. The descrip­tions have been arranged according to parameter group and number.

9.1 Motor settings (Control panel: Menu PAR -> P1)

1.7 CURRENT LIMIT

This parameter determines the maximum motor current from the frequency converter. To avoid motor overload, set this parameter according to the rated current of the motor. The current limit is equal to (1.5*In) by default.

1.8 MOTOR CONTROL MODE

With this parameter the user can select the motor control mode. The selec­tions are:
0 = Frequency control: Drive frequency reference is set to output frequency without s lip com-
pensation. Motor actual speed is finally defined by motor load.
1 = Open loop speed control: Drive frequency reference is set to motor speed reference. The motor
speed remains the same regardless of motor load. Slip is compensat­ed.

1.9 U / F RATIO

There are three selections for this parameter:
0 = Linear:
The voltage of the motor changes linearly with the frequency in the constant flux area from 0 Hz to the field weakening point where the field weakening point voltage is supplied to the motor. Linear U / f ratio should be used in constant torque applications. See Figure 9.1.
This default setting should be used if there is no special need for an­other setting.
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
U[V]
f[Hz]
Un
Par. 1.11
Par. 1.14
Par. 1.10
Default: Nominal voltage of the m otor
Linear
Squared
Field weakening point
Default: Nominal frequency of t he motor
parameter descriptions vacon 65
1 = Square:
The voltage of the motor changes following a squared curve form with the frequency in the area from 0 Hz to the field weakening point w here the field weakening point voltage is also supplied to the motor. The motor runs under magnetised below the field weakening point and produces less torque, power losses and electromechanical noise. Squared U / f ratio can be used in applications where torque demand of the load is proportional to the square of the speed, e.g. in centrifugal fans and pumps.
Figure 9.1: Linear and squared change of motor voltage
2 = Programmable U / f curve:
The U / f curve can be programmed with three different points. Pro­grammable U / f curve can be used if the other settings do not satisfy the needs of the application.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
66 vacon parameter descriptions
Un
Par.1.11
U[V]
f[Hz ]
Par.1.13
Par.1.14
Default: Nominal voltage of the motor
Field weakening point
Default: Nominal frequency of the motor
Par.1.12 Par.1.10
Figure 9.2: Programmable U / f curve

1.10 FIELD WEAKENING POINT

The field weakening point is the output frequency at which the output voltage reaches the value set with par. 1.11.

1.11 FIELD WEAKENING POINT VOLTAGE

Above the frequency at the field weakening point, the output voltage remains at the value set with this parameter. Below the frequency at the field weaken­ing point, the output voltage depends on the setting of the U / f curve param­eters. See parameters 1.9-1.14 and Figures 9.1 and 9.2.
When the parameters 1.1 and 1.2 (nominal voltage and nominal frequency of the motor) are set, the parameters 1.10 and 1.11 are automatically given the corresponding values. If you need different values for the field weakening point and the voltage, change these parameters after setting the parameters
1.1 and 1.2.

1.12 U / F MIDDLE POINT FREQUENCY

If the programmable U / f curve has been selected with the parameter 1.9, this parameter defines the middle point frequency of the curve. See Figure 9.2.

1.13 U / F MIDDLE POINT VOLTAGE

If the programmable U / f curve has been selected with the parameter 1.9, this parameter defines the middle point voltage of the curve. See Figure 9.2.

1.14 ZERO FREQUENCY VOLTAGE

This parameter defines the zero frequency voltage of the curve. See Figures
9.1 and 9.2.
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon 67

1.15 TORQUE BOOST

When this parameter has been activated, the voltage to the motor changes au­tomatically with high load torque which makes the motor produce sufficient torque to start and run at low frequencies. The voltage increase depends on the motor type and power. Automatic torque boost can be used in applications with high load torque, e.g. in conveyors.
0 = Disabled 1 = Enabled
Note: In high torque - low speed applications - it is likely that the motor will
overheat. If the motor has to run a prolonged time under these conditions, special attention must be paid to cooling the motor. Use external cooling for the motor if the temperature tends to rise too high.
Note: The best performance can be reached by running motor identification, see par. 1.18.

1.16 SWITCHING FREQUENCY

Motor noise can be minimised using a high switching frequency. Increasing the switching frequency reduces the capacity of the frequency converter unit.
Switching frequency for Vacon 10: 1.5…16 kHz.

1.17 BRAKE CHOPPER

Note! An internal brake chopper is installed in three phase supply MI2 and MI3 size drives.
0 = Disable (No brake chopper used) 1 = Enable: Always (Used in Run and Stop state) 2 = Enable: Run state (Brake chopper used in Run state)
When the frequency converter is decelerating the motor, the energy stored to the in­ertia of the motor and the load are fed into an external brake resistor, if the brake chopper has been activated. This enables the frequency converter to decelerate the load with a torque equal to that of acceleration (provided that the correct brake re­sistor has been selected). See separate Brake resistor installation manual.

1.19 MOTOR IDENTIFICATION

0 = Not active 1 = Standstill identification
When Standstill identification is selected, the drive will perform an ID-run when it is started from selected control place. Drive has to be started within 20 seconds, otherwise identification is aborted.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
68 vacon parameter descriptions
The drive does not rotate the motor during Standstill identification. When ID run is ready the drive is stopped. Drive will start normally, when the next start command is given.
After end the identification, the drive need stop the start command. If control place is Keypad, user need press stop button. If control place is IO,user need put DI(Control signal) inactivate. If control place is fieldbus, user need set the control bit to 0.
The ID run improves the torque calculations and the automatic torque boost function. It will also result in a better slip compensation in speed control (more accurate RPM).
The parameters below will change after ID run successfully,
a. P1.8 Motor control mode b. P1.9 U / f ratio c. P1.12 U / f mid point frequency d. P1.13 U / f mid point voltage e. P1.14 Zero freq voltage f. P1.19 Motor identification (1->0) g. P1.20 Rs voltage drop
Note! The nameplate data of the motor has to be set BEFORE doing ID run.

1.21 OVERVOLTAGE CONTROLLER

0 = Disabled 1 = Enabled, Standard mode (Minor adjustments of OP frequency are
made) 2 = Enabled, Shock load mode (Controller adjusts OP freq. up to
max.freq.)

1.22 UNDERVOLTAGE CONTROLLER

0 = Disable 1 = Enable
These parameters allow the under-/overvoltage controllers to be switched out of operation. This may be useful, for example, if the mains supply voltage varies more than –15% to +10% and the application will not tolerate this over­/undervoltage. In this case, the regulator controls the output frequency taking the supply fluctuations into account.
When a value other than 0 is selected also the Closed Loop overvoltage controller becomes active (in Multi-Purpose Control application).
Note! Over-/undervoltage trips may occur when controllers are switched out of operation.
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon 69

9.2 Start / stop setup (Control panel: Menu PAR -> P2)

2.1 REMOTE CONTROL PLACE SELECTION

With this parameter, the user can select the active control place.Frequency reference can be selected by Parameter P3.3 The selections are:
0 = I / O terminal 1 = Fieldbus
The priority order of selecting the control place is:
1. Force to I/O when the digital input of P5.13 (Force to I/O) is active.
2. Loc/Rem button or P2.5 (Local/Remote) =1.
3. Determined by P2.1 (Remote Control Place Selection).
Note: You can select control place by pressing Loc / Rem button or with par.
2.5, P2.1 will have no effect in local mode.
Local = Keypad is the control place Remote = I / O terminal or FieldBus

2.2 START FUNCTION

The user can select two start functions for Vacon 10 with this parameter:
0 = Ramp start
The frequency converter starts from 0 Hz and accelerates to the set frequency reference within the set acceleration time (See detailed de­scription: ID103). (Load inertia, torque or starting friction may cause prolonged acceleration times).
1 = Flying start
The frequency converter is able to start into a running motor by apply­ing small current pulses to motor and searching for the frequency cor­responding to the speed the motor is running at. Searching starts from the maximum frequency towards the actual frequency until the cor­rect value is detected. Thereafter, the output frequency will be in­creased/decreased to the set reference value according to the set acceleration/deceleration parameters.
Use this mode if the motor is coasting when the start command is giv­en. With the flying start it is possible to start the motor from actual speed without forcing the speed to zero before ramping to reference.

2.3 STOP FUNCTION

Two stop functions can be selected in this application:
0 = Coasting
The motor coasts to a halt without control from the frequency convert­er after the Stop command.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
70 vacon parameter descriptions
FWD
REV
Set
frequency
Set
frequency
0Hz
Runenable
Ctrl s ignal 1
Ctrl s ignal 2
Keypad
start button
Keypad
stopbutton
1 2 3 4 5 6 7 8 9
10 11 12 13
Output frequency
t
1 = Ramping
After the Stop command, the speed of the motor is decelerated ac­cording to the set deceleration parameters.
If the regenerated energy is high it may be necessary to use an exter­nal braking resistor for to be able to decelerate the motor in accepta­ble time.

2.4 I / O START STOP LOGIC

Values 0...3 offer possibilities to control the starting and stopping of the AC drive with digital signal connected to digital inputs. CS = Control signal.
The selections including the text 'edge' shall be used to exclude the possibility of an unintentional start when, for example, power is connected, re-connected after a power failure, after a fault reset, after the drive is stopped by Run En­able (Run Enable = False) or when the control place is changed to I / O control.
The Start / Stop contact must be opened before the motor can be started.
Selection
number
9
Selection name Note
CS1:Forward
0
CS2:Backward
The functions take place when the contacts are closed.
Figure 9.3: Start/Stop logic, selection 0
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon 71
Explanations 1 Control signal (CS) 1 actives causing the
output frequency to rise. The motor runs forward.
2 CS2 activates which, however, has no
effect on the output frequency because the first selected direction has the high­est priority.
3 CS1 is inactivated which caused the
direction to start changing (FWD to REV) because CS2 is still active.
4 CS2 inactivates and the frequency fed to
the motor drops to 0.
5 CS2 actives again causing the motor to
accelerate (REV) towards the set fre­quency.
6 CS2 inactivates and the frequency fed to
the motor drops to 0.
7 CS1 actives and the motor accelerates
(FWD) towards the set frequency.
8 Run enable signal is set to FALSE, which
drops the frequency to 0.The run enable signal is configured with par. 5.7.
9 Run enable signal is set to TRUE, which
causes the frequency to rise towards the set frequency because CS1 is still active.
10 Keypad stop button is pressed and the
frequency fed to the motor drops to 0.
11 The drive starts through pushing the
Start button on the keypad.
12 The keypad stop button is pushed again
to stop the drive.
13 The attempt to start the drive through
pushing the Start button is not success­ful because CS1 is inactive.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
72 vacon parameter descriptions
FWD
REV
Set
frequency
Set
frequency
0Hz
Runenable
Ctrl signal 1
Ctrl signal 2
Keypad
stop button
1 2 3 4 5 6 7 8 9
Output frequency
t
Selection
number
Selection name Note
CS1:Forward(edge)
1
CS2:Inverted stop
Figure 9.4: Start/Stop logic, selection 1
Explanations 1 Control signal (CS) 1 actives causing the
output frequency to rise. The motor runs forward.
2 CS2 inactivates causing the frequency to
drop to 0.
3 CS1 activates causi ng the output fre-
quency to rise again. The motor runs forward.
4 Run enable signal is set to FALSE, which
drops the frequency to 0. The run enable signal is configured with par. 5.7.
5 Start attempt with CS1 is not successful
because Run enable signal is still FAL SE.
9
6 CS1 activates an d the motor accelerates
(FWD) towards the set frequency because the Run enable signal has been set to TRUE.
7 Keypad stop button is pressed and the
frequency fed to the motor drops to 0.
8 CS1 activates causing the output fre-
quency to rise again. The motor runs forward.
9 CS2 inac tivates causing the frequency to
drop to 0.
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon 73
FWD
REV
Set
frequency
Set
frequency
0Hz
Runenable
Ctrl signal 1
Ctrl signal 2
Keypad
stop button
1 2 3 5 6 7 8 9
10 11 12
Output frequency
t
`
4
Selection
number
2
Figure 9.5: Start/Stop logic, selection 2
Explanations: 1 Control signal (CS) 1 actives causing the
output frequency to rise. The motor runs forward.
2 CS2 activates which, however, has no
effect on the output frequency because the first selected direction has the high­est priority.
3 CS1 is inactivated which causes the
direction to start changing (FWD to REV) because CS2 is still active.
4 CS2 inactivates and the frequency fed to
the motor drops to 0.
5 CS2 activates aga in causing the motor to
accelerate (REV) towards the set fre­quency.
6 CS2 inactivates and the frequency fed to
the motor drops to 0.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
Selection name Note
CS1:Forward(edge) CS2:Backward(edge)
Shall be used to exclude the possibility of an unintentional start. The Start / Stop contact must be opened before the motor can be restarted.
7 CS1 activates an d the motor accelerates
(FWD) towards the set frequency.
8 CS1 activates and the motor accelerates
(FWD) towards the set frequency because the Run enable signal has been set to TRUE.
9 CS1 activates again causing the motor to
accelerate (REV) towards the set fre­quency.
10 CS1 is opened and closed again which
causes the motor to start.
11 CS1 inactivates and the frequency fed to
the motor drops to 0.
9
74 vacon parameter descriptions
FWD
REV
Set
frequency
Set
frequency
0Hz
Runenable
Ctrl signal 1
Ctrl signal 2
Keypad
start button
Keypad
stop button
1 2 3 4 5 6 7 8 9
10 11 12
Output frequency
t
Selection
number
3
Figure 9.6: Start/Stop logic, selection 3
Explanations: 1 Control signal (CS) 1 actives causing the
output frequency to rise. The motor runs forward.
2 CS2 activates whi ch causes the direction
to start changing (FWD to REV).
3 CS2 is inactivated which causes the
direction to start changing (REV to FWD) because CS1 is still active.
4 Also CS1 inactivates and the frequency
drops to 0.
5 Despite the activates of CS2,the motor
does not start because CS1 is inactive.
6 CS1 activates causi ng the output fre-
quency to rise again. The motor runs forward because CS2 is inactive.
9
Selection name Note
CS1:Start CS2:Reverse
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
7 R un enable signal i s set to FAL SE, whic h
drops the frequency to 0.The run enable signal is configured with par. 5.7.
8 Run enable signal is set to TRUE, which
causes the frequency to rise towards the set frequency because CS1 is still active.
9 Keypad stop button is pressed and the
frequency fed to the motor drops to 0.
10 The drive starts through pushing the
11 The drive is stopped again with the Stop
12 The attempt to start the drive through
Start button on the keypad.
button on the Keypad.
pushing the Start button is not success­ful because CS1 is inactive.
parameter descriptions vacon 75

2.5 LOCAL / REMOTE

This parameter defines whether the control place of the drive is remote (I / O or FieldBus) or local.
0 = Remote Control 1 = Local Control
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
76 vacon parameter descriptions

9.3 Frequency references (Control panel: Menu PAR -> P3)

3.3 REMOTE CONTROL PLACE FREQUENCY REFERENCE SELECTION

It defines the selected frequency reference source when the drive is remote control.
1 = Preset speed 0-7 2 = Keypad reference 3 = Fieldbus Reference 4 = AI1 5 = AI2 6 = PI

3.4 - 3.11 PRESET SPEEDS 0 - 7

Preset speeds 0 - 7 can be used to determine frequency references that are applied when appropriate combinations of digital inputs are activated. Preset speeds can be activated from digital inputs when Par.3.3 (Remote control place frequency reference selection) =1.
Parameter values are automatically limited between the minimum and maxi­mum frequencies. (par. 3.1, 3.2).
Speed
Preset speed 0 Preset speed 1 x Preset speed 2 x Preset speed 3 x x Preset speed 4 x Preset speed 5 x x Preset speed 6 x x Preset speed 7 x x x
Table 9.1: Preset speeds 0 - 7
Preset
speed B2
Preset
speed B1
Preset
speed B0
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
P4.2, 4.3
[Hz]
[t]
P4.1
P4.1
parameter descriptions vacon 77

9.4 Ramps & brakes setup (Control panel: Menu PAR -> P4)

4.1 RAMP S-SHAPE

The start and end of the acceleration and deceleration ramp can be smoothed with this parameter. Setting value 0 gives a linear ramp shape which causes acceleration and deceleration to act immediately to the changes in the refer­ence signal.
Setting value 0.1…10 seconds for this parameter produces an S-shaped accel­eration/deceleration. The acceleration and deceleration times are determined with parameters 4.2 and 4.3.
Figure 9.7: S-shaped acceleration/deceleration
4.2 ACCELERATIO N TIME 1
4.3 DECELERATION TIME 1
4.4 RAMP S-SHAPE 2
4.5 ACCELERATIO N TIME 2
4.6 DECELERATION TIME 2
These limits correspond to the time required for the output frequency to ac­celerate from the zero frequency to the set maximum frequency, or to decel­erate from the set maximum frequency to zero frequency.
The user can set two different acceleration/deceleration time and set two dif­ferent ramp s-shape for one application.The active set can be selected with the selected digital input (par. 5.11).
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
78 vacon parameter descriptions

4.7 FLUX BRAKING

Instead of DC braking, flux braking is a useful form of braking with motors of max. 15 kW.
When braking is needed, the frequency is reduced and the flux in the motor is increased, which in turn increases the motor's capability to brake. Unlike DC braking, the motor speed remains controlled during braking.
0 = Off 1 = Deceleration 2 = Chopper 3 = Full Mode
Note: Flux braking converts the energy into heat at the motor, and should be
used intermittently to avoid motor damage.

4.10 STOP DC CURREN T TIME

Determines if braking is ON or OFF and the braking time of the DC-brake when the motor is stopping. The function of the DC-brake depends on the stop function, par. 2.3.
0 = DC brake is not active >0 = DC brake is active and its function depends on the Stop function,
(par. 2.3). The DC braking time is determined with this parameter.
Par. 2.3 = 0 (Stop function = Coasting):
After the stop command, the motor coasts to a stop without control from the frequency converter.
With the DC injection, the motor can be electrically stopped in the shortest possible time, without using an optional external braking resistor.
The braking time is scaled by the frequency when the DC-braking starts. If the frequency is greater, or equal to the nominal frequency of the motor, the set value of parameter 4.10 determines the braking time.When the frequency is 10% of the nominal, the braking time is 10% of the set va lue of parameter 4.10.
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
f
n
f
n
t
t
t=1xpar.4.10
t=0,1x par.4.10
0,1 x f
n
RUN
STOP
RUN
STOP
Outputf requency
Motorspeed
Output frequency
Motor speed
DC-brakingON
DC-braking ON
f
out
f
out
t=par.4.
t
Par.4.1
Motorspeed
Output frequ
ency
DC- brak in g
RUN STOP
f
out
1
10
parameter descriptions vacon 79
Figure 9.8: DC-braking time when Stop mode = Coasting
Par. 2.3 = 1 (Stop function = Ramp):
After the Stop command, the speed of the motor is reduced according to the set deceleration parameters, if the inertia of the motor and load allows that, to the speed defined with parameter 4.11, where the DC-braking starts.
The braking time is defined with parameter 4.10. See Figure 9.9.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
Figure 9.9: DC-braking time when Stop mode = Ramp
9
80 vacon parameter descriptions
t
Pa r4.12
Par 4.9
RUN STO P
Output frequency
DC-braking current

4.11 STOP DC CURREN T FREQUENCY

It is the output frequency at which the DC-braking is applied.

4.12 START DC CURRENT TIME

DC-brake is activated when the start command is given. This parameter de­fines the time of the DC-braking. After the brake is released, the output fre­quency increases according to the set start function by par. 2.2.
Figure 9.10: DC braking time at start
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon 81

9.5 Digital inputs (Control panel: Menu PAR -> P5)

These parameters are programmed using the FTT-method (Function To Ter­minal), where you have a fixed input or output that you define a certain func­tion for. You can also define more than one function to a digital input, e.g. Start signal 1 and Preset Speed B1 to DI1.
The selections for these parameters are:
0 = Not used 1 = DI1 2 = DI2 3 = DI3 4 = DI4 5 = DI5
6 = DI6
5.1 I / O

5.2 I / O CTRL SIGNAL 2

5.3 REVERSE

5.4 EXTERNAL FAULT CLOSE
5.5 EXTERNAL FAULT OPEN
5.6 FAULT RESET
5.7 RUN ENABLE
5.8 PRESET SPEED B0
5.9 PRESET SPEED B1
5.10 PRESET SPEED B2
5.11 RAMP TIME 2 SELECTION
CTRL SIGNAL 1
The digital input only active when P2.4 (I/O Start stop logic) =1
The motor will run in reverse when the rising edge of P5.3 is happened.
Contact open: Acceleration / Deceleration time 1 and Ramp S-shape selected Contact closed: Acceleration / Deceleration time 2 and Ramp S-shape2 selected
Set Acceleration / Deceleration times with parameters 4.2 and 4.3 and the al­ternative ramp times with 4.4 and 4.5.
Set Ramp S-shape with Par. 4.1 and the alternative Ramp S-shape2 with Par. 4.4.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
82 vacon parameter descriptions
%
100%
63%
Par. 6 .4 Par. 6 .8
t[s]
Filtered signal
Unfiltered signal

9.6 Analogue inputs (Control panel: Menu PAR -> P6)

6.4 AI1 FILTER TIME
6.8 AI2 FILTER TIME
This parameter, given a value greater than 0, activates the function that filters out disturbances from the incoming analogue signal.
Long filtering time makes the regulation response slower. See Figure 9.11.
Figure 9.11: AI1 and AI2 signal filtering
6.2 AI1 CUSTOM MIN IMUM
6.3 AI1 CUSTOM MAX IMUM
6.6 AI2 CUSTOM MIN IMUM
6.7 AI2 CUSTOM MAX IMUM
These parameters set the analogue input signal for any input signal span from
-100 to 100%.
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon 83

9.7 Digital outputs (Control panel: Menu PAR -> P8)

8.1 RO1 SIGNAL SELECTION
8.2 RO2 SIGNAL SELCETION
8.3 DO1 SIGNAL SELCETION
Setting Signal content
0 = Not used Output is not in operation. 1 = Ready The frequency converter is ready to operate. 2 = Run The frequency converter operates (motor is running). 3 = Faul t A fault trip has occurred. 4 = Fault inverted A fault trip has not occurred. 5 = Warn ing A warning is active.
6 = Reversed
7 = At speed The output frequency has reached the set reference.
8 = Motor regulator active
9 = FB Con trol Word.B13 Output can be controlled with B13 in the fieldbus control word. 10 = FB Control Word.B14 Output can be controlled with B14 in the fieldbus control word. 11 = FB C ontrol Word.B 15 O utput can be controlled with B15 in the fieldbus control word.
Table 9.2: Output signals via RO1, RO2 and DO1
The reverse command has been selected, output frequency to
Each of motoring current regulator,generating current reg.
the motor is negative.
,over voltage reg. ,under voltage reg. is active.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
84 vacon parameter descriptions

9.8 Analogue outputs (Control panel: Menu PAR -> P9)

9.1 ANALOG OUTPUT SIGNAL SELECTION

9.2 ANALOG OUTPUT MINIMUM

0 = Not used 1 = Output frequency (0 - f 2 = Output current (0 - I 3 = Motor torque (0 - T 4 = PID output (0 - 100%)
0 = 0 mA 1 = 4 mA
nMotor
nMotor
max
)
)
)
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon 85
f
I
Inmotor *1.3
25Hz
Stall ar ea

9.9 Protections (Control panel:Menu Par->P13)

13.5 STALL PROTECTION

13.6 UNDER LOAD PROTECTION

0 = No action 1 = Alarm 2 = Fault, coast
The motor stall protection protects the motor from short time overload situa­tions such as one caused by a stalled shaft. The stall current is I stall time 15 seconds and stall frequency limit 25 Hz . If the current is higher than the limit and output frequency is lower than the limit, the stall state is true and the drive reacts according to this parameter. There is actually no real indication of the shaft rotation.
Figure 9.12: Stall characteristics
nMotor
0 = No action 1 = Alarm 2 = Fault, coast
The purpose of the motor underload protection is to ensure that there is load on the motor when the drive is running. If the motor loses its load there might be a problem in the process, e.g. a broken belt or a dry pump.
The underload protection time limit is 20 seconds, which is the maximum time allowed for an underload state to exist before causing a trip according to this parameter.
*1.3,
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
86 vacon parameter descriptions
Underload curve a t zero freq. = 10%
f
5 Hz
Underl oad curve a t nominal freq. = 50 %
Field we akening point, P1.11
Underload area
To rq ue
Figure 9.13: Underload protection

13.7 MOTOR THERMAL PROTECTION

The motor thermal protection is to protect the motor from overheating. The drive is capable of supplying higher than nominal current to the motor. If the load requires this high current there is a risk that the motor will be thermally overloaded. This is the case especially at low frequencies. At low frequencies the cooling effect of the motor is reduced as well as its capacity. If the motor is equipped with an external fan the load reduction at low speeds is small. The motor thermal protection is based on a calculated model and it uses the output current of the drive to determine the load on the motor. The motor thermal protection can be adjusted with parameters. The thermal current IT specifies the load current above which the motor is overloaded. This current limit is a function of the output frequency.
9
0 = No action 1 = Alarm 2 = Fault, coast
If tripping is selected the drive will stop and activate the fa ult stage, if the tem­perature of the motor becomes too high. Deactivating the protection, i.e. set­ting parameter to 0, will reset the thermal model of the motor to 0%.
CAUTION! The calculated model does not protect the motor if the airflow to the motor is reduced by blocked air intake grill.
NOTE! To comply with UL 508C requirements motor over-tempera­ture sensing is required at installation if the parameter is set to 0.
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon 87
f
f
n
par. = 40%
0
I
100%
Overload area
cooling
.913

13.8 MTP:AMBIENT TEMPERATURE

When the motor ambient temperature must be taken into consideration, it is recommended to set a value for this parameter. The value can be set between
-20 and 100 degrees Celsius.

13.9 MTP:ZERO SPEED COOLING

The cooling power can be set between 0 - 150.0% x cooling power at nominal frequency. See Figure 9.14.
P
T
Figure 9.14: Motor cooling power

13.10 MTP:THERMAL TIME CONSTANT

This time can be set between 1 and 200 minutes.
This is the thermal time constant of the motor. The bigger the motor, the long­er the time constants. The time constant is the time within which the calculat­ed thermal model has reached 63% of its final value.
The motor thermal time is specific to the motor design and it varies between different motor manufacturers.
If the motor's t6-time (t6 is the time in seconds the motor can safely operate at six times the rated current) is known (given by the motor manufacturer) the time constant parameter can be set basing on it. As a rule of thumb, the motor thermal time constant in minutes equals to 2 x t6. If the drive is in stop state the time constant is internally increased to three times the set parameter val­ue. See also Figure 9.15.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
88 vacon parameter descriptions
105%
Q=(I/IT)2x(1-e
-t/T )
I/I
T
Trip area
Mot or temp eratu re
Time
Motor temper atur e
TimeconstantT
*)
*)
Changes by motor size and adjusted with parameter
Fault
/warning activation point if selec ted
with
par.
Moto r current
.1013
.713
,
Figure 9.15: Motor temperature calculation
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon 89
Fault trigge r
Motor stop signal
Mot or
start signal
Su perv isio n
Restart 1 Restart 2
Trial time
par.14.3
Fa ul t a ct iv e
RESET/ Fault reset
Autoreset function: (Trials = 2)
Wait time
par.14.2
Wait t ime
par.1 4.2
Wait ti me
par.14. 2

9.10 Automatic reset (Control panel: Menu PAR -> P14)

14.1 AUTOMAT IC RESET

Activate the Automatic reset after fault with this parameter.
NOTE: Automatic reset is allowed for certain faults only.
Fault: 1. Under voltage
2. Over voltage
3. Over current
4. Motor temperature
5. Under load

14.3 TRIAL TIME

The Automatic restart function restarts the frequency converter when the faults have disappeared and the waiting time has elapsed.
The time count starts from the first autoreset. If the number of faults occur­ring during the trial time exceeds three, the fault state becomes active. Oth­erwise the fault is cleared after the trial time has elapsed and the next fault starts the trial time count again. See Figure 9.16.
If a single fault remains during the trial time, a fault state is true.
Figure 9.16: Example of Automatic restarts with two restarts
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
90 vacon parameter descriptions
0V 0
mA
par. 15.5
Custommin par.6.2/6.6
Custommax
par. 15.6
10V 20mA
Controller feedback(%)
Analogue input with cust om min and max scaling (%)
par.6.3 /6.7

9.11 PI control parameters (Control panel: Menu PAR -> P15)

15.7 P GAIN

This parameter defines the gain of the PI controller. If the value of the param­eter is set to 100%, a change of 10% in the error value causes the controller output to change by 10%.

15.8 I-TIME

This parameter defines the integration time of the PI controller. If this param­eter is set to 1,00 second, the controller output is changed by a value corre­sponding to the output caused from the gain every second. (Gain*Error)/s.

15.9 PID CONTROLLER D-TIME

This parameter defines the derivative time of the PID controller. If this param­eter is set to 1,00 second, a change of 10% in the error value causes the con­troller output to change by 10%.
15.5 FEEDBACK VALUE MINIMUM
15.6 FEEDBACK VALUE MAXIMUM
This parameter sets the minimum and maximum scaling points for feedback value.
Figure 9.17: Feedback minimum and maximum
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon 91
FAULTALARMSTOPREADY
RUN
REF
MON
PAR
SYS
FAULTALARMSTOPREADY RUN
REF
MON
PAR
SYS
FAULTALARMSTOPREADY RUN
REF
MON
PAR
SYS
FWD REV I/O KEY PAD BUS
FWD REV I/O KEY PAD BUS
FWD REV I/O KEY PAD BUS
FWD REV I/O KEY PAD BUS
2
1
4
3
Change
P1.3
value with Up/Dow n button and press OK to comfirm
Perform t he same procedure for P1. 4, motor nomi nal current
Press O K enter edit mode
Enter Par. menu, sel ect P1.3 motor nominal speed
FAULTALARMSTOPREADY RUN
REF
MON
PAR
SYS
OK
OK
rpm

9.12 Application setting (Control panel: Menu PAR->P17)

17.1 DRIVE SETUP

With this parameter you can easily set up your drive for four different applica­tions.
Note! This parameter is only visible when the Startup Wizard is active. The startup wizard will start in first power-up. It can also be started as follows. See the figures below.
NOTE! Running the startup wizard will always re turn all parameter
NOTE! StartUp-Wizard can be skipped after pressing STOP button
settings to their factory defaults!
continuously for 30 seconds
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
Figure 9.18: Startup wizard
9
92 vacon parameter descriptions
1
2
3
4
Selections:
Parameters affected:
P1.7 Currentlimit (A) P1.8 Moto r control mod e P1.15 Torque boost P2.2 Startfunction
P2.3 Sto p function P3.1 Min frequency P4.2 Acc. time (s) P4.3 Dec time (s)
Startup wizard showns par 17.1 numbe r.
Press OK to enter edit mode.
Press OK to confirm drivesetup
Selectbetween 0-3, seebelow!
OK
OK
READY RUN STOP ALARM FAULT
REF
MON
PA R
SYS
READY RUN STOP ALARM FAULT
FWD REV I/O KEYPAD BUS FWD REV I/O KEYPAD BUS FWD REV I/O K EYPA D B U S
READY RUN STOP ALARM FAULT
REF
MON
PAR
SYS
REF
MON
PA R
SYS
READY RUN STOP ALARM FAULT
REF
MON
PA R
SYS
FWD REV I/O K EYPA D B U S
1.7 P 1.8 P1.15 P2.2 P4.3
0=Basic
1=Pumpdrive
2=Fandrive
0= Not used
0= Frequecny control
0= Frequecny control
0= Frequecny control
1=Open loop speed
ontrol
0= Not used
0= Not used
1= used
0= Ramp
0= Ramp
1= Flying
0= Ramp
P2.3
1= Ramp
0= Coast
0= Coast
0= Coast
P3.1
0Hz
0Hz
20 Hz
20 Hz
3s
5s
1s
20s
P4.2
3s
5s
1s
20s
P
1,1 x
I
NMOT
1,1 x
I
NMOT
1,5 x
I
NMOT
1,5 x
I
NMOT
3 = High Torque dri ve
Figure 9.19: Drive setup
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon 93
ON
OFF

9.13 Modbus RTU

Vacon 10 has a built-in Modbus RTU bus interface. The signal level of the interface is in accordance with the RS-485 standard. The built-in Modbus connection of Vacon 10 supports the following function codes:
Funct ion code
Table 9.3: Modbus RTU

9.13.1 Termination resistor

The RS-485 bus is terminated with termination resistors of 120 ohms in both ends. Vacon 10 has a built-in termination resistor which is switched off as a default (pre­sented below). The termination resistor can be switched on and off with the right hand dip switch located above IO-terminals in the front of the drive (see below).

9.13.2 Modbus address area

The Modbus interface of Vacon 10 uses the ID numbers of the application parameters as addresses. The ID numbers can be found in the parameter tables in chapter 8. When several parameters / monitoring values are read at a time, they must be con­secutive. 11 addresses can be read and the addresses can be parameters or moni­toring values.
Note! With some PLC manufacturers, the interface driver for Modbus
Function name Address
03 Read Holding Registers All ID numbers No 04 Read Input Registers All ID numbers No 06 Write Single Registers All ID numbers Yes 16 Write multiple registers All ID numbers Yes
Figure 9.20: Vacon 10 I/O
RTU communication may contain an offset of 1 (the ID number to be used would then subtract 1).
Broadcast messages
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
94 vacon parameter descriptions

9.13.3 Modbus process data

Process data is an address area for fieldbus control. Fieldbus control is active when the value of parameter 2.1 (Control place) is 3 (= fieldbus). The content of the process data has been determined in the application. The following tables present the pro­cess data contents in the General Purpose Application.
ID Modbus register Name Scale Type
2101 32101, 42101 FB Status Word - Binary coded 2102 32102, 42102 FB General Status Word - Binary coded 2103 32103, 42103 Reserved 0,01 % 2104 32104, 42104 Output frequency 0.01 +/- Hz 2105 32105, 42105 Motor speed 1 +/- Rpm 2106 32106, 42106 Motor current 0.01 A 2107 32107, 42107 Motor torque 0,1 +/- % (of nominal) 2108 32108, 42108 Motor power 0,1 +/- % (of nominal) 2109 32109, 42109 Motor voltage 0,1 V 2110 32110, 42110 DC link voltage 1 V 2111 32111, 42111 Active fault code 1 -
Table 9.4: Output process data
ID Modbus register Name Scale Ty pe
2001 32001, 42001 FB Control Word - Binary coded 2002 32002, 42002 FB General Control Word - Binary coded 2003 32003, 42003 Reserved 0,01 % 2004 32004, 42004 Programmable by P15.1 2005 32005, 42005 Programmable by P15.4 2006 32006, 42006 - - ­2007 32007, 42007 - - ­2008 32008, 42008 - - ­2009 32009, 42009 - - ­2010 32010, 42010 - - ­2011 32011, 42011 - - -
Table 9.5: Input process data
Note! 2004 can set as PI Control Reference by setting P15.1(Setpoint se-
lection) or 2005 can be set as PI Actual value by setting P15.4 (Feed­back value selection)!
9
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
parameter descriptions vacon 95
Status word (output process data)
Information about the status of the device and messages is indicated in the Status word. The Status word is composed of 16 bits the meanings of which are described in the table below:
Bit
B0, RDY Drive not ready Drive ready B1, RUN Stop Run B2, DIR Clockwise Counter-clockwise B3, FLT No fault Fault active B4, W No alarm Alarm active B5, AREF Ramping Speed reference reached B6, Z - Drive is running at zero speed B7 - B15 - -
Table 9.6: Status word (output process data)
Value = 0 Value = 1
Actual speed (output process data)
This is actual speed of the frequency converter. The scaling is -10000...10000. The value is scaled in percentage of the frequency area between set minimum and max­imum frequency.
Control word (input process data)
The three first bits of the control word are used to control the frequency converter. By using control word it is possible to control the operation of the drive. The mean­ings of the bits of control word are explained in the table below:
Bit
B0, RUN Stop Run B1, DIR Clockwise Counter-clockwise B2, RST Rising edge of this bit will reset active fault
Table 9.7: Control word (input process data)
Valu e = 0 Val ue = 1
Description
Description
Speed reference (input process data)
This is the Reference 1 to the frequency converter. Used normally as Speed refer­ence. The allowed scaling is 0...10000. The value is scaled in percentage of the fre­quency area between the set minimum and maximum frequencies.
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
96 vacon technical data

10. TECHNICAL DATA

10.1 Vacon 10 technical data

Mains connection
Supply network
Motor connection
Control connection
Control characteristics
Table 10.1: Vacon 10 technical data
Input voltage U
Input frequency 45…66 Hz Connection to mains Once per minute or less (normal case)
Networks
Short circuit current Maximum short circuit current has to be < 50 kA.
Output voltage
Output current
Starting current / torque
Output frequency 0…320 Hz Frequency resolution 0,01 Hz Digital input Positive; Logic 1 : 8…+30V; Logic 0: 0…1.5V, Ri = 20K Analogue input voltage 0….+10V, Ri = 300 K (min) Analogue input current 0(4)…20mA, Ri = 200 Analogue output 0(4)….20mA,RL= 500 Digital output Open collector, max. load 35V/50mA
Relay output
Auxiliary voltage ±20%,max.load 50mA
Control method
Switching frequency 1...16 kHz; Factory default 4 kHz Frequency reference Resolution 0.01 Hz Field weakening point 30…320 Hz Acceleration time 0.1…3000 sec Deceleration time 0.1…3000 sec
Braking torque
115 V, -15%...+10% 1~ 208…240 V, -15%...+10% 1~ 208…240 V, -15%...+10% 3~
in
380 - 480 V, -15%...+10% 3~ 600 V, -15%...+10% 3~
Vacon 10 (400 V) cannot be used with corner grounded networks
0 - U
in
Continuous rated current IN at ambient temperature max. +50 ºC (depends on the unit size), overload
max.
1.5 x I
N
1 min / 10 min Current 2 x I
for 2 sec in every 20 sec period. Torque
N
depends on motor
Switching load: 250Vac/3A,
Frequency Control U / f Open Loop Sensorless Vector Control
with brake option (only in 3~ drives sizes MI2-5 )
100%*T
N
without brake option
30%*T
N
24V DC 3A
10
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
technical data vacon 97
-10 °C (no frost)…+40 / 50°C (depends on the unit size):
Ambient operating temperature
Storage temperature -40°C…+70°C
Relative humidity
Air quality:
Ambient conditions
EMC
- chemical vapours
- mech. particles
Altitude
Vibration: EN60068-2-6
Shock IEC 68-2-27
Enclosure class IP20 / IP21 / Nema1 for MI1-3 Pollution degree PD2 Immunity Complies with EN5008 2-1, -2, EN61800-3
Emissions
Standards
Certificates and manufac­turer’s decla­rations o f conformi ty
Table 10.1: Vacon 10 technical data
rated loadability I Side by side installation for MI1-3 it is always 40°C; For IP21/Nema1 option in MI1-3 the maximum temparture is also 40 °C.
0…95% RH, non-condensing, non-corrosive, no dripping water
IEC 721-3-3, unit in operation, class 3C2 IEC 721-3-3, unit in operation, class 3S2
100% load capacity (no derating) up to 1000 m. 1% der­ating for each 100 m above 1000 m; max. 2000 m
3...150 Hz Displacement amplitude 1(peak) mm at 3...15.8 Hz Max acceleration amplitude 1 G at 15.8...150 Hz
UPS Drop Test (for applicable UPS weights) Storage and shipping: max 15 G, 11 ms (in package)
230V: Complies with EMC category C2; With an internal RFI filter 400V: Complies with EMC category C2; With an internal RFI filter Both: No EMC emission protection (Vacon level N): With­out RFI filter
For EMC: EN61800-3 For safety: UL508C, EN61800-5
For safety: CE, UL, cUL, KC For EMC: CE, KC (see unit nameplate for more detailed approvals)
N
24-hour support (0)201 212 575 • Email: vacon@vacon.com
10
Loading...