Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Safetyvacon • 5
9000.emf
13006.emf
9001.emf
9000.emf
9000.emf
9000.emf
9000.emf
9000.emf
9000.emf
1.SAFETY
This manual contains clearly marked cautions and warnings that are intended for your personal
safety and to avoid any unintentional damage to the product or connected appliances.
Read the information included in cautions and warnings carefully.
The cautions and warnings are marked as follows:
Table 1. Warning signs
= DANGER! Dangerous voltage
= WARNING or CAUTION
= Caution! Hot surface
1.1Danger
The components of the power unit are live when the drive is connected to mains
potential. Coming into contact with this voltage is extremely dangerous and may
cause death or severe injury.
The motor terminals U, V, W and the brake resistor terminals are live when the
AC drive is connected to mains, even if the motor is not running.
After disconnecting the AC drive from the mains, wait until the indicators on the
keypad go out (if no keypad is attached, see the indicators on the cover). Wait 5
more minutes before doing any work on the connections of the drive. Do not open
the cover before this time has expired. After expiration of this time, use a
measuring equipment to absolutely ensure that no
ensure absence of voltage before starting any electrical work!
The control I/O-terminals are isolated from the mains potential. However, the
relay outputs and other I/O-terminals may have a dangerous control voltage
present even when the AC drive is disconnected from mains.
voltage is present.
Always
Before connecting the AC drive to mains make sure that the front and cable
covers of the drive are closed.
During a ramp stop (see the Application Manual), the motor is still generating
voltage to the drive. Therefore, do not touch the components of the AC drive
before the motor has completely stopped. Wait until the indicators on the keypad
go out (if no keypad is attached, see the indicators on the cover). Wait additional 5
minutes before starting any work on the drive.
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
1
vacon • 6Safety
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
1.2Warnings
The AC drive is meant for fixed installations only.
Do not perform any measurements when the AC drive is connected to the mains.
The earth leakage current of the AC drives exceeds 3.5mA AC. According to
standard EN61800-5-1, a reinforced protective ground connection must be
ensured. See Chapter 1.3.
If the AC drive is used as a part of a machine, the machine manufacturer is responsible for providing the machine with a supply disconnecting device (EN
60204-1).
Only spare parts delivered by VACON
®
can be used.
At power-up, power break or fault reset the motor will start immediately if the
start signal is active, unless the pulse control for
Start/Stop logic has been selected
Furthermore, the I/O functionalities (including start inputs) may change if
parameters, applications or software are changed. Disconnect, therefore, the
motor if an unexpected start can cause danger.
The motor starts automatically after automatic fault reset if the auto restart
function is activated. See the Application Manual for more detailed information.
Prior to measurements on the motor or the motor cable, disconnect the motor
cable from the AC drive.
Do not touch the components on the circuit boards. Static voltage discharge may
damage the components.
Check that the EMC level of the AC drive corresponds to the requirements of your
supply network.
.
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
1
Safetyvacon • 7
13006.emf 13006.emf
1.3Grounding and earth fault protection
CAUTION!
The AC drive must always be earthed with an grounding conductor connected to the grounding
terminal marked with .
The earth leakage current of the drive exceeds 3.5mA AC. According to EN61800-5-1, one or more
of the following conditions for the associated protective circuit must be satisfied:
a)The protective conductor must have a cross-sectional area of at least 10 mm
Al, through its total run.
b)Where the protective conductor has a cross-sectional area of less than 10 mm
2
Al, a second protective conductor of at least the same cross-sectional area must be
mm
provided up to a point where the protective conductor has a cross-sectional area not less
than 10 mm
2
Cu or 16 mm2 Al.
c)Automatic disconnection of the supply in case of loss of continuity of the protective
conductor.
2
Cu or 1 6 mm2
2
Cu or 16
The cross-sectional area of every protective grounding conductor which does not form part of the
supply cable or cable enclosure must, in any case, be not less than:
-2.5mm
-4mm
2
if mechanical protection is provided or
2
if mechanical protection is not provided.
The earth fault protection inside the AC drive protects only the drive itself against earth faults in the
motor or the motor cable. It is not intended for personal safety.
Due to the high capacitive currents present in the AC drive, fault current protective switches may
not function properly.
Do not perform any voltage withstand tests on any part of the AC drive. There is
a certain procedure according to which the tests must be performed. Ignoring
this procedure can cause damage to the product.
NOTE! You can download the English and French product manuals with applicable safety,
warning and caution information from https://www.danfoss.com/en/service-and-support/.
REMARQUE Vous pouvez télécharger les versions anglaise et française des manuels produit
contenant l’ensemble des informations de sécurité, avertissements et mises en garde
applicables sur le site https://www.danfoss.com/en/service-and-support/.
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
1
vacon • 8General
2.GENERAL
OPTE2/E8 RS-485 multiple protocols field option board supports both Modbus RTU and Metasys N2
protocols. With these fieldbuses, the AC drives can then be controlled and monitored from the
master.
®
OPTE2/E8 RS485 can be installed to the following VACON
•VACON® 20
®
•VACON
•VACON
•VACON
•VACON
•VACON
•VACON
•VACON
20 X / CP
®
100 INDUSTRIAL
®
FLOW
®
HVAC
®
100 X
®
NXP
®
NXS
AC drives:
2
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Option board technical datavacon • 9
3.OPTIONBOARDTECHNICALDATA
3.1General
Table 2. Technical da ta
ProtocolsModbus RTU / Metasys N2
Interface
Data transfer
Communications
method
Transfer cableShielded Twisted Pair
Electrical isolation500 VDC
Ambient operating
temperature
Storing temperature -40°C–70°C
Environment
Humidity<95%, no condensation allowed
AltitudeMax. 1,000 m
Vibration0.5 G at 9–200 Hz
• Support for VACON® NXP and VACON® NXS AC drives. See control firmware requirements in Chapter 6 "Installation".
• Support for 16 Modbus RTU process data items in VACON
®
NXP, VACON
drives. See details in Chapter 8.3 "Modbus data mapping" and
Chapter 12 "Appendix C - Fieldbus option board communication".
• Support for OPTC2/OPTC8 backward compatibility mode in
VACON
"OPTC2/OPTC8 RS485 compatibility mode".
• Support for VACON® 100 INDUSTRIAL, VACON® 100 FLOW,
VACON
drives.
•Initial version.
®
®
100 INDUSTRIAL and VACON® 100 FLOW AC
NX and VACON® 100 family AC drives. See Chapter
100 X, VACON® 100 HVAC and VACON® 20X/CP AC
Table 3. OPTE2/E8 RS485 firmware versions
New featuresFirmware version
®
V003
V002
V001
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
3
vacon • 10Layout and connections
4.LAYOUTANDCONNECTIONS
The difference between OPTE2 option board and OPTE8 option board is bus connector. OPTE2 option
board has a 5-pin pluggable bus connector, and OPTE8 option board has a 9-pin female D-SUB
connector. Except that, they have the same LED indications, jumpers and interface board connector.
4.1OPTE2 (screw plug) option board layout
Figure 1. OPTE2 (screw plug) option board layout
Table 4. OPTE2 (screw plug) connector pinout
SignalPinDescription
Shield1Cable Shield
VP2Supply voltage - plus (5V)
RxD / TxD-P3Receive/Transmit data - plus(B)
RxD / TxD-N4Receive/Transmit data - minus(A)
DGND5Data ground (reference potential for VP)
NOTE! When replacing the OPTC2 option board with the OPTE2 option board, note that Receive/
Transmit data - plus (B) and Receive/Transmit data - minus (A) pins have switched places. In OPTC2,
the pin 1 is not connected to the cable shield.
Table 5. OPTC2 (screw plug) connector pinout
SignalPinDescription
NC1No connection
VP2Supply voltage - plus (5V)
RxD / TxD-N3Receive/Transmit data - minus (A)
RxD / TxD-P4Receive/Transmit data - plus (B)
4
DGND5Data ground (reference potential for VP)
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Shield1Cable Shield
VP6Supply voltage - plus (5V)
RxD / TxD-P3Receive/Transmit data - plus (B)
RxD / TxD-N8Receive/Transmit data - minus (A)
DGND5Data ground (reference potential for VP)
NOTE! When replacing the OPTC8 option board with the OPTE8 option board, note that Receive/
Transmit data - plus (B) and Receive/Transmit data - minus (A) pins have switched places.
Shield1Cable Shield
VP6Supply voltage - plus (5V)
RxD / TxD-N3Receive/Transmit data - minus (A)
RxD / TxD-P8Receive/Transmit data - plus (B)
DGND5Data ground (reference potential for VP)
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
4
vacon • 12Layout and connections
4.3LED indications
There are three LEDs on OPTE2/E8 option board to indicate board and communication status. This
table describes their indications.
Table 8. LED indications
LEDsIndication
• Green ON when protocol is communicating
PS
BS
FS
Figure below lists possible LED indication combinations.
• Yellow blinking (1s ON / 1s OFF) when protocol is ready for external communication
• OFF when protocol is not ready for communications
• Green blinking (fast) when firmware is corrupted or missing
• Green ON when board is operational.
• Red blinking (1s ON / 1s OFF) when protocol is in fault state
• Green ON when protocol is communicating.
• OFF when protocol is not communicating.
Table 9. LED combinations
LED combinations
Description
PSBSFS
DimDimDimNo power. All LEDs are OFF
GreenDimDimOption board firmware is corrupted or missing. PS is blinking fast
Dim
Yello w GreenDim Protocol is ready for communications. PS is blinking (1s ON / 1s OFF)
Green Green Green
Yello wRedDim
GreenDimOption board is operational
Protocol is communicating. The option board is receiving requests
from the PLC master and sending responses to the requests.
Protocol communication fault. BS is blinking to indicate a fault. PS is
blinking to indicate that protocol is ready for communications.
4.4Jumpers
Setting of termination resistance and cable shield grounding options is described in Chapter 5.
4
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Layout and connectionsvacon • 13
Bus termination ON
GND connected to cable shield
Jumper X13, termination resistor
Cable shield is connected to PE through RC
Cable shield is connected directly to PE
Cable shield is not connected
Bus termination OFF
GND not connected to cable shield
Jumper X14, upper row
Jumper X14, lower row
3022B_uk
Factory default
setting
Factory default
setting
Factory default
setting
Figure 4. Position definition of jumpers
4.5Bus terminal and bias resistors
If VACON® AC drive is the last device of RS-485 line, the bus termination must be set. Use jumper
X13 (ON position) or external termination resistors.
Bus biasing is required to ensure faultless communication between devices at RS-485 bus. Bus
biasing makes sure that the bus state is at proper potential when no device is transmitting. Without
biasing, faulty messages can be detected when the bus is in idle state. RS-485 bus state should be
neither +0.200...+7 V or -0.200...-7 V. Illegal bus state is <200 mV...-200 mV.
The resistance of internal termination and biasing are 120 Ω and 560 Ω.
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Figure 5. Bus termination
4
vacon • 14Layout and connections
If necessary, external termination and biasing can be added depending on number of nodes and
total length of cable.
Table 10. Bias resistance and termination resistance
Number of nodesBias resistanceTermination resistance
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Cabling instructionsvacon • 15
5.CABLINGINSTRUCTIONS
5.1Selecting cable
In EIA-485 systems, use only shielded cables with twisted-pair signal wires. With EIA-485 protocols,
use for example:
•Lapp Kabel UNITRONICR BUS LD FD P A, part number 2170813 or 2170814
5.2Setting the termination resistance
Install termination resistors at or near both ends of the EIA-485 segment. The typically termination
resistor for EIA-485 is 120 Ω.
A. The termination is activatedD. The bus termination
B. The termination is deactivatedE. The fieldbus cable
C. The termination is activated with a jumper
Figure 7. Setting the termination resistance
5.3Shield grounding options
The equipotential bonding system in an installation refers to metalwork that is used to bring earth
potential everywhere in the installation to a common level, the system earth. The purpose is that the
earth potential for all devices and equipment would be same, avoiding undesirable current flow
through paths not normally designed to carry current, and to allow efficient shielding of cables.
5.3.1Shield grounding when equipotential bonding is good
When the equipotential bonding is good, the fieldbus cable shield can be grounded at each AC drive.
The grounding can be done by connecting the shield to the drive frame directly, or it can be done
through the fieldbus connector and the grounding tab in the option board.
Figure 8. Jumper X14 setting (all points in system)
If the fieldbus cable is subjected to tensile load, it is recommended to do this grounding via the
fieldbus board connector and grounding tab. The strain relief of the cable is then done without
exposing the cable shield, which reduces the risk of mechanical wear on the cable.
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
5
vacon • 16Cabling instructions
Figure 9. Grounding by clambing the cable to the AC drive frame
5.3.2Shield grounding when equipotential bonding is poor
In a situation where the equipotential bonding is poor, the fieldbus cable should be grounded directly
only at one point in the system. This can be a VACON
the system. The fieldbus cable should not be directly grounded elsewhere in the system, because
difference in electrical potential can cause equalization currents to appear in the shield, causing
unnecessary disturbances.
Figure 10. Jumper X14 setting (cable grounding to drive)
Figure 11. Jumper X14 setting (cable shield to RC filter)
In VACON
filter, which helps filter out disturbances in the shield without directly connecting it to the earth. In
this case, the shield is connected to the option board connector and through an RC filter to the
grounding tab in the option board. The strain relief is done without exposing the cable shield.
®
AC drives, the fieldbus cable can in these cases be connected to ground through an RC
®
AC drive but can also be some other point in
5
Figure 12. Grounding with RC filter
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Installationvacon • 17
6.INSTALLATION
Following table shows which drives support OPTE2/E8 option board.
Table 11. OPTE2/E8 option board support
VACON
VACON
VACON
VACON
VACON
VACON
VACON
DriveSlot
®
20
®
20 X/CP
®
100 INDUSTRIAL /100 X
®
100 FLOW
®
100 HVAC
®
NXP
®
NXS
Since drive software
version
EFW0107V013FW0204V002
EFW00117V012FW0204V002
D, EFW0072V026FW0204V002
D, EFW0159V017FW0204V002
D, EFW0065V035FW0204V002
D, ENXP00002V197FW0204V003
D, ENXS00002V184FW0204V003
Since OPTE2/E8
software version
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
6
vacon • 18Installation
13006.emf
6.1Installation in VACON® 20
6.1.1Enclosures MI1, MI2, MI3
Make sure power is disconnected before installing the option board mounting kit.
Remove the cable connector lid from AC
drive.
1
2
11555A_00
Select a correct grounding plate and attach it to the
option board mounting frame. The grounding plate is
marked with the supported enclosure size.
11649_00
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
6
Installationvacon • 19
11556A_
11558A_00
Attach an option board mounting frame to the
AC drive.
3
Connect the flat cable from the option board mounting frame to the AC drive.
4
5
11557A_00
If a cable strain relief is required, attach the parts as shown in the figure.
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
6
vacon • 20Installation
11559A_00
11650_00
11560A_00
Install the option board to the option board
holder. Make sure that the option board is
securely fastened.
6
Cut free a sufficiently wide opening for the
option board connector.
7
8
Attach the option board cover to the AC drive. Attach the strain relief cable clamp
with screws if needed.
6
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Installationvacon • 21
13006.emf
11562_00
11563_00
6.1.2Enclosures MI4, MI5
Make sure power is disconnected before opening the cover of the AC drive.
1a: For MI4: Open the cover.
1
11561_00
1b: For MI5: Open the cover and release the fan connector.
OPTE2: Attach the option board support.
OPTE8: Option board support is not used.
2
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
6
vacon • 22Installation
11564_00
11565_00
Connect the flex cable to option board connector PCB.
3
Connect the option board to connector PCB.
4
5
Attach the option board with connector PCB to the AC drive and connect the flex
cable.
11566_00
6
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Installationvacon • 23
MI 04
MI 05
11567_00
11568_00
Attach a suitable grounding plate to VACON® 20. The grounding plate is marked
with supported enclosure size.
6
7
Assemble a clamp on top of the grounding plate on both sides of the option board.
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
6
vacon • 24Installation
11569_00
11570_00
8a: For MI4: Close the cover.
8
8b: For MI5: Remount the fan connector and close the cover.
6
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Installationvacon • 25
13006.emf
13006.emf
6.2Installation in VACON® 20 X and 20 CP
Do not add or replace option boards or fieldbus boards on an AC
drive with the power switched on. This may damage the boards.
Open the cover of the drive.
1
11643_00
MU3 example
The relay outputs and other I/O-terminals may have a dangerous control voltage
present even when the drive is disconnected from mains.
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
6
vacon • 26Installation
7089_00
Remove the option slot cover.
2
3
Install the option board into the slot as shown in the figure.
6
7090_00
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Installationvacon • 27
7091_007091_00
Mount the option slot cover. Remove the plastic opening for the option board
terminals.
4
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
6
vacon • 28Installation
13006.emf
M4x55
9174.emf
DANGER
6.3Installation in VACON® 100 family
Do not add or replace option boards or fieldbus boards on an AC
drive with the power switched on. This may damage the boards.
Open the cover of the AC drive.
1
The relay outputs and other I/O-terminals may have a dangerous control voltage
®
present even when VACON
100 family AC drive is disconnected from mains.
6
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Installationvacon • 29
3023.emf
DE
3024.emf
Open the inner cover to reveal the option board slots (C,D,E). See the figure
below.
2
3
Install the fieldbus board into slot D or E. See the figure below.
®
NOTE! Incompatible boards cannot be installed on VACON
Compatible boards have a slot coding
that enable the placing of the board.
100 family AC drive.
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
6
vacon • 30Installation
f
9202.emf
Fieldbus
cables
Unless already done for the other control cables,
cut free the opening on the AC drive cover for the
fieldbus cable (protection class IP21).
NOTE! Cut the opening on the same side you
have installed the board in
4
5
9201.em
Remount the AC drive cover and run the cable as shown in the figure.
NOTE! When planning the cable runs, remember
to keep the distance between the fieldbus cable
and the motor cable at a minimum of 30 cm. It is
recommended to route the option board cables
away from the power cables as shown in the
figure.
6
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Loading...
+ 69 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.