USV-S valves are to be used in radiator heating
systems to limit the flow in risers or horizontal
loops.
USV-S valves are designed for manual hydronic
balancing of heating and cooling systems.
USV-S (black knob) is used to limit the flow
in heating or cooling installation or can work
separately as manual balancing valves for flow
limitation.
USV-S is compact valves in which the operating
elements and connections are placed within
an arc of 90°, so that in spite of small valve
dimensions, access for installation and operation
is optimal. Insulation caps for temperature up to
80 oC or 120 oC are available as accessory.
USV-S is supplied in a set-pack with internal
thread.
DEN-SMT/SI
USV-S in radiator application - vertical riser
USV-S can also be used in floor heating systems.
To limit the flow, every manifold with constant
flow should be used together with USV-S valves.
Diaphragm and O-rings ...................................... EPDM
Spring ........................................................ Stainless steel
Port A Port B
• turn the valve knob ① fully counter clockwise
so that the mark on the knob is opposite »0«
on the scale ④. The valve is now open as
many turns from the closed position (2.2) as
indicated by the convertion from required
flow.
• to annul the setting, turn the hexagon socket
key fully clockwise (until a stop can be felt).
Remember, at the same time the knob must be
held on its »0« setting.
A. Correct valve size USV-S
B. Correct USV-S presetting
Given:
1. Required max. flow in the riser
Q = 0,80 [m3/h]
2. Pressure drop across riser
Δps = 15 [kPa]
3. Available pump pressure
Δpo = 35 [kPa]
4. Connection pipe: DN 25
Solution:
A) USV-S DN20 is selected (same size as
connection pipe).
A straight line conecting this point and
Q = 0,80 [m3/h] intersects the differential
pressure bar at Δpv (USV-S) = 10 [kPa].
Δpo = Δps + Δpv (USV-S)
B) Correct valve size and presetting of USV-S:
The differential pressure across USV-S can be
calculated as follows:
Δpv (USV-S) = Δpo – Δp
s
Δpv = 35 [kPa] – 15 [kPa]
The example selects USV-S DN 20. Presetting
is read from the sizing diagram (page 5) by
taking a straight line from from max. flow
Q = 0,80 [m3/h] to the differential pressure Δpv
(USV-S)= 20 [kPa] and to the intersection with
kV-axis at kV = 1,8 [m3/h].
Draw a horizontal line from this point to the
adjustment curve of the chosen valve
(DN 20). Starting from closed valve, the
presetting of 1,6 turns is required.
USV-S should be instaled in the ow or return
pipe. The direction of the ow must follow the
direction of the arrow on the valve body.
Small installation dimensions enable easy
installation and shut-o of the system.
Max. test pressure ............................................... 25 bar
1
aa
H
2
H
USV-S can be installed in any positions if
installation instructions are being observed. It is
recommended that a lter i.e. Danfoss Typ FV is
installed in the supply pipe.