The Danfoss UnoFloor Mixing is a preassembled
pressure independent underfloor heating
balancing and control distribution unit. UnoFloor
comes wired and premounted. UnoFloor Mixing
includes Danfoss Icon™ 230V Wiring Center or
Danfoss Icon™ 24V Master Controller.
The SSM stainless-steel manifold is used for
controlling water flow. Each tube of the floor
heating system is connected to the manifold,
thus making it possible to control water flow
or heat supply to each room in the building
individually.
The AB-PM set ensures optimal hydronic balance.
Flow limitation independent of differential
pressure is now guaranteed.
The Danfoss compact mixing shunt is used for
regulation of flow and supply temperature in
hydronic floor heating systems.
The SSM manifold is used for controlling water
flow in under floor heating systems. Each tube of
the floor heating system is connected to the
manifold, thus making it possible to control water
flow or heat supply to each room in the building
individually.
088U1005
088U1015
088U1025
Part of assembly
Pre-setting diagram
Presetting the manifold
valves
DescriptionType
Manifold set 4+4, with flowmeterSSM-4F
Manifold set 5+5, with flowmeterSSM-5F
Manifold set 6+6, with flowmeterSSM-6F
Manifold set 7+7, with flowmeterSSM-7F
Manifold set 8+8, with flowmeterSSM-8F
Manifold set 10+10, with flowmeterSSM-10F
Manifold set 12+12, with flowmeterSSM-12F
Manifold,
with flowmeter
The diagram shows the capacities for each
heating circuit at different presettings of the
manifold valves.
Based on the above calculations and capacity diagram each manifold valve is preset by rotating
the red ring until the correct value on the ring is
in-line with the sight mark on the valve.
The FH-ST safety thermostat is fixed on the tube
and protects floor and system against too high
temperatures, especially important for wooden
floors. The FH-ST thermostat switches off the pow-
automatically and the floor heating system is protected.
The FH-ST55 can also be connected to a pump or
a zone valve.
er supply of the floor heating base unit, when the
temperature reaches 55 °C.
By switching off the power supply of the floor
Note! The electrical installation must be carried out
by an authorized installer only (230 V DC).
heating base unit, the actuators (NC) will close
Code no.088U0301
Shut-off temperature55 °C
Switch difference4 K
ClassificationIP 40 (mounted)
FTC is a self-acting thermostatic sensor used for
flow temperature control of floor heating.
The water temperature is measured by a surface
sensor. The snap-lock connector of the sensor element secures a firm connection to the valve.