Danfoss ULX 1800o, ULX 3000o, ULX 3600o, ULX 5400o User Manual

UniLynx Outdoor
User Manual Benutzerhandbuch Manuel de l’Utilisateur Manual del Usario Manuale dell’Utente
ULX 1800o • ULX 3000o • ULX 3600o • ULX 5400o
SOLAR INVERTERS
Choice of Language - Sprachauswahl - Choix de la langue ­Selección de idioma - Scelta della lingua
Page 2
English UK
Seite 13
Deutsch
Page 25
Français
Página 37
Español
Pagina 49
Italiano
L00410362-05_2q 1
Contents
1. Introduction
3
Introduction 3
2. Function Description
4 Definition of Operation Modes 4 PV Configuration 4 LEDs 6 Display 6 Overview Menu Section A 6 Overview Menu Section B 7
3. Troubleshooting
10 Troubleshooting 10 Inverter Event Messages 10
4. Maintenance
12 Maintenance 12 Cleaning the Cabinet 12 Cleaning the Heatsink 12
Contents
2 L00410362-05_2q
1. Introduction
1.1. Introduction
This manual describes Danfoss photovoltaic inverters. These products are among the most tech­nologically advanced and efficient inverters on the market and are designed to supply the owner with reliable solar energy for many years.
Illustration 1.1: ULX Outdoor Inverter with Display
CE marking - This certifies the conformity of the equipment with the regula­tions which apply in accordance with the directives 2004/108/EC and 2006/95/ EC.
1. Introduction
L00410362-05_2q 3
1
2. Function Description
2.1. Definition of Operation Modes
The inverter has four modes:
Standby mode:
In standby mode, the inverter is ready to switch into connecting mode. As decision variable the input voltage of the PV generator is used. If the input voltage exceeds a preset nominal value, the inverter shifts from “standby” to “connecting”, or continues into the operation mode “OFF” if the PV voltage drops.
Connecting mode:
After performing the system tests, which check whether all connection conditions are met, the inverter goes from standby mode to connecting mode. During the specified cut-in time, the in­verter continues testing the system values and connects the inverter to the grid if the system tests are okay. The minimum cut-in time is specified by the supplier and authorities and can vary from region to region.
Grid mode:
In this mode, the inverter is connected to the grid and supplies power to the grid. The inverter is only uncoupled from the grid in case of abnormal grid conditions or when PV power is not available.
PV configuration mode
Having completed the connecting mode the PV module wiring is automatically tested to detect whether any of the DC inputs are wired in parallel string configuration. If so, the DC modules are automatically run in parallel string configuration mode (Master/Slave).
Derating temperature
If the display shows (DRT. TEMP), the inverter is derating due to high temperatures.
Derating grid
If the display shows (DRT GRID), the inverter is derating due to high voltage on the grid.
Off:
If there is no PV power available, the inverter waits ten minutes (specified value) before it disen­gages. In this mode, the power supply to all processors is switched off to conserve energy. This is the normal night mode.
2.1.1. Grid Surveillance
In order to safeguard the people working on AC power lines and the inverter, the inverter shuts down in the event of abnormal grid conditions or failures. The inverter continuously monitors grid voltage and frequency by means of an internal control circuit. Subsequently, the inverter will re­connect as soon as the grid is within limits.
2.1.2. PV Configuration
Upon connecting to grid an automatic test of the PV module wiring is performed by the inverter. This test is made in order to determine the wiring configuration of the modules. It is established whether the modules are connected in individual string configuration or in parallel string config­uration and the inverter is automatically configured accordingly.
2. Function Description
4 L00410362-05_2q
2
The test works by activating the input one by one. The test takes 1-2 minutes and the inverter continues to produce energy meanwhile. In menu B the result of the test can be read in the display menu called PV configuration. Upon test completion the display will automatically show the PV configuration detected; however, only if the buttons on the display have not been used in the past 3 minutes.
For ULX 5400o, 2 out of 3 DC modules must be powered for the test to run. If not enough PV power is available to power 2 modules, the test is postponed until sufficient PV power is available for the second DC module to run.
Notice that the inverter continues to produce energy in the meantime.
DC3
+
DC2 DC2
+ +
DC1 DC1 DC1
t
On Grid Test end
Illustration 2.1: PV configuration test
The display readout shows the status of the test. The first line shows that this concerns the PV configuration and the second line shows which status the test is in or which configura­tion it has detected.
PV configuration INDIVIDUAL
The status field may show the following:
Display Text Description
IDLE PV configuration test has not yet been run. Shown before the inverter connects to
grid.
OFF PV configuration test is disabled. Applicable to ULX 1800o and to inverters where
the test is otherwise disabled.
WAITING The PV configuration test is ready to run, but only solar radiation for one PV input
is available. (Applicable to ULX 5400o). The inverter can only determine the con-
figuration of all three modules, when two are running. PV-AUTODETECTING The PV configuration test is running. No result yet. INDIVIDUAL The PV modules are connected in individual string configuration PARALLEL 1-2* The PV configuration has ended, concluding that inputs 1 and 2 are connected in
parallel string configuration. PARALLEL 1-3* The PV configuration has ended, concluding that inputs 1 and 3 are connected in
parallel string configuration. PARALLEL 2-3* The PV configuration has ended, concluding that inputs 2 and 3 are connected in
parallel string configuration. PARALLEL 1-2-3 The PV configuration has ended, concluding that inputs 1, 2 and 3 are connected
in parallel string configuration.
Table 2.1: PV Configuration Test Status Field Text
*) The “PARALLEL 1-2” is only allowed for the ULX 3000o / 3600o inverter. The “PARALLEL 1-2”, “PARALLEL 1-3”, and “PARALLEL 2-3” is not allowed for the ULX 5400o inverter.
2. Function Description
L00410362-05_2q 5
2
2.1.3. LEDs
The green LED indicators show the production in percentage of the nominal inverter power rating. The leftmost green LED is always lit when the inverter is connected to the grid. While connecting to grid both the red LED and the leftmost green LED will be on. When the inverter is off grid, the red LED to the left is lit to indicate that the inverter is in standby mode. No green LEDs are lit. If no LED’s are on the inverter is off. If the inverter is forced into standby mode because of an event in the inverter or the peripheral connections, e.g. disconnection from the grid, the red LED starts flashing.
For a description of events, please refer to the section on
Troubleshooting
.
2.1.4. Display
Through the integrated display on the inverter front, the user has access to all information about the PV system and the inverter. When the inverter is in OFF mode (at night), the inverter can be activated by pressing the left button (ESC).
Illustration 2.2: Display
θ
ESC Goes one step backwards/up in the menu
structure
Up Scrolls back to the previous menu display
Down Scrolls forward to the next menu display
OK
Enter New menu level or changing of settings
The parameters shown in the display refer to internally measured voltages and currents. The parameters shown may deviate.
The display information is organised in a menu structure divided into two sections: A and B
Section A: Contains information about the in­verter and PV system performance. Section B: Displays all measurement values and user settings.
2.1.5. Overview Menu Section A
The table below gives an overview of the menu structure. The values shown are only intended as examples of display texts. The display text (shown in the first column Display Functions ) is divided between 2 lines, with 16 characters available per line. The line division is illustrated with the symbol |.
Menu Structure A
Display Functions Description
Output power | 0 W Current output power in watt.
Inverter name |
Use Service Tool to enter inverter name. If the inverter name is undefined this menu is skipped.
Total production | 22.991 kWh Total energy production in kWh since first inverter start-up.
Total operating time | 00028h 57m 02s Total operating time (time with power on) displayed in hours, minutes and seconds.
Production today | 19637 Wh Energy production today in Wh.
Go to menu B Jumps to menu level B when OK is pressed.
Table 2.2: Overview Menu Structure A
2. Function Description
6 L00410362-05_2q
2
2.1.6. Overview Menu Section B
The table below gives an overview of the menu structure. The two menu levels are clearly indicated by an arrow followed by a submenu. The values shown are only intended as examples of display texts.
The display text (shown in the first column Display Functions ) is divided between 2 lines, with 16 characters available per line. The line division is illustrated with the symbol |.
Menu Structure B
Display Functions Description
Operation mode | STANDBY
Displays present inverter operation mode. See operation mode definitions in chapter 2.
PV configuration | IDLE
Shows the status of the automatic PV configuration test and the results found.
Event: Mod. | ENS FL. CH DCAC
If the inverter is not connected to the grid because of a failure, the red LED starts flashing, and the reason for the failure is shown here.
Language | ENGLISH View and choose display language. Does not affect any other settings.
Grid voltage | 0 V Displays the present grid AC voltage.
Grid current | 0.00 A Displays the present current flow to the grid.
Grid frequency | 0.00 Hz Displays the present grid frequency.
Grid impedance | 0.0 ohm Displays the present grid impedance.
PV voltage | Press OK to view Press OK to access submenu for recorded values.
Submenu
PV voltage no. 1 | 303.0 V Present voltage at PV input 1 (upper position in inverter).
PV voltage no. 2 | 303.0 V Present voltage at PV input 2 (second position in inverter)*.
PV voltage no. 3 | 303.0 V Present voltage at PV input 3 (third position in inverter)*.
PV current | PRESS OK to view Press OK to access submenu for recorded values.
Submenu
PV current no. 1 | 0.0 A Present current at PV input 1 (upper position in inverter).
PV current no. 2 | 0.0 A Present current at PV input 2 (second position in inverter)*.
PV current no. 3 | 0.0 A Present current at PV input 3 (third position in inverter)*.
Maximum values | Press OK to view Press OK to access submenu for recorded values.
Submenu
AC out: 1844 W | 8.356 A 263 V
Maximum values recorded at AC output since last resetting of max. value memory.
DC1 in: 2220 W** | 8.004 A 509 V
Maximum values recorded at DC1 input since last resetting of max. value memory.
DC2 in: 2220 W** | 8.004 A 509 V
Maximum values recorded at DC2* input since last resetting of max. value memory.
DC3 in: 2220 W** | 8.004 A 509 V
Maximum values recorded at DC3* input since last resetting of max. value memory.
Table 2.3: Overview Menu Structure B
*) The PV2 and PV3 menus are only displayed in inverters equipped with two or three inputs.
2. Function Description
L00410362-05_2q 7
2
Menu Structure B- Continued
Display Functions Description
Maximum values | Press OK to view Press OK to access submenu for recorded values.
Submenu
AC out: 1844 W | 8.356 A 263 V
Maximum values recorded at AC output since last resetting of max. value memory.
DC1 in: 2220 W** | 8.004 A 509 V
Maximum values recorded at DC1 input since last resetting of max. value memory.
DC2 in: 2220 W** | 8.004 A 509 V
Maximum values recorded at DC2* input since last resetting of max. value memory.
DC3 in: 2220 W** | 8.004 A 509 V
Maximum values recorded at DC3* input since last resetting of max. value memory.
Total drt. Temp. - Press OK to view
Total Derating Temperature. Shows the total amount of time the inverter has derated due to high temperature.
Submenu
DC1 derate temp. | 3h 35m
DC1 Derating Temperature. Shows the amount of time the inverter has derated due to high temperature.
DC2 derate temp. | 3h 35m
DC2* Derating Temperature. Shows the amount of time the inverter has derated due to high temperature.
DC3 derate temp. | 3h 35m
DC3* Derating Temperature. Shows the amount of time the inverter has derated due to high temperature.
Total drt. Grid | 0h 00 min
Total Derating Grid. Shows the amount of time the inverter has derated due to unstable grid conditions.
Power-down time | 00600 seconds
Time before inverter goes into ‘OFF’ mode when no solar power is avail­able.
Code numbers | PRESS OK to view Press OK to access submenu for recorded values.
Submenu
Inverter code no. | Indicates inverter product code.
AC code number | C0070105602 Indicates AC module product code.
DC1 code number | C0070105402 Indicates DC1 module product code.
DC2 code number | C0070105402 Indicates DC2* module product code.
DC3 code number | C0070105402 Indicates DC3* module product code.
Serial numbers | Press OK to view Press OK to go to submenu for recorded values.
Submenu
Inverter SN: | Indicates inverter serial number.
AC SN: | 117500C0408 Indicates AC module serial number.
DC1 SN: | 642800C0808 Indicates DC1 module serial number.
DC2 SN: | 642800C0808 Indicates DC2* module serial number.
DC3 SN: | 642800C0808 Indicates DC3* module serial number.
Table 2.4: Overview Menu Structure B
*) The DC2 and DC3 menus are only displayed in inverters equipped with two or three inputs. **) The maximum values for PV power may reach more than 2000 W in inverters where the inputs are connected in parallel. This is normal.
In menu section A the display will continue to show the menu point last chosen by the user.
In menu B the display automatically switches to menu A when there has been no keyboard activity for 3 minutes.
2. Function Description
8 L00410362-05_2q
2
If the inverter is off grid and no keys have been pressed for a certain number of seconds, the display will automatically switch to the operation mode display.
If the inverter is on grid and there has been no keyboard activity for 3 minutes, the display au­tomatically switches to the display Production today. When the PV configuration test initiates and terminates the display temporarily changes to menu B to show the state of the PV configuration test.
If the inverter is disconnected from the grid because of a failure, the red LED will start flashing, and the display automatically switches to menu B, where the event is shown.
If an earthing fault occurs, the display will indicate this by a flash of the lit green LEDs. The display will change to “current event”, if it has not been operated in the past 10 minutes. The inverter will continue to produce energy. In case an earth fault occurs, this does not indicate an inverter error and technical assistance must be called to check the PV panel connection. Only applicable if earth fault detection is enabled. By default, earth fault detection is enabled for the following countries: Austria, France and Spain.
2. Function Description
L00410362-05_2q 9
2
3. Troubleshooting
3.1. Troubleshooting
Note:
Remember that only trained and authorised personnel familiar with electrical systems and safety issues may work on inverters and electrical installations.
In the following, the term 'Event' describes all events that prevent the inverter from operating properly. An event may occur anywhere in the installation (grid, PV module, cable and connections, inverter) at any time. Not all events indicate an inverter error.
If the PV system does not supply power to the grid as expected, please go through the following checklist:
1. Check that the grid is connected properly to the inverter and that the grid is ready for operation.
2. Check that there is sufficient solar radiation to generate power.
3. Check for shading and loose cables/connections in the PV system.
4. Check the installation of the PV modules if the voltages of the PV modules is not within the expected values.
5. Check the event in menu B. If the red LED is flashing, this indicates a failure.
6. If the above-mentioned points are OK, wait 15 minutes to find out whether there is a permanent failure.
7. If the PV system still does not supply any power to the grid, please check the voltage, current and power of the PV module as well as voltage, current and power of the grid in menu B.
8. If the voltage values of the grid do not lie within the threshold values, please contact your public utility for technical assistance.
3.1.1. Inverter Event Messages
Event: Mod. U-GRID DCAC
The red LED will start flashing in case of an inverter event. Please check the event in menu B.
The event text is a short text describing the event. If the inverter reports an event ID number to the display instead of a text, no event text has been predefined for that particular event ID num­ber. This could be the case if the display software is older than the inverter software. Module designation identifies the module that caused the event (DC1, DC2, DC3 or AC).
3. Troubleshooting
10 L00410362-05_2q
3
Event text Description Fault
origin
Action in the event of a permanent fail-
ure U 3.3 Internal power supply outside limits Inverter Service inverter U 5.0 Internal power supply outside limits Inverter Service inverter U 15.0 Internal power supply outside limits Inverter Service inverter U PV Input voltage from PV string too high PV system Request technical service from PV system
supplier
U-SNUBBER Snubber voltage too high Inverter Service inverter U DC-BUS DC bus voltage too high Inverter Service inverter U-GRID AC grid voltage outside the threshold
values (higher or lower than setting)
AC grid In case of repeated occurrence: Request
technical service from utility F-GRID Grid frequency outside limits (outside
settings)
AC grid In case of repeated occurrence: Request
technical service from utility IPM CURRENT The DC content in the AC current is too
high
Inverter Service inverter
ENS ENS error AC grid In case of repeated occurrence: Request
technical service from utility
ENS RAM ENS memory error Inverter Service inverter ENS FL. CHKSM Flash memory error after self-test Inverter Service inverter ENS EP. CHKSM EPROM memory error after self-test Inverter Service inverter HW TRIP Hardware trip – current too high Inverter Service inverter TEMP HIGH Temperature in integrated power mod-
ule too high
Environ­ment
Check whether inverter is covered.
Check inverter for free air flow through heat
sink. Clean heat sink.
Check that ambient temperature is within
limits. EPRM PAR. LIM Validity check of grid voltage and fre-
quency settings. Settings too far away from actual grid voltage and frequency values.
Inverter Request service to check inverter settings
ENS COM ERR Error in communication with ENS board Inverter Service inverter ENS impedance Grid impedance step higher than limit AC grid In case of repeated occurrence: Request
technical service from utility PV—CONFIG—ERR Error detected by PV configuration test PV system Check the cabling of the PV panels. Two DC
inputs are wired in parallel string configura-
tion, one is not
Not recorded in the event log - red LED does not flash Event text Description Fault
origin
Action in the event of a permanent fail-
ure EARTHFAULT Current event shown in grid mode PV system Earth fault, check PV system for earthing to
avoid damage to PV panels. Request techni-
cal service from the PV system supplier or in-
staller.
Table 3.1: Inverter Event Log
A “permanent failure” is defined by an event having been present for more than 15 minutes.
3. Troubleshooting
L00410362-05_2q 11
3
4. Maintenance
4.1. Maintenance
Normally, the ULX outdoor inverters need no maintenance or calibration. It should be ensured, however, that the cooling is not obstructed.
To ensure the functionality of the DC-switch, all switches should be switched on and off (by turning the switch to on and off positions ten times), once a year, to clean the contacts.
4.1.1. Cleaning the Cabinet
Clean inverter by means of pressurised air or a soft cloth or a brush. Do not use a water hose, aggressive chemicals, cleaning solvents or strong detergents to clean the inverter.
4.1.2. Cleaning the Heatsink
In order to secure proper function and long inverter life, it is essential that the free air circulation around the heatsink at the back of the inverter and by the fan at the bottom of the inverter is not obstructed. If the free air circulation is obstructed, e.g. by dust or snow, this has to be removed. Clean the heatsink by means of pressurised air or a soft cloth or a brush. Do not use a water hose, aggressive chemicals, cleaning solvents or strong detergents to clean the inverter.
The heatsink can reach a temperature of more than 70°C during operation. Touching components of this temperature may result in serious injuries!
Note:
Do not cover the inverter.
4. Maintenance
12 L00410362-05_2q
4
Inhaltsverzeichnis
1. Einführung
14
Einführung 14
2. Funktionsbeschreibung
15 Definition der Betriebsarten 15 PV-Konfiguration 16 LEDs 17 Display 17 Überblick Menübereich A 18 Überblick Menübereich B 19
3. Fehlerbehebung
22 Fehlerbehebung 22 Wechselrichter – Ereignismeldungen 22
4. Wartung
24 Wartung 24 Reinigen des Schaltschranks 24 Reinigen des Kühlkörpers 24
Inhaltsverzeichnis
L00410362-05_2q 13
1. Einführung
1.1. Einführung
Dieses Handbuch beschreibt die photovoltaischen Wechselrichter von Danfoss. Diese Produkte zählen zu den technologisch fortschrittlichsten und effizientesten Wechselrichtern auf dem Markt und ermöglichen eine verlässliche Versorgung mit Solarenergie über viele Jahre hinweg.
Abbildung 1.1: ULX-Wechselrichter für den Außenbereich – mit Display
CE-Kennzeichnung: Diese Kennzeichnung gibt an, dass die Geräte den gel­tenden Vorschriften der Richtlinien 2004/108/EG und 2006/95/EG entspre­chen.
1. Einführung
14 L00410362-05_2q
1
2. Funktionsbeschreibung
2.1. Definition der Betriebsarten
Der Wechselrichter hat vier Betriebsarten:
Standby-Modus:
Im Standby-Modus ist der Wechselrichter bereit, auf den Anschlussmodus umzuschalten. Als Ent­scheidungsgröße wird die Eingangsspannung des PV-Generators herangezogen. Übersteigt die Eingangsspannung einen definierten Sollwert, wechselt der Wechselrichter aus der Betriebsart Standby in den Anschlussmodus oder leitet bei Verringerung der PV-Spannung in die Betriebsart „AUS“ über.
Anschlussmodus:
Nach Durchführung der Systemprüfungen, bei denen geprüft wird, ob alle Anschlussbedingungen erfüllt sind, geht der Wechselrichter vom Standby-Modus in den Anschlussmodus über. Der Wech­selrichter fährt während der vorgegebenen Aufschaltzeit mit der Prüfung der Systemwerte fort und verbindet, soweit die Systemprüfungen erfolgreich sind, den Wechselrichter mit dem Netz. Die minimale Aufschaltzeit ist von den Versorgungsunternehmen und Behörden vorgegeben und kann von Region zu Region unterschiedlich sein.
Netzbetrieb:
Bei dieser Betriebsart ist der Wechselrichter mit dem Netz verbunden und liefert Strom ins Netz. Der Wechselrichter wird nur bei einer abnormalen Netzbedingung oder bei fehlender PV-Leistung vom Netz abgekoppelt.
PV-Konfigurationsbetrieb
Nach Beendigung des Anschlussmodus wird die PV-Modulverdrahtung automatisch geprüft, um zu erkennen, ob alle DC-Eingänge in Parallelstrangkonfiguration verdrahtet sind. Ist dies der Fall, werden die DC-Module automatisch im Parallelstrangkonfigurationsbetrieb ausgeführt (Master/ Slave ).
Temperaturminderung
Wenn das Display die Meldung (Temp.mind.) anzeigt, wird der Wechselrichter aufgrund von hohen Temperaturen gedrosselt.
Leistungsreduzierung wegen Spannung
Wenn das Display die Meldung (Spann. mind.) anzeigt, wird der Wechselrichter aufgrund von hoher Netzspannung gedrosselt.
Aus:
Ist kein PV-Strom vorhanden, wartet der Wechselrichter zehn Minuten (vorgegebener Wert), be­vor er abschaltet. In dieser Betriebsart ist die Stromversorgung zu allen Prozessoren abgeschaltet, um Strom zu sparen. Das ist der normale Nachtbetrieb.
2.1.1. Netzüberwachung
Um an Leistungskabeln arbeitendes Personal und den Wechselrichter zu schützen, schaltet der Wechselrichter bei abnormalem Netzverhalten oder Netzausfall ab. Der Wechselrichter überwacht über einen internen Prüfstrang ständig die Netzspannung und -frequenz. Daher stellt der Wech­selrichter die Verbindung wieder her, wenn sich die Netzwerte wieder innerhalb der Grenzwerte befinden.
2. Funktionsbeschreibung
L00410362-05_2q 15
2
2.1.2. PV-Konfiguration
Bei Anschluss an das Netz führt der Wechselrichter eine automatische Prüfung der PV-Modul­verdrahtung durch. Diese Prüfung bestimmt die Verkabelungskonfiguration der Module. Es wird ermittelt, ob die Module in Einzelstrangkonfiguration oder Parallelstrangkonfiguration angeschlos­sen sind, und der Wechselrichter wird automatisch entsprechend konfiguriert. Die Prüfung akti­viert nacheinander jeden Eingang. Sie nimmt 1 - 2 Minuten in Anspruch, und der Wechselrichter erzeugt dabei weiterhin Energie. In Menü B kann das Prüfergebnis im Displaymenü für die PV­Konfiguration abgelesen werden. Nach Abschluss der Prüfung zeigt das Display automatisch die erkannte PV-Konfiguration, allerdings nur, wenn die Tasten am Display in den letzten drei Minuten nicht betätigt wurden. Bei ULX 5400o müssen zwei von drei DC-Modulen für den Test mit Strom versorgt werden. Steht nicht genügend PV-Energie zur Versorgung von zwei Modulen zur Verfügung, wird die Prüfung verschoben, bis genügend PV-Energie für den Betrieb des zweiten DC-Moduls vorliegt.
Dabei erzeugt der Wechselrichter weiterhin Energie.
Abbildung 2.1: PV-Konfigurationsprüfung
Die Displayanzeige zeigt den Prüfstatus. Die erste Zeile zeigt, dass dies die PV-Konfigura­tion betrifft, und die zweite Zeile zeigt den Status der Prüfung oder die erkannte Konfi­guration.
Das Statusfeld kann Folgendes zeigen:
Angezeigter Text Beschreibung
LEERLAUF Die PV-Konfigurationsprüfung wurde noch nicht ausgeführt. Dies wird vor dem
Anschluss des Wechselrichters an das Netz gezeigt.
AUS PV-Konfigurationsprüfung deaktiviert. Gilt für ULX 1800o sowie für Wechselrichter,
bei denen die Prüfung auf andere Weise deaktiviert wurde.
WARTEN Die PV-Konfigurationsprüfung ist betriebsbereit, es ist jedoch nur genügend Ein-
strahlung für einen PV-Eingang verfügbar. (Gültig für ULX 5400o). Der Wechsel­richter kann nur die Konfiguration aller drei Module bestimmen, wenn zwei von
ihnen laufen. PV-AUTOERKENNUNG Der PV-Konfigurationstest wird ausgeführt. Es liegt jedoch noch kein Ergebnis vor. INDIVIDUELL Die PV-Module sind in Einzelstrangkonfiguration angeschlossen. PARALLEL 1-2* Die PV-Konfiguration ist beendet und hat ergeben, dass die Eingänge 1 und 2 in
Parallelstrangkonfiguration angeschlossen sind. PARALLEL 1-3* Die PV-Konfiguration ist beendet und hat ergeben, dass die Eingänge 1 und 3 in
Parallelstrangkonfiguration angeschlossen sind. PARALLEL 2-3* Die PV-Konfiguration ist beendet und hat ergeben, dass die Eingänge 2 und 3 in
Parallelstrangkonfiguration angeschlossen sind. PARALLEL 1-2-3 Die PV-Konfiguration ist beendet und hat ergeben, dass die Eingänge 1, 2 und 3
in Parallelstrangkonfiguration angeschlossen sind.
Tabelle 2.1: Text im Statusfeld zur PV-Konfigurationsprüfung
*) „PARALLEL 1-2“ ist nur für den Wechselrichter ULX 3000o / 3600o zulässig. „PARALLEL 1-2“, „PARALLEL 1-3“ und „PARALLEL 2-3“ ist nicht beim Wechselrichter ULX 5400o zulässig.
2. Funktionsbeschreibung
16 L00410362-05_2q
2
2.1.3. LEDs
Die grünen LED-Anzeigen geben die Produktion in Prozent der Nennleistung des Wechselrichters an. Die ganz links befindliche grüne LED leuchtet immer auf, wenn der Wechselrichter mit dem Netz verbunden ist. Bei Netzanschaltung leuchten sowohl die rote LED als auch die grüne LED ganz links. Wenn der Wechselrichter vom Netz getrennt ist, leuchtet die rote LED links auf, um anzu­zeigen, dass sich der Wechselrichter im Standby-Modus befindet. Es leuchten keine grünen LEDs. Wenn keine LEDs leuchten, ist der Wechselrichter ausgeschaltet. Befindet sich der Wechselrichter aufgrund eines Ereignisses im Wechselrichter oder der peripheren Anschlüsse, z. B. einem Netz­abwurf, zwangsweise im Standby-Modus, beginnt die rote LED zu blinken.
Eine Beschreibung der Ereignisse enthält der Abschnitt
Fehlersuche und -behebung
.
2.1.4. Display
Der Benutzer hat über das integrierte Display auf der Vorderseite des Wechselrichters Zugang zu allen Informationen über das PV-System und den Wechselrichter. Befindet sich der Wechselrichter im OFF-Betrieb (bei Nacht), ist es möglich, den Wechselrichter durch eine Betätigung der linken Taste (ESC-Taste) am Display zu aktivieren.
Abbildung 2.2: Display
θ
ESC Einen Schritt zurück/nach oben in der
Menüstruktur
Nach oben Blättert zum vorherigen Menü
Nach unten Blättert zum nächsten Menü
OK
Eingabetaste Neue Menüebene oder Änderung der
Einstellungen
Die angezeigten Parameter im Display bezie­hen sich auf intern gemessene Spannungen und Ströme. Die angezeigten Parameter kön­nen Abweichungen aufweisen.
Die Display-Informationen sind in einer in zwei Bereiche unterteilten Menüstruktur organi­siert: A und B
Abschnitt A: Enthält Informationen über die Wechselrichter- und PV-Systemleistung. Abschnitt B: Zeigt alle Messwerte und Benut­zereinstellungen an.
2. Funktionsbeschreibung
L00410362-05_2q 17
2
2.1.5. Überblick Menübereich A
Die nachfolgende Tabelle bietet einen Überblick der Menüstruktur. Die angegebenen Werte dienen nur als Beispiel für die Displaytexte. Der Displaytext (siehe erste Spalte Displayfunktionen) wird auf zwei Zeilen à 16 Zeichen angezeigt. Der Zeilenumbruch ist durch das Symbol | gekennzeichnet.
Menüstruktur A
Displayfunktionen Beschreibung
Ausgangsleistung | 0 W Aktuelle Ausgangsleistung in Watt.
Wechselr. Name
Verwenden Sie das Service Tool zur Eingabe des Wechselrichternamens. Wenn der Name des Wechselrichters nicht definiert ist, wird dieses Menü übersprungen.
Energie gesamt | 22.991 kWh Gesamte Energieerzeugung in kWh seit Start des Wechselrichters.
Betriebsdauer | 00028h 57m 02s
Die Gesamtbetriebsdauer (Zeit der Stromeinspeisung) wird in Stunden, Minuten und Se­kunden angezeigt.
Energie heute | 19637 Wh Energieerzeugung von heute in Wh.
Menü B wählen Springt nach Betätigung von OK zu Menüebene B.
Tabelle 2.2: Überblick Menüstruktur A
2. Funktionsbeschreibung
18 L00410362-05_2q
2
Loading...
+ 43 hidden pages