Thermostat type AT
Application
Technical Data
Accessories
The AT pipe thermostat is used to regulate the medium temperature in the pipe on which the thermostat is mounted. AT senses the temperature in the pipe through its contact surface and is therefore suitable to control boiler or flow temperature in central heating systems.
The AT pipe thermostat comprises a bimetallic sensor, a contact system and a setting knob. On connection to terminals CO and NC the thermostat breaks on a rise in temperature.
On connection to terminals CO and NO the thermostat closes on a rise in temperature.
The AT thermostat can be mounted on the pipe without emptying the plant of water.
Temperature range |
30 to 90 °C |
||
Temperature scale |
external (type 041E0000) |
||
Temperature differential |
8 K |
|
|
Max. temperature plant surface |
Ts90 |
||
Max. ambient temperature |
55 °C |
||
Storage temperature |
-20 to 90 °C |
||
Switch system |
SPDT |
||
Enclosure |
IP40 |
||
Terminal CO-NC |
Breaks on temperature rise |
||
Terminal CO-NO |
Closes on temperature rise |
||
Switch load |
6 (2.5) A, 250 Vac |
||
0.1 A, 250 Vdc |
|||
|
|||
-marking in accordance with the directives |
• |
EMC |
|
|
• |
LVD |
|
|
• |
RoHS |
|
Environment |
Normal |
||
Installation |
Installed in any position |
||
Product |
Code no. |
||
Heat-conductive compound ~ 6 g |
041E0115 |
||
Heat-conductive compound ~ 454 g |
041E0116 |
© Danfoss | 2021.05 |
AI040586453748en-010201 | 1 |
|
|
|
|
|
|
|
|
|
|
|
|
Data sheet |
Thermostat type AT |
|
|||
|
|||||
Installation |
The AT thermostats are mounted directly on a |
|
|||
|
pipe with the steel band provided, suitable for |
|
|||
|
pipe sizes G ½ to 3. |
|
|||
|
A tube containing heat-conductive compound is |
|
|||
|
supplied with the thermostat. The compound has |
|
|||
|
very good heat conducting properties and should |
|
|||
|
be applied between the thermostat contact |
|
|||
|
surface and the pipe. |
|
|||
Electrical connections |
Internal ground terminal screw in the base, M3.5. |
|
|
||
|
|
||||
|
Alternatively, plug connection (AMP). |
|
|
||
|
Electrical connection, M3.5 screw terminals or |
|
|
||
|
plug (AMP). |
|
|
||
|
|
|
|
|
|
Dimensions
Additional documentation on burner components is available on http://heating.danfoss.com/
2 | © Danfoss | DCS-SGDPT/DK | 2021.05 |