Danfoss ThermoClean Data sheet

Data sheet
ThermoClean®
Domestic water heating system with legionella growth prevention through thermal disinfection
Description / Application The ThermoClean® system is compact and
effective solution for legionella-free domestic water heating. The system uses the thermal disinfection methods, whereby the reaction temperature inside the installation is kept at a constant temperature of 70 °C. The ThermoClean® system is dimensioned in such a way that the water is warranted to remain in the reaction area of the device for at least 5 minutes. During tap operation, the reaction temperature of 70 °C is cooled down to the required hot water temperature within the system. This is not achieved by the addition of cold water, but through an additional re-cooling heat exchanger which cools the disinfected water, while preheating cold water, that simultaneous preheat the cold water. The hot water temperature can be set at any temperature between 50 °C and 60 °C.1 It means that the installation of a scaling protection device on the taps is redundant if the temperature is adjusted accordingly. Due to the connection of the circulation into the system a continual thermal disinfection of the hot water is ensured. The high quality stainless steel design of reaction and buffer storage tank, heat exchanger and piping is hygienically perfect, offers a maximum in operational safety and can be universally used in combination with the wide range of materials used in the connected domestic water supply network.
1
The recommended temperature is 60 °C.
Main system data:
Primary Secondary Typ e DL / Combi Max. operating temp. (°C) 100 (150) Max. operating pressure (bar) 16 (25) Working medium Circulation water DHW
2
On request
Approvals and Standards:
- DVGW3 – Working paper W 553 – Calculation for circulation systems in DHW installations,
- DVGW3 – Working paper W 551 – Technical method for prevention of legionella growth,
- DIN 1988 – Code of practice for drinking water installations (TRWI) (when related),
- DIN EN 806 – Specifications for installations inside buildings conveying water for human consumstions,
- DIN EN 1717 – Protection against pollution of potable water installations and general requirements of devices to prevent pollution by backflow.
3
German Technical and Scientific Association for Gas and Water
© Danfoss | 2018.10 VD.KR.D6.02 | 1
2
2
90 10
Data sheet ThermoClean®
ThermoClean®-DL
Domestic water heating system with electronic controls, a stainless steel reaction storage tank, charging and re-cooling brazed plate heat exchangers as well as charging pump, shut-off valves and complete stainless steel piping.
Ordering Explanation, ThermoClean® types
ThermoClean®-DL 200 ECL XB Type heatexchanger Electronic controller type
Reaction tank volume (liter) Typ e
DL – with reaction storage tank and brazed plate heat exchangers Combi – with combined reaction and DHW storage tank and brazed plate heat exchangers
Domestic water heating system with charging
ThermoClean®
Typ e
200 00 4X1618 - 350 004X1619 004X1634 500 004X1620 004X1635
750 00 4X1621 004X1636 1000 004X1622 00 4X1637 130 0 004X1623 -
-DL -Combi
ThermoClean®-Combi
Domestic water heating system with electronic controls, a combined stainless steel reaction and domestic hot water storage tank, charging and re-cooling brazed plate heat exchangers as well as charging pump, shut-off valves and complete stainless steel piping. The ThermoClean®-Combi requires less installation space provided adequate height in the installation place is available.
and re-cooling system unit
Code-No.
incl. electronic controller ThermoContol
2 | VD.KR.D6.02 © Danfoss | 2018.10
Data sheet ThermoClean®
Accessories
4
ThermoClean®-DL
Domestic hot water storage tank The ThermoClean® system must be combined with additional domestic hot water storage tanks to provide the required capacity for peak consumption. The required storage tank capacity is based on the calculated peak flow and the length of the consumption period. The recommendations provided overleaf for the total storage tank capacity are based on peak consumptions lasting 1 hour or according to customer demands. If the consumption periods are shorter, the storage tank capacity can be reduced accordingly. We recommend the utilization of the following storage tanks:
- Stainless steel domestic hot water storage tank series SE,
- Tank sizes: 150 ... 8000 liters,
- Optimum adaptation to requirements due to optional combination of multiple storage tanks.
4
accessories for separately order
Technical data
Perfor-
Typ e
-DL
-Combi
5
Performance index NL acc. to DIN 4708
6
Dependent on the additional storage tank(s)
mance
200 -
350 -
500 -
750 -
1000 -
130 0 -
350 15 .. 9 55 .. 30 91 162 0 870 .. 390 4000 1 ,111 15 60 690 .. 1170 20 56 18
500 28 .. 13 71 .. 39 119 2120 1130 .. 510 4000 1,111 2040 910 .. 1530 21 56 19
750 41 .. 21 88 .. 48 147 2620 1400 .. 630 7000 1,944 2520 1120 .. 1890 22 49 14
1000 52 .. 29 101 .. 55 168 2970 1600 .. 720 7000 1,9 44 2880 1280 .. 2160 24 49 14
Connected
index
NL
6
6
6
6
6
6
load
5
kW kW l/h l/h l/h l/s l/h l/h kPa kPa kPa
84 .. 46 140 2480 1330 .. 600 5000 1,389 2400 1070 .. 1800 24 54 19
147 .. 80 245 4440 2330 .. 1050 7500 2,083 420 0 1870 .. 3150 20 64 20
210 .. 114 350 6480 3330 . . 1500 9000 2,500 6000 2670 .. 4500 22 58 20
315 .. 171 525 9650 5000 .. 2250 12000 3,333 9000 4000 .. 6750 23 59 23
420 .. 228 700 12960 6670 .. 300 0 15000 4,167 12000 5330 .. 9000 29 65 27
546 .. 296 910 1698 0 8670 .. 3900 20000 5,556 156 00 6930 .. 11700 35 86 30
consumption
Max. power
for peak
Heating
(Hot)
water flow
= 75 °C
at ϑ
VL
Domestic hot water
capacities
Permanent
capacity
Peak
capacity
Charge
flow total
Circ. flow
(max.)
Heating
water
Resistance
DHW
(max.)
Circ.
(max.)
VD.KR.D6.02 | 3© Danfoss | 2018.10
Data sheet ThermoClean®
Design and function
CPU
ECD
1 3 2 47
45
DTA
46
reaction tank/vessel
RTA
HEX charging/load
HEL
HEX cooling
HEC
charging pump/load
LPU
circulation pump (on site/by customer)
CPU
safety valve
SFV
control valve electrical
CVE
electronic controller DHW
ECD
control valve electrical domestic
CVD
domestic buffer tank (accessory)
DTA
shut off device
balancing valve
sensor (direct, cable/universal, surface)
RTA
SFV
LPU
HEL
4
CVE
HEC
domestic water cold
1) domestic water hot
2) circulation
3) heating supply
4) heating return
5) to domestic buffer tank (stainless steel) top
45) from domestic buffer tank (stainless steel)
46)
CVD
below from domestic buffer tank
47)
thermometer
drain / air vent (on site / by customer)
check valve
sampling valve
The heat exchanger brings the system volume to the disinfection temperature of 70 °C. A temperature sensor at the exit of the heat exchanger monitors this temperature and regulates the application of heat energy accordingly. The system is dimensioned to ensure that the domestic hot water remains in the reaction area for at least 4 minutes to warrant the extermination of the legionella bacteria. The entire system volume is maintained at the defined disinfection temperature. Only when the water is tapped, the required quantity of water is cooled down to the demanded network temperature (50 ... 60 °C) while the new cold water that is being added is preheated.
Temperature fluctuations are balanced out by the mixing valve, so that the precise degree of water temperature indicated is definitely being maintained. Proven control technology ensures that the domestic hot water network is not heated up during breaks in tapping. If the consumption volume during peak times exceeds the charge flow of the system, the available storage tank volume is tapped. The optionally available over-tapping protection ensures that during unexpected functions (e.g. peak tapping continues for a period exceeding the determined consumption period) the cold water supply is suspended until sufficient thermally disinfected domestic water is once again available through the charging process via the reaction tank. The circulation water from the network enters the system, is once again heated up to 70 °C by the charge heat exchanger and consequently incorporated into the thermal disinfection process continually.
Sizing For dimensioning and selection of ThermoClean®
system please contact with Danfoss local sales representative.
4 | VD.KR.D6.02 © Danfoss | 2018.10
Data sheet ThermoClean®
Mounting ThermoClean®-DL
After setting up, connect reaction and DHW storage tank, charge/re-cooling system unit via the pre-installed connections. Next the heating and domestic water connections, mains connections. Commissioning as described in the installation and operating instructions.
ThermoClean®-Combi After setting up, connect combination and DHW storage tank, charge/re-cooling system via the pre-installed connections. Next the heating and domestic hot water connections, mains connections. Commissioning as described in the installation and operating instructions.
Dimensions
ThermoClean®-DL ThermoClean®-Combi
B1
B2
1 4 3 2
4
1
47
3 2
47
H2
T2
T1
H1
25
D
d
45
46
H1
25
45
D
d
46
B1
4
2 3
1
H2
B2
2
4
3
T2
T1
1
Typ e
H1 d D
mm mm mm mm mm mm mm mm G/Rp G/Rp DN G/Rp kg kg kg 200 1600 350 2045 1795 1950 G 1¾” G 1½” 40 G 1¾” 90 160 ­500 2090 600 800 18 45 2060 825
-DL 750 2240 750
1000 2525 800 130 0 2610 900
500 700
9
950 1970 2365 110 0 990 G 23/8” 155 230 -
9
1000 2220 2570 120 0 965
9
110 0 2245 2720 1250 995
350 1825 550 750
-Combi
500 1865 650 850 1630 25/20 90 20
750 2145 750 950 1780
1000 2145 85091050 190 0 780 195
7
For ThermoClean® type -DL incl. charging unit
8
Mounted on the ThermoClean®-Combi’s tank
9
min. door width; when needed components has to demounted
10
max. width of frame
11
raw weight (without insulation/package)
All connection axis measures are approximate and have a tolerance of +/- 15 mm.
H2
approx. B1approx. B2approx. T1approx. T2approx.
173 0 1950
1000
725 600
1530
9
1800
800
780
Connections Weight
3
G 2
Rp 2 ½”
-
Storage
tank
/8”
210 250 -
145
10
1, 2 3 4, 5 45-47
G 1½” G 1¼” 25/20 G 1½” 70 14 0 -
9
650
920
9
G 1¾”
G 23/8”
Rp 2”
Rp 2½”
Rp 2 ½”
G 1½” G 1¼”
50/40
65/50 235 300 -
20
­G 1¾” G 1½” 32/20
11
Re-cooli ng
unit
Charging
90 170 -
70
100
105 25
unit
8
15
VD.KR.D6.02 | 5© Danfoss | 2018.10
Data sheet ThermoClean®
© Danfoss | DHS-SMTL/PL | 2018.106 | VD.KR.D6.02
Loading...