Fact sheet
Termix VX Compact 28
District heating substation for indirect heating with electronic controls. Designed for wall-mounting.
Application
The Termix VX Compact 28 is a complete solution for space heating with optimal safety, efficient energy transfer, service-friendly construction and a compact design. The substation is applicable, if a heat exchanger is required or on a conversion to district heating, where the existing equipment is unsuitable for direct connection. The Termix VX Compact 28 substation is ideal, where a high level of security against burst pipes and water damage in the heating system is required.
District heating (DH)
The district heating circuit is prefabricated with a flow controller with integrated control valve, thermometers and ball valves.
Heating (HE)
The heating circuit consists of a plate heat exchanger, safety valve, manometer, thermometers, ball valves, drain valve, air valve and circulation pump.
The heating temperature is controlled by an electronic controller with an outdoor temperature sensor. Depending on the application, different heat exchangers dimensioned for central or floor heating can be used.
Domestic hot water (DHW)
Termix VX Compact 28 is supplied with connection pipes for a DHW tank on the supply line.
Options
Termix VX Compact 28 can be delivered with white-lacquered steel cover or with filling line.
Construction
All pipes are made of stainless steel. The connections are made by nuts and gaskets.Other information about other required components
FEATURES AND BENEFITS
••Substationwithhighefficiencybrazed plateheatexchangersforproperties ofbetween1to30apartments,made fromacid-proofstainlesssteel
••Wall-mountedconstruction
••Suitablefornewbuildingsas wellasrenovationprojects
••Small,lightweight,compact construction
••Electroniccontrollersforheating anddomestichotwatersystems
••Advancedgasketsystem-primaryside
••Fastandreliabledelivery
••Danfosssubstationsandheat exchangersaremanufactured accordingtoEuropeanPressure DirectivePED9979797/23/WE
www.heating.danfoss.com
CIRCUIT DIAGRAM - EXAMPLE
25 bar
1 |
18 |
25 |
9 |
DN 25
25 bar
1 |
18 |
25 |
DN 25
A Plate heat exchanger HE F Electronic controller
1 Ball valve
4 Safety valve
9Strainer
10Circulation pump
16Outdoor sensor
18Thermometer
Technical parameters: |
|
|
Nominal pressure: |
|
PN 16 |
DH supply temperature: |
Tmax = 120 °C |
|
Brazing material (HEX): |
|
Copper |
Weight: |
|
approx. 50 kg |
Insulation: |
|
EPP λ 0.039 |
Dimensions (mm) |
|
|
Without cover: |
H 970 × W 620 × D 420 |
|
With cover: |
H 970 × W 640 × D 522 |
|
Electrical supply: |
|
230 V AC |
|
|
|
16 |
|
230 V |
|
|
|
|
|
|
|
|
F |
|
|
|
|
|
|
|
|
|
4 bar |
|
|
|
|
|
|
|
|
1 |
48 |
26 |
19 |
10 |
18 |
1 |
|
|
|
|
|
|
|
|
DN 25 |
|
|
|
|
|
4 |
|
|
|
|
24 |
1 |
18 |
27 |
19 |
|
|
18 |
1 |
9 |
|
|
|
|
|||||||
|
|
30 |
A |
|
20 |
|
|
DN 25 |
|
|
|
|
|
|
|
||||
1 |
|
1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
DN 20 |
|
|
|
|
|
|
19Surface sensor
20Filling/drain valve
24Delivered loose with unit
25Manometer with ball valve
26Manometer
27Actuator
30 Flow control w. control valve
48 Air escape, manual
Connections:
1. District heating (DH) supply
2. District heating (DH) return
3. Heating (HE) supply
wall 4. Heating (HE) return 5. Tank (DHW) supply
6. Tank (DCW) return
|
|
|
|
|
|
|
Connection sizes: |
||
<![if ! IE]> <![endif]>105 |
|
|
|
|
|
|
DH + HE |
G 1”(int. thread) |
|
1 |
2 |
3 |
4 |
5 |
6 |
Options: |
|
||
|
|
||||||||
|
|
|
|
|
|
|
• |
Cover |
|
|
100 |
100 |
100 |
|
90 |
130 |
• |
Filling line |
|
|
|
|
|
|
Seen from above
CAPACITY, WEIGHT AND DIMENSIONS
Substation type |
Heating |
Heating circuit |
Heating circuit |
Pressure loss |
Flow rate |
Flow rate |
Termix VX |
capacity |
primary |
secondary |
primary |
primary |
secondary |
Compact 28 |
[kW] |
[°C] |
[°C] |
[kPa] |
[l/h] |
[l/h] |
VX - 1 |
45 |
80 / 55 |
50 / 70 |
50 |
1580 |
1974 |
VX - 1 |
50 |
100 / 62 |
60 / 80 |
50 |
1168 |
2204 |
VX - 1 |
50 |
120 / 71 |
70 / 90 |
50 |
899 |
2210 |
VX - 1 |
80 |
90 / 46 |
40 / 70 |
50 |
1625 |
2333 |
VX - 2 |
75 |
80 / 55 |
50 / 70 |
50 |
2652 |
3290 |
VX - 2 |
80 |
100 / 62 |
60 / 80 |
50 |
1868 |
3525 |
VX - 2 |
80 |
120 / 71 |
70 / 90 |
50 |
1439 |
3536 |
VX - 2 |
110 |
90 / 46 |
40 / 70 |
50 |
2187 |
3205 |
VX - 3 |
95 |
80 / 55 |
50 / 70 |
50 |
3314 |
4168 |
VX - 3 |
100 |
100 / 62 |
60 / 80 |
50 |
2317 |
4403 |
VX - 3 |
100 |
120 / 71 |
70 / 90 |
50 |
1793 |
4420 |
VX - 3 |
140 |
90 / 46 |
40 / 70 |
50 |
2757 |
4079 |
Gemina Termix A/S · Member of the Danfoss Group · Navervej 15-17 · DK-7451 Sunds · Denmark Tel.: +45 9714 1444 · Fax: +45 9714 1159 · mail@termix.dk · www.heating.danfoss.com
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice.This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary eady agreed.