Fact sheet
Termix VX Compact 28
District heating substation for indirect heating with electronic controls. Designed for wall-mounting.
Application
The Termix VX Compact 28 is a complete solution for space heating with
optimal safety, efficient energy transfer, service-friendly construction and
a compact design. The substation is
applicable, if a heat exchanger is required or on a conversion to district
heating, where the existing equipment is unsuitable for direct connection. The Termix VX Compact 28 substation is ideal, where a high level of
security against burst pipes and water damage in the heating system is
required.
District heating (DH)
The district heating circuit is prefabricated with a flow controller with integrated control valve, thermometers
and ball valves.
Heating (HE)
The heating circuit consists of a plate
heat exchanger, safety valve, manometer, thermometers, ball valves, drain
valve, air valve and circulation pump.
The heating temperature is controlled by an electronic controller
with an outdoor temperature sensor.
Depending on the application, different heat exchangers dimensioned
for central or floor heating can be
used.
Domestic hot water (DHW)
Termix VX Compact 28 is supplied
with connection pipes for a DHW
tank on the supply line.
Options
Termix VX Compact 28 can be delivered with white-lacquered steel cover or with filling line.
Construction
All pipes are made of stainless steel.
The connections are made by nuts
and gaskets.Other information about
other required components
FEATURES AND BENEFITS
• Substation with high efficiency brazed
plate heat exchangers for properties
of between 1 to 30 apartments, made
from acid-proof stainless steel
• Wall-mounted construction
• Suitable for new buildings as
well as renovation projects
• Small, lightweight, compact
construction
• Electronic controllers for heating
and domestic hot water systems
• Advanced gasket system - primary side
• Fast and reliable delivery
• Danfoss substations and heat
exchangers are manufactured
according to European Pressure
Dire ctive PED 9979797/23/WE
www.heating.danfoss.com
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alterations can be made without subsequential changes being necessary eady agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
CIRCUIT DIAGRAM - EXAMPLE
25 bar
25
25 bar
25
= 120 °C
max
9
18
1
DN 25
181
DN 25
A Plate heat exchanger HE
F Electronic controller
1 Ball valve
4 Safety valve
9 Strainer
10 Circulation pump
16 Outdoor sensor
18 Thermometer
Technical parameters:
Nominal pressure: PN 16
DH supply temperature: T
Brazing material (HEX): Copper
Weight: approx. 50 kg
Insulation: EPP λ 0.039
Dimensions (mm)
Without cover: H 970 × W 620 × D 420
With cover: H 970 × W 640 × D 522
Electrical supply: 230 V AC
1 18
1
19 Surface sensor
20 Filling/drain valve
24 Delivered loose with unit
25 Manometer with ball valve
26 Manometer
27 Actuator
30 Flow control w. control valve
48 Air escape, manual
105
1 2 3 4 5 6
27 19
30
DN 20
100 100 100 90 130
Seen from above
16
1
A
1
F
4 bar
48
4
230 V
26 19 10
20
wall
1
18
DN 25
24
18
Connections:
1. District heating (DH) supply
2. District heating (DH) return
3. Heating (HE) supply
4. Heating (HE) return
5. Tank (DHW) supply
6. Tank (DCW) return
Connection sizes:
DH + HE G 1” (int. thread)
Options:
• Cover
• Filling line
1
DN 25
9
CAPACITY, WEIGHT AND DIMENSIONS
Substation type
Ter mix VX
Compact 28
VX - 1 45 80 / 55 50 / 70 50 1580 1974
VX - 1 50 100 / 62 60 / 80 50 1168 2204
VX - 1 50 120 / 71 70 / 90 50 899 2210
VX - 1 80 90 / 46 40 / 70 50 1625 2333
VX - 2 75 80 / 55 50 / 70 50 2652 3290
VX - 2 80 100 / 62 60 / 80 50 1868 3525
VX - 2 80 120 / 71 70 / 90 50 1439 3536
VX - 2 110 90 / 46 40 / 70 50 2187 3205
VX - 3 95 80 / 55 50 / 70 50 3314 4168
VX - 3 100 100 / 62 60 / 80 50 2317 4403
VX - 3 100 120 / 71 70 / 90 50 1793 4420
VX - 3 140 90 / 46 40 / 70 50 2757 4079
Heating
capacity
[kW]
Heating circuit
primary
[°C]
Heating circuit
secondary
[°C]
Pressure loss
primary
[kPa]
Flow rate
primary
[l/h]
Flow rate
secondary
Gemina Termix A/S · Member of the Danfoss Group · Navervej 15-17 · DK-7451 Sunds · Denmark
Tel.: +45 9714 1444 · Fax: +45 9714 1159 · mail@termix.dk · www.heating.danfoss.com
© Danfoss | DHS-SRMT/ PL | 2016. 05
[l/h]
VL.EH.J3.02