Danfoss Termix VX Fact sheet

Fact sheet
Termix VX
Indirect substation for single and multi-family houses with up to 7 apartments
Application
The Termix VX is a complete solution for space heating with optimal safety, efficient energy transfer, service-friendly construction and a compact design. The substation is used if a heat exchanger is required or on a conversion to district heating where the existing equipment is unsuitable for direct connection. The Termix VX substation is ideal, when a high level of security against burst pipes and water damage in the heating system is required.
District heating (DH)
The substation is prefabricated with a differ­ential pressure controller, fitting piece and sensor pockets for insertion of a heat meter as well as strainers and ball valves.
Heating (HE)
The heating side consists of a stainless steel plate heat exchanger, safety valve, manom­eter, thermometers, ball valves, drain valve, air valve, expansion vessel and circulation pump. The temperature of the heating can be controlled thermostatically or by an electronic temperature controller with an outdoor
temperature sensor. Depending on the application, different heat exchangers dimensioned for central or floor heating can be used. As an option the substation can be equipped with a thermostat with safety monitor. This is possible only for substations with electronic temperature controller.
Domestic hot water (DHW)
The substation is supplied with connection pipes for a hot water tank on the primary side of the heat exchanger.
Construction
All pipes are made of stainless steel. The connections are made by nuts and gaskets. The Termix VX is completed by a white steel cover in attractive modern design.
FEATURES AND BENEFITS
• Substation for single and multi-family houses
• Indirect heating, connections for domestic hot water tank
• Thermostatic or electronic regulation of heating (HE) temperature
• Capacity: 18 – 54 kW heating
• Minimum space required for installation
• Pipes and plate heat exchanger made of stainless steel
www.danfoss.com
CIRCUIT DIAGRAM - EXAMPLE
DH
Supply
DH
Return
Technical parameters:
Nominal pressure: PN 10* DH supply temperature: T Brazing material (HEX): Copper
*PN 16 versions are available on enquiry
Weight incl. cover: 30 kg (incl. packing)
Cover: White-lacquered steel sheet
Dimensions (mm):
Without cover: H 750 × W 500 × D 360 With connections: H 800 × W 540 × D 430
14
9
= 120 °C
max
311441
4 bar
1
B
7
1
Connections:
1. District heating (DH) supply
2. District heating (DH) return
3. Heating (HE) supply
4. Heating (HE) return
5. Cylinder supply
6. Cylinder return
45
1 2 3 4 5 6
70 70 70 70 80
Seen from above
48
26
4
10
20
A Plate heat exchanger HE 1 Ball valve 4 Safety valve 7 Thermostatic valve 9 Strainer 10 Circulation pump 14 Sensor pocket, heat meter 18 Thermometer
18
18
Wall
HE Supply
24
38
9
20 Filling / drain valve 24 Delivered loose with unit 26 Pressure gauge 31 Differential pressure controller 38 Expansion vessel 41 Fitting piece, heat meter 48 Air escape, manual
Connection sizes:
DH + HE: G ¾ (int. thread)
Options:
• Separate mixing circuit
• White-lacquered steel cover
• Possibility for electronic controller
• Room thermostat
• Zone valve with actuator
• Air screw (DH supply)
• Connection for hot water tank
HE Return
CAPACITY, WEIGHT AND DIMENSIONS
CAPACITY, WEIGHT AND DIMENSIONS
Substation type
VX – 1
VX– 2
VX – 3
Heating capacity
[kW]
18 70 35/60 25 650 20 80 40/70 25 603 24 90 40/70 25 724 30 70 35/60 35 1084 34 80 40/70 35 1025 40 90 40/70 35 1206 45 70 35/60 45 1629 50 80 40/70 45 1509 54 90 40/70 45 1629
Heating circuit
primary [°C]
Heating circuit secondary [°C]
Pressure loss
primary
[kPa]