Danfoss Termix VMTD-F-B Installation Manual

Page 1
InstallationGuide
TermixVMTD-F-B
1.0TableofContents
1.0TableofContents.............................................1
........................................................................2
2.0Functionaldescription......................................3
3.0Safetynotes.....................................................4
4.0Mounting........................................................5
4.1Mounting...........................................................5
4.2Start-up..............................................................6
4.3Electricalconnections.............................................7
5.0Design.............................................................8
5.1Design...............................................................8
5.2Schematicdiagram................................................9
6.0Controls..........................................................10
6.1Heatingcircuit......................................................10
6.2DHWtemperaturecontrol........................................11
6.3Other.................................................................11
6.4Maintenance........................................................14
7.0Troubleshooting..............................................15
7.1Troubleshootingingeneral......................................15
7.2TroubleshootingDHW............................................15
7.3TroubleshootingHE...............................................16
7.4Disposal.............................................................17
8.0Declaration......................................................19
8.1Declarationofconformity........................................19
DanfossDistrictEnergy
VI.CW.C3.02/L UK40110
DEN-GT
1
Page 2
InstallationGuideTermixVMTD-F-B
2
DEN-GT
VI.CW.C3.02/L UK40110
DanfossDistrictEnergy
Page 3
InstallationGuideTermixVMTD-F-B
2.0Functionaldescription
Districtheatingsubstationfordirectheatingand instantaneousdomestichotwater.
Application
TheTermixVMTD-F-Bisacompletesolutionwithbuilt-inwater heaterandadifferentialpressurecontrolledheatingsystem.Termix VMTD-F-Bisapplicableforsingleandmulti-familyhousesandfor decentralizedsystems.
Districtheating(DH)
Thesubstationisprefabricatedwithadifferentialpressure controller,attingpieceandsensorpocketsforinsertionofaheat meteraswellasstrainerandballvalves.
Heating(HE)
Theheatingcircuitisdesignedfordirectgenerationofheat. Thedifferentialpressurecontrolsetstheoptimumoperation conditionsforradiatorthermostaticvalvesinordertoenable individualtemperaturecontrolineachroom.Inordertoenablea time-dependingtemperaturecontrolprogram,azonevalvewith actuatorandaroomthermostatcanbeincludedasanoption.
Domestichotwater(DHW)
Thedomestichotwaterispreparedintheheatexchangerandthe temperatureisregulatedwithathermostaticcontrolvalve.The patentedsensoracceleratoracceleratestheclosingoftheDanfoss AVTBvalveandprotectstheheatexchangeragainstoverheating andlimescaleformation.TheheatexchangercoolstheDHwater veryefciently,therebycreatingaverygoodoperatingeconomy. ThesensoracceleratorandAVTBvalvealsoworksasabypass keepingthehousesupplylinewarm.Thisshortensthewaiting periodsduringsummerwhentheheatingsystemisinreduced operation.Thesensoracceleratorhelpstoensureastablehot watertemperatureregardlessofvaryingloads,owtemperatures anddifferentialpressurewithouttheneedforreadjustingthevalve.
DanfossDistrictEnergy
VI.CW.C3.02/L UK40110
DEN-GT
3
Page 4
InstallationGuideTermixVMTD-F-B
3.0Safetynotes
3.1SafetyNotes–general
Thefollowinginstructionsrefertothestandarddesignof substation.Specialversionsofsubstationsareavailableon request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation andstart-upofthesubstation.Themanufactureracceptsno liabilityfordamageorfaultsthatresultfromnon-compliancewith theoperatingmanual.Pleasereadandfollowalltheinstructions carefullytopreventaccidents,injuryanddamagetoproperty. Assembly,start-upandmaintenanceworkmustbeperformedby qualiedandauthorizedpersonnelonly. Pleasecomplywiththeinstructionsissuedbythesystem manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass. Themaximumchloridecompoundsoftheowmediumshouldnot behigherthan150mg/l. Theriskofequipmentcorrosionincreasesconsiderablyifthe recommendedlevelofpermissiblechloridecompoundsis exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary sourceofenergy.However,alsootherenergysourcescanbeused wheretheoperatingconditionsallowitandalwaysarecomparable todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse installationinafrost-freeroom,wherethetemperaturedoesnot exceed50°Candthehumiditydoesnotexceed60%.Donotcover orwallupthesubstationorinanyotherwayblocktheentrance tothestation.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat thesubstationcanbeseparatedfromallenergysources(also powersupply).
Emergency
Incaseofdangeroraccidents-re,leaksorotherdangerous circumstances-interruptallenergysourcestothestationif possible,andseekexperthelp. Incaseofdiscolouredorbad-smellingdomestichotwater,closeall shut-offvalvesonthesubstation,informtheoperatingpersonnel andcallforexperthelpimmediately.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto installationshouldbeinconditionswhicharedryandheated.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallation’ spermissiblesystempressureand temperature.
Themaximumtemperatureoftheowmediuminthesubstationis 120°C.
Themaximumoperatingpressureofthesubstationis10bar.PN16 versionsareavailableonenquiry.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases considerablyiftherecommendedpermissibleoperatingparameters areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves, however,alwaysinaccordancewithlocalregulations.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns. Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen position.Thesurfacesofthesubstationcangethot,whichcancause skinburns.Theballvalvesondistrictheatingsupplyandreturnshould beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallangeconnections,screwjoints andelectricalclampandscrewconnectionsmustbecheckedand tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen addedtothesystemandthesystemhasbeenputintooperation, re-tightenALLconnections.
4
DEN-GT
VI.CW.C3.02/L UK40110
DanfossDistrictEnergy
Page 5
InstallationGuideTermixVMTD-F-B
4.0Mounting
4.1Mounting
Installationmustbeincompliancewithlocalstandardsand regulations. Districtheating(DH)-Inthefollowingsections,DHreferstothe heatsourcewhichsuppliesthesubstations.Avarietyofenergy sources,suchasoil,gasorsolarpower,couldbeusedasthe primarysupplytoDanfosssubstations.Forthesakeofsimplicity, DHcanbetakentomeantheprimarysupply.
Connections:
1.Hotwatercirculation(HWC)(Optional)
2.Districtheating(DH)supply
3.Districtheating(DH)return
4.Coldwatermains(CWM)
5.Domesticcoldwater(DCW)
6.Domestichotwater(DHW)
7.Heating(HE)supply
8.Heating(HE)return
Connectionsizes:
DH+HE:
G¾”(int.thread)
CWM+DCW+DHW:
G¾”(int.thread)
Dimensions(mm):
Withoutcover: H710xW528xD150 Withcover(mountonwallvariant): H800xW540xD190 Withcover(built-inwallvariant): H915–980xW610xD150
Weight(approx.):20kg
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualiedandauthorizedpersonnelonly.
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote themarkingsonthestation.
DanfossDistrictEnergy
VI.CW.C3.02/L UK40110
DEN-GT
5
Page 6
InstallationGuideTermixVMTD-F-B
4.1.1Installation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes andlabelsareplacedcorrectly.Ifyouwishtomountthestation differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe cleanedandrinsed.
Tightening
Duetovibrationduringtransport,allsubstationconnectionsmust becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha plug.Shouldtheplugsrequireremoval,thismustonlybedoneby anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbettedaccording toschematicdiagram.Pleasenotethatthestrainermaybe suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe madeusingthreaded,angedorweldedconnections.
Keyholeformounting.
4.2Start-up
Start-up,Directheating
Theshut-offvalvesshouldbeopenedandtheunitobservedas itentersservice.Visualcheckingshouldconrmtemperatures, pressures,acceptablethermalexpansionandabsenceofleakage. Iftheheatexchangeroperatesinaccordancewithdesign,itcanbe puttoregularuse.
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen putintooperation,re-tightenALLconnections.
Re-thightenconnections
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen putintooperation,re-tightenALLconnections.
6
DEN-GT
VI.CW.C3.02/L UK40110
DanfossDistrictEnergy
Page 7
InstallationGuideTermixVMTD-F-B
4.3Electricalconnections
Beforemakingelectricalconnections,pleasenotethe following:
Safetynotes
Pleasereadtherelevantpartsofthesafetynotes.
230V
Thesubstationmustbeconnectedto230VACandearth.
Disconnection
Thesubstationmustbeelectricallyconnectedsothatitcanbe disconnectedforrepairs.
Outdoortemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto directsunlight.Theyshouldnotbeplacedclosetodoors,windows orventilationoutlets.
Theoutdoorsensormustbeconnectedtothestationonthe terminalblockundertheelectroniccontrol.
Authorizedelectrician
Electricalconnectionsmustbemadebyanauthorizedelectricianonly.
Localstandards
Electricalconnectionsmustbemadeinaccordancewithcurrent regulationsandlocalstandards.
DanfossDistrictEnergy
VI.CW.C3.02/L UK40110
DEN-GT
7
Page 8
InstallationGuideTermixVMTD-F-B
5.0Design
5.1Design
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
B
Heatexchanger,DHW
14
Sensorpocket,energymeter
O
Termixsensoraccelerator
31
Differentialpressurecontroller
7
Thermostaticvalve,DHW
41A
Fittingpiece,coldwatermains
9
Strainer
41BFittingpiece,energymeter
8
DEN-GT
VI.CW.C3.02/L UK40110
DanfossDistrictEnergy
Page 9
InstallationGuideTermixVMTD-F-B
5.2Schematicdiagram
DHW
CWM
DCW
DH
Supply
HE Supply
DH
Return
HE Return
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
B
Heatexchanger,DHW
31
Differentialpressurecontroller
7
Thermostaticvalve,DHW
41A
Fittingpiece,coldwatermains
9
Strainer
41BFittingpiece,energymeter
14
Sensorpocket,energymeter
DHW:DomesticHotWater CWM:
ColdWaterMains
DCW:
DomesticColdWater
DHSupply:DistrictHeatingSupply DHReturn:DistrictHeatingReturn HESupply:HeatingSupply HEReturn:HeatingReturn
5.2.1Technicalparameters
Technicalparameters
Nominalpressure:PN10(PN16versionsareavailableonenquiry) Max.DHsupplytemperature:
120°C
Min.DCWstaticpressure:
0.5bar
Brazingmaterial(HEX):
Copper Heatexchangerstestpressure:30bar Soundlevel:≤55dB
DanfossDistrictEnergy
VI.CW.C3.02/L UK40110
DEN-GT
9
Page 10
InstallationGuideTermixVMTD-F-B
6.0Controls
6.1Heatingcircuit
6.1.1Differentialpressurecontroller
Thedifferentialpressurecontrollersmoothsouttheuctuationsin pressurearrivingfromthedistrictheatingnetwork.Theoperating pressureinthesubstationisthusheldsteady.
6.1.2TP7000
TP7000electronic7dayprogrammableroomthermostat. Signalsfromtheroomthermostatcanbeusedtocontrolzone valves.
10
DEN-GT
VI.CW.C3.02/L UK40110
DanfossDistrictEnergy
Page 11
InstallationGuideTermixVMTD-F-B
6.2DHWtemperaturecontrol
DHWtemperaturecontrol
TherearevarioustypesofDHWtemperaturecontrolusedin Danfosssubstations. DHWtemperatureshouldbeadjustedto45-50°C,asthisprovides optimalutilisationofDHwater.AtDHWtemperaturesabove55°C, thepossibilityoflimescaledepositsincreasessignicantly.
6.2.1AVTBcontroller(20–60°)
Thetemperaturesettingisasfollows: 1=20°C 2=35°C 3=50°C 4=60°C 5=70°C
Thevaluesareintendedasaguide.
TheAVTBoperatesatitsbestatDHsupplytemperaturesofupto 90°C.
Thermostaticcontrol
DHWtemperatureisadjustedasfollows: Toincreasetemperature,turnthehandleonthethermostatic controllertoselectahighernumber. Todecreasetemperature,turnthehandleonthethermostatic controllertoselectalowernumber.
6.3Other
6.3.1Safetyvalve
Thepurposeofthesafetyvalveistoprotectthesubstationfrom excessivepressure. Theblow-offpipefromthesafetyvalvemustnotbeclosed.The blow-offpipeoutletshouldbeplacedsothatitdischargesfreely anditispossibletoobserveanydrippingfromthesafetyvalve. Itisrecommendedtochecktheoperationofsafetyvalvesat intervalsof6months.Thisisdonebyturningthevalveheadin directionindicated.
DanfossDistrictEnergy
VI.CW.C3.02/L UK40110
DEN-GT
11
Page 12
InstallationGuideTermixVMTD-F-B
6.3.2Strainer
Strainersshouldbecleanedregularlybyauthorizedpersonnel.The frequencyofcleaningwoulddependonoperatingconditionsand themanufacturer’sinstructions.
6.3.3GTUPressureEqualizer
TheGTUPressureEqualizerabsorbstheexpansiononthe secondarysideoftheTermixwaterheatersandcanbeusedasa substitutetothesafetyvalve. Furthermorethepressureequalizerabsorbsapossibleincreasein pressure,soadischargeoutletisomitted. TheGTUPressureEqualizermaynotbeappliedinsystemswithhot watercirculation.
6.3.4ReturntemperaturelimiterFJVR(10-80°C)
ThereturnlimitertypeF JVRautomaticallycontrolsthereturn temperaturefromradiators,convectorsandunderoorheating pipes.
12
DEN-GT
VI.CW.C3.02/L UK40110
DanfossDistrictEnergy
Page 13
InstallationGuideTermixVMTD-F-B
6.3.5Fittingpiece
Thesubstationisequippedwithattingpieceforenergymeter .
Assemblyofenergymeters:
1:Closeballvalves
ClosetheballvalvesonDHSupplyandDHReturn,ifthereiswater onthesystem.
2:Loosennuts
Loosenthenutsonthettingpiece.
3:Removettingpiece
Removethettingpieceandreplaceitwiththeenergymeter.Do notforgetthegaskets.
4:Tightenconnections
Aftermountingoftheenergymeterremembertocheckand tightenallthreadedconnections.
Sensorpocket,energymeter
Thesensorsoftheenergymeterismountedinthesensorpockets.
DanfossDistrictEnergy
VI.CW.C3.02/L UK40110
DEN-GT
13
Page 14
InstallationGuideTermixVMTD-F-B
6.4Maintenance
Thesubstationrequireslittlemonitoring,apartfromroutine checks.Itisrecommendedtoreadtheenergymeteratregular intervals,andtowritedownthemeterreadings.
RegularinspectionsofthesubstationaccordingtothisInstruction arerecommended,whichshouldinclude:
Strainers
Cleaningofstrainers.
Meters
Checkingofalloperatingparameterssuchasmeterreadings.
Temperatures
Checkingofalltemperatures,suchasDHsupplytemperatureand DHWtemperature.
Connections
Checkingallconnectionsforleakages.
Safetyvalves
Theoperationofthesafetyvalvesshouldbecheckedbyturning thevalveheadintheindicateddirection.
Venting
Checkingthatthesystemisthoroughlyvented.
Inspectionsshouldbecarriedoutminimumeverytwoyears.
SparepartscanbeorderedfromDanfoss.Pleaseensurethatany enquiryincludesthesubstationserialnumber.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualiedandauthorizedpersonnelonly.
14
DEN-GT
VI.CW.C3.02/L UK40110
DanfossDistrictEnergy
Page 15
InstallationGuideTermixVMTD-F-B
7.0Troubleshooting
7.1Troubleshootingingeneral
Intheeventofoperatingdisturbances,thefollowingbasicfeatures shouldbecheckedbeforecarryingoutactualtroubleshooting:
thesubstationisconnectedtoelectricity,
thestrainerontheDHsupplypipeisclean,
thesupplytemperatureoftheDHisatthenormallevel
(summer,atleast60°C-winter ,atleast70°C),
thedifferentialpressureisequaltoorhigherthanthenormal
(local)differentialpressureintheDHnetwork–ifindoubt,ask theDHplantsupervisor,
pressureonthesystem-checktheHEpressuregauge.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualiedandauthorizedpersonnelonly.
7.2TroubleshootingDHW
ProblemPossiblecauseSolution
Strainerinsupplyorreturnlineclogged.Cleanstrainer(s).
DHWcirculationpumpoutoforderorwith toolowsetting.
Checkcirculationpump.
Defectiveorcloggednon-returnvalve.
Replace–clean.
Noelectricity.Check.
Wrongsettingofautomaticcontrols,ifany.Toadjustanelectroniccontrollerfor
DHW,pls.noteenclosedinstructionsfor electroniccontroller.
Scalingoftheplateheatexchanger.
Replace–rinseout.
Defectivemotorizedvalve.Check(usemanualfunction)–replace.
Defectivetemperaturesensors.
Check–replace.
ToolittleornoDHW .
Defectivecontroller.
Check–replace.
DCWisbeingmixedwiththeDHW,e.g.in adefectivethermostaticmixingvalve.
Check–replace. Hotwaterinsometapsbutnotinall.
Defectiveorcloggednon-returnvalveon circulationvalve.
Replace–clean.
Taptemperaturetoohigh;DHWtapload toohigh.
Thermostaticvalveadjustedtoatoohigh level.
Check–set.
Scalingoftheplateheatexchanger.
Replace–rinseout. Temperaturedropduringtapping.
LargerDHWowthanthesubstationhas beendesignedfor .
ReduceDHWow.
Thermostaticcontrolvalvedoesnotclose
TemperaturedifferencebetweenDH supplyandDHWsetpointtoolow.
Lowerthesetpointtemperatureor increasetheDHsupplytemperature.
DanfossDistrictEnergy
VI.CW.C3.02/L UK40110
DEN-GT
15
Page 16
InstallationGuideTermixVMTD-F-B
7.3TroubleshootingHE
ProblemPossiblecauseSolution
Toolittleornoheat.StrainercloggedinDHorHEcircuit
(radiatorcircuit).
Cleangate/strainer(s).
ThelterintheenergymeteronDHcircuit clogged.
Cleanthelter(afterconsultingtheDH plantoperator).
Defectiveorwronglyadjusteddifferential pressurecontroller.
Checktheoperationofthedifferential pressurecontroller–cleanthevalveseatif required.
Sensordefective–orpossiblydirtinthe valvehousing.
Checktheoperationofthethermostat– cleanthevalveseatifrequired.
Automaticcontrols,ifany,wronglysetor defective-possiblypowerfailure.
Checkifthesettingofthecontroller iscorrect–seeseparateinstructions. Checkthepowersupply.Temporary settingofmotorto“manual”control–see instructionsonautomaticcontrols.
Pumpoutofoperation.Checkifthepumpisreceivingpowerand
thatitturns.Checkifthereisairtrappedin thepumphousing–seepumpmanual.
Thepumpissetattoolowspeedof rotation.
Setthepumpathigherspeedofrotation.
Pressuredrop–thepressuredropon theradiatorcircuitshowslowerthan recommendedoperatingpressure.
Fillwateronthesystemandcheckthe functioningofthepressureexpansion vesselifrequired.
Airpocketsinthesystem.Venttheinstallationthoroughly.
Limitingofthereturntemperature adjustedtoolow.
Adjustaccordingtoinstructions.
Defectiveradiatorvalves.
Check–replace.
Unevenheatdistributioninbuilding becauseofincorrectlysetbalancingvalves, orbecausetherearenobalancingvalves.
Adjust/installbalancingvalves.
Diameterofpipetosubstationtoosmallor branchpipetoolong.
Checkpipedimensions.
Unevenheatdistribution.Airpocketsinthesystem.Venttheinstallationthoroughly.
DHsupplytemperaturetoohigh.
Wrongsettingofthermostatorof automaticcontrols,ifany.
Adjustautomaticcontrols,–see instructionsforautomaticcontrols.
Defectivecontroller.Thecontrollerdoes notreactasitshouldaccordingtothe instructions.
Callautomaticcontrolsmanufactureror replacetheregulator.
Defectivesensoronself-actingthermostat.
Replacethermostat–orsensoronly.
DHsupplytemperaturetoolow.
Wrongsettingofautomaticcontrols,ifany.
Adjustautomaticcontrols–seeinstructions forautomaticcontrols.
Defectivecontroller.Thecontrollerdoes notreactasitshouldaccordingtothe instructions.
Callinautomaticcontrolsmanufactureror replacecontroller.
Defectivesensoronself-actingthermostat.
Replacethermostat–orsensoronly.
Wrongplacement/ttingofoutdoor temperaturesensor.
Adjustlocationofoutdoortemperature sensor.
Strainerclogged.Cleangate/strainer.
16
DEN-GT
VI.CW.C3.02/L UK40110
DanfossDistrictEnergy
Page 17
InstallationGuideTermixVMTD-F-B
ToohighDHreturntemperature.
Toosmallheatingsurface/toosmall radiatorscomparedtothetotalheating requirementofthebuilding.
Increasetotalheatingsurface.
Poorutilizationofexistingheatingsurface. Defectivesensoronself-actingthermostat.
Makesuretheheatisdistributedevenly acrossthefullheatingsurface–openall radiatorsandkeeptheradiatorsinthe systemfromheatingupatthebottom.It isextremelyimportanttokeepthesupply temperaturetotheradiatorsaslowas possible,whilemaintainingareasonable levelofcomfort.
Thesystemissinglepipeloop.
Thesystemshouldfeatureelectronic controlsaswellasreturnsensors.
Pumppressuretoohigh.Adjustpumptoalowerlevel.
Airinsystem.
Ventthesystem.
Defectiveorincorrectlysetradiator valve(s).Singlepipeloopsystemsrequire specialone-piperadiatorvalves.
Check–set/replace.
Dirtinthemotorizedvalveorinthe differentialpressurecontroller.
Check–cleanout.
Defectivemotorizedvalve,sensoror automaticcontroller.
Check–replace.
Electroniccontrollernotadjustedcorrectly.Adjustaccordingtoinstructions.
Noiseinsystem.
Pumppressuretoohigh.Adjustpumptoalowerlevel.
Heatloadtoohigh.
Defectivemotorizedvalve,sensoror electroniccontroller.
Check–replace.
7.4Disposal
Disposal
Thisproductshouldbedismantledanditscomponents sorted,ifpossible,invariousgroupsbeforerecycling ordisposal.
Alwaysfollowthelocaldisposalregulations.
DanfossDistrictEnergy
VI.CW.C3.02/L UK40110
DEN-GT
17
Page 18
InstallationGuideTermixVMTD-F-B
18
DEN-GT
VI.CW.C3.02/L UK40110
DanfossDistrictEnergy
Page 19
InstallationGuideTermixVMTD-F-B
8.0Declaration
8.1Declarationofconformity
8.1.1Category0withelectricalequipment
EC–DeclarationofConformity
GeminaT ermixA/S MemberoftheDanfossGroup Navervej15-17 DK-7451Sunds
Declaresonoursoleresponsibilitythatthebelowproducts:
Substations–Category0withelectricalequipment,
coveredbythisdeclarationareinconformitywiththefollowingdirectives,standardsandothernormative documents,providedthattheyareusedaccordingtoourinstructions.
MachineryDirective2006/42/EC
DS/EN60204-1/A1:2009.Safetyofmachinery– Part1–GeneralRequirements. DS/EN12100:2011.Safetyofmachinery–Risk assessment.
LVD–LowVoltageDirective–2006/95/EC
DS/EN60204-1/A1:2009.Safetyofmachinery– Part1–GeneralRequirements.
EMC–Directive–2004/108/EC
DS/EN61000-6-2/Corr.:2005.Electromagnetic compatibility–Genericstandard:Immunity industry. DS/EN61000-6-3:2007.Electromagnetic compatibility–Genericstandard:Emissionfor residential,commercial&lightindustry.
Sunds–2014.01.31
PlaceanddateofissueClausGjøderumMortensen
Quality&EnvironmentManager
DanfossDistrictEnergy
VI.CW.C3.02/L UK40110
DEN-GT
19
Page 20
InstallationGuideTermixVMTD-F-B
ProducedbyDanfossA/S©09/2014