Danfoss TERMIX PM2+P Installation Manual

InstallationGuide
TermixWaterheater–PM2+P
1.0TableofContents
1.0TableofContents.............................................1
........................................................................2
2.0Functionaldescription......................................3
3.0Safetynotes.....................................................4
4.0Mounting........................................................5
4.1Mounting...........................................................5
5.0Design.............................................................6
5.1Design...............................................................6
5.2Schematicdiagram................................................7
6.0Controls..........................................................9
6.1DHWtemperaturecontrol........................................9
6.2Maintenance........................................................10
7.0Troubleshooting..............................................11
7.1Troubleshootingingeneral......................................11
7.2TroubleshootingDHW............................................11
7.3Disposal.............................................................12
8.0Declaration......................................................15
8.1Declarationofconformity........................................15
DanfossDistrictEnergy
VI.GE.O2.02/LUK38042
DEN-GT
1
InstallationGuideTermixWaterheater–PM2+P
2
DEN-GT
VI.GE.O2.02/LUK38042
DanfossDistrictEnergy
InstallationGuideTermixWaterheater–PM2+P
2.0Functionaldescription
Instantaneouswaterheaterwithheatexchangerand owcompensatedtemperaturecontroller.Designedfor wall-mounting.
Application
TheT ermixWaterheaterisaninstantaneouswaterheaterfeaturing superbheatextractionandhighperformance.TheTermixWater heaterissuitableforats,single-familyhousesaswellasforsmall apartmentbuildings.Thewaterheaterisavailableintwosizes, eitherfor1apartment,orupto4apartments.TheTermixWater heaterisapplicablefordecentralizedheatingsystems.Theheat exchangerintheTermixWaterheatercoolsthedistrictheating waterveryefciently,therebycreatingaverygoodoperation economy.
Domestichotwater(DHW)
Thedomestichotwaterispreparedintheheatexchangerandthe temperatureisregulatedbyaowcontrollerwithaintegrated differentialpressurecontroller.
DanfossDistrictEnergy
VI.GE.O2.02/LUK38042
DEN-GT
3
InstallationGuideTermixWaterheater–PM2+P
3.0Safetynotes
3.1SafetyNotes–general
Thefollowinginstructionsrefertothestandarddesignof substation.Specialversionsofsubstationsareavailableon request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation andstart-upofthesubstation.Themanufactureracceptsno liabilityfordamageorfaultsthatresultfromnon-compliancewith theoperatingmanual.Pleasereadandfollowalltheinstructions carefullytopreventaccidents,injuryanddamagetoproperty. Assembly,start-upandmaintenanceworkmustbeperformedby qualiedandauthorizedpersonnelonly. Pleasecomplywiththeinstructionsissuedbythesystem manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass. Themaximumchloridecompoundsoftheowmediumshouldnot behigherthan150mg/l. Theriskofequipmentcorrosionincreasesconsiderablyifthe recommendedlevelofpermissiblechloridecompoundsis exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary sourceofenergy.However,alsootherenergysourcescanbeused wheretheoperatingconditionsallowitandalwaysarecomparable todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse installationinafrost-freeroom,wherethetemperaturedoesnot exceed50°Candthehumiditydoesnotexceed60%.Donotcover orwallupthesubstationorinanyotherwayblocktheentrance tothestation.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat thesubstationcanbeseparatedfromallenergysources(also powersupply).
Emergency
Incaseofdangeroraccidents-re,leaksorotherdangerous circumstances-interruptallenergysourcestothestationif possible,andseekexperthelp. Incaseofdiscolouredorbad-smellingdomestichotwater,closeall shut-offvalvesonthesubstation,informtheoperatingpersonnel andcallforexperthelpimmediately.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto installationshouldbeinconditionswhicharedryandheated.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallation’ spermissiblesystempressureand temperature.
Themaximumtemperatureoftheowmediuminthesubstationis 120°C.
Themaximumoperatingpressureofthesubstationis10bar.PN16 versionsareavailableonenquiry.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases considerablyiftherecommendedpermissibleoperatingparameters areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves, however,alwaysinaccordancewithlocalregulations.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns. Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen position.Thesurfacesofthesubstationcangethot,whichcancause skinburns.Theballvalvesondistrictheatingsupplyandreturnshould beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallangeconnections,screwjoints andelectricalclampandscrewconnectionsmustbecheckedand tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen addedtothesystemandthesystemhasbeenputintooperation, re-tightenALLconnections.
4
DEN-GT
VI.GE.O2.02/LUK38042
DanfossDistrictEnergy
InstallationGuideTermixWaterheater–PM2+P
4.0Mounting
4.1Mounting
Installationmustbeincompliancewithlocalstandardsand regulations. Districtheating(DH)-Inthefollowingsections,DHreferstothe heatsourcewhichsuppliesthesubstations.Avarietyofenergy sources,suchasoil,gasorsolarpower,couldbeusedasthe primarysupplytoDanfosssubstations.Forthesakeofsimplicity, DHcanbetakentomeantheprimarysupply.
Connections:
1.Domesticcoldwater(DCW)
2.Domestichotwater(DHW)
3.Districtheating(DH)supply
4.Districtheating(DH)return
Connectionsizes:
DH:
G¾”(ext.thread)
DCW+DHW:
G¾”(ext.thread)
Dimensions(mm):
Type1+2withinsulation: H450xW300xD155 Type1+2withcover: H470xW315xD155
Weightincl.cover:7–9kg(incl.packing)
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualiedandauthorizedpersonnelonly.
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote themarkingsonthestation.
DanfossDistrictEnergy
VI.GE.O2.02/LUK38042
DEN-GT
5
InstallationGuideTermixWaterheater–PM2+P
5.0Design
5.1Design
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
B
Heatexchanger,DHW
9
Strainer
73
PM2+Pcontroller,DHW
6
DEN-GT
VI.GE.O2.02/LUK38042
DanfossDistrictEnergy
InstallationGuideTermixWaterheater–PM2+P
5.2Schematicdiagram
DHW
DCW
DH
Supply
DH
Return
GTU. Maynotbeappliedtostationswithhotwater circulation.
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
SchematicdescriptionwithPM2+P–withGTU
B
Heatexchanger,DHW
62
GTUPressureequalizer
63
Sieve
73
PM2+Pcontroller
DHW
DCW
DH
Supply
DH
Return
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
SchematicdescriptionwithPM2+P–withsafetyvalve
B
Heatexchanger,DHW
2
Singlecheckvalve
4
Safetyvalve
63
Sieve
73
PM2+Pcontroller
DanfossDistrictEnergy
VI.GE.O2.02/LUK38042
DEN-GT
7
InstallationGuideTermixWaterheater–PM2+P
DHW:DomesticHotWater DCW:
DomesticColdWater
DHSupply:DistrictHeatingSupply DHReturn:DistrictHeatingReturn
5.2.1Technicalparameters
Technicalparameters
Nominalpressure:PN10(PN16versionsareavailableonenquiry) Max.DHsupplytemperature:
120°C
Min.DCWstaticpressure:
0.5bar
Brazingmaterial(HEX):
Copper Heatexchangerstestpressure:30bar Soundlevel:≤55dB
8
DEN-GT
VI.GE.O2.02/LUK38042
DanfossDistrictEnergy
InstallationGuideTermixWaterheater–PM2+P
6.0Controls
6.1DHWtemperaturecontrol
DHWtemperaturecontrol
TherearevarioustypesofDHWtemperaturecontrolusedin Danfosssubstations. DHWtemperatureshouldbeadjustedto45-50°C,asthisprovides optimalutilisationofDHwater.AtDHWtemperaturesabove55°C, thepossibilityoflimescaledepositsincreasessignicantly.
6.1.1PM2+Pcontroller
PM2+Pisaself-actingproportionalowcontrollerwithintegrated differentialpressurecontroller. ThePM2+PoperatesatitsbestatDHsupplytemperaturesofupto 100°C. Byturningthehandlefortemperaturesetting,theindicatorof temperaturesettingmovestowardsredorbluedot.Thismeans thattemperaturesettingisincreasedordecreased.
6.1.2Safetyvalve
Thepurposeofthesafetyvalveistoprotectthesubstationfrom excessivepressure. Theblow-offpipefromthesafetyvalvemustnotbeclosed.The blow-offpipeoutletshouldbeplacedsothatitdischargesfreely anditispossibletoobserveanydrippingfromthesafetyvalve. Itisrecommendedtochecktheoperationofsafetyvalvesat intervalsof6months.Thisisdonebyturningthevalveheadin directionindicated.
6.1.3Strainer
Strainersshouldbecleanedregularlybyauthorizedpersonnel.The frequencyofcleaningwoulddependonoperatingconditionsand themanufacturer’sinstructions.
DanfossDistrictEnergy
VI.GE.O2.02/LUK38042
DEN-GT
9
InstallationGuideTermixWaterheater–PM2+P
6.1.4GTUPressureEqualizer
TheGTUPressureEqualizerabsorbstheexpansiononthe secondarysideoftheTermixWaterheatersandcanbeusedasa substitutetothesafetyvalve. Furthermorethepressureequalizerabsorbsapossibleincreasein pressure,soadischargeoutletisomitted. TheGTUPressureEqualizermaynotbeappliedinsystemswithhot watercirculation.
6.1.5IdlecontrollerFJVR(10-80°C)
Theidlecontrollercankeeptheapplicationoronlythesupplyline pre-heatedatnoload.
6.2Maintenance
Thesubstationrequireslittlemonitoring,apartfromroutine checks.Itisrecommendedtoreadtheenergymeteratregular intervals,andtowritedownthemeterreadings.
RegularinspectionsofthesubstationaccordingtothisInstruction arerecommended,whichshouldinclude:
Strainers
Cleaningofstrainers.
Meters
Checkingofalloperatingparameterssuchasmeterreadings.
Temperatures
Checkingofalltemperatures,suchasDHsupplytemperatureand DHWtemperature.
Connections
Checkingallconnectionsforleakages.
Safetyvalves
Theoperationofthesafetyvalvesshouldbecheckedbyturning thevalveheadintheindicateddirection.
Venting
Checkingthatthesystemisthoroughlyvented.
Inspectionsshouldbecarriedoutminimumeverytwoyears.
SparepartscanbeorderedfromDanfoss.Pleaseensurethatany enquiryincludesthesubstationserialnumber.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualiedandauthorizedpersonnelonly.
10
DEN-GT
VI.GE.O2.02/LUK38042
DanfossDistrictEnergy
InstallationGuideTermixWaterheater–PM2+P
7.0Troubleshooting
7.1Troubleshootingingeneral
Intheeventofoperatingdisturbances,thefollowingbasicfeatures shouldbecheckedbeforecarryingoutactualtroubleshooting:
thesubstationisconnectedtoelectricity,
thestrainerontheDHsupplypipeisclean,
thesupplytemperatureoftheDHisatthenormallevel (summer,atleast60°C-winter,atleast70°C),
thedifferentialpressureisequaltoorhigherthanthenormal (local)differentialpressureintheDHnetwork–ifindoubt,ask theDHplantsupervisor,
pressureonthesystem-checktheHEpressuregauge.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualiedandauthorizedpersonnelonly.
7.2TroubleshootingDHW
ProblemPossiblecauseSolution
Strainerinsupplyorreturnlineclogged.Cleanstrainer(s).
DHWcirculationpumpoutoforderorwith toolowsetting.
Checkcirculationpump.
Defectiveorcloggednon-returnvalve.
Replace–clean.
Noelectricity.Check.
Wrongsettingofautomaticcontrols,ifany.Toadjustanelectroniccontrollerfor
DHW,pls.noteenclosedinstructionsfor electroniccontroller.
Scalingoftheplateheatexchanger.
Replace–rinseout.
Defectivemotorizedvalve.Check(usemanualfunction)–replace.
Defectivetemperaturesensors.
Check–replace.
ToolittleornoDHW.
Defectivecontroller.
Check–replace.
DCWisbeingmixedwiththeDHW,e.g.in adefectivethermostaticmixingvalve.
Check–replace.
Hotwaterinsometapsbutnotinall.
Defectiveorcloggednon-returnvalveon circulationvalve.
Replace–clean.
Taptemperaturetoohigh;DHWtapload toohigh.
Thermostaticvalveadjustedtoatoohigh level.
Check–set.
Scalingoftheplateheatexchanger.
Replace–rinseout.
Temperaturedropduringtapping.
LargerDHWowthanthesubstationhas beendesignedfor .
ReduceDHWow.
Thermostaticcontrolvalvedoesnotclose
TemperaturedifferencebetweenDH supplyandDHWsetpointtoolow.
Lowerthesetpointtemperatureor increasetheDHsupplytemperature.
DanfossDistrictEnergy
VI.GE.O2.02/LUK38042
DEN-GT
11
InstallationGuideTermixWaterheater–PM2+P
7.3Disposal
Disposal
Thisproductshouldbedismantledanditscomponents sorted,ifpossible,invariousgroupsbeforerecycling ordisposal.
Alwaysfollowthelocaldisposalregulations.
12
DEN-GT
VI.GE.O2.02/LUK38042
DanfossDistrictEnergy
InstallationGuideTermixWaterheater–PM2+P
DanfossDistrictEnergy
VI.GE.O2.02/LUK38042
DEN-GT
13
InstallationGuideTermixWaterheater–PM2+P
14
DEN-GT
VI.GE.O2.02/LUK38042
DanfossDistrictEnergy
InstallationGuideTermixWaterheater–PM2+P
8.0Declaration
8.1Declarationofconformity
Declarationofcompliance
We:
GeminaT ermixA/S MemberoftheDanfossGroup Navervej15-17 DK-7451Sunds
doherebyonourownresponsibilitydeclarethatthefollowingproducts:
TermixSubstations
coveredbythisdeclarationisinconformitywiththefollowingdirective(s), standard(s)orothernormativedocument(s), providedthattheproductsareusedinaccordancewithourinstructions.
EUDirectives:
MachineryDirective2006/42/EEC
ENISO14121-1Safetyofmachinery-Riskassessment EN60204-1Safetyofmachinery-Electricalequipmentofmachines
EMCDirective2004/108/EEC
EN61000-6-22007Electromagneticcompatibility
-Genericstandard:Immunityindustry EN61000-6-32007Electromagneticcompatibility
-Genericstandard:Emissionforresidential,commercialandlightindustry
PEDDirective97/23/EEC
AllsubstationsthatfallsunderArticle3.3andcategory1shallnotbeCE-marked accordingtothisdirective,howeverallessentialsafetyrequirementsfromthe PEDDirective97/23/EECarefollowedtoensurehydraulicsafety
Thisdeclarationisimmediatelyannulled,iftheproductisinterferedwithinanyway, whichinterfereswiththeabovementioneddirectivesandstandards, withoutthewrittenconsentfromGeminaT ermixA/S.
2010.01.05—Sunds
Timeandplace
LarsGinnerup
Responsibleforquality
DanfossDistrictEnergy
VI.GE.O2.02/LUK38042
DEN-GT
15
InstallationGuideTermixWaterheater–PM2+P
ProducedbyDanfossA/S©01/2012