Danfoss Termix One Solar Fact sheet

Fact sheet
Termix One Solar
Domestic hot water module for flats, single-family houses and apartment buildings with up to 10 apartments
Application
The Termix One Solar is an instanta­neous water heater, featuring superb heat extraction and high performance. The Termix One Solar is applicable for heating systems with buffer accu­mulators, solar systems or for other heat sources, where a very low return temperature is preferred. The water heater is available in three sizes, either for 1 apartment, for 1-4 apartments or for 5 up to 10 apartments. The large heat exchanger cools out the water in the primary return line very effi­ciently, thereby creating a very good operation economy. A flow switch in cold water mains is controlling the primary heating pump. An optional circulation pump together with a ther­mostat can maintain the circulating temperature at a desired temperature.
Domestic hot water (DHW)
The domestic hot water is prepared in the heat exchanger and the tempera­ture is regulated with a thermostatic control valve. The patented sensor accelerator accelerates the closing of the thermostatic control valve and protects the heat exchanger against
overheating and lime scale formation. The sensor accelerator and the ther­mostatic control valve also works as a bypass keeping the heat exchanger and supply line warm. This shortens the waiting periods. The sensor ac­celerator helps to ensure a stable hot water temperature by varying loads, flow temperatures and differential pressure without the need for read­justing the valve. There is no addi­tional pressure loss on the secondary side of the DHW heat exchanger with a thermostatic control. Therefore this type of regulation can be used by low pressure in the cold water mains.
Options
The water heater can be supplied with built in non-return valve and safety valve mounted in the cold water supply.
Construction
All pipes are made of stainless steel. The connections are made by nuts and gaskets. The Termix One Solar is delivered with an attractive steel grey cover in modern design, emphasising the high level of quality and comfort which characterises this product.
FEATURES AND BENEFITS
• Domestic hot water module
• DHW regulation with an accelerated thermostatic control
• Capacity: Up to 90 kW on DHW
• DHW in sufficient quantity
• Operates independent of differential pressure and flow temperature
• Minimum space required for installation
• Pipes and plate heat exchanger made of stainless steel
• Minimized risk of lime scale and bacteria formation
www.danfoss.com
CIRCUIT DIAGRAM - EXAMPLE
BT
supply
BT
return
BT
supply
BT
return
DHW
DCW
DHW
Cirk.
DCW
Termix One Solar O Termix Sensor Accelerator
B Plate heat exchanger DHW 1 Ball valve 2 Single check valve 7 Thermostatic valve 13 Charging pump 35 Ball valve / non-return
valve
Termix One Solar – with circulation
O Termix Sensor Accelerator B Plate heat exchanger DHW 1 Ball valve 2 Single check valve 4 Safety valve 7 Thermostatic valve 11 Circulation pump DHW 13 Charging pump
39 Connection closed 45 Flow switch 48 Air vent, manual 63 Sieve
24 Delivered
loose with unit
35 Ball valve
/ non-return valve 39 Connection closed 45 Flow switch 48 Air vent, manual 63 Sieve
Technical parameters:
Nominal pressure: PN 16 DH supply temperature: T DCW static pressure: p Brazing material (HEX): Copper
Weight incl. cover: 20 kg
Cover: Grey-lacquered steel
Dimensions (mm):
Without cover: H 770 × B 300 × T 160 With cover: H 770 × B 315 × T 165 With circulation: Without cover: H 960 × B 400 × T 190 With cover: H 960 × B 400 × T 190
CAPACITY, WEIGHT AND DIMENSIONS
DHW: CAPACITY EXAMPLES, 10°C / 50°C
Substation type
Type 1
w/AVTB 15
1 household
Type 3
w/AVTB 20
5 to 10* households
* Capacity for 10 households at 70 °C DH flow temperature
(incl. packing)
sheet
DHW
Capacity
[kW]
29,3 60 23,0 20 630 38,2 60 25,2 45 822 47,1 60 26,8 45 1014 37,8 70 20,0 20 816 45,1 70 21,3 20 972 52,3 70 22,4 45 1128 65,6 70 23,8 45 1410
60 60 23,0 35 1280 66 60 24,0 45 1426 – 80 70 20,3 35 1730 – 90 70 21,0 45 1940
= 120 °C
max
= 0,5 bar
min
Supply
flow
Primary
[°C]
Primary
Connections:
1 Domestic cold water (DCW) 2 Domestic hot water (DHW) 3 Buffer tank (BT) supply 4 Buffer tank (BT) return 5 Circulation
Return
flow
[°C]
Pressure
loss
Primary
[kPa]
Seen from above
Flow
rate
Secondary
[l/h]
Wall
Substation type
Type 2
w/AVTB 20
up to 4 households
Connections sizes:
All connections: G ¾” (int. thread)
Options:
Circulation set for Termix One Solar
DHW
Capacity
[kW]
34,7 60 24,4 20 744
Supply
flow
Primary
[°C]
Return
flow
Primary
[°C]
Pressure
loss
Primary
[kPa]
Flow
rate
Secondary
[l/h]
© Danfoss | DCS-SGDPT/ PL | 2021 . 08