Danfoss Termix One-B-FI Fact sheet

Fact sheet
Termix One-B-FI
Instantaneous water heater for flats, single-family houses and small apartment buildings with up to 4 flats
Application
The Termix One is an instantaneous water heater featuring superb heat extraction and high performance. The Termix One is suitable for flats, single-family houses as well as for small apartment buildings with up to 4 apartments. The water heater is available in two sizes, either for 1 apartment or for 1-4 apartments. The Termix One is applicable for decentralized heating systems – as well as for district heating networks with summer operation at low temperatures or changes in differ­ential pressure. The Termix One heat exchanger cools the district heating water very efficiently, thereby creat­ing a very good operation economy.
Domestic hot water (DHW)
The domestic hot water is prepared in the heat exchanger and the temperature is regulated with a ther­mostatic control valve. The patented sensor accelerator accelerates the closing of the Danfoss AVTB valve and protects the heat exchanger against overheating and lime scale forma-
tion. The sensor accelerator and AVTB valve also works as a bypass keeping the house supply line warm. This shortens the waiting periods during summer when the heating system is in reduced operation. The sensor accelerator helps to ensure a stable hot water temperature by varying loads, flow temperatures and differential pressure without the need for readjusting the valve. There is no additional pressure loss on the secondary side of the DHW heat exchanger with a thermostatic control. Therefore this type of regu­lation can be used by low pressure on the in the cold water mains.
Construction
All pipes are made of stainless steel. The connections are made by nuts and gaskets. The Termix One comes with a complete fully insulated cover thus minimizing the heat loss both during tapping of domestic hot water but also in standby mode.
FEATURES AND BENEFITS
• Instantaneous water heater
• DHW regulation with an accelerated thermostatic control
• Capacity: up to 29 – 45 kW on DHW
• DHW in sufficient quantity
• Operates independently of differential pressure and flow temperature
• Minimum space required for installation
• Pipes and plate heat exchanger made of stainless steel
• Minimized risk of lime scale and bacteria formation
• Low heat loss
www.danfoss.com
CIRCUIT DIAGRAM – EXAMPLE
Termix One-B with complete insulation
B Plate heat exchanger DHW 7 Thermostatic valve
DH
supply
DH
return
Technical parameters:
Nominal pressure: PN 16 DH supply temperature: T DCW static pressure: p Brazing material (HEX): Copper
= 120 °C
max
= 0,5 bar
min
Weight: 10 – 12 kg
(incl. packing)
Dimensions (mm):
H 435 × W 355 × D 195 (type 1+2)
Connections sizes:
DH + DCW + DHW: G ¾” (ext. thread)
Connections:
1 Domestic cold water (DCW) 2 Domestic hot water (DHW) 3 District heating (DH) supply 4 District heating (DH) return
Wall
Seen from above
DHW
DCW
Options:
• Booster pump (increases DH flow)
• Safety valve and non-return valve (10 bar)
• Safety valve with thermostatic circulation set
• Thermostatic circulation set
• Non-return and pressure equalizer (GTU)
DHW: CAPACIT Y EXAM PLES, 10°C / 50°C
DHW
Substation type
Type 1
w/AVTB 15
1 household
capacity
Supply flow
primary
[kW]
29,3 60 23,0 20 630 38,2 60 25,2 45 822 47,1 60 26,8 45 1014 37,8 70 20,0 20 816 45,1 70 21,3 20 972
© Danfoss | DCS-SDGPT/ PL | 2021. 08
Return flow
[°C]
primary
[°C]
Pressure
loss primary
[kPa]
Flow rate
secondary
[l/h]
Substation type
Type 2
w/AVTB 20
up to 4 households
DHW
capacity
Supply flow
primary
[kW]
34,7 60 24,4 20 744
[°C]
Return flow
primary
[°C]
Pressure
loss primary
[kPa]
AM195786467432en-020301
Flow rate
secondary
[l/h]
Loading...