Danfoss Termix HD MIX Compact 28 Installation Manual

Page 1
InstallationGuide
TermixHDMIXCompact28
1.0TableofContents
1.0TableofContents.............................................1
2.0Functionaldescription......................................2
3.0Safetynotes.....................................................3
3.1SafetyNotes–general............................................3
4.0Mounting........................................................4
4.2Start-up..............................................................6
4.3Electricalconnections.............................................7
5.0Design.............................................................8
5.1Design...............................................................8
6.0Controls..........................................................10
6.1Heatingcircuit......................................................10
6.2Other.................................................................12
6.3Maintenance........................................................14
7.0Troubleshooting..............................................15
7.1Troubleshootingingeneral......................................15
7.2TroubleshootingHE...............................................15
7.3Disposal.............................................................16
8.0Declaration......................................................19
8.1Declarationofconformity........................................19
DanfossDistrictEnergy
VI.GP .E1.02/LUK42860
DEN-GT
1
Page 2
InstallationGuideTermixHDMIXCompact28
2.0Functionaldescription
Districtheatingsubstationfordirectheatingwithmixingloop.
Application
TheTermixHDMIXCompact28isacompletesolutionfor spaceheatingwithoptimalsafety,efcientenergytransfer, service-friendlyconstructionandacompactdesign.
Districtheating(DH)
Thedistrictheatingcircuitisprefabricatedwithaowcontroller withintegratedcontrolvalve,thermometersandballvalves.
Heating(HE)
Theheatingcircuitconsistsofthermometers,ballvalves,drain valve,airvalveandcirculationpump.Theheatingtemperaturecan becontrolledthermostaticallyorbyanelectroniccontrollerwith anoutdoortemperaturesensor.
2
DEN-GT
VI.GP .E1.02/LUK42860
DanfossDistrictEnergy
Page 3
InstallationGuideTermixHDMIXCompact28
3.0Safetynotes
3.1SafetyNotes–general
Thefollowinginstructionsrefertothestandarddesignof substation.Specialversionsofsubstationsareavailableon request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation andstart-upofthesubstation.Themanufactureracceptsno liabilityfordamageorfaultsthatresultfromnon-compliancewith theoperatingmanual.Pleasereadandfollowalltheinstructions carefullytopreventaccidents,injuryanddamagetoproperty. Assembly,start-upandmaintenanceworkmustbeperformedby qualiedandauthorizedpersonnelonly. Pleasecomplywiththeinstructionsissuedbythesystem manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass. Themaximumchloridecompoundsoftheowmediumshouldnot behigherthan150mg/l. Theriskofequipmentcorrosionincreasesconsiderablyifthe recommendedlevelofpermissiblechloridecompoundsis exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary sourceofenergy.However,alsootherenergysourcescanbeused wheretheoperatingconditionsallowitandalwaysarecomparable todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse installationinafrost-freeroom,wherethetemperaturedoesnot exceed50°Candthehumiditydoesnotexceed60%.Donotcover orwallupthesubstationorinanyotherwayblocktheentrance tothestation.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat thesubstationcanbeseparatedfromallenergysources(also powersupply).
Emergency
Incaseofdangeroraccidents-re,leaksorotherdangerous circumstances-interruptallenergysourcestothestationif possible,andseekexperthelp. Incaseofdiscolouredorbad-smellingdomestichotwater,closeall shut-offvalvesonthesubstation,informtheoperatingpersonnel andcallforexperthelpimmediately.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto installationshouldbeinconditionswhicharedryandheated.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallation’ spermissiblesystempressureand temperature.
Themaximumtemperatureoftheowmediuminthesubstationis 120°C.
Themaximumoperatingpressureofthesubstationis10bar.PN16 versionsareavailableonenquiry.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases considerablyiftherecommendedpermissibleoperatingparameters areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves, however,alwaysinaccordancewithlocalregulations.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns. Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen position.Thesurfacesofthesubstationcangethot,whichcancause skinburns.Theballvalvesondistrictheatingsupplyandreturnshould beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallangeconnections,screwjoints andelectricalclampandscrewconnectionsmustbecheckedand tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen addedtothesystemandthesystemhasbeenputintooperation, re-tightenALLconnections.
DanfossDistrictEnergy
VI.GP .E1.02/LUK42860
DEN-GT
3
Page 4
InstallationGuideTermixHDMIXCompact28
4.0Mounting
4.1Mounting
Installationmustbeincompliancewithlocalstandardsand regulations. Districtheating(DH)-Inthefollowingsections,DHreferstothe heatsourcewhichsuppliesthesubstations.Avarietyofenergy sources,suchasoil,gasorsolarpower,couldbeusedasthe primarysupplytoDanfosssubstations.Forthesakeofsimplicity, DHcanbetakentomeantheprimarysupply.
Connections:
1.Districtheating(DH)supply
2.Districtheating(DH)return
3.Heating(HE)supply
4.Heating(HE)return
Connectionsizes:
DH+HE:
G1”(int.thread)
Dimensions(mm):
Withoutcover:
H970xW620xD420
Withcover:
H970xW640xD522
Weight(approx.):50kg
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualiedandauthorizedpersonnelonly.
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote themarkingsonthestation.
4
DEN-GT
VI.GP .E1.02/LUK42860
DanfossDistrictEnergy
Page 5
InstallationGuideTermixHDMIXCompact28
4.1.1Installation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes andlabelsareplacedcorrectly.Ifyouwishtomountthestation differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe cleanedandrinsed.
Thightening
Duetovibrationduringtransport,allsubstationconnectionsmust becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha plug.Shouldtheplugsrequireremoval,thismustonlybedoneby anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbettedaccording toschematicdiagram.Pleasenotethatthestrainermaybe suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe madeusingthreaded,angedorweldedconnections.
Keyholeformounting.
DanfossDistrictEnergy
VI.GP .E1.02/LUK42860
DEN-GT
5
Page 6
InstallationGuideTermixHDMIXCompact28
4.2Start-up
Start-up,Heatingwithmixingloop
Start-up:
1:Pumpspeed
Setthepumptohighestspeedbeforestart-up.
2:Startpump
Startthepumpandheatthroughthesystem.
3:Openshut-offvalves
Theshut-offvalvesshouldthenbeopenedandtheunitobserved asitentersservice.Visualcheckingshouldconrmtemperatures, pressures,acceptablethermalexpansionandabsenceofleakage. Ifthesystemoperatesinaccordancewithdesign,itcanbeput toregularuse.
4:Ventsystem
Switchoffthepumpandventtheinstallationaftertheradiators havebeenwarmedup.
5:Adjustpumpspeed
Setthepumptothelowestspeedconsistentwithcomfortand electricityconsumption. Normallythechange-overswitchissetinthemidposition(default). Howeverforsystemswithunderoorheatingorsinglepipeloop systems,itmaybenecessarytoturnthechange-overswitch upwards. Higherpumpspeedsareonlyusediftheheatingrequirement increases.
Re-thightenconnections
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen putintooperation,re-tightenALLconnections.
Pump
Thepumpmustbeswitchedoffduringsystemll.
Underoorheating:
Pumpstopfunction
Ifthesubstationisusedinconnectionwithunderoorheating,the circulationpumpmustbeconnectedtothepumpstopfunctionin theunderoorheatingcontroller.Thepumpmustbestoppedif allunderoorheatingcircuitsareclosed.
Warranty
Ifthisisnotpossible,thenowmustbecontinuedthroughthe by-pass.Failingthis,thepumpwillbeatriskofseizureandany remainingwarrantywillbewithdrawn.
Summeroperation:
Switchoffpump
Insummerthecirculationpumpmustbeswitchedoffandthe shut-offvalvetoHEsupplyclosed.
Runningpumpbi-weekly
Itisrecommendedtostartupthecirculationpump(for2minutes) onceamonthduringsummer;theshut-offvalveoftheHEsupply mustbeshut.
Electroniccontroller
Mostelectroniccontrollerswillstartupthepumpautomatically (pleasenotemanufacturer´sinstructions).
6
DEN-GT
VI.GP .E1.02/LUK42860
DanfossDistrictEnergy
Page 7
InstallationGuideTermixHDMIXCompact28
4.3Electricalconnections
Beforemakingelectricalconnections,pleasenotethe following:
Safetynotes
Pleasereadtherelevantpartsofthesafetynotes.
230V
Thesubstationmustbeconnectedto230VACandearth.
Disconnection
Thesubstationmustbeelectricallyconnectedsothatitcanbe disconnectedforrepairs.
Outdoortemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto directsunlight.Theyshouldnotbeplacedclosetodoors,windows orventilationoutlets.
Theoutdoorsensormustbeconnectedtothestationonthe terminalblockundertheelectroniccontrol.
Authorizedelectrician
Electricalconnectionsmustbemadebyanauthorizedelectricianonly.
Localstandards
Electricalconnectionsmustbemadeinaccordancewithcurrent regulationsandlocalstandards.
DanfossDistrictEnergy
VI.GP .E1.02/LUK42860
DEN-GT
7
Page 8
InstallationGuideTermixHDMIXCompact28
5.0Design
5.1Design
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
F
Electroniccontroller
14
Sensorpocket,energymeter
29
2-waymotorizedvalve
2
Singlecheckvalve
20
Filling/drainvalve
31
Differentialpressurecontroller
9
Strainer
25
Pressuregaugewithballvalve
41
Fittingpiece,energymeter
10
Circulatorpump
27
Actuator,HE
48
Airvent,manual
8
DEN-GT
VI.GP .E1.02/LUK42860
DanfossDistrictEnergy
Page 9
InstallationGuideTermixHDMIXCompact28
5.2Schematicdiagram
DH
Supply
HE Supply
DH
Return
HE Return
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
F
Electroniccontroller
16
Outdoorsensor
27
Actuator
1
Ballvalve
18
Thermometer
29
2-waymotorizedvalve
2
Singlecheckvalve
19
Surfacesensor
31
Differentialpressurecontroller
9
Strainer
20
Filling/drainvalve
41
Fittingpiece,energymeter
10
Circulationpump
24
Deliveredloosewithunit
48
Airvent,manual
14
Sensorpocket,energymeter
25
Pressuregaugewithballvalve
DHSupply:DistrictHeatingSupply DHReturn:DistrictHeatingReturn HESupply:HeatingSupply HEReturn:HeatingReturn
5.2.1Technicalparameters
Technicalparameters
Nominalpressure:
PN16
Max.DHsupplytemperature:
120°C
Soundlevel:≤55dB
DanfossDistrictEnergy
VI.GP .E1.02/LUK42860
DEN-GT
9
Page 10
InstallationGuideTermixHDMIXCompact28
6.0Controls
6.1Heatingcircuit
6.1.1Differentialpressurecontroller
Thedifferentialpressurecontrollersmoothsouttheuctuationsin pressurearrivingfromthedistrictheatingnetwork.Theoperating pressureinthesubstationisthusheldsteady.
6.1.2AVTBcontroller(30–100°)
Thetemperaturesettingisasfollows: 1=35°C 2=55°C 3=75°C 4=95°C 5=100°C
Thevaluesareintendedasaguide.
Thermostaticcontrol
ThetemperatureoftheHEowlineisadjustedasfollows: Toincreasetemperature,turnthehandleonthethermostatic controllertoselectahighernumber. Todecreasetemperature,turnthehandleonthethermostatic controllertoselectalowernumber.
10
DEN-GT
VI.GP .E1.02/LUK42860
DanfossDistrictEnergy
Page 11
InstallationGuideTermixHDMIXCompact28
6.1.3Flowcontrollerwithintegratedcontrolvalve
Thecontrollerisaself-actingowcontrollerwithintegratedcontrol valve.Thecontrollercloseswhensetmax.owisexceededand canbeusedincombinationwithDanfosselectricalactuatorswith orwithoutsafetyfunction.Springreturnmotorcanbeusedas safetyfunctionbypowerfailure.
6.1.4Electric2–waymotorizedvalve
Actuatorswithorwithoutsafetyfunctionareavailablefor3-point controls.Spring-returnactuatorscanbeusedtoprovidesafety shut-offintheeventofpowerfailure.
6.1.5Electroniccontrol
Substationswithelectroniccontrolmustbesetinaccordancewith manufacturer´sinstructions. Wheretheroomtemperatureiscontrolledbyradiatorthermostats, itisrecommendedthatthermostatsbesetforminimum temperatureineachroom.
DanfossDistrictEnergy
VI.GP .E1.02/LUK42860
DEN-GT
11
Page 12
InstallationGuideTermixHDMIXCompact28
6.1.6Outdoortemperaturesensor(ESMT)
Outdoorsensorsshouldbemountedsoastoavoidexposureto directsunlight.Theyshouldnotbeplacedclosetodoors,windows orventilationoutlets.
6.1.7Circulationpump
TheGrundfosMAGNArangeisdesignedforheating,district heatinganddomestichotwatersupplyinbuildingsonanyscale. TheMAGNAsarespeed-controlledpumpswithbuilt-inintelligence thatletsthemanalyzecurrentconditionsandadjusttheir performanceaccordingly. EnergylabellingclassA
6.2Other
6.2.1Strainer
Strainersshouldbecleanedregularlybyauthorizedpersonnel.The frequencyofcleaningwoulddependonoperatingconditionsand themanufacturer’sinstructions.
12
DEN-GT
VI.GP .E1.02/LUK42860
DanfossDistrictEnergy
Page 13
InstallationGuideTermixHDMIXCompact28
6.2.2Fittingpiece
Thesubstationisequippedwithattingpieceforenergymeter .
Assemblyofenergymeters:
1:Closeballvalves
ClosetheballvalvesonDHSupplyandDHReturn,ifthereiswater onthesystem.
2:Loosennuts
Loosenthenutsonthettingpiece.
3:Removettingpiece
Removethettingpieceandreplaceitwiththeenergymeter.Do notforgetthegaskets.
4:Tightenconnections
Aftermountingoftheenergymeterremembertocheckand tightenallthreadedconnections.
Sensorpocket,energymeter
Thesensorsoftheenergymeterismountedinthesensorpockets.
DanfossDistrictEnergy
VI.GP .E1.02/LUK42860
DEN-GT
13
Page 14
InstallationGuideTermixHDMIXCompact28
6.3Maintenance
Thesubstationrequireslittlemonitoring,apartfromroutine checks.Itisrecommendedtoreadtheenergymeteratregular intervals,andtowritedownthemeterreadings.
RegularinspectionsofthesubstationaccordingtothisInstruction arerecommended,whichshouldinclude:
Strainers
Cleaningofstrainers.
Meters
Checkingofalloperatingparameterssuchasmeterreadings.
Temperatures
Checkingofalltemperatures,suchasDHsupplytemperatureand DHWtemperature.
Connections
Checkingallconnectionsforleakages.
Safetyvalves
Theoperationofthesafetyvalvesshouldbecheckedbyturning thevalveheadintheindicateddirection.
Venting
Checkingthatthesystemisthoroughlyvented.
Inspectionsshouldbecarriedoutminimumeverytwoyears.
SparepartscanbeorderedfromDanfoss.Pleaseensurethatany enquiryincludesthesubstationserialnumber.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualiedandauthorizedpersonnelonly.
14
DEN-GT
VI.GP .E1.02/LUK42860
DanfossDistrictEnergy
Page 15
InstallationGuideTermixHDMIXCompact28
7.0Troubleshooting
7.1Troubleshootingingeneral
Intheeventofoperatingdisturbances,thefollowingbasicfeatures shouldbecheckedbeforecarryingoutactualtroubleshooting:
thesubstationisconnectedtoelectricity,
thestrainerontheDHsupplypipeisclean,
thesupplytemperatureoftheDHisatthenormallevel (summer,atleast60°C-winter ,atleast70°C),
thedifferentialpressureisequaltoorhigherthanthenormal (local)differentialpressureintheDHnetwork–ifindoubt,ask theDHplantsupervisor,
pressureonthesystem-checktheHEpressuregauge.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualiedandauthorizedpersonnelonly.
7.2TroubleshootingHE
ProblemPossiblecauseSolution
Toolittleornoheat.StrainercloggedinDHorHEcircuit
(radiatorcircuit).
Cleangate/strainer(s).
ThelterintheenergymeteronDHcircuit clogged.
Cleanthelter(afterconsultingtheDH plantoperator).
Defectiveorwronglyadjusteddifferential pressurecontroller.
Checktheoperationofthedifferential pressurecontroller–cleanthevalveseatif required.
Sensordefective–orpossiblydirtinthe valvehousing.
Checktheoperationofthethermostat– cleanthevalveseatifrequired.
Automaticcontrols,ifany,wronglysetor defective-possiblypowerfailure.
Checkifthesettingofthecontroller iscorrect–seeseparateinstructions. Checkthepowersupply.Temporary settingofmotorto“manual”control–see instructionsonautomaticcontrols.
Pumpoutofoperation.Checkifthepumpisreceivingpowerand
thatitturns.Checkifthereisairtrappedin thepumphousing–seepumpmanual.
Thepumpissetattoolowspeedof rotation.
Setthepumpathigherspeedofrotation.
Pressuredrop–thepressuredropon theradiatorcircuitshowslowerthan recommendedoperatingpressure.
Fillwateronthesystemandcheckthe functioningofthepressureexpansion vesselifrequired.
Airpocketsinthesystem.Venttheinstallationthoroughly.
Limitingofthereturntemperature adjustedtoolow.
Adjustaccordingtoinstructions.
Defectiveradiatorvalves.
Check–replace.
Unevenheatdistributioninbuilding becauseofincorrectlysetbalancingvalves, orbecausetherearenobalancingvalves.
Adjust/installbalancingvalves.
Diameterofpipetosubstationtoosmallor branchpipetoolong.
Checkpipedimensions.
Unevenheatdistribution.Airpocketsinthesystem.Venttheinstallationthoroughly.
DanfossDistrictEnergy
VI.GP .E1.02/LUK42860
DEN-GT
15
Page 16
InstallationGuideTermixHDMIXCompact28
DHsupplytemperaturetoohigh.
Wrongsettingofthermostatorof automaticcontrols,ifany.
Adjustautomaticcontrols,–see instructionsforautomaticcontrols.
Defectivecontroller.Thecontrollerdoes notreactasitshouldaccordingtothe instructions.
Callautomaticcontrolsmanufactureror replacetheregulator.
Defectivesensoronself-actingthermostat.
Replacethermostat–orsensoronly.
DHsupplytemperaturetoolow.
Wrongsettingofautomaticcontrols,ifany.
Adjustautomaticcontrols–seeinstructions forautomaticcontrols.
Defectivecontroller.Thecontrollerdoes notreactasitshouldaccordingtothe instructions.
Callinautomaticcontrolsmanufactureror replacecontroller.
Defectivesensoronself-actingthermostat.
Replacethermostat–orsensoronly.
Wrongplacement/ttingofoutdoor temperaturesensor.
Adjustlocationofoutdoortemperature sensor.
Strainerclogged.Cleangate/strainer.
ToohighDHreturntemperature.
Toosmallheatingsurface/toosmall radiatorscomparedtothetotalheating requirementofthebuilding.
Increasetotalheatingsurface.
Poorutilizationofexistingheatingsurface. Defectivesensoronself-actingthermostat.
Makesuretheheatisdistributedevenly acrossthefullheatingsurface–openall radiatorsandkeeptheradiatorsinthe systemfromheatingupatthebottom.It isextremelyimportanttokeepthesupply temperaturetotheradiatorsaslowas possible,whilemaintainingareasonable levelofcomfort.
Thesystemissinglepipeloop.
Thesystemshouldfeatureelectronic controlsaswellasreturnsensors.
Pumppressuretoohigh.Adjustpumptoalowerlevel.
Airinsystem.
Ventthesystem.
Defectiveorincorrectlysetradiator valve(s).Singlepipeloopsystemsrequire specialone-piperadiatorvalves.
Check–set/replace.
Dirtinthemotorizedvalveorinthe differentialpressurecontroller.
Check–cleanout.
Defectivemotorizedvalve,sensoror automaticcontroller.
Check–replace.
Electroniccontrollernotadjustedcorrectly.Adjustaccordingtoinstructions.
Noiseinsystem.
Pumppressuretoohigh.Adjustpumptoalowerlevel.
Heatloadtoohigh.
Defectivemotorizedvalve,sensoror electroniccontroller.
Check–replace.
7.3Disposal
Disposal
Thisproductshouldbedismantledanditscomponents sorted,ifpossible,invariousgroupsbeforerecycling ordisposal.
Alwaysfollowthelocaldisposalregulations.
16
DEN-GT
VI.GP .E1.02/LUK42860
DanfossDistrictEnergy
Page 17
InstallationGuideTermixHDMIXCompact28
DanfossDistrictEnergy
VI.GP .E1.02/LUK42860
DEN-GT
17
Page 18
InstallationGuideTermixHDMIXCompact28
18
DEN-GT
VI.GP .E1.02/LUK42860
DanfossDistrictEnergy
Page 19
InstallationGuideTermixHDMIXCompact28
8.0Declaration
8.1Declarationofconformity
8.1.1Category0withelectricalequipment
EC–DeclarationofConformity
GeminaT ermixA/S MemberoftheDanfossGroup Navervej15-17 DK-7451Sunds
Declaresonoursoleresponsibilitythatthebelowproducts:
Substations–Category0withelectricalequipment,
coveredbythisdeclarationareinconformitywiththefollowingdirectives,standardsandothernormative documents,providedthattheyareusedaccordingtoourinstructions.
MachineryDirective2006/42/EC
DS/EN60204-1/A1:2009.Safetyofmachinery– Part1–GeneralRequirements. DS/EN12100:2011.Safetyofmachinery–Risk assessment.
LVD–LowVoltageDirective–2006/95/EC
DS/EN60204-1/A1:2009.Safetyofmachinery– Part1–GeneralRequirements.
EMC–Directive–2004/108/EC
DS/EN61000-6-2/Corr.:2005.Electromagnetic compatibility–Genericstandard:Immunity industry. DS/EN61000-6-3:2007.Electromagnetic compatibility–Genericstandard:Emissionfor residential,commercial&lightindustry.
Sunds–2013.03.15
PlaceanddateofissueClausGjøderumMortensen
Quality&EnvironmentManager
DanfossDistrictEnergy
VI.GP .E1.02/LUK42860
DEN-GT
19
Page 20
InstallationGuideTermixHDMIXCompact28
ProducedbyDanfossA/S©09/2013