Danfoss Termix BL Operating guide

OperatingGuide
TermixBL

1.0TableofContents

1.0TableofContents.............................................1
........................................................................2
2.0Functionaldescription......................................3
3.0Safetynotes.....................................................4
3.1SafetyNotes–general............................................4
4.0Mounting........................................................5
4.2Electricalconnections.............................................7
5.0Design.............................................................8
5.1Design...............................................................8
5.3Design...............................................................10
5.4Schematicdiagram................................................11
6.0Controls..........................................................12
6.1DHWtemperaturecontrol........................................12
6.2Other.................................................................14
6.3Maintenance........................................................15
7.0Troubleshooting..............................................16
7.1Troubleshootingingeneral......................................16
7.2TroubleshootingDHW............................................17
7.3Disposal.............................................................18
8.0Declaration......................................................22
8.1Declarationofconformity........................................22
©Danfoss|2019.04VI.EH.D5.02/LUK41570|1
OperatingGuideTermixBL
2|©Danfoss|2019.04
VI.EH.D5.02/LUK41570
OperatingGuideTermixBL

2.0Functionaldescription

Instantaneouswaterheaterwithheatexchangerand automaticcontrols.Designedforwall-mounting.
Application
TheTermixBLisawaterheaterwithautomaticcontrolsprepared forachargingsystem.TheTermixBLissuitableforlargeapartment houses,sportsarenasandschools,wherelargeamountsofhot waterareneeded.Thehotwatersystemsareavailablein7different sizeswithanoutputfrom70-222kW.TheTermixBLunitissupplied withPUinsulatedplateheatexchangers.
Domestichotwater(DHW)
TheTermixBLisavailableforchargingsystemswithlarge momentarydemandsforhotwaterorininstallationswithrelatively lowsupplycapacity.TheT ermixBLchargingsystemisdelivered withDanfossautomaticcontrolsforregulationofthecharging temperatureandthetemperatureinthehotwaterbuffertank.The controlvalvewithintegratedpressurecontrolhelpstoavoidcyclic variationsofthedifferentialpressureinthedistrictheatingsupply.
Domestichotwatercirculation
TheT ermixBLsubstationissuppliedwithconnectionsforDHW circulationincludingcirculationpumpandanon-returnvalveas astandard.
VI.EH.D5.02/LUK41570
©Danfoss|2019.04|3
OperatingGuideTermixBL

3.0Safetynotes

3.1SafetyNotes–general

Thefollowinginstructionsrefertothestandarddesignof substation.Specialversionsofsubstationsareavailableon request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation andstart-upofthesubstation.Themanufactureracceptsno liabilityfordamageorfaultsthatresultfromnon-compliancewith theoperatingmanual.Pleasereadandfollowalltheinstructions carefullytopreventaccidents,injuryanddamagetoproperty. Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly. Pleasecomplywiththeinstructionsissuedbythesystem manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass. Themaximumchloridecompoundsoftheflowmediumshouldnot behigherthan150mg/l. Theriskofequipmentcorrosionincreasesconsiderablyifthe recommendedlevelofpermissiblechloridecompoundsis exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary sourceofenergy.However,alsootherenergysourcescanbeused wheretheoperatingconditionsallowitandalwaysarecomparable todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse installationinafrost-freeroom,wherethetemperaturedoesnot exceed50°Candthehumiditydoesnotexceed60%.Donotcover orwallupthesubstationorinanyotherwayblocktheentrance tothestation.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallation’spermissiblesystempressureand temperature.
Themaximumtemperatureoftheflowmediuminthesubstationis 120°C.
Themaximumoperatingpressureofthesubstationis16bar.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases considerablyiftherecommendedpermissibleoperatingparameters areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves, however,alwaysinaccordancewithlocalregulations.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat thesubstationcanbeseparatedfromallenergysources(also powersupply).
Emergency
Incaseofdangeroraccidents-fire,leaksorotherdangerous circumstances-interruptallenergysourcestothestationif possible,andseekexperthelp. Incaseofdiscolouredorbad-smellingdomestichotwater,closeall shut-offvalvesonthesubstation,informtheoperatingpersonnel andcallforexperthelpimmediately.
REACH
AllDanfossA/SproductsfulfilltherequirementsinREACH. OneoftheobligationsinREACHistoinformcustomersabout presenceofCandidatelistsubstancesifany,weherebyinform youaboutonesubstanceonthecandidatelist:Theproduct containsbrasspartswhichcontainslead(CASno:7439-92-1)ina concentrationabove0.1%w/w.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto installationshouldbeinconditionswhicharedryandheated.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns. Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen position.Thesurfacesofthesubstationcangethot,whichcancause skinburns.Theballvalvesondistrictheatingsupplyandreturnshould beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallflangeconnections,screwjoints andelectricalclampandscrewconnectionsmustbecheckedand tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen addedtothesystemandthesystemhasbeenputintooperation, re-tightenALLconnections.
4|©Danfoss|2019.04
VI.EH.D5.02/LUK41570
OperatingGuideTermixBL

4.0Mounting

4.1Mounting

Installationmustbeincompliancewithlocalstandardsand regulations. Districtheating(DH)-Inthefollowingsections,DHreferstothe heatsourcewhichsuppliesthesubstations.Avarietyofenergy sources,suchasoil,gasorsolarpower,couldbeusedasthe primarysupplytoDanfosssubstations.Forthesakeofsimplicity, DHcanbetakentomeantheprimarysupply.
Connections:
1.Districtheating(DH)supply
2.Districtheating(DH)return
3.Hotwatercirculation(HWC)
4.Domestichotwater(DHW)
5.Domesticcoldwater(DCW)
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly.
Type2–5
Connectionsizes:
DH+DCW+DHW: HWC:
Dimensions(mm):
Type2-5withoutcover: H660xW510xD240 Type2-5withcover: H800xW540xD360
Type6-8withoutcover: H920xW720xD385 Type6-8withcover: H920xW800xD450
Weight(approx.):20–40kg
G1”(int.thread) G¾”(int.thread)
Type6–8
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote themarkingsonthestation.
VI.EH.D5.02/LUK41570
©Danfoss|2019.04|5
OperatingGuideTermixBL
4.1.1Installation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes andlabelsareplacedcorrectly.Ifyouwishtomountthestation differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe cleanedandrinsed.
Keyholeformounting.
Tightening
Duetovibrationduringtransport,allsubstationconnectionsmust becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha plug.Shouldtheplugsrequireremoval,thismustonlybedoneby anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbefittedaccording toschematicdiagram.Pleasenotethatthestrainermaybe suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe madeusingthreaded,flangedorweldedconnections.
6|©Danfoss|2019.04
VI.EH.D5.02/LUK41570
OperatingGuideTermixBL

4.2Electricalconnections

Beforemakingelectricalconnections,pleasenotethe following:
Safetynotes
Pleasereadtherelevantpartsofthesafetynotes.
230V
Thesubstationmustbeconnectedto230VACandearth.
Potentialbonding
Potentialbondingshouldbecarriedoutaccording to60364-4-41:2007andIEC60364-5-54:2011. Bondingpointonthemountingplatebelowrightcornermarked withearthsymbol.
Disconnection
Thesubstationmustbeelectricallyconnectedsothatitcanbe disconnectedforrepairs.
Outdoortemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto directsunlight.Theyshouldnotbeplacedclosetodoors,windows orventilationoutlets.
Theoutdoorsensormustbeconnectedtothestationonthe terminalblockundertheelectroniccontrol.
Authorizedelectrician
Electricalconnectionsmustbemadebyanauthorizedelectricianonly.
Localstandards
Electricalconnectionsmustbemadeinaccordancewithcurrent regulationsandlocalstandards.
VI.EH.D5.02/LUK41570
©Danfoss|2019.04|7
OperatingGuideTermixBL

5.0Design

5.1Design

Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
B
Heatexchanger,DHW
G
Electroniccontroller,DHW
2
Singlecheckvalve
11
Domestichotwaterpump
27
Actuator
30
Flowcontrolwithcontrolvalve
8|©Danfoss|2019.04
VI.EH.D5.02/LUK41570
OperatingGuideTermixBL

5.2Schematicdiagram

Schematicdiagramtype2-5(example)
DH
Supply
DH
Return
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
B
Heatexchanger,DHW
D
Hotwatertank
G
Electroniccontroller,DHW
L
Borderofdelivery
1
Ballvalve
2
Singlecheckvalve
DHW:DomesticHotWater DCW: HWC: DHSupply:DistrictHeatingSupply DHReturn:DistrictHeatingReturn
DomesticColdWater HotWaterCirculation
4
Safetyvalve
11
Domestichotwaterpump
13
Chargingpump
18
Thermometer
19
Surfacesensor
24
Deliveredloosewithunit
27
Actuator
30
Flowcontrolwithcontrolvalve
36
Balancingvalve
40
Immersionsensor
43
Ballvalveclosed
44
Immersionsensor
DHW
DCW
HWC
5.2.1Technicalparameters
Technicalparameters
Nominalpressure: Max.DHsupplytemperature: Min.DCWstaticpressure: Brazingmaterial(HEX): Heatexchangerstestpressure:30bar Soundlevel:≤55dB
PN16 120°C
0.5bar Copper
VI.EH.D5.02/LUK41570
©Danfoss|2019.04|9
OperatingGuideTermixBL

5.3Design

Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
B
Heatexchanger,DHW
G
Electroniccontroller,DHW
2
Singlecheckvalve
11
Domestichotwaterpump
13
Chargingpump
27
Actuator
30
Flowcontrolwithcontrolvalve
10|©Danfoss|2019.04
VI.EH.D5.02/LUK41570
OperatingGuideTermixBL

5.4Schematicdiagram

Schematicdiagramtype6-8(example)
DH
Supply
DH
Return
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
B
Heatexchanger,DHW
D
Hotwatertank
G
Electroniccontroller,DHW
L
Borderofdelivery
1
Ballvalve
2
Singlecheckvalve
DHW:DomesticHotWater DCW: HWC: DHSupply:DistrictHeatingSupply DHReturn:DistrictHeatingReturn
DomesticColdWater HotWaterCirculation
4
Safetyvalve
11
Domestichotwaterpump
13
Chargingpump
18
Thermometer
19
Surfacesensor
27
Actuator
30
Flowcontrolwithcontrolvalve
36
Balancingvalve
40
Immersionsensor
43
Ballvalveclosed
44
Immersionsensor
DHW
DCW
HWC
5.4.1Technicalparameters
Technicalparameters
Nominalpressure: Max.DHsupplytemperature: Min.DCWstaticpressure: Brazingmaterial(HEX): Heatexchangerstestpressure:30bar Soundlevel:≤55dB
VI.EH.D5.02/LUK41570
PN16 120°C
0.5bar Copper
©Danfoss|2019.04|11
OperatingGuideTermixBL

6.0Controls

6.1DHWtemperaturecontrol

DHWtemperaturecontrol
TherearevarioustypesofDHWtemperaturecontrolusedin Danfosssubstations. DHWtemperatureshouldbeadjustedto45-50°C,asthisprovides optimalutilisationofDHwater.AtDHWtemperaturesabove55°C, thepossibilityoflimescaledepositsincreasessignificantly.
6.1.1Electroniccontrol
Substationswithelectroniccontrolmustbesetinaccordancewith manufacturer´sinstructions. Wheretheroomtemperatureiscontrolledbyradiatorthermostats, itisrecommendedthatthermostatsbesetforminimum temperatureineachroom.
6.1.2Electric2–waymotorizedvalve
Actuatorswithorwithoutsafetyfunctionareavailablefor3-point controls.Spring-returnactuatorscanbeusedtoprovidesafety shut-offintheeventofpowerfailure.
12|©Danfoss|2019.04
VI.EH.D5.02/LUK41570
OperatingGuideTermixBL
6.1.3Domestichotwaterpump
Important!
Itisnecessarytomountadomestichotwatercirculationpumpon thewaterheatertoavoidregulationproblems. Thecirculationpumpcannotbeswitchedoff,sincethiswillresult inregulationproblems.(noflowatthesensor).
VI.EH.D5.02/LUK41570
©Danfoss|2019.04|13
OperatingGuideTermixBL

6.2Other

6.2.1Safetyvalve
Thepurposeofthesafetyvalveistoprotectthesubstationfrom excessivepressure. Theblow-offpipefromthesafetyvalvemustnotbeclosed.The blow-offpipeoutletshouldbeplacedsothatitdischargesfreely anditispossibletoobserveanydrippingfromthesafetyvalve. Itisrecommendedtochecktheoperationofsafetyvalvesat intervalsof6months.Thisisdonebyturningthevalveheadin directionindicated.
14|©Danfoss|2019.04
VI.EH.D5.02/LUK41570
OperatingGuideTermixBL

6.3Maintenance

Thesubstationrequireslittlemonitoring,apartfromroutine checks.Itisrecommendedtoreadtheenergymeteratregular intervals,andtowritedownthemeterreadings.
RegularinspectionsofthesubstationaccordingtothisInstruction arerecommended,whichshouldinclude:
Strainers
Cleaningofstrainers.
Meters
Checkingofalloperatingparameterssuchasmeterreadings.
Temperatures
Checkingofalltemperatures,suchasDHsupplytemperatureand DHWtemperature.
Connections
Checkingallconnectionsforleakages.
Safetyvalves
Theoperationofthesafetyvalvesshouldbecheckedbyturning thevalveheadintheindicateddirection.
Venting
Checkingthatthesystemisthoroughlyvented.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly.
Inspectionsshouldbecarriedoutminimumeverytwoyears.
SparepartscanbeorderedfromDanfoss.Pleaseensurethatany enquiryincludesthesubstationserialnumber.
VI.EH.D5.02/LUK41570
©Danfoss|2019.04|15
OperatingGuideTermixBL

7.0Troubleshooting

7.1Troubleshootingingeneral

Intheeventofoperatingdisturbances,thefollowingbasicfeatures shouldbecheckedbeforecarryingoutactualtroubleshooting:
thesubstationisconnectedtoelectricity,
thestrainerontheDHsupplypipeisclean,
thesupplytemperatureoftheDHisatthenormallevel (summer,atleast60°C-winter,atleast70°C),
thedifferentialpressureisequaltoorhigherthanthenormal (local)differentialpressureintheDHnetwork–ifindoubt,ask theDHplantsupervisor,
pressureonthesystem-checktheHEpressuregauge.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly.
16|©Danfoss|2019.04
VI.EH.D5.02/LUK41570
OperatingGuideTermixBL

7.2TroubleshootingDHW

ProblemPossiblecauseSolution
ToolittleornoDHW.
Taptemperaturetoohigh;DHWtapload toohigh.
Temperaturedropduringtapping.
Thermostaticcontrolvalvedoesnotclose
Strainerinsupplyorreturnlineclogged.Cleanstrainer(s).
DHWcirculationpumpoutoforderorwith toolowsetting.
Defectiveorcloggednon-returnvalve.
Noelectricity.Check.
Wrongsettingofautomaticcontrols,ifany.Toadjustanelectroniccontrollerfor
Scalingoftheplateheatexchanger.
Defectivemotorizedvalve.Check(usemanualfunction)–replace.
Defectivetemperaturesensors.
Defectivecontroller.
DCWisbeingmixedwiththeDHW,e.g.ina defectivethermostaticmixingvalve.
Defectiveorcloggednon-returnvalveon circulationvalve.
Thermostaticvalveadjustedtoatoohigh level.
Scalingoftheplateheatexchanger.
LargerDHWflowthanthesubstationhas beendesignedfor.
TemperaturedifferencebetweenDH supplyandDHWsetpointtoolow.
Checkcirculationpump.
Replace–clean.
DHW,pls.noteenclosedinstructionsfor electroniccontroller.
Replace–rinseout.
Check–replace.
Check–replace.
Check–replace. Hotwaterinsometapsbutnotinall.
Replace–clean.
Check–set.
Replace–rinseout.
ReduceDHWflow.
Lowerthesetpointtemperatureorincrease theDHsupplytemperature.
VI.EH.D5.02/LUK41570
©Danfoss|2019.04|17
OperatingGuideTermixBL

7.3Disposal

Disposal
Thisproductshouldbedismantledanditscomponents sorted,ifpossible,invariousgroupsbeforerecycling ordisposal.
Alwaysfollowthelocaldisposalregulations.
18|©Danfoss|2019.04
VI.EH.D5.02/LUK41570
OperatingGuideTermixBL
19|©Danfoss|2019.04
VI.EH.D5.02/LUK41570
OperatingGuideTermixBL
20|©Danfoss|2019.04
VI.EH.D5.02/LUK41570
OperatingGuideTermixBL
21|©Danfoss|2019.04
VI.EH.D5.02/LUK41570
OperatingGuideTermixBL

8.0Declaration

8.1Declarationofconformity

8.1.1Substationlabel
Normallythebelowmentioneddeclarationofconformityapplies: "Substations-Category0withelectricalequipment".
Unlessfittedwithayellowlabel(PEDKAT.1)onthesubstationlabel thenthefollowingdeclarationofconformityapplies:"Substations­Category1withelectricalequipment" .
Category0withelectricalequipment
22|©Danfoss|2019.04
VI.EH.D5.02/LUK41570
OperatingGuideTermixBL
Category1withelectricalequipment
VI.EH.D5.02/LUK41570
©Danfoss|2019.04|23
OperatingGuideTermixBL
24|©Danfoss|2019.04
VI.EH.D5.02/LUK41570