Danfoss ST-1, ST-2 Data sheet

Data sheet
Safety thermostats ST-1/ST-2
Application
ST-1 ST-2
Ordering
Technical data
Safety thermostats ST-1 and ST-2 can be used in directly or indirectly connected district heating systems where extra safety is required.
ST-1 incorporates a thermostat (TR) and a safety monitor (STW) with automatic reset.
If ST-1 or ST-2 is used together with an AMV(E) 13, 23, or 33 three-point controlled actuator, the safety monitor (STW) or safety limit cutout (STB) releases the spring return function for forced closure of the motorized control valve.
The safety thermostats are approved in accord­ST-2 incorporates a thermostat (TR) with auto­matic reset and a safety limit cutout (STB) with manual reset.
ance with DIN 3440 with the following
DIN Register Nos.:
ST-1: TR STW 1175 05
ST-2: TR STB 1176 05
Typ e
ST-1 (TR/STW) 30 - 120 oC 100 - 120 oC - 087N1050 ST-2 (TR/STB) 30 - 90 oC - 95 oC 087N1051
Accessory Sensor pocket (Cu/Ms) for ST1 / ST2 087N12 01
ST-1 TR STW ST-2 TR STB Setting 30 - 120 oC 100 - 120 oC Setting 30 - 90 oC 95 oC Differential 4 ± 1 K 12 ± 3 K Differential 4 ± 1 K 12 ± 3 K Reset Auto Auto Reset Auto Manual
Contacts Ag 1000/1000 Contact loads 10 (2.5) A 250 V ~ / 7 A 380 V ~ Max. ambient temperature 80 oC Max. sensor temperature 130 oC Cut-out accuracy +0 K - -6 K Enclosure IP 40 Mounting direction No restrictions Sensor connection R ½ Cable entry M 20 Pressure stage PN 10 Medium Water, pH 7 - 10 Sensor 2 off Ø 9 x 100 Sensor pockets (takes both sensors) Brass Ms 58/copper Storage and transport temperature -15 oC - +80 oC Approvals DIN 3440 and VDE 0631
TR STW STB
Setting
Code no.
© Danfoss | 2022.02
AI000086465317en-010701 | 1
Data sheet Safety thermostats ST-1/ST2
Electrical connections
Dimensions
ST-1 with Danfoss ECL Comfort 210/310 and AMV(E) 13, 23, or 33 connected
2 | © Danfoss | DCS-SGDPT/DK | 2022.02
AI000086465317en-010701