Danfoss SC18, SC18CL Data sheet

SC18/18CL LBP/MBP Twin Compressor R404A/R507 220-240V 50Hz
General
Code number 104L4090
Approvals EN 60335-2-34
Application
Application LBP/MBP
Frequency Hz 50 60
Evaporating temperature °C -45 to -5
Voltage range V 198 - 254
Max. condensing temperature continuous (short) °C 55 (60)
Max. winding temperature continuous (short) °C 125 (135)
Cooling requirements
Frequency Hz 50 60
Application
32°C F2F2–
38°C F
43°C
Remarks on application:
LBP MBP HBP LBP MBP HBP
2F2
S =Staticcoolingnormallysufcient
O = Oil cooling F1 = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) F2 = Fan cooling 3.0 m/s necessary
SG =Suctiongascoolingnormallysufcent
– = not applicable in this area
Motor
Motor type CSR
LRA (rated after 4 sec. UL984) *, HST | LST A 2 x 20.0
Cut in Current *, HST | LST A 2 x 20.0
Resistance, main | start winding (25°C) 3.7 14.1
* Operational current for the second compressor time-delayed.
Design
Displacement cm
Oil quantity (type) cm
Maximum refrigerant charge g 2200
Free gas volume in compressor cm
Weight without electrical equipment kg 29.1
Dimensions
Height mm A 259
Suction connector (service valve) location/I.D. mm C 16 | 37°
Suction connector (solder connector) location/I.D. mm C 16 | 37°
Process connector location/I.D. mm | angle D 6.2 | 37°
material | comment Cu-plated steel | Al cap
Discharge connector location/I.D. mm | angle E 6.2 | 37°
material | comment Cu-plated steel | Al cap
Oil cooler connector location/I.D. mm | angle F
material | comment
Connector tolerance I.D. mm ±0.09
Remarks:
3
3
3
1220 (polyolester)
B 254
B1 193
B2 110
2 x 17.69
2920
Dec 2011 Manufactured by Secop for Danfoss - CF.54.I5.02 / 520N1185 1/2
EN 12900 Household (CECOMAF) 220V, 50Hz, fan cooling F
2
Evap. temp. in °C -45 -40 -35 -30 -25 -23.3 -20 -15 -10 -6.7 -5 0 5 7.2 10 15 20
Capacity in W 333 541 789 1083 1430 1562 1836 2307 2849 3249 3469
Power cons. in W 587 752 910 1068 1230 1286 1400 1585 1788 1935 2015
Current cons. in A 5.22 5.59 6.04 6.58 7.21 7.44 7.92 8.72 9.61 10.24 10.58
COP in W/W 0.57 0.72 0.87 1.01 1.16 1.21 1.31 1.46 1.59 1.68 1.72
ASHRAE LBP/MBP 220V, 50Hz, fan cooling F
2
Evap. temp. in °C -45 -40 -35 -30 -25 -23.3 -20 -15 -10 -6.7 -5 0 5 7.2 10 15 20
Capacity in W 386 627 915 1256 1660 1813 2133 2683 3317 3769 4043
Power cons. in W 587 752 910 1068 1230 1286 1400 1585 1788 1935 2015
Current cons. in A 5.22 5.59 6.04 6.58 7.21 7.44 7.92 8.72 9.61 10.24 10.58
COP in W/W 0.66 0.83 1.00 1.18 1.35 1.41 1.52 1.69 1.85 1.95 2.01
Accessories SC18/18CL pcs. Code number Test conditions
Starting device 470 mm cable length
550 mm cable length 117-7027 Ambient temperature 32°C 32°C
650 mm cable length 117-7046 Suction gas temperature 32°C 32°C
2
117-7012 Condensing temperature 45°C 45°C
EN 12900/
CECOMAF
ASHRAE
LBP/MBP
1000 mm cable length 117-7040 Liquid temperature no subcooling 32°C
Starting relay 6.3 mm spade connectors 2
Start. capacitor 80 µF 6.3 mm spade connectors 2
Cover 2 103N2009
Cord relief 2 103N1004
Time-delay relay 1 117N0001
Check valve (to be used with time-delay relay) 2 020-1014
Service valve 12 mm 1
Solder connector (alternative) 12 mm 1
Service valve 16 mm 1 118-7351
Solder connector (alternative) 16 mm 1 118-7405
Seal ring for service valve and solder connector 1 118-3638
Mounting accessories pcs. Code number
Bolt joint for one compressor Ø: 16 mm 2 118-1917
Bolt joint in quantities Ø: 16 mm 2 118-1918
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to
productsalreadyonorderprovidedthatsuchalterationscanbemadewithoutsubsequentialchangesbeingnecessaryinspecicationsalreadyagreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
2/2 Manufactured by Secop for Danfoss - CF.54.I5.02 / 520N1185 Dec 2011
Loading...