SC12MLX
MBP Compressor
R404A/R507
208-230V 60Hz & 220-240V 50Hz
General
Code number 104L2606
Approvals EN 60335-2-34, UL984
Compressors on pallet 80
Application
Application MBP
Frequency Hz 50 60
Evaporating temperature °C -23.3 to 7.2 -23.3 to 7.2
Voltage range V 187 - 254 187 - 254
Max. condensing temperature continuous (short) °C 50 (60) 50 (60)
Max. winding temperature continuous (short) °C 125 (135) 125 (135)
Cooling requirements
Frequency Hz 50 60
Application
32°C – F2– – F2–
38°C – F
43°C – F
Remarks on application:
Not applicable for 208V 60Hz at 0°C or higher evaporating temperature.
Motor
Motor type CSIR
LRA (rated after 4 sec. UL984), HST | LST A 23.4 –
Cut in Current, HST | LST A 23.4 –
Resistance, main | start winding (25°C) Ω 3.4 14.4
Design
Displacement cm
Oil quantity (type) cm
Maximum refrigerant charge g 1300
Free gas volume in compressor cm
Weight without electrical equipment kg 13.9
Dimensions
Height mm A 219
Suction connector location/I.D. mm | angle C 8.2 | 37°
material | comment Cu-plated steel | Al cap
Process connector location/I.D. mm | angle D 6.5 | 37°
material | comment Cu-plated steel | Al cap
Discharge connector location/I.D. mm | angle E 6.5 | 37°
material | comment Cu-plated steel | Al cap
Oil cooler connector location/I.D. mm | angle F –
material | comment –
Connector tolerance I.D. mm ±0.09
Remarks:
LBP MBP HBP LBP MBP HBP
– – F2–
2
– – F2–
2
3
3
3
B 213
B1 193
B2 110
12.87
600 (polyolester)
1460
S =Staticcoolingnormallysufcient
O = Oil cooling
F1 = Fan cooling 1.5 m/s
(compressor compartment temperature
equal to ambient temperature)
F2 = Fan cooling 3.0 m/s necessary
SG =Suctiongascoolingnormallysufcent
– = not applicable in this area
Dec 2011 Manufactured by Secop for Danfoss - DEHC.ED.401.B3.02 / 520N0608 1/2

ASHRAE MBP 230V, 60Hz, fan cooling F
2
Evap. temp. in °C -45 -40 -35 -30 -25 -23.3 -20 -15 -10 -6.7 -5 0 5 7.2 10 15 20
Capacity in W 554 667 859 1080 1245 1335 1629 1965 2127
Power cons. in W 552 609 692 775 830 860 949 1046 1092
Current cons. in A 3.39 3.57 3.87 4.21 4.46 4.59 5.01 5.47 5.68
COP in W/W 1.00 1.10 1.24 1.39 1.50 1.55 1.72 1.88 1.95
ASHRAE MBP 220V, 50Hz, fan cooling F
2
Evap. temp. in °C -45 -40 -35 -30 -25 -23.3 -20 -15 -10 -6.7 -5 0 5 7.2 10 15 20
Capacity in W 498 592 754 942 1083 1162 1415 1706 1847
Power cons. in W 507 548 609 667 705 724 780 836 860
Current cons. in A 3.72 3.84 4.03 4.25 4.40 4.48 4.72 4.99 5.11
COP in W/W 0.98 1.08 1.24 1.41 1.54 1.60 1.81 2.04 2.15
EN 12900 Household (CECOMAF)* 230V, 60Hz, fan cooling F
2
Evap. temp. in °C -45 -40 -35 -30 -25 -23.3 -20 -15 -10 -6.7 -5 0 5 7.2 10 15 20
Capacity in W 659 773 970 1199 1370 1465 1770 2118 2286
Power cons. in W 561 601 664 729 776 801 882 975 1021
Current cons. in A 3.38 3.52 3.76 4.05 4.26 4.37 4.73 5.14 5.32
COP in W/W 1.18 1.29 1.46 1.64 1.77 1.83 2.01 2.17 2.24
EN 12900 Household (CECOMAF)* 220V, 50Hz, fan cooling F
2
Evap. temp. in °C -45 -40 -35 -30 -25 -23.3 -20 -15 -10 -6.7 -5 0 5 7.2 10 15 20
Capacity in W 572 669 838 1038 1188 1272 1542 1852 2001
Power cons. in W 493 525 572 620 651 667 714 762 783
Current cons. in A 3.67 3.76 3.91 4.08 4.20 4.27 4.47 4.69 4.79
COP in W/W 1.16 1.27 1.46 1.68 1.83 1.91 2.16 2.43 2.55
Accessories for SC12MLX Figure Code number Test conditions EN 12900/
CECOMAF*
PTC starting device 6.3 mm spade connectors
4.8 mm spade connectors – Ambient temperature 32°C 35°C
a1
– Condensing temperature 45°C 54.4°C
ASHRAE
MBP
Starting relay 6.3 mm spade connectors a2 117U6011 Suction gas temperature 32°C 35°C
Cover b 103N2008 Liquid temperature no subcooling 46.1°C
Start. capacitor 80 µF 6.3 mm spade connectors c 117U5017
Cord relief d 103N1004 Mounting accessories Code number
Protection screen for PTC g – Bolt joint for one comp. Ø: 16 mm 118-1917
Bolt joint in quantities Ø: 1 6 mm 118-1918
Snap-on in quantities Ø : 16 mm 118-1919
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to
productsalreadyonorderprovidedthatsuchalterationscanbemadewithoutsubsequentialchangesbeingnecessaryinspecicationsalreadyagreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
2/2 Manufactured by Secop for Danfoss - DEHC.ED.401.B3.02 / 520N0608 Dec 2011